Flowmeters: Problems and SolutionsMarch 28, 2018
![Page 2: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/2.jpg)
• Why do we use flowmeters in water treatment• What technologies are being used• What are the limitations of each technologies• Installation Recommendations• What are the solutions when a flow meter goes
south on you
Flow Meters: Problems and Solutions
![Page 3: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/3.jpg)
Why Using a Flowmeter?Pacing chemical dosage systems (GPM)• Chlorine Gas• Chlorine Liquid• pH solutions (Lime, Soda Ash, Caustic)• Alum and Other Coagulents• High Flow Alarms to SCADA SystemDetermine Water Usage (Gallons)• Of your own Town• Of another Town• Of the Fish PlantDetermine Distribution System Leaks• Noticing more volume than usual
– Flow rate going up– Flow Total going up
![Page 4: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/4.jpg)
Technologies Most Used
• Paddlewheel• Magmeter• Insertion magmeter• Ultrasonic Clamp‐on
![Page 5: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/5.jpg)
Flowmeter Components
Flow SensorFlow TransmitterCompact Design• Flow Transmitter mounted to the sensor
![Page 6: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/6.jpg)
Paddlewheel
![Page 7: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/7.jpg)
Paddlewheel – Pros & ConsBenefit(s):• Low Purchase Cost• Low Installation Cost• Easy to remove
Downside(s):• Susceptible to Dirt and Wear
– Dirt (Weed)• Sluggist or stop sensing all together
– Wear (Bearing)
• No Output Signal Below a Certain Velocity
![Page 8: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/8.jpg)
Magmeter
![Page 9: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/9.jpg)
Magmeter – Pros & Cons
Benefit(s):• Full bore• No moving parts• Long Life• Will Provide Output Signal at Most Velocity
Downside:• In‐Line• Requires Good Pipe/Flowmeter Grounding
![Page 10: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/10.jpg)
Insertion Magmeter
![Page 11: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/11.jpg)
Insertion Magmeter – Pros & Cons
Benefit(s):• Low Installation Cost• Easy to remove• No moving parts• Long Life
Downside:• In Dirt Path• Requires Great Pipe/Flowmeter Grounding
![Page 12: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/12.jpg)
Ultrasonic Clamp‐On
![Page 13: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/13.jpg)
Ultrasonic Clamp‐On – Pros & Cons
Benefit(s):• Not Intrusive• Low Installation Cost• Same price small or large pipe• Installs on all pipe materials• Easy to remove• No moving parts• Long Life
Downside:• Same price small or large pipe
![Page 14: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/14.jpg)
Installation Recommendations
![Page 15: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/15.jpg)
Installation Recommendations
![Page 16: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/16.jpg)
Installation Recommendations
Size does matter!• Pipes too large have low velocity• Some technologies will not provide an output at low flows or at all
![Page 17: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/17.jpg)
Installation Recommendations
What is 4‐20mA Output Signal?• Flow proportional signal to pace the dosage system: Gas, Sodium Hypo
Pump, pH Pump…• Signal Varies between 4mA and 20mA (i.e. 0 – 300GPM)
– 4mA = 0 GPM– 20mA = Maximum of the set range 300 GPM– If fish plant closed permanently, flow range should be set lower and pump dosage re‐
adjusted
• Polarity Sensitive– 2‐wire output– Wired backward = 0 signal
![Page 18: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/18.jpg)
Flowmeter Issues
• Submersed– Most electronic enclosures not made to be submersed– Magmeters coils will be damaged if submersed. Not repairable.
• Dirty– Paddlewheel locks up– Magmeter electrodes don’t sense the magnetic field
• Air in Pipe– What is the cause of the entrained air?– Verify air release valve functionality
![Page 19: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/19.jpg)
Flowmeter Solutions
• Submersed– Replace any kind of flowmeter
• Dirty– Paddlewheel: Clean and re‐install: Random/Recurring Problem– Magmeter electrodes don’t sense the magnetic field, clean or
replace flow sensor
• Old Age!
![Page 20: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/20.jpg)
Flowmeter Solutions
• Install Ultrasonic Clamp‐on Flowmeter– Will fit in most typical installation– Leave existing magmeter in place.– Install new clamp‐on flowmeter nearby within the upstream and
downstream straight pipe requirements.– The transmitter will prompt for the pipe size, material, liner to
determine how far apart the sensors have to be.
![Page 21: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/21.jpg)
Paddlewheel and Ultrasound Clampon
![Page 22: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/22.jpg)
Magmeter
![Page 23: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/23.jpg)
Magmeter – Flanged and InsertionText
• Text
![Page 24: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/24.jpg)
Ultrasonic Clampon
![Page 25: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/25.jpg)
Takeaways
• Flowmeters Serve Multiple Purpose• Correct Technology and Proper Installation avoids Random
Issues• Easy Installation Can Be Done With the Use of Non‐
Intrusive Technologies Such as Ultrasonic Clampon.
![Page 26: Flowmeters: Problems and Solutions · Installation Recommendations What is 4‐20mAOutputSignal? • Flow proportional signal to pace the dosage system: Gas, Sodium Hypo Pump, pH](https://reader031.vdocuments.us/reader031/viewer/2022013019/5e53f511d5cb12721e185306/html5/thumbnails/26.jpg)
Newfoundland (709) 722‐5690 / (1‐800) 563‐9595126 Glencoe DriveDonovans Industrial ParkMount Pearl, NL A1N 4S9
Nova Scotia(902) 468‐1955 / (1‐800) 567‐195521 Frazee AvenueBurnside Industrial ParkDartmouth, NS B3B 1Z4
(902) 867‐1200 / 1‐866‐867‐12004630 Highway #7 Salt SpringsAntigonish County, NS B2G 2L3
Prince Edward Island(902) 201‐1766 / 1‐800‐867‐120051 Fourth Street, West Royalty ParkCharlottetown, PE, C1E 2B6