RSIC ACOUSTIC ASSEMBLY
FLOOR CEILING ASSEMBLY
DIRECT FIX TO WOOD OPEN WEB TRUSS
F4545.01 STC 62 IIC 53
CONSTRUCTIONHacker Industries, Inc. Firm-Fill Gypsum ConcreteHacker Industries, Inc. Firm-Fill SCM-250 Sound Control MatOriented Strand Board SheathingGuardian Faces R-13 Fiberglass InsulationYork PB Truss L/360 Open Web Truss @ 24" O.C.RSIC-1 Installed @ 24"x48"Clark Dietrich 087F125-18 Furring Channel @ 24" O.C.National Gypsum Gold Bond Fire-Shield C Gypsum Board
STC 62Test Number F4545.01 IIC 53
©2016 PAC International, LLC. All Rights Reserved. • (866) 774-2100 • Fax (866) 649-2710RSIC® is a registered Trade Mark of PAC International, LLC.
ST
C
IIC
1 HourSee www.UL.com
World Leader in Noise Control
Solutions
53
F4545.01-113-11-R2
ACOUSTICAL PERFORMANCE TEST REPORT
ASTM E 90 AND ASTM E 492
Rendered to
HACKER INDUSTRIES, INC.
Series/Model: FIRM-FILL® Brand Gypsum Concrete and FIRM-FILL® SCM-250
Sound Control Mat - Bare
Specimen Type: Open Web Truss - 457 mm
Overall Size: 3023 mm by 3632 mm
STC 62
IIC
Test Specimen Identification:
Subfloor Topping: 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete
Subfloor Underlayment: 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat
Subfloor: 18.8 mm Oriented Strand Board Sheathing
Insulation: 88.9 mm Guardian Faced R-13 Fiberglass Insulation
Truss: 457.2 mm York PB Truss L/360 Open Web Truss
Ceiling Isolation: 28 mm PAC International RSIC-1 Classic Isolation Clips
Ceiling Isolation: 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel
Ceiling: 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board
Reference should be made to Intertek-ATI Report F4545.01-113-11 for complete test specimen
description. This page alone is not a complete report.
130 Derry Courtaa
York, PA 17406aa
p. 717.764.7700
f. 717.764.4129www.archtest.com · www.intertek.com/building
F4545.01-113-11-R2
Page 1 of 4
Acoustical Performance Test Report
HACKER INDUSTRIES, INC.
1600 Newport Center Drive, Suite 275
Newport Beach, California 92660
Report F4545.01-113-11
Test Date 02/02/16
Report Date 03/03/16
Revision Date 04/29/16
Project Scope
Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted to conduct
airborne sound transmission loss and impact sound transmission tests. The complete test data is
included as attachments to this report. The client provided the test specimen. The specimen was
constructed on the date of testing.
Test Methods
The acoustical tests were conducted in accordance with the following standards. The equipment
listed in the attachments meets the requirements of the following standards.
ASTM E 90-09, Standard Test Method for Laboratory Measurement of Airborne Sound
Transmission Loss of Building Partitions
ASTM E 413-10, Classification for Rating Sound Insulation
ASTM E 492-09, Standard Test Method for Laboratory Measurement of Impact Sound
Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine
ASTM E 989-06 (2012), Classification for Determination of Impact Insulation Class (IIC)
ASTM E 2235-04 (2012) Standard Test Method for Determination of Decay Rates for Use in
Sound Insulation Test Methods
Test Procedure
All testing was conducted in the VT test chambers at Intertek-ATI located in York,
Pennsylvania. The microphones were calibrated before conducting the tests.
The airborne transmission loss test was conducted in accordance with the ASTM E 90 test
method using the single direction method. Two background noise sound pressure level and five
sound absorption measurements were conducted at each of five microphone positions. Four
sound pressure level measurements were made simultaneously in both rooms, at each of five
microphone positions.
130 Derry Courtaa
York, PA 17406aa
p. 717.764.7700
f. 717.764.4129www.archtest.com · www.intertek.com/building
F4545.01-113-11-R2
Page 2 of 4
Test Procedure (Continued)
The impact sound transmission test was conducted in accordance with the ASTM E 492 test
method. Two background noise sound pressure level, two sound pressure level measurements
with the tapping machine operating at each position specified by ASTM E 492, and five sound
absorption measurements were conducted at each of five microphone positions.
The air temperature and relative humidity conditions were monitored and recorded during all
measurements.
Test Conditions
Source Room Receive Room
Average Temperature 16.6°C Average Temperature 15.5°C
Average Relative Humidity 57% Average Relative Humidity 54%
Test Calculations
The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated
in accordance with ASTM E 413 and ASTM E 989, respectively.
Test Specimen Materials and Installation Details
MaterialDimensions
(mm)
Thickness
(mm)Manufacturer and Series Quantity
Average
Weight
Gypsum Concrete3632 by 3023 25.4
Hacker Industries, Inc. FIRM-
FILL® Brand10.98 m² 47.85 kg/m²
Note: The gypsum concrete was allowed to cure for a minimum of 14 days. The gypsum layer had a
closed cell foam perimeter isolation. The product name was specified by client.
Sound Control Mat1219 by 3023 6.4
Hacker Industries, Inc. FIRM-
FILL® SCM-25010.98 m² 0.49 kg/m²
Note: The SCM was installed as per manufacturer's specifications with seams overlapping and taped.
Oriented Strand
Board Sheathing
1219 by 2438 18.8 N/A 10.98 m² 13.82 kg/m²
Note: The OSB was adhered to the trusses with Loctite PL 400 Subfloor adhesive. It was attached
with 9D nails on 203 mm centers along perimeter and 305 mm centers along trusses.
Fiberglass Insulation2962 by 584 88.9 Guardian Faced R-13 10.98 m² 1.33 kg/m²
Note: Installed in the cavity between trusses flush with the OSB. Hanger wire was used to keep
insulation secure on 305mm
Open Web Truss88.9 by 2933.7 457.2 York PB Truss L/360 7 m² 19.05 kg/m²
Note: Installed on 610 centers using JUS414 hanger brackets.
Isolation Clips76.9 by 35.6 28.0 PAC International RSIC-1 Classic 24 clips 0.06 kg/clip
Note: Fastened to joists in a 610 mm by 1220 mm traditional pattern.
F4545.01-113-11-R2
Page 3 of 4
Test Specimen Materials and Installation Details (Continued)
MaterialDimensions
(mm)
Thickness
(mm)Manufacturer and Series Quantity
Average
Weight
Furring/Hat Channel3657.6 by 76.2 22.3 ClarkDietrich 087F125-18 29.1 lin m 0.48 kg/m
Note: Installed into the PAC International RSIC-1 Classic, spaced 610 mm on center.
Gypsum Board1219 by 3023 15.9
National Gypsum Gold Bond®
Fire-Shield C™10.35 m² 10.74 kg/m²
Note: Fastened to furring channels on 305 mm centers with 25.4 mm type S screws. Seams finished
with joint compound. Perimeter sealed with acoustical caulk.
Comments
The total weight of the floor/ceiling assembly was 957.2 kg. Intertek-ATI will store samples of
the test specimen for four years. A drawing of the test specimen is included in the attachments.
Intertek-ATI will service this report for the entire test record retention period. Test records,
such as detailed drawings, datasheets, representative samples of test specimens, or other
pertinent project documentation, will be retained by Intertek-ATI for the entire test record
retention period. The test record retention period ends four years after the test date.
This report does not constitute certification of this product nor an opinion or endorsement by
this laboratory. It is the exclusive property of the client so named herein and relates only to the
specimen tested. This report is intended to help in the client’s quality assurance program, but it
does not represent a continuous or exhaustive evaluation of the specimen tested or of other
products or materials that were not evaluated. The statements and data provided herein do not
constitute approval, disapproval, certification, or acceptance of performance or materials.
This report may not be reproduced, except in full, without the written approval of
Intertek-ATI.
FOR INTERTEK-ATI:
David M. Dacheux Jordan Strybos
Technician II - Acoustical Testing Project Manager - Acoustical Testing
Attachments (6 Pages): This report is complete only when all attachments are included.
* Stated by Client/Manufacturer
N/A - Non Applicable
F4545.01-113-11-R2
Page 4 of 4
Revision Log
Revision Date Page(s) Description
R0 03/03/16 N/A Original Report Issue
R1 03/10/16 Cover page "Bare" added to Series/Model listing
R2 04/29/16 Page 2 Clip spacing installation note corrected
This report produced from controlled document template ATI 00629(d), Revised 02/09/15.
F4545.01-113-11-R2
Attachments
Instrumentation
Instrument Manufacturer Model ATI NumberDate of
Calibration
Data Acquisition Unit National Instruments PXI-1033 63763 06/14 *
Microphone Calibrator Norsonic 1251 Y002919 07/15
Receive Room Microphone Scantek 378B20 63748 05/15
Receive Room Microphone PCB Piezotronics 378B20 63744 05/15
Receive Room Microphone PCB Piezotronics 378B20 63745 05/15
Receive Room Microphone PCB Piezotronics 378B20 63746 05/15
Receive Room Microphone PCB Piezotronics 378B20 63747 05/15
Receive Room Environmental
IndicatorComet T7510
63810
63811
10/15
10/15
Source Room Microphone PCB Piezotronics 378B20 63738 04/15
Source Room Microphone PCB Piezotronics 378B20 63739 04/15
Source Room Microphone PCB Piezotronics 378B20 63740 04/15
Source Room Microphone PCB Piezotronics 378B20 63742 04/15
Source Room Microphone Scantek 378B20 63741 04/15
Source Room Environmental
IndicatorComet T7510 63812 11/15
Tapping Machine Look Line s.r.l. EM50 (TM50) 65351 11/15
* The calibration frequency for this equipment is every two years per the manufacturer's recommendation.
Test Chambers
VT Receive Room Volume 155.77 m³
VT Source Room Volume 190 m³
Page 1 of 6
STC Rating (Sound Transmission Class)
Deficiencies (Sum of Deficiencies)
F4545.01-113-11-R2
AIRBORNE SOUND TRANSMISSION LOSS
ASTM E 90
Test Date 02/02/16
Data File No. F4545.01
Client Hacker Industries, Inc.
Description 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250
Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, 457.2 mm
York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich
087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board
Specimen Area 10.98 m²
Technician David M. Dacheux
FreqBackground
AbsorptionSource Receive Specimen
TL
95% Number
SPL SPL SPL Confidence of
(Hz) (dB) (m²) (dB) (dB) (dB) Limit Deficiencies
50 43.5 26.8 100 66 32 4.60 -
63 43.9 23.0 100 64 35 3.60 -
80 51.8 17.4 109 68 40 4.80 -
100 38.7 12.6 106 67 40 2.10 -
125 39.3 9.6 106 67 41 1.30 5
160 28.2 9.0 108 65 44 1.50 5
200 24.8 10.1 105 58 49 1.20 3
250 27.6 10.6 104 53 53 1.00 2
315 24.1 10.3 106 54 54 0.70 4
400 21.4 8.2 105 50 57 0.50 4
500 23.6 7.7 105 48 60 0.40 2
630 22.3 7.4 106 47 63 0.40 0
800 22.4 7.3 105 45 63 0.20 1
1000 23.6 7.1 105 43 65 0.50 0
1250 23.1 7.2 105 41 67 0.40 0
1600 19.7 7.3 105 39 69 0.30 0
2000 12.1 8.6 104 39 68 0.40 0
2500 8.1 9.5 103 36 69 0.50 0
3150 7.3 10.8 104 33 72 0.40 0
4000 6.5 12.3 105 31 74 0.50 0
5000 6.2 14.9 104 28 76 0.50 -
6300 6.6 19.9 98 18 78 0.80 -
8000 7.5 25.9 97 14 81 0.80 -
10000 7.3 33.7 92 8 81 0.70 -
62
26
Notes: 1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.
2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.
3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied
ATI 00614 Revised 02/09/15 Page 2 of 6
F4545.01-113-11-R2
AIRBORNE SOUND TRANSMISSION LOSS
ASTM E 90
Test Date 02/02/16
Data File No. F4545.01
Client Hacker Industries, Inc.
Description 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250
Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, 457.2 mm
York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich
087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board
Specimen Area 10.98 m²
Technician David M. Dacheux
ATI 00614 Revised 02/09/15 Page 3 of 6
0
10
20
30
40
50
60
70
80
90
100
63
125
250
500
100
0
200
0
400
0
800
0
Sou
nd
Tra
nsm
issi
on
Loss
(d
B)
Frequency (Hz)
Airborne Sound Transmission Loss
Specimen TL
Contour Curve
IIC Rating (Impact Insulation Class)
Deficiencies (Sum of Deficiencies)
F4545.01-113-11-R2
IMPACT SOUND TRANSMISSION
ASTM E 492
Test Date 02/02/16
Data File No. F4545.01
Client Hacker Industries, Inc.
Description 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250
Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, 457.2 mm
York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich
087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board
Specimen Area 10.98 m²
Technician David M. Dacheux
Freq Background SPL AbsorptionNormalized Impact
SPL
95% Number
Confidence of
(Hz) (dB) (m²) (dB) Limit Deficiencies
50 51.3 28.4 71 2.5 -
63 47.7 26.4 64 2.5 -
80 50.7 17.7 62 2.4 -
100 42.2 11.9 60 1.6 1
125 40.8 10.0 56 1.3 0
160 32.4 9.0 59 1.0 0
200 27.5 10.3 58 1.2 0
250 29.6 10.4 57 0.8 0
315 24.6 10.1 59 0.3 0
400 23.3 8.4 58 1.3 0
500 25.0 7.5 58 0.2 1
630 25.5 7.5 59 0.5 3
800 23.3 7.2 58 0.2 3
1000 24.7 7.2 56 0.3 2
1250 25.8 7.1 52 0.0 1
1600 21.1 7.4 51 0.3 3
2000 13.9 8.6 51 0.2 6
2500 9.8 9.6 44 0.5 2
3150 10.2 10.7 36 0.4 0
4000 10.0 12.2 28 0.3 -
5000 8.0 15.1 21 0.4 -
6300 8.6 20.0 14 0.3 -
8000 9.4 26.1 12 0.4 -
10000 8.5 33.3 11 0.7 -
53
22
Note: Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.
ATI 00615 Revised 02/09/15 Page 4 of 6
F4545.01-113-11-R2
IMPACT SOUND TRANSMISSION
ASTM E 492
Test Date 02/02/16
Data File No. F4545.01
Client Hacker Industries, Inc.
Description 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250
Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, 457.2 mm
York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich
087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board
Specimen Area 10.98 m²
Technician David M. Dacheux
ATI 00615 Revised 02/09/15 Page 5 of 6
10
20
30
40
50
60
70
80
90
100
1100
10
20
30
40
50
60
70
80
90
100
63
125
250
500
100
0
200
0
400
0
800
0
Imp
act
In
sula
tion
Cla
ss (
IIC
)
So
un
d P
ress
ure
Lev
el (
dB
)
Frequency (Hz)
Impact Sound Transmission
Normalized Impact SPL
Contour Curve
Drawing
F4545.01-113-11-R2
1-Subfloor Topping
2-Subfloor Underlayment
3-Subfloor
4-Insulation
5-Truss
6-Ceiling Isolation
7-Ceiling
Page 6 of 6