first revision no. 30-nfpa 68-2016 [ global input ]€¦ · first revision no. 30-nfpa 68-2016 [...

64
First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout the standard, unless specified as "bar-abs" or "psia". This does not apply to Annex G or units for change in pressure (P). Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Feb 10 10:53:57 EST 2016 Committee Statement Committee Statement: Section 1.8 specifies that all pressures are gauge pressure unless otherwise specified. However, this is not apparent to some users. This revision will aid in the application of the standard. Response Message: National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 50 3/22/2016 10:02 AM Page 1 of 64

Upload: others

Post on 06-Dec-2019

17 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 30-NFPA 68-2016 [ Global Input ]

Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout the standard, unless specified as"bar-abs" or "psia".

This does not apply to Annex G or units for change in pressure (∆P).

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 10 10:53:57 EST 2016

Committee Statement

CommitteeStatement:

Section 1.8 specifies that all pressures are gauge pressure unless otherwise specified.However, this is not apparent to some users. This revision will aid in the application of thestandard.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 50 3/22/2016 10:02 AM

Page 1 of 64

Page 2: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 26-NFPA 68-2016 [ Section No. 1.6 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 50 3/22/2016 10:02 AM

Page 2 of 64

Page 3: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

1.6 Conversion Factors.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 50 3/22/2016 10:02 AM

Page 3 of 64

Page 4: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

The conversion factors in Table 1.6 are useful for understanding the data presented in this standard.

Table 1.6 Conversion Factors

Parameter Unit Equivalent

Length 1 m3.28 ft

39.4 in.

1 in. 25.4 mm

1 ft 305 mm

1 μm 1.00 × 10−6 m

Area 1 m2 10.8 ft2

1 in.2 6.45 cm2

Volume 1 L 61.0 in.3

1 ft3 7.48 U.S. gal

1 m3 35.3 ft3

264 U.S. gal

1 U.S. gal 3.78 L

231 in.3

0.134 ft3

Pressure 1 atm 760 mm Hg

101 kPa

14.7 psi

1.01 bar

1 psi 6.89 kPa

1 N/m2 1.00 Pa

1 bar 100 kPa

14.5 psi

0.987 atm

1 kg/cm2 14.2 psi

1 kg/m2 0.205 lb/ft2 (psf)

Energy 1 J 1.00 W-s

1 Btu 1055 J

1 J 0.738 ft-lb

KStK G and 1 bar-m/s 47.6 psi-ft/s

conversion 1 psi-ft/s 0.021 bar-m/s

Concentration 1 oz avoirdupois/ft3 1000 g/m3

Key to abbreviations:

atm = atmosphere

Btu = British thermal unit

cm = centimeter

ft = foot

g = gram

gal = gallon

Hg = mercury

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 50 3/22/2016 10:02 AM

Page 4 of 64

Page 5: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

in. = inch

J = joule

kg = kilogram

kPa = kilopascal

L = liter

lb = pound

m = meter

mm = millimeter

N = newton

oz = ounce

Pa = pascal

psf = pounds per square foot

psi = pounds per square inch

s = second

W = watt

μm = micron (micrometer)

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 09 17:12:44 EST 2016

Committee Statement

Committee Statement: As of the 2013 edition, K_G is no longer used in this standard.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 50 3/22/2016 10:02 AM

Page 5 of 64

Page 6: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 25-NFPA 68-2016 [ Section No. 1.7 ]

1.7 Symbols.

The following symbols are defined for the purpose of this standard:

A = area (m2, ft2, or in.2)

AS = internal surface area of enclosure (m2 or ft2)

Av = vent area (m2 or ft2)

C = constant used in venting equations as defined in each specific use

dP/dt = rate of pressure rise (bar/s or psi/s)

Fr = reaction force constant (lb)

K G = deflagration index for gases (bar-m/s)

KSt = deflagration index for dusts (bar-m/s)

Ln = linear dimension of enclosure [m or ft (n = 1, 2, 3)]

Lx = distance between adjacent vents

L/D = length to diameter ratio (dimensionless)

LFL = lower flammable limit (percent by volume for gases, weight per volume for dusts and mists)

MEC = minimum explosible concentration (g/m3 or oz/ft3)

MIE = minimum ignition energy (mJ)

p = perimeter of duct cross-section (m or ft)

P = pressure (bar bar-g or psi psig )

Pes = enclosure strength (bar bar-g or psi psig )

Pex = explosion pressure (bar bar-g or psi psig )

Pmax = maximum pressure developed in an unvented vessel (bar bar-g or psi psig )

P0 = initial pressure (bar bar-g or psi psig )

Pred =reduced pressure [i.e., maximum pressure actually developed during a vented deflagration(bar bar-g or psi psig )]

Pstat = static activation pressure (bar bar-g or psi psig )

dP = pressure differential (bar or psi)

Su = fundamental burning velocity (cm/s)

Sf = flame speed (cm/s)

tf = duration of pressure pulse (s)

UFL = upper flammable limit (percent by volume)

V = volume (m3 or ft3)

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 50 3/22/2016 10:02 AM

Page 6 of 64

Page 7: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Zip:

Submittal Date: Tue Feb 09 17:11:25 EST 2016

Committee Statement

Committee Statement: As of the 2013 edition, K_G is no longer used in this standard.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 50 3/22/2016 10:02 AM

Page 7 of 64

Page 8: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 4-NFPA 68-2016 [ Chapter 2 ]

Chapter 2 Referenced Publications

2.1 General.

The documents or portions thereof listed in this chapter are referenced within this standard and shall beconsidered part of the requirements of this document.

2.2 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 69, Standard on Explosion Prevention Systems, 2008 2014 edition.

NFPA 70®, National Electrical Code®, 2011 2017 edition.

NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing,and Handling of Combustible Particulate Solids, 2013 2017 edition.

NFPA 704, Standard System for the Identification of the Hazards of Materials for Emergency Response,2012 2017 edition.

2.3 Other Publications.

2.3.1 API Publications.

American Petroleum Institute, 1220 L Street, NW, Washington, DC 20005-4070.

API STD 650, Welded Steel Tanks for Oil Storage, 2007 2013, Errata, 2014 .

2.3.2 ASME Publications.

American Society of Mechanical Engineers ASME International , Two Park Avenue, New York, NY10016-5990.

ASME Boiler and Pressure Vessel Code, 2010 2015 .

2.3.3 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM E1226, Standard Test Method for Explosibility of Dust Clouds,2010 2012A .

2.3.4 ISO Publications.

International Organization for Standardization, 1, rue de Varembè, Case postale 56, CH-1211 Geneve20 ISO Central Secretariat, BIBC II, 8, Chemin de Blandonnet, CP 401, 1214 Vernier, Geneva ,Switzerland.

ISO 6184/ - 1, Explosion Protection Systems — Part 1: Determination of Explosion Indices of CombustibleDust in Air, 1985.

2.3.5 Other Publications.

Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003.

2.4 References for Extracts in Mandatory Sections.

NFPA 53, Recommended Practice on Materials, Equipment, and Systems Used in Oxygen-EnrichedAtmospheres, 2011 2016 edition.

NFPA 484, Standard for Combustible Metals, 2012 edition.

NFPA 652, Standard on the Fundamentals of Combustible Dust, 2016 edition.

NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing,and Handling of Combustible Particulate Solids, 2013 2017 edition.

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 50 3/22/2016 10:02 AM

Page 8 of 64

Page 9: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Feb 01 08:27:03 EST 2016

Committee Statement

CommitteeStatement:

Referenced current standards development organization names, addresses, standardnames, numbers, and editions.

ResponseMessage:

Public Input No. 1-NFPA 68-2015 [Chapter 2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 50 3/22/2016 10:02 AM

Page 9 of 64

Page 10: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 27-NFPA 68-2016 [ Section No. 3.3.5 ]

3.3.5 Deflagration Index.

Value indicated by the use of the variable, K. (See 3.3.19 , K G , and 3.3.19, KSt.)

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 09 17:14:43 EST 2016

Committee Statement

Committee Statement: As of the 2013 edition, K_G is no longer used in this standard.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 50 3/22/2016 10:02 AM

Page 10 of 64

Page 11: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 28-NFPA 68-2016 [ Section No. 3.3.19 ]

3.3.19 K G .

The deflagration index of a gas cloud.

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 09 17:15:30 EST 2016

Committee Statement

Committee Statement: As of the 2013 edition, K_G is no longer used in this standard. A.3.3.19 is also deleted.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 50 3/22/2016 10:02 AM

Page 11 of 64

Page 12: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 2-NFPA 68-2016 [ Section No. 3.3.30 ]

3.3.29 Replacement-in-Kind.

A replacement that satisfies the design specifications. [484 , 2012 652, 2016 ]

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jan 29 16:43:07 EST 2016

Committee Statement

CommitteeStatement:

Updating extract reference. NFPA 484 was revised in 2015 to extract the definition forReplacement-in-Kind from NFPA 652.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 50 3/22/2016 10:02 AM

Page 12 of 64

Page 13: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 17-NFPA 68-2016 [ New Section after 6.1.2.2 ]

6.1.2.3*

For aluminum, hafnium, magnesium, tantalum, and titanium, unless K St and P max are determined

in nominal 1 m 3 or larger calibrated test vessels, the K St value shall be multiplied by a factor of 2 for

application of the design methods.

Supplemental Information

File Name Description

NFPA_68_FR_17_New_annex.doc

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 02 14:40:16 EST 2016

Committee Statement

CommitteeStatement:

Additional research and testing demonstrated the degree of change in KSt between 20 L and 1 m3test results for a number of metal dusts and the associated change in experimental results duringvented deflagration tests. Iron, zinc, silicon and aluminum dusts were recently compared in bothstandard test vessels along with a control cornstarch. While the cornstarch KSt remained essentiallyconstant, as intended, iron and zinc exhibited 30-40% increase in KSt, silicon a 60% decrease, andaluminum a 100% increase when comparing 1 m3 results with 20 L results.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 50 3/22/2016 10:02 AM

Page 13 of 64

Page 14: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

A.6.1.2.3 Recent testing has shown that certain metal dusts exhibit KSt values that are significantly larger in 1 m3 tests than in 20 L tests. There is evidence of nonconservative vent area predictions for aluminum, when based on 20 L tests, while silicon vent area is overpredicted. It is currently hypothesized that flame temperature is a significant related parameter and it is therefore considered appropriate to require either testing in the larger 1 m3 vessel or application of a safety factor to 20 L results for aluminum, hafnium, magnesium, tantalum, and titanium. These metals all have maximum adiabatic flame temperatures higher than 3300°C. Until more information is available, KSt results for aluminum, hafnium, magnesium, tantalum, and titanium in smaller test vessels are adjusted to provide additional confidence in application of the design methods. It is possible that the adjusted 20 L value will exceed the actual KSt when measured in the 1 m3 vessel and, where available, the measured KSt should be used. If the adjusted KSt value exceeds 800 bar-m/s, testing in a 1 m3 vessel is recommended because this exceeds the limitations of the dust venting equations. (See Table A.6.1.2.3.) Table A.6.1.2.3 Determining Kst and Pmax for Aluminum, Hafnium, Magnesium, Tantalum, and Titanium Multiply KSt from 20 L sphere tests by a factor of 2 AND use Pmax from 20 L sphere tests OR Use KSt/Pmax from 1 m3 vessel tests  

Page 14 of 64

Page 15: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 29-NFPA 68-2016 [ Section No. 6.1.3 ]

6.1.3

The most accurate value of K G shall be determined directly by test, as outlined in Annex C For gases,

P max shall be determined in approximately spherical calibrated test vessels of at least 5 L (1.3 gal)

capacity with initially quiescent mixture with low energy ignition source (i.e., less than 100 J) .

6.1.3.1

If testing cannot be done to determine K G for a particular gas, K G shall be permitted to be

approximated by ratioing from the K G of propane (100 bar-m/s) on the basis of the corresponding

fundamental burning velocity (see Annex D ) of propane (46 cm/s) and the fundamental burningvelocity of the gas in question.

6.1.3.2

For gases, P max shall be determined in approximately spherical calibrated test vessels of at least 5 L

(1.3 gal) capacity with initially quiescent mixture with low energy ignition source (less than 100 J).

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 09 17:17:44 EST 2016

Committee Statement

Committee Statement: As of the 2013 edition, K_G is no longer used in this standard.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 50 3/22/2016 10:02 AM

Page 15 of 64

Page 16: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 20-NFPA 68-2016 [ Section No. 7.2.6.1 ]

7.2.6.1

The baseline value, λ0, of λ shall be calculated from Equations 7.2.6.1a through 7.2.6.1f:

( [ 7.2.6.1a) ]

( [ 7.2.6.1b) ]

( [ 7.2.6.1c) ]

( [ 7.2.6.1d) ]

( [ 7.2.6.1e) ]

( [ 7.2.6.1f) ]

where:

ρu = mass density of unburned gas-air mixture (kg/m3) = 1.2 for flammable gases with stoichiometricconcentrations less than 5 vol%, and an initial temperature of 20°C

Su = fundamental burning velocity of gas-air mixture (m/s)

Dhe = the enclosure hydraulic equivalent diameter as determined in Chapter 6 (m)

µu = the unburned gas-air mixture dynamic velocity = 1.8 × 10-5 kg/m-s for gas concentrations lessthan 5 vol% at ambient temperatures

β 1 = 1.23

β 2 = 0.0487 m/s 2.37 × 10 −3 m/s

Dv = the vent diameter as determined through iterative calculation (m)

u v = maximum velocity through vent (m/s)

Pred = the maximum pressure developed in a vented enclosure during a vented deflagration (bar-g)

au = the unburned gas-air mixture sound speed = 343 m/s for gas concentrations less than 5 vol% atambient temperatures

θ = 0.39

Supplemental Information

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 50 3/22/2016 10:02 AM

Page 16 of 64

Page 17: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

File Name Description

FR_20_replace_equation_7.2.6.1_e_.docx Equation to replace 7.2.6.1e. For staff use.

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 02 15:32:28 EST 2016

Committee Statement

CommitteeStatement:

Application of the gas equation for Phi_2 for low burning velocity materials was found toinappropriately result in unrealistic results. The correlation 7.2.6.1c was adjusted consistent withthe original range of test data to produce a more appropriately bounded vent area as Suapproaches zero.

The original equation 7.2.6.1e was valid for venting of air at near ambient conditions but did notinclude the possibility of higher initial temperatures, and thus the velocity could have beencalculated as greater than the speed of sound.

This revision also adds a definition for uv.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 50 3/22/2016 10:02 AM

Page 17 of 64

Page 18: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 16-NFPA 68-2016 [ Sections 7.2.6.3, 7.2.6.4 ]

7.2.6.3

When Aobs < 0.4 2 AS, λ1 shall be equal to λ0 as determined in 7.2.6.1.

7.2.6.4

When Aobs > 0.4 2 AS, λ1 shall be determined as follows:

( [ 7.2.6.4) ]

Supplemental Information

File Name Description

FR_16_replace_equation_7.2.6.4.docx For staff use.

FR_16_obstructed_enclosure_gas_venting_example.jpgThe committee is working on an example of applying these equations to this arrangement.

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 02 12:00:33 EST 2016

Committee Statement

CommitteeStatement:

This revision is based on further review of large scale test data with obstructed enclosures. Thethreshold criteria for accounting for obstructions was revised and the equation to represent theeffect of those obstructions was revised to be more consistent with test data.

The committee is working on an example of applying these equations to the arrangement in theattached figure.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 50 3/22/2016 10:02 AM

Page 18 of 64

Page 19: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Page 19 of 64

Page 20: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 22-NFPA 68-2016 [ Section No. 7.3.3 ]

7.3.3

For M > MT, the required vent area, Av2, shall be calculated as follows:

( [ 7.3.3) ]

where:

M = mass of vent panel (kg/m2)

Av1 = vent area determined in 7.2.7 (m2)

FSH = vent closure shape factor as defined in Chapter 8 1 for translating panels or 1.1 for hinged panels

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 02 16:18:55 EST 2016

Committee Statement

CommitteeStatement:

This revision eliminates confusion between F_SH used in Chapters 7 and 8 and shapefactor,c_s, used in Annex G.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 50 3/22/2016 10:02 AM

Page 20 of 64

Page 21: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 31-NFPA 68-2016 [ Sections 8.1, 8.2, 8.3, 8.4 ]

8.1 Introduction.

8.1.1

This chapter shall apply to all enclosures with L/Dless than or equal tosix ≤ 6 handling combustible dustsor hybrid mixtures.

8.1.1.1

This chapter shall be used with the information contained in the rest of this standard.

8.1.1.2

In particular, Chapters 6, 7, 10, and 11 shall be reviewed before the information in this chapter isapplied.

8.1.1.3

This chapter provides a number of equations and calculation procedures that shall be used to treat avariety of vent sizing applications.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 50 3/22/2016 10:02 AM

Page 21 of 64

Page 22: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

8.1.1.4

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 50 3/22/2016 10:02 AM

Page 33 of 64

Page 23: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

The general flowchart given in Figure 8.1.1.4 shall be used to select applicable vent sizing methods.

Figure 8.1.1.4 Dust Explosion Vent Sizing Calculation Flowchart.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 50 3/22/2016 10:02 AM

Page 34 of 64

Page 24: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

8.1.2*

Where actual material is not available for test, vent sizing shall be permitted to be based on KSt values for

similar composition materials of particle size no greater than the specified particle size range per thechosen standard: ASTM E1226, Standard Test Method for Explosibility of Dust Clouds, or ISO 6184-1,Explosion Protection Systems — Part 1: Determination of Explosion Indices of Combustible Dust in Air.

8.1.2.1

Where the actual material intended to be produced is smaller than the size determined by 8.1.2, testsshall be performed near the intended particle size.

8.1.2.2

When the actual material is available, the KSt shall be verified by test.

8.2 Venting by Means of Low-Inertia Vent Closures.

Global FR-30

8.2.1 Minimum Vent Area Requirement.

8.2.1.1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 50 3/22/2016 10:02 AM

Page 35 of 64

Page 25: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Equation 8.2.2 8.2.1.1 shall be used to calculate the minimum necessary vent area, Av0:

[8.2.1.1]

where:

A v 0 = vent area (m2)

Pstat = nominal static burst pressure of the vent (bar-g)

KSt = deflagration index (bar-m/s)

V = enclosure volume (m3)

Pmax = maximum pressure of a deflagration (bar-g)

Pred = reduced pressure after deflagration venting (bar-g)

[115]

8.2.3.1

Equation 8.2.2 shall apply to initial pressures before ignition of 1 bar-abs ± 0.2 bar.

8.2.1.2

The following limitations shall be applicable to Equation 8.2.2 1.1:

) 5 bar bar-g ≤ Pmax ≤ 12 bar bar-g

) 10 bar-m/s ≤ KSt ≤ 800 bar-m/s

) 0.1 m3 ≤ V ≤ 10,000 m3

) Pstat ≤ 0.75 bar bar-g

8.2.2

The L/D of the enclosure shall be determined according to Section 6.4 .

8.2.2 Effects of Elevated L/D.

8.2.2.1

The L/D of the enclosure shall be determined according to Section 6.4.

8.2.2.2

When L/Dis less than or equal to ≤ 2, Av1 shall be set equal to Av0.

8.2.2.3

For L/D values greater than 2 and less than or equal to 6 For 2 < L/D ≤ 6 , the required vent area, Av1,

shall be calculated as follows (where exp (A) = eA, e is the base of the natural logarithm [114]):

( [ 8.2.2. 3) ]

where:

A v0 = vent area as calculated by Equation 8.2.1.1

L/D = length-to-diameter ratio

P red = reduced pressure after deflagration venting (bar-g)

8.2.2.4*

It shall be permitted to extend Equation 8.2.2. 3 to values of L/D of 8 for top-fed bins, hoppers, and silos,provided the calculated required vent area, after application of all correction factors, does not exceed theenclosure cross-sectional area.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 50 3/22/2016 10:02 AM

Page 36 of 64

Page 26: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

8.2.2.5

For situations where vents can be distributed along the major axis of the enclosure, Equation 8.2.2 1.1and Equation 8.2.2. 3 shall be permitted to be applied where L is the spacing between vents along themajor axis.

8.2.3

For L/D values greater than 2 and less than or equal to 6, the required vent area, A v 1 , shall be

calculated as follows (where exp( A ) = e A , e is the base of the natural logarithm [114]):

(8.2.3)

where:

A v0 = vent area as calculated by Equation 8.2.1.1

L/D = length-to-diameter ratio

P red = reduced pressure after deflagration venting (bar-g)

8.2.3.1*

It shall be permitted to extend Equation 8.2.3 to values of L/D of 8 for top-fed bins, hoppers, and silos,provided the calculated required vent area, after application of all correction factors, does not exceedthe enclosure cross-sectional area.

8.2.3 Effects of Initially Elevated or Subatmospheric Pressure.

8.2.3.1

When the initial pressure is between −0.2 bar bar-g and 0.2 bar bar-g , Avep shall be set equal to Av1.

8.2.3.2*

When enclosure pressure is initially greater than > 0.2 bar bar-g (20 kPa) or less than < −0.2 bar bar-g(−20 kPa), Avep/Av0 shall be determined from the following equation:

(8.4.1) [8.2.3.2

where:

Avep = vent area (m2)

A v 1 = vent area as calculated by 8.2.2.2 or Equation 8.2.2.3

Pstat = static burst pressure of the vent (bar bar-g )

Pinitial = enclosure pressure at moment of ignition (bar bar-g )

Peffective = 1/3Pinitial (bar bar-g )

Πeffective = (Pred − Peffective)/(PEmax − Peffective)

Pred = reduced pressure

PEmax = [(Pmax + 1) · (Pinitial + 1)/(1 bar-abs) − 1] maximum pressure of the unvented deflagration

at pressure (bar bar-g )

Pmax = maximum pressure of an unvented deflagration initially at atmospheric pressure (bar bar-g )

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 50 3/22/2016 10:02 AM

Page 37 of 64

Page 27: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

8.2.3.3*

When enclosure pressure is initially less than < −0.2 bar bar-g , the vent area correction in Equation8.4.1 8.2.3.2 shall be evaluated over the range between operating pressure and atmospheric pressureand the largest vent area correction applied.

8.2.3.4

When enclosure pressure is initially less than < −0.2 bar bar-g , it shall be permitted to use a value of 1.1as the vent area correction for this section.

8.2.3.5

When enclosure pressure is initially greater than > 0.2 bar bar-g , deflagration vents shall be permittedonly when the following conditions are met:

(1) Vent duct length L/D ≤ 1

(2) Panel density M ≤ MT and ≤ 40 kg/m2

(3) vaxial and vtan < 20 m/s

(4) No allowance for partial volume

(5) Equation 8.4.1 8.2.3.2 used to calculate the necessary vent area adjustment

8.2.4 Effects of Additional Turbulence.

8.2.4.1*

For this application, average air axial velocity shall be calculated according to the following equation:

( [ 8.2.4.1 5.2) ]

where:

v = average axial gas velocity (m/s)

Q = volumetric air flow rate (m3/s)

A = average cross-sectional area of the flow path (m2) [118, 119]

8.2.4.2*

If a circumferential (i.e., tangential) air velocity is in the equipment, vtan shall be given by 0.5 vtan_max,

where vtan_max is the maximum tangential air velocity in the equipment.

8.2.4.3

Values of Q, vaxial, vtan_max, and vtan shall be measured or calculated by engineers familiar with the

equipment design and operation.

8.2.4.4

The measurements or calculations shall be documented and made available to vent designers and theauthority having jurisdiction.

8.2.4.5

When the maximum values derived for vaxial and vtan are less than 20 m/s, Av2 shall be set equal to

Avep.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 50 3/22/2016 10:02 AM

Page 38 of 64

Page 28: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

8.2.4.6*

When either vaxial or vtan is larger than 20 m/s, Av2 shall be determined from the following equation

where max (A, B) = maximum value of either A or B [118, 119]:

( [ 8.2.4.6 5.7) ]

where:

v axial = axial air velocity (m/s)

v tan = tangential air velocity (m/s)

A vep = vent area calculated by 8.2.3.1 or Equation 8.2.3.2

8.2.4.7*

Vent areas for buildings in which there is a dust explosion hazard shall be determined from Equation8.2.5.8 4.7 [118, 119]:

( [ 8.2.4.7 5.8) ]

where:

A vep = vent area calculated by 8.2.3.1 or Equation 8.2.3.2

8.2.4.8

The required vent areas for these buildings shall be permitted to be reduced through use of the partialvolume Equation 8.3 4 .1.

8.2.4

Three different general equations (Equations 8.2.3, 8.2.5.7, and 8.2.5.8) shall be applied to thedetermination of dust deflagration minimum required vent areas.

8.2.4.1

Equation 8.2.3, which produces the smallest required vent areas, shall apply to dust handling andstorage equipment within which the average air axial velocity, v axial , and the tangential velocity,

v tan , are both less than 20 m/s during all operating conditions.

8.3* Effects of Panel Inertia.

8.3.1

When the mass of the vent panel is less than or equal to ≤ 40 kg/m2, Equation 8.2.6. 3. 2 shall be used todetermine whether an incremental increase in vent area is needed and the requirements of 8.3.4 shall beused to determine the value of that increase.

Global FR-30

8.3.2

The vent area shall be adjusted for vent mass where the vent mass exceeds MT as calculated in

Equation 8.2.6. 3.2:

( [8.2.6. 3.2) ]

where:

MT = threshold mass (kg/m2)

Pred = reduced pressure after deflagration venting (bar bar-g)

n = number of panels

V = volume (m3)

K St = deflagration index (bar-m/s)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 50 3/22/2016 10:02 AM

Page 39 of 64

Page 29: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

8.3.3

Where Mis greater than > 40 kg/m2, it shall be permitted to use the procedure provided in Annex G.

Global FR-30

8.3.4

For M > MT , the required vent area A v3, shall be calculated as follows:

( [8.3.4 2.7) ]

where:

FSH = 1 for translating panels or 1.1 for hinged panels

M = mass of vent panel (kg/m2)

K St = deflagration index (bar-m/s)

n = number of panels

V = volume (m 2 )

P red = Reduced pressure after deflagration venting (bar-g)

A v 2 = vent area calculated by 8.2.5.6, Equation 8.2.5.7 4.6, or Equation 8.2.5.8 4.7, as applicable

8.3.5

If KSt < 75 bar-m/s, KSt = 75 shall be used in Equation 8.2.7 3.4 .

8.3.6

Where M ≤ MT, Av3 shall be set equal to Av2.

8.4* Effects of Partial Volume.

8.4.1

When the volume fill fraction, Xr, can be determined for a worst-case explosion scenario, the minimum

required vent area shall be permitted to be calculated from the following equation:

( [ 8.3 4 .1) ]

where:

A v4 = vent area for partial volume deflagration

A v3 = vent area for full volume deflagration as determined from Equation 8.2.7 3.4 or from 8.3.6

Xr = fill fraction > Π

Π = Pred/Pmax

8.4.1.1*

If Xr ≤ Π, deflagration venting shall not be required.

8.4.1.2

Where partial volume is not applied, Av4 shall be set equal to Av3.

8.4.2* Process Equipment Partial Volumes.

Process equipment involving nonsolvent drying shall be permitted to use partial volume venting inaccordance with Equation 8.3 4 .1.

8.4.2.1

In applications involving dryers with recirculation of dry product, the fill fraction shall be taken as 1.0.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 50 3/22/2016 10:02 AM

Page 40 of 64

Page 30: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

8.4.2.2

Furthermore, if If the solvent is flammable, hybrid deflagration KSt values shall be determined.

8.4.2.3

In applications such as a spray dryer or fluidized bed dryer, the specific fill fraction to be used for ventdesign shall be based on measurements with representative equipment and process materials.

8.4.2.4

In applications involving spray dryers where a partial volume venting is calculated in accordance withEquation 8.3 4 .1, the vent shall be mounted within the chosen partial volume zone of the dryer thatcontains the driest fraction of material.

8.4.2.5

In these applications, the determination of Xr shall be documented and submitted to the authority having

jurisdiction for review and concurrence.

8.4.3 Building Partial Volumes.

(See Annex I .)

8.4.3.1

This subsection shall apply to large process buildings in which a dust explosion hazard is associated withcombustible material deposits on the floor and other surfaces, and with the material contained in processequipment.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 50 3/22/2016 10:02 AM

Page 41 of 64

Page 31: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

8.4.3.2

The minimum required deflagration vent area for the building dust explosion hazard shall be based eitheron the full building volume or on a partial volume determined as follows:

(1) Collect at least three representative samples of the floor dust from either the actual building or afacility with similar process equipment and materials. The samples shall be obtained from measured

floor areas, Afs, that are each 0.37 m2 (4 ft2) or larger.

(2)Weigh each sample and calculate the average mass, (grams), of the floor samples.

(3) Collect at least two representative samples from measured sample areas, Ass, on other surfaces

with dust deposits. These surfaces on any plane could include beams, shelves, and externalsurfaces of process equipment and structures. Calculate the total area, Asur, of these surfaces with

dust deposits.

(4)Weigh each sample and calculate the average mass, (grams), of the surface samples.

(5) Determine the total mass, Me, of combustible dust that could be released from the process

equipment in the building.

(6) Test the dust samples per ASTM E1226, Standard Test Method for Explosibility of Dust Clouds, todetermine Pmax, KSt, and the worst-case concentration, cw, corresponding to the largest value of

KSt.

(7) Using the highest values of Pmax and KSt, the building volume, V, and Π = Pred/Pmax, use

Equation 8.2.7 3.5 or 8.3.6 to calculate the vent area, Av3, needed if the full building volume were

filled with combustible dust.

(8) Calculate the worst-case building partial volume fraction, Xr, in accordance with 8.4.3.3.

(9) If the calculated Xr > 1, the minimum required vent area is equal to Av3 .

(a) If Xr ≤ Π, no deflagration venting is needed.

(b) If 1 > Xr > Π, the minimum required vent area, Av4, is calculated from Equation 8.3 4 .1 as

follows:

( [ 8.3.4 4.3 .2)

where:

A v 4 = vent area for partial volume deflagration

A v 3 = vent area for full volume deflagration as determined from Equation 8.3.4 or from 8.3.6

X r = fill fraction > Π

Π = P red / P max

8.4.3.3

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 50 3/22/2016 10:02 AM

Page 42 of 64

Page 32: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

The worst-case building partial volume fraction, Xr, shall be calculated from the following equation:

( [ 8.3.4 4.3 .3)

where:

Xr = worst-case building partial fraction

= average mass of floor samples (g)

Af-dusty = total area of floor with dust deposits (m2)

ηDfloor = entrainment factor for floor accumulations

Afs = measured floor areas (m2)

V = building volume (m3)

cw = worst-case dust concentration (g/m3)

= average mass of surface samples (g)

Asur = total area of surfaces with dust deposits (m3)

ηDsur = entrainment factor for surface accumulations

Ass = measured sample areas of surfaces with dust deposits (m2)

Me = total mass of combustible dust that could be released from the process equipment in thebuilding (g)

8.4.3.3.1

If a measured value of cw is available, the lowest value of cw for the various samples shall be used in

Equation 8.3.4 4.3 .3.

8.4.3.3.2

If a measured value of cw is not available, a value of 200 g/m3 shall be permitted to be used in Equation

8.3.4 4.3 .3.

8.4.3.3.3*

If measured values of and are not available, and if the facility is to bemaintained with dust layer thickness in accordance with NFPA 654, Standard for the Prevention of Fireand Dust Explosions from the Manufacturing, Processing, and Handling of Combustible ParticulateSolids , an approximate value for these ratios shall be permitted to be used, based on a dust layer bulk

density of 1200 kg/m3 and a layer thickness of 0.8 mm (1⁄32 in.) over the entire floor area and othersurfaces defined in 8.4.3.3.4.

8.4.3.3.4

The total mass of dust that could be released from process equipment in the building/room Me, shall be

determined as follows:

(1) Evaluate equipment with exposed dust accumulations, such as but not limited to screeners, open-topconveyors or conveyor belts, open packaging or shipping containers, and enclosureless dustcollectors.

(2) Evaluate anticipated episodic spills from equipment in light of current housekeeping procedures andpractices.

(3) Do not include material in closed packaging or shipping containers, material in enclosed silos orstorage bins, or in otherwise explosion-protected equipment.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 50 3/22/2016 10:02 AM

Page 43 of 64

Page 33: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

8.4.3.3.5

The entrainment factor, ηD for each representative area shall be determined by one of the following

methods:

(1) Assume an entrainment factor of 1.

(2) Calculate the entrainment factor as follows:

(a) Determine the average particle density, ρp for each sampled dust layer.

(b) Determine the entrainment threshold velocity using the following equation:

[8.3.4.3.5(2)(b

where:

Ut = threshold velocity (m/s)

ρp = particle density (kg/m3)

(c) Assume a maximum free-stream velocity, U, of 50 m/s or establish a different free-streamvelocity calculated from a maximum credible initiating event.

(d) Determine a maximum entrainment rate using the following equation:

[8.3.4.3.5(2)(d

where:

m" = entrained mass flux (kg/m2-s)

ρ = gas density (kg/m3)

U = free-stream velocity (m/s) > Ut

Ut = threshold velocity (m/s)

(e) Determine initiating event time, t, by dividing the building or enclosure building’s or enclosure’slongest dimension by 1⁄2 the maximum free-stream velocity.

(f) Using the appropriate surface area, A, determine the maximum mass, Mmax, from the

presumed initiating event using the following equation:

[8.3.4.3.5(2)(f

where:

m" = entrained mass flux (kg/m 2 -s)

A = surface area (m 2 )

t = initiating event time (s)

(g) Determine the entrainment factor using the following equation:

[8.3.4.3.5(2)(g

where:

M = average mass of the sample (g)

Supplemental Information

File Name Description

FR_31_Chapter_8_Reorganization.docx

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 50 3/22/2016 10:02 AM

Page 44 of 64

Page 34: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 10 14:23:47 EST 2016

Committee Statement

CommitteeStatement:

Though Figure 8.1.1.4 is intended to guide the user through the vent sizing process, the text andorder of equations make it quite difficult to navigate the actual calculation procedure. By organizingthe sections by order of intended execution, the user will be able to follow the flow of section 8.2without needing to jump through the chapter.

ResponseMessage:

Public Input No. 7-NFPA 68-2015 [Chapter 8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 50 3/22/2016 10:02 AM

Page 45 of 64

Page 35: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Draft copy for NFPA 68 Committee work only

Chapter 8 Venting of Deflagrations of Dusts and Hybrid Mixtures

8.1 Introduction.

8.1.1

This chapter shall apply to all enclosures with L/D less than or equal to six handling combustible

dusts or hybrid mixtures.

8.1.1.1

This chapter shall be used with the information contained in the rest of this standard.

8.1.1.2

In particular, Chapters 6, 7, 10, and 11 shall be reviewed before the information in this chapter is

applied.

8.1.1.3

This chapter provides a number of equations and calculation procedures that shall be used to treat a

variety of vent sizing applications.

8.1.1.4

The general flowchart given in Figure 8.1.1.4 shall be used to select applicable vent sizing methods.

Figure 8.1.1.4 Dust Explosion Vent Sizing Calculation Flowchart. Commented [ML1]: This will need to be renumbered based on new section numbers

Page 36: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Draft copy for NFPA 68 Committee work only

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

Page 37: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Draft copy for NFPA 68 Committee work only

8.1.2*

Where actual material is not available for test, vent sizing shall be permitted to be based on KSt

values for similar composition materials of particle size no greater than the specified particle size

range per the chosen standard: ASTM E 1226, Standard Test Method for Explosibility of Dust

Clouds, or ISO 6184-1, Explosion Protection Systems — Part 1: Determination of Explosion Indices

of Combustible Dust in Air.

8.1.2.1

Where the actual material intended to be produced is smaller than the size determined by 8.1.2,

tests shall be performed near the intended particle size.

8.1.2.2

When the actual material is available, the KSt shall be verified by test.

8.2 Venting by Means of Low-Inertia Vent Closures.

8.2.1

The L/D of the enclosure shall be determined according to Section 6.4.

8.2.1 Minimum Vent Area Requirement

8.2.1.12

Equation 8.2.2 1.1 shall be used to calculate the minimum necessary vent area, Av0:

(8.2.2)

where:

Av0 = vent area (m2)

Pstat = nominal static burst pressure of the vent (bar)

KSt = deflagration index (bar-m/s)

V = enclosure volume (m3)

Pmax = maximum pressure of a deflagration (bar-g)

Pred = reduced pressure after deflagration venting (bar) [115]

8.2.2.1

Equation 8.2.2 shall apply to initial pressures before ignition of 1 bar-abs ± 0.2 bar.

8.2.21.2

The following limitations shall be applicable to Equation 8.2.21.1:

(1) 5 bar ≤ Pmax ≤ 12 bar

(2) 10 bar-m/s ≤ KSt ≤ 800 bar-m/s

(3) 0.1 m3 ≤ V ≤ 10,000 m3

(4) Pstat ≤ 0.75 bar

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

Commented [ML2]: This is moving above current section 8.2.2.3

Commented [ML3]: deleted

Page 38: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Draft copy for NFPA 68 Committee work only

8.2.2 Effects of Elevated L/D

8.2.2.1

The L/D of the enclosure shall be determined according to Section 6.4.

8.2.2.3 2

When L/D is less than or equal to 2, Av1 shall be set equal to Av0.

8.2.2.3

For L/D values greater than 2 and less than or equal to 6, the required vent area, Av1, shall be calculated

as follows (where exp(A) = eA, e is the base of the natural logarithm [114]):

(8.2.2.3) .

8.2.3.12.4*

It shall be permitted to extend Equation 8.2.3 2.3 to values of L/D of 8 for top-fed bins, hoppers, and silos,

provided the calculated required vent area, after application of all correction factors, does not exceed the

enclosure cross-sectional area.

8.2.2.54

For situations where vents can be distributed along the major axis of the enclosure, Equation 8.2.2 and

Equation 8.2.3 shall be permitted to be applied where L is the spacing between vents along the major

axis.

8.2.3 Effects of Initially Elevated or Subatmospheric Pressure.

8.2.3.1 When the initial pressure is between -0.2 bar and 0.2 bar, Avep shall be set equal to Av1.

8.2.3.2*

When enclosure pressure is initially greater than 0.2 bar-g (20 kPa) or less than -0.2 bar-g (-20 kPa), Avep

shall be determined from the following equation:

(8.4.1)

where:

Avep = vent area (m2)

Pstat = static burst pressure of the vent (bar-g)

Pinitial = enclosure pressure at moment of ignition (bar-g)

Peffective = 1/3Pinitial (bar-g)

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

Commented [ML4]: Came from 8.2.1

Commented [ML5]: This section and all underneath are moving here from 8.4

Commented [ML6]: “/Av0” is being deleted here

Page 39: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Draft copy for NFPA 68 Committee work only

Πeffective = (Pred - Peffective)/(PEmax - Peffective)

Pred = reduced pressure (bar-g)

PEmax = [(Pmax + 1) · (Pinitial + 1)/(1 bar-abs) - 1] maximum pressure of the unvented deflagration at

pressure (bar-g)

Pmax = maximum pressure of an unvented deflagration initially at atmospheric pressure (bar-g)

8.2.3.3*

When enclosure pressure is initially less than -0.2 bar-g, the vent area correction in Equation 8.4.1 shall

be evaluated over the range between operating pressure and atmospheric pressure and the largest vent

area correction applied.

8.2.3.4

When enclosure pressure is initially less than -0.2 bar-g, it shall be permitted to use a value of 1.1 as the

vent area correction for this section.

8.2.3.5

When enclosure pressure is initially greater than 0.2 bar-g, deflagration vents shall be permitted only

when the following conditions are met:

(1) Vent duct length L/D ≤ 1

(2) Panel density M ≤ MT and ≤ 40 kg/m2

(3) vaxial and vtan < 20 m/s

(4) No allowance for partial volume

(5) Equation 8.4.1 used to calculate the necessary vent area adjustment

When the initial pressure is between -0.2 bar and 0.2 bar, Avep shall be set equal to Av1.

8.2.45 Effects of Additional Turbulence

Three different general equations (Equations 8.2.3, 8.2.5.7, and 8.2.5.8) shall be applied to the

determination of dust deflagration minimum required vent areas.

8.2.5.1

Equation 8.2.3, which produces the smallest required vent areas, shall apply to dust handling and storage

equipment within which the average air axial velocity, vaxial, and the tangential velocity, vtan, are both less

than 20 m/s during all operating conditions.

8.2.4.15.2*

For this application, average air axial velocity shall be calculated according to the following equation:

(8.2.5.2)

where:

v = average axial gas velocity (m/s)

Q = volumetric air flow rate (m3/s)

A = average cross-sectional area of the flow path (m2) [118,119]

8.2.4.25.3*

If a circumferential (tangential) air velocity is in the equipment, vtan shall be given by 0.5 vtan_max, where

vtan_max is the maximum tangential air velocity in the equipment.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

Commented [ML7]: This requirement is moving up to 8.2.3.1

Page 40: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Draft copy for NFPA 68 Committee work only

8.2.4.35.4

Values of Q, vaxial, vtan_max, and vtan shall be measured or calculated by engineers familiar with the

equipment design and operation.

8.2.4.45.5

The measurements or calculations shall be documented and made available to vent designers and the

authority having jurisdiction.

8.2.4.55.6

When the maximum values derived for vaxial and vtan are less than 20 m/s, Av2 shall be set equal to Avep.

8.2.4.65.7*

When either vaxial or vtan is larger than 20 m/s, Av2 shall be determined from the following equation where

max (A, B) = maximum value of either A or B [118,119]:

(8.2.5.7) .

8.2.4.75.8*

Vent areas for buildings in which there is a dust explosion hazard shall be determined from Equation

8.2.5.8 [118,119]:

(8.2.5.8)

8.2.4.85.9

The required vent areas for these buildings shall be permitted to be reduced through use of the partial

volume Equation 8.3.1.

8.32.6* Effects of Panel Inertia.

8.3.12.6.1

When the mass of the vent panel is less than or equal to 40 kg/m2, Equation 8.2.6.2 shall be used to

determine whether an incremental increase in vent area is needed and the requirements of 8.2.7 shall be

used to determine the value of that increase.

8.3.22.6.2

The vent area shall be adjusted for vent mass where the vent mass exceeds MT as calculated in Equation

8.2.6.2:

(8.2.6.2)

where:

MT = threshold mass (kg/m2)

Pred = reduced pressure after deflagration venting (bar)

n = number of panels

V = volume (m3)

8.3.32.6.3

Where M is greater than 40 kg/m2, it shall be permitted to use the procedure provided in Annex G.

8.3.42.7

For M > MT, the required vent area Av3, shall be calculated as follows:

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

Page 41: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Draft copy for NFPA 68 Committee work only

(8.2.7)

where:

FSH = 1 for translating panels or 1.1 for hinged panels

M = mass of vent panel (kg/m2)

n = number of panels

Av2 = vent area calculated by 8.2.5.6, Equation 8.2.5.7, or Equation 8.2.5.8, as applicable

8.3.52.7.1

If KSt < 75 bar-m/s, KSt = 75 shall be used in Equation 8.2.7.

8.3.62.8

Where M ≤ MT, Av3 shall be set equal to Av2.

8.43* Effects of Partial Volume.

8.43.1

When the volume fill fraction, Xr, can be determined for a worst-case explosion scenario, the minimum

required vent area shall be permitted to be calculated from the following equation:

(8.3.1)

where:

A v4 = vent area for partial volume deflagration

A v3 = vent area for full volume deflagration as determined from Equation 8.2.7 or from 8.2.8

Xr = fill fraction > Π

Π = Pred/Pmax

8.4.1.13.2*

If Xr ≤ Π, deflagration venting shall not be required.

8.4.1.23.2.1

Where partial volume is not applied, Av4 shall be set equal to Av3.

8.4.23.3* Process Equipment Partial Volumes.

Process equipment involving nonsolvent drying shall be permitted to use partial volume venting in

accordance with Equation 8.3.1.

8.43.23.1

In applications involving dryers with recirculation of dry product, the fill fraction shall be taken as 1.0.

8.43.23.2

Furthermore, if the solvent is flammable, hybrid deflagration KSt values shall be determined.

8.43.23.3

In applications such as a spray dryer or fluidized bed dryer, the specific fill fraction to be used for vent

design shall be based on measurements with representative equipment and process materials.

8.43.23.4

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

Commented [ML8]: Change N to lowercase n

Page 42: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Draft copy for NFPA 68 Committee work only

In applications involving spray dryers where a partial volume venting is calculated in accordance with

Equation 8.3.1, the vent shall be mounted within the chosen partial volume zone of the dryer that contains

the driest fraction of material.

8.43.23.5

In these applications, the determination of Xr shall be documented and submitted to the authority having

jurisdiction for review and concurrence.

8.43.34 Building Partial Volumes.

(See Annex I.)

8.43.34.1

This subsection shall apply to large process buildings in which a dust explosion hazard is associated with

combustible material deposits on the floor and other surfaces, and with the material contained in process

equipment.

8.43.34.2

The minimum required deflagration vent area for the building dust explosion hazard shall be based either

on the full building volume or on a partial volume determined as follows:

(1) Collect at least three representative samples of the floor dust from either the actual building or a

facility with similar process equipment and materials. The samples shall be obtained from measured floor

areas, Afs, that are each 0.37 m2 (4 ft2) or larger.

(2) Weigh each sample and calculate the average mass, (grams), of the floor samples.

(3) Collect at least two representative samples from measured sample areas, Ass, on other surfaces with

dust deposits. These surfaces on any plane could include beams, shelves, and external surfaces of

process equipment and structures. Calculate the total area, Asur, of these surfaces with dust deposits.

(4) Weigh each sample and calculate the average mass, (grams), of the surface samples.

(5) Determine the total mass, Me, of combustible dust that could be released from the process

equipment in the building.

(6) Test the dust samples per ASTM E 1226, Standard Test Method for Explosibility of Dust Clouds, to

determine Pmax, KSt, and the worst-case concentration, cw, corresponding to the largest value of KSt.

(7) Using the highest values of Pmax and KSt, the building volume, V, and Π = Pred/Pmax, use Equation

8.2.7 or 8.2.8 to calculate the vent area, Av3, needed if the full building volume were filled with

combustible dust.

(8) Calculate the worst-case building partial volume fraction, Xr, in accordance with 8.3.4.3.

(9) If the calculated Xr > 1, the minimum required vent area is equal to Av3 . (a) If Xr ≤ Π, no deflagration venting is needed. (b) If 1 > Xr > Π, the minimum required vent area, Av4, is calculated from Equation 8.3.1 as follows:

(8.3.4.2)

8.43.34.3

The worst-case building partial volume fraction, Xr, shall be calculated from the following equation:

(8.3.4.3)

where:

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

Page 43: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Draft copy for NFPA 68 Committee work only

Xr = worst-case building partial fraction

= average mass of floor samples (g)

Af-

dusty

= total area of floor with dust deposits (m2)

ηDfloor = entrainment factor for floor accumulations

Afs = measured floor areas (m2)

V = building volume (m3)

cw = worst-case dust concentration (g/m3)

= average mass of surface samples (g)

Asur = total area of surfaces with dust deposits (m3)

ηDsur = entrainment factor for surface accumulations

Ass = measured sample areas of surfaces with dust deposits (m2)

Me = total mass of combustible dust that could be released from the process equipment in the

building (g)

8.4.33.4.3.1

If a measured value of cw is available, the lowest value of cw for the various samples shall be used in

Equation 8.3.4.3.

8.43.34.3.2

If a measured value of cw is not available, a value of 200 g/m3 shall be permitted to be used in Equation

8.3.4.3.

8.43.34.3.3*

If measured values of and are not available, and if the facility is to be

maintained with dust layer thickness in accordance with NFPA 654, Standard for the Prevention of Fire

and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate

Solids, an approximate value for these ratios shall be permitted to be used, based on a dust layer bulk

density of 1200 kg/m3 and a layer thickness of 0.8 mm (1⁄32 in.) over the entire floor area and other

surfaces defined in 8.3.4.3.4.

8.43.34.3.4

The total mass of dust that could be released from process equipment in the building/room Me, shall be

determined as follows:

(1) Evaluate equipment with exposed dust accumulations, such as but not limited to screeners, open-top

conveyors or conveyor belts, open packaging or shipping containers, and enclosureless dust collectors.

(2) Evaluate anticipated episodic spills from equipment in light of current housekeeping procedures and

practices.

(3) Do not include material in closed packaging or shipping containers, material in enclosed silos or

storage bins, or in otherwise explosion-protected equipment.

8.43.34.3.5

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location. The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

Page 44: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Draft copy for NFPA 68 Committee work only

The entrainment factor, ηD for each representative area shall be determined by one of the following

methods:

(1) Assume an entrainment factor of 1.

(2) Calculate the entrainment factor as follows: (a) Determine the average particle density, ρp for each sampled dust layer. (b) Determine the entrainment threshold velocity using the following equation:

[8.3.4.3.5(2)(b)] where:

Ut = threshold velocity (m/s)

ρp = particle density (kg/m3)

(c) Assume a maximum free-stream velocity, U, of 50 m/s or establish a different free-stream velocity

calculated from a maximum credible initiating event.

(d) Determine a maximum entrainment rate using the following equation:

[8.3.4.3.5(2)(d)] where:

m" = entrained mass flux (kg/m2-s)

ρ = gas density (kg/m3)

U = free-stream velocity (m/s) > Ut

Ut = threshold velocity (m/s)

(e) Determine initiating event time, t, by dividing the building or enclosure longest dimension by 1⁄2 the

maximum free-stream velocity.

(f) Using the appropriate surface area, A, determine the maximum mass, Mmax, from the presumed

initiating event using the following equation:

[8.3.4.3.5(2)(f)] (g) Determine the entrainment factor using the following equation:

[8.3.4.3.5(2)(g)] where:

M = average mass of the sample (g)

8.4 Effects of Initially Elevated or Subatmospheric Pressure.

8.4.1*

When enclosure pressure is initially greater than 0.2 bar (20 kPa) or less than -0.2 bar (-20 kPa), Avep/Av0

shall be determined from the following equation:

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

Commented [ML9]: Moved to 8.2.3

Page 45: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Draft copy for NFPA 68 Committee work only

(8.4.1)

where:

Avep = vent area (m2)

Pstat = static burst pressure of the vent (bar)

Pinitial = enclosure pressure at moment of ignition (bar)

Peffective = 1/3Pinitial (bar)

Πeffective = (Pred - Peffective)/(PEmax - Peffective)

Pred = reduced pressure

PEmax = [(Pmax + 1) · (Pinitial + 1)/(1 bar-abs) - 1] maximum pressure of the unvented deflagration at

pressure (bar)

Pmax = maximum pressure of an unvented deflagration initially at atmospheric pressure (bar)

8.4.2*

When enclosure pressure is initially less than -0.2 bar, the vent area correction in Equation 8.4.1 shall be

evaluated over the range between operating pressure and atmospheric pressure and the largest vent

area correction applied.

8.4.3

When enclosure pressure is initially less than -0.2 bar, it shall be permitted to use a value of 1.1 as the

vent area correction for this section.

8.4.4

When enclosure pressure is initially greater than 0.2 bar, deflagration vents shall be permitted only when

the following conditions are met:

(1) Vent duct length L/D ≤ 1

(2) Panel density M ≤ MT and ≤ 40 kg/m2

(3) vaxial and vtan < 20 m/s

(4) No allowance for partial volume

(5) Equation 8.4.1 used to calculate the necessary vent area adjustment

8.4.5

When the initial pressure is between -0.2 bar and 0.2 bar, Avep shall be set equal to Av1.

The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.

Page 46: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 9-NFPA 68-2016 [ Section No. 8.5.5 ]

8.5.5

Equation 8.5.1a shall not be used if the initial pressure exceeds ± 0.2 bar-g.

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Feb 01 16:22:42 EST 2016

Committee Statement

CommitteeStatement:

The limitation given in 8.5.5 incorrectly included both positive and negative pressure limitationswhere the limitation indicated in Table 8.5.10 is only relevant for positive pressures above 0.2 bar.Equation 8.5.1a can be used for vacuum conditions.

ResponseMessage:

Public Input No. 10-NFPA 68-2015 [Section No. 8.5.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 50 3/22/2016 10:02 AM

Page 46 of 64

Page 47: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 6-NFPA 68-2016 [ Sections 8.8.3.1, 8.8.3.2, 8.8.3.3 ]

Global FR-30

8.8.3.1

The owner/operator shall be permitted to choose a design strength based on a P red of either 0.2, 0.5 ,

or 1.0 bar bar-g .

8.8.3.2

The casing(s), head, and boot shall all be designed for the same Pred chosen from 8.8.3.1.

Global FR-30

8.8.3.3

Additional vents shall be installed in each casing at center-to-center spacing distance along the elevatoraxis based on the bucket elevator classification, the KSt of the material being handled, and the design

strength based on Pred, as given in Table 8.8.3.3.

Table 8.8.3.3 Additional Vent Spacing

Spacing (m)

Bucket Elevator ClassificationK St

(bar-m/s)

P red

≤ 0.2 bar bar-g

P red

≤ 0.5 bar bar-g

P red

≤ 1.0 bar bar-g

Double-casing (twin leg) <100 6 None required None required

100–150 3 10 19

151–175 N/A 4 8

176–200 N/A 3 4

>200 N/A N/A 3

Single-casing (single leg) <100 N/A* None required None required

100–150 N/A 7 14

151–175 N/A 4 5

176–200 N/A 3 4

>200 N/A N/A 3

N/A: Not allowed.

*For Pred≤ = 0.3 bar bar-g , vent spacing of 6 m is appropriate.

Source: [120]

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Feb 01 14:38:08 EST 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 50 3/22/2016 10:02 AM

Page 47 of 64

Page 48: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Committee Statement

CommitteeStatement:

This revision clarifies that the values in the table are reduced pressure values, not enclosurestrength pressures.

The headings of each column were revised to show that the given spacing and Kst values willproduce no more than the listed Pred values.

The information from A.8.8.3.3 is being moved to 8.8.3.4 and A.8.8.3.4. See FR 8.

Public Input No. 13-NFPA 68-2015 [Section No. 8.8.3.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 50 3/22/2016 10:02 AM

Page 48 of 64

Page 49: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 8-NFPA 68-2016 [ New Section after 8.8.3.3 ]

8.8.3.4*

Where plastic buckets are used, the corresponding elevator design P red of 0.2, 0.5, or 1.0 bar-g shall

be increased by the factors given in Table 8.8.3.4 .

Table 8.8.3.4 Design P red Adjustment for Plastic Buckets

K St (bar-m/s) Percent Increase

<100 20%

100–150 35%

151–200 50%

Source : [120].

Supplemental Information

File Name Description

NFPA_68_FR_8_New_annex.doc New Annex and new table

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Feb 01 15:41:24 EST 2016

Committee Statement

CommitteeStatement:

Information on plastic buckets was not readily apparent to the user, and due to the increasing useof plastic buckets, this information was relocated from the Annex to the body of the standard. TheTechnical Committee is asking for Public Comments on the use of plastic buckets including anytesting to support the provision on plastic buckets in VDI 2263.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 50 3/22/2016 10:02 AM

Page 49 of 64

Page 50: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Table 8.8.3.4 Design Pred Adjustment for Plastic Buckets

KSt .

(bar-m/s) Percent Increase

<100 20%

100–150 35%

151–200 50%

Source: [120].

A.8.8.3.4 Changing from metal to plastic buckets has been demonstrated to increase the explosion pressures. For example, if designing a double-casing bucket elevator with plastic buckets for a KSt of 100–150 bar-m/s, and intending to space vents at no more than 10 m, then the enclosure strength should be based on a Pred of 0.5 x 1.35 = 0.68 bar.

Page 50 of 64

Page 51: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 10-NFPA 68-2016 [ Sections A.6.3.1.1, A.6.3.1.2 ]

A.6.3.1.1

This is also referred to as “explosion pressure shock resistant design” in European documents, such asEN 14460, Explosion Resistant Equipment .

A.6.3.1.2

If the enclosure is intended to be reused following an event, the owner or operator should design thesystem to prevent permanent deformation of the enclosure. This is also referred to as “explosion pressureresistant design” in European documents such as VDI 3673, Pressure Venting of Dust Explosions, and EN13237, “ Potentially explosive atmospheres — Terms and definitions for equipment and protective systemsintended for use in potentially explosive atmospheres.”

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Feb 01 16:56:16 EST 2016

Committee Statement

CommitteeStatement:

The descriptions given in A.6.3.1.1 and A.6.3.1.2 are reversed when referencing the standard text insections 6.3.1.1 and 6.3.1.2. 6.3.1.1 describes a design scenario allowing deformation, not rupture.The description in 6.3.1.1 is equivalent to "Explosion pressure shock resistant" design in the EUharmonized standards such as EN 14460 "Explosion Resistant Equipment." A.6.3.1.2 shoulddescribe the design scenario where no deformation is allowed, which is equivalent to "explosionpressure resistant" design as defined in EU harmonized standard EN 14460, "Explosion ResistantEquipment."

ResponseMessage:

Public Input No. 6-NFPA 68-2015 [Section No. A.6.3.1.2]

Public Input No. 5-NFPA 68-2015 [Section No. A.6.3.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 50 3/22/2016 10:02 AM

Page 51 of 64

Page 52: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 15-NFPA 68-2016 [ Section No. A.8.7.1(2) ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 50 3/22/2016 10:02 AM

Page 52 of 64

Page 53: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

A.8.7.1(2)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 50 3/22/2016 10:02 AM

Page 53 of 64

Page 54: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Another approach to provide a clear path is to provide a flow area equivalent to the vent area immediatelyadjacent to the vent. Figure A.8.7.1(2)(a) and Figure A.8.7.1(2)(b) show a side view and a plan view,respectively, for vertical elements. Figure A.8.7.1(2)(c) and Figure A.8.7.1(2)(d) show an end view and aside view, respectively, for Version 1 of the horizontal elements, while Figure A.8.7.1(2)(e) shows an endview for Version 2 of the horizontal elements.

Figure A.8.7.1(2)(a) Free Area Normal to Vent for Vertical Filter Elements — Side View.

Figure A.8.7.1(2)(b) Free Area Normal to Vent for Vertical Filter Elements — Plan View.

Figure A.8.7.1(2)(c) Free Area Normal to Vent for Horizontal Elements — Version 1, End View.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 50 3/22/2016 10:02 AM

Page 54 of 64

Page 55: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Figure A.8.7.1(2)(d) Free Area Normal to Vent for Horizontal Filter Elements — Version 1, SideView.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 50 3/22/2016 10:02 AM

Page 55 of 64

Page 56: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Figure A.8.7.1(2)(e) Free Area Normal to Vent for Horizontal Filter Elements — Version 2, EndView.

Supplemental Information

File Name Description

FR_15_A.8.7.1_2_d_.pngchange figure as shown- the black bar should be shortened to the height of the vent (D)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 50 3/22/2016 10:02 AM

Page 56 of 64

Page 57: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 02 10:24:43 EST 2016

Committee Statement

Committee Statement: Figure A.8.7.1(2)(d) is being edited to clarify the restraint of full-length cartridges.

Response Message:

Public Input No. 12-NFPA 68-2015 [Sections A.8.7.1(1), A.8.7.1(2)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 50 3/22/2016 10:02 AM

Page 57 of 64

Page 58: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 14-NFPA 68-2016 [ Section No. A.8.7.3 ]

A.8.7.3

Figure A.8.7.3, in comparison to Figure A.8.7.1(1)(a) and Figure A.8.7.1(2)(a), shows asituation situations for vertical and horizontal elements in which neither separation nor a clear path isprovided. A similar situation can exist for horizontal elements.

Figure A.8.7.3 Insufficient Separation for Vertical and Horizontal Filter Elements.

Supplemental Information

File Name Description

FR_14_new_images.png Replace current figure with the three arrangements shown in the attached file.

Submitter Information Verification

Submitter Full Name: Laura Montville

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 50 3/22/2016 10:02 AM

Page 58 of 64

Page 59: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 02 10:20:11 EST 2016

Committee Statement

CommitteeStatement:

Graphics are revised to indicate more realistic applications and to clearly show when to use fullfilter housing volume in venting equations. The committee will confirm that venting correlations aresufficiently conservative that filter elements can be placed in front of the vent.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 50 3/22/2016 10:02 AM

Page 59 of 64

Page 60: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 18-NFPA 68-2016 [ Section No. A.8.9.2 ]

A.8.9.2

If the vented material exits from the vent horizontally, the horizontal length of the fireball is anticipated. It isextremely important to note that the fireball can, in fact, extend downward as well as upward [91, 108]. Insome deflagrations, buoyancy effects can allow the fireball to rise to elevations well above the distancesspecified.

Equation 8.9.2 calculates the fireball dimension, but that is not the only factor to consider in evaluating thehazard from an emerging vented deflagration. Other factors to consider include, but are not limited to,environmental matters such as prevailing wind speed and direction, external nearby structures, particlesize, vent configuration and weight, and nearby operations. A safety factor should be considered basedon an assessment of the risk elements that are present in or near the anticipated path of travel of theemerging flame and unburned dust.

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 02 14:57:32 EST 2016

Committee Statement

CommitteeStatement:

A task group compared available data with the predicted flame reach, and equation 8.9.2adequately covers the data, so no change to the equation is required. However, it is advised toconsider other factors when evaluating fireball hazards.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

46 of 50 3/22/2016 10:02 AM

Page 60 of 64

Page 61: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 11-NFPA 68-2016 [ New Section after B.1.2.5 ]

B.1.2.6

Beginning with the 2013 edition of NFPA 68, the fundamental burning velocity, S u , is used to

characterize the burning rate of gases. Earlier editions used a normalized maximum rate of pressurerise, K G , analogous to K St for dusts. Venting correlations were based on K G tested in an

initially quiescent mixture. Differences in test conditions could result in significant change in measuredK G . In particular, increasing the volume of the test enclosure and increasing the ignition energy could

result in increased K G values, as described in Annex E of the 2007 edition.

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Feb 01 17:15:29 EST 2016

Committee Statement

Committee Statement: As of the 2013 edition, K_G is no longer used in this standard.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 50 3/22/2016 10:02 AM

Page 61 of 64

Page 62: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

First Revision No. 5-NFPA 68-2016 [ Chapter K ]

Annex K Informational References

K.1 Referenced Publications.

The documents or portions thereof listed in this annex are referenced within the informational sections ofthis standard and are not part of the requirements of this document unless also listed in Chapter 2 forother reasons.

K.1.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 30, Flammable and Combustible Liquids Code, 2012 2015 edition.

NFPA 30B, Code for the Manufacture and Storage of Aerosol Products, 2011 2015 edition.

NFPA 33, Standard for Spray Application Using Flammable or Combustible Materials, 2011 2016 edition.

NFPA 35, Standard for the Manufacture of Organic Coatings, 2011 2016 edition.

NFPA 52, Vehicular Gaseous Fuel Systems Code, 2013 2016 edition.

NFPA 61, Standard for the Prevention of Fires and Dust Explosions in Agricultural and Food ProcessingFacilities, 2013 2017 edition.

NFPA 69, Standard on Explosion Prevention Systems, 2008 2014 edition.

NFPA 400, Hazardous Materials Code, 2013 2016 edition.

NFPA 484, Standard for Combustible Metals, 2012 2015 edition.

NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing,and Handling of Combustible Particulate Solids, 2013 2017 edition.

NFPA 750, Standard on Water Mist Fire Protection Systems, 2010 2015 edition.

NFPA 5000®, Building Construction and Safety Code®, 2012 2015 edition.

Fire Protection Guide to Hazardous Materials, 2001 edition.

K.1.2 Other Publications.

K.1.2.1 ANSI Publications.

American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY 10036.

ANSI Z535.4 , Product Safety Signs and Labels,1998 2011 .

K.1.2.2 API Publications.

American Petroleum Institute, 1220 L. Street, N.W., Washington, DC 20005-4070.

API RP 752, Management of Hazards Associated with Location of Process Plant Permanent Buildings,2003 2009 .

K.1.2.3 ASCE Publications.

American Society of Civil Engineers, 1801 Alexander Bell Drive, Reston, VA 20191–4400.

ASCE, Design of Blast-Resistant Buildings in Petrochemical Facilities, 2010.

ASCE/SEI 7, Minimum Design Loads for Buildings and Other Structures, 2010.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

48 of 50 3/22/2016 10:02 AM

Page 62 of 64

Page 63: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

K.1.2.4 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM D5680a , Standard Practice for Sampling Unconsolidated Solids in Drums or SimilarContainers,2001 2014 .

ASTM E502, Standard Test Method for Selection and Use of ASTM Standards for the Determination ofFlash Point of Chemicals by Closed Cup Methods,2000 2007, reapproved 2013 .

ASTM E582, Standard Test Method for Minimum Ignition Energy and Quenching Distance in GaseousMixtures,2004 2007, (2013 e1) .

ASTM E681, Standard Test Method for Concentration Limits of Flammability of Chemicals (Vapors andGases),2004 2009, reapproved 2015 .

ASTM E1226, Standard Test Method for Explosibility of Dust Clouds, 2010 2012A .

ASTM E1515, Standard Test Method for Minimum Explosible Concentration of Combustible Dusts,1998 2014 .

ASTM E2019, Standard Test Method for Minimum Ignition Energy of a Dust Cloud in Air, 2003,reapproved 2013 .

K.1.2.5 CCPS Publications.

Center for Chemical Process Safety, 3 Park Avenue, 19th Floor, New York, NY 10016.

Guidelines for Safe Handling of Powders and Bulk Solids, 2004.

K.1.2.6 CENELEC Publications.

European Committee for Electrotechnical Standardization, CEN-CENELEC Management Centre, 17,Avenue Marnix, 4th floor, B-1000 Brussels.

EN 13237, Potentially Explosive Atmospheres — Terms and Definitions for Equipment and ProtectiveSystems Intended for Use in Potentially Explosive Atmospheres , 2012.

EN 14460, Explosion Resistant Equipment , 2006.

K.1.2.7 ISO Publications.

International Organization for Standardization, 1, rue de Varembé, Case postale 56, CH-1211 Geneve20 ISO Central Secretariat, BIBC II, 8, Chemin de Blandonnet, CP 401, 1214 Vernier, Geneva ,Switzerland.

ISO 6184-1, Explosion Protection Systems — Part 1: Determination of Explosion Indices of CombustibleDust in Air, 1985.

K.1.2.8 NACE Publications.

NACE International, 1440 South Creek Drive, Houston, TX 77084-4906.

National Association of Corrosion Engineers Handbook, 2nd edition, 1991.

K.1.2.9 U.S. Government Publications.

U.S. Government Printing Publishing Office, 732 North Capitol Street, NW, Washington, DC20402 20401-0001 .

TM5-1300, Structures to Resist the Effects of Accidental Explosions, Department of Defense ExplosivesSafety Board, 1990.

UFC 3-340-02, Structures to Resist the Effects of Accidental Explosions , Department of Defense, 2014.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

49 of 50 3/22/2016 10:02 AM

Page 63 of 64

Page 64: First Revision No. 30-NFPA 68-2016 [ Global Input ]€¦ · First Revision No. 30-NFPA 68-2016 [ Global Input ] Change pressure units "bar" to "bar-g" and "psi" to "psig" throughout

K.1.2.10 Other Publications.

Biggs, J. M., Introduction to Structural Dynamics, New York: McGraw-Hill, 1964.

Darby, R., Chemical Engineering Fluid Mechanics, 2nd Edition, New York: Marcel Dekker, 2001.

Holbrow, P., S. Andrews, and G. A. Lunn, “Dust explosions in interconnected vented vessels,” Journal ofLoss Prevention in the Process Industries, Vol. 9, No. 1, pp. 91–103 (1996).

Holbrow, P., G. A. Lunn, and A. Tyldesley, “Dust explosion protection in linked vessels: Guidance forcontainment and venting,” Journal of Loss Prevention in the Process Industries, Vol. 12, No. 3, pp.227–234 (1999).

Krishna, K., W., Rogers, and M. Sam Mannan, “The use of aerosol formation, flammability, and explosioninformation for heat-transfer fluid selection,” Journal of Hazardous Materials 104, 2003.

Lees, F. P., Lees' Loss Prevention in the Process Industries, 2nd Edition, Oxford, U.K.: Butterworth–Heinemann, 1996.

Lunn, G. A., P. Holbrow, S. Andrews, and J. Gummer, “Dust Explosions in Totally Closed InterconnectedVessels,” Journal of Loss Prevention in the Process Industries, Vol. 9, No. 1, pp. 45–58 (1996).

Moore, P. E., and J. A. Senecal, “Industrial Explosion Protection — How Safe Is Your Process?” DustExplosion Symposium, Fire Protection Research Foundation, Baltimore, MD, May 13–14, 2009. Seehttp:www.nfpa.org/assets/files/PDF/Foundation%20proceedings/Industrial_Explosion_Protection.pdf.

Roser, M., “Investigation of dust explosion phenomenon in interconnected process vessels,”Forschungsgesellschaft fur angewandle Systemsicherheit und Arbeitsmedizin PhD Thesis, University ofLoughborough.

Roser, M., A. Vogel, S. Radant, W. Malalasekera, and R. Parkin, “Investigations of flame front propagationbetween interconnected process vessels. Development of a new flame front propagation time predictionmodel,” Journal of Loss Prevention in the Process Industries, Vol. 12, Issue 5, pp. 421–436 (1999).

Yu, X., and Young, K.-J., The Dynamic Load Factor of Pressure Vessels in Deflagration Events.

K.2 Informational References. (Reserved)

NFPA 652 , Standard on the Fundamentals of Combustible Dust , 2016 edition.

K.3 References for Extracts in Informational Sections. (Reserved)

Submitter Information Verification

Submitter Full Name: Laura Montville

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Feb 01 08:31:22 EST 2016

Committee Statement

Committee Statement: Referenced current SDO names, addresses, standard names, numbers, and editions.

Response Message:

Public Input No. 2-NFPA 68-2015 [Chapter K]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

50 of 50 3/22/2016 10:02 AM

Page 64 of 64