    A.8.17.4.6 Where backflow prevention devices are installed,they should be in an accessible location to provide for serviceand maintenance.

    A.8.17.4.6.1 The full flow test of the backflow preventionvalve can be performed with a test header or other connectiondownstream of the valve. A bypass around the check valve inthe fire department connector line with a control valve in thenormally closed position can be an acceptable arrangement.

    When flow to a visible drain cannot be accomplished, closed

    loop flow can be acceptable if a flowmeter or site glass is incor-porated into the system to ensure flow. When a backflow pre-

    vention device is retroactively installed on a pipe schedule sys-tem, the revised hydraulic calculation still follows the pipeschedule method of 11.2.2 with the inclusion of friction lossfor the device.

    A.8.17.5.1.1 One and one-half inch (40 mm) fire hose packsare not required unless designated by the authority having

    jurisdiction, as it is not likely that such hoses will be adequatelymaintained for safe use by first responders. Civilian workers

    who are not properly trained in fire-fighting techniques areexpected to evacuate the building in the event of a fire.

    A.8.17.5.1.4 This standard covers 112in. (40 mm) hose con-nections for use in storage occupancies and other locations

    where standpipe systems are not required. Where Class IIstandpipe systems are required, see the appropriate provisionsof NFPA 14 with respect to hose stations and water supply forhose connections from sprinkler systems.

    A.8.17.5.2.2 See Figure A.8.17.5.2.2(a) and FigureA.8.17.5.2.2(b).

    30

    0 150

    120

    9060

    Indicating-type floor control valvewith supervisory switch

    Waterflow switch

    Pressure gauge

    Feed main

    Sectionaldrainvalve

    To drain

    Riser Test valve

    Sight glassUnion with corrosion-resistant orificegiving flowequivalent tothe smallestsprinklerorifice inthe system

    FIGURE A.8.17.4.2(b) Floor Control Valve.

    See note

    Branch line

    Pitch

    Test valve in accessiblelocation

    Plug for testing remove

    and install temporaryconnection

    Union

    45ell

    Smooth borecorrosion-resistant outletgiving flow equivalentto one sprinkler

    Note: To minimize condensation of water in the drop to thetest connection, provide a nipple-up off of the branch line.

    FIGURE A.8.17.4.3 System Test Connection on Dry PipeSystem.

    Tosprinklersystem

    Indicating-type floor controlvalve with supervisory switch Check

    valve

    PressuregaugeWaterflowswitch

    Combination sprinkler/standpipe riser

    Inspectorstest and drainconnection

    Drainriser

    Fire hose valve

    FIGURE A.8.17.5.2.2(a) Acceptable Piping Arrangement forCombined Sprinkler/Standpipe System. [14:Figure A.6.3.5(a)]

    Tosprinklersystem

    Indicating-type floor controlvalve with supervisory switch Check

    valve

    Pressuregauge

    Waterflowswitch

    Combination sprinkler/standpipe riser

    Inspectorstest and drainconnection

    Drainriser

    2in.(65 mm) min.

    Fire hose valve

    FIGURE A.8.17.5.2.2(b) Acceptable Piping Arrangement forCombined Sprinkler/Standpipe System. [14:Figure A.6.3.5(b)]