Distributed Power ModulesModel 5495 Model 5499
6 Amps 9 Amps
![Page 3: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/3.jpg)
3 Amps per output
4 Notification outputs
1 Aux output
Fuseless Design
Dip switch programmable
Distributed Power Modules
![Page 4: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/4.jpg)
Distributed Power Modules
Fully Supervised
Flexible wiring (Class A or Class B)
2 Input circuits (Activated and supervised by FACP)
![Page 5: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/5.jpg)
Synchronization Built-in for appliances from System Sensor, Gentex, Faraday or Wheelock.
.
Distributed Power Modules
![Page 6: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/6.jpg)
SWITCHING v.s. LINEAR DESIGN
-Up to 50% more efficient.
-Puts out less damaging heat.
-Faster input re-action.
-Gives you lighter weight. LOWER SHIPPING COSTS!!
-Switching power supply’s are used in computers.
Distributed Power Modules
![Page 7: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/7.jpg)
Signal Input TerminalsClass B wiring from a FACP
The fire panel supervises its notification output the same way it supervises ordinary notification circuits (open circuit = trouble). The power supplies emulates the trouble behavior by breaking the EOL supervision current for any power supply trouble, putting the fire panel into a notification circuit trouble.
![Page 8: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/8.jpg)
The power supplies will accurately sense the polarity of the fire panel’s notification circuit to drive the outputs whether or not the supervision connection is intact. During the Alarm Condition (ON) the fire panel will not sense trouble conditions though its notification circuits.
Signal Input TerminalsClass B wiring from a FACP
Alarm Condition (ON)
![Page 9: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/9.jpg)
CURRENT REQUIREMENTS (Battery Calculations)
1.) Current Draw From Host Fire Panel = 15mA
2.) Current Draw From Batteries = ?
![Page 10: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/10.jpg)
Only the green AC LED should be on in a normal condition.
5495 Board
![Page 11: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/11.jpg)
Only the green AC LED should be on in a normal condition.
5499 Board
![Page 12: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/12.jpg)
Trouble Relay
The Trouble Relay is one option to signal the trouble condition to the FACP, the primary way is though the FACP Notification circuit connected to the input.
![Page 13: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/13.jpg)
Notification PowerClass A wiring from a FACP
![Page 14: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/14.jpg)
Notification PowerClass B wiring from a FACP
Input 1 will short terminal 19 to terminal 17 during normal operation, and open during trouble conditions. Same operation if using input 2 (terminals 14 and 16).
![Page 15: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/15.jpg)
Notification PowerExtend Class B Circuit
Notification devices powered from the main fire panel.
The EOL must be the only thing connected to terminals 17 and 14!
![Page 16: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/16.jpg)
DIP Switch Settings
![Page 17: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/17.jpg)
DIP Switch Settings ANSI Temporal Output
Input
Output
4 sec.
.5 sec. on, .5 sec. o ff, .5 sec. on, .5 sec. o ff, .5 sec. on, 1 .5 sec. o ff(repeat)
![Page 18: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/18.jpg)
DIP Switch Settings
![Page 19: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/19.jpg)
DIP Switch Settings / Sync.
![Page 20: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/20.jpg)
DIP Switch Settings / Sync.
![Page 21: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/21.jpg)
DIP Switch Settings
![Page 22: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/22.jpg)
Notification PowerClass B wiring from a FACP
![Page 23: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/23.jpg)
Notification PowerClass B wiring from a FACP
![Page 24: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/24.jpg)
Notification PowerClass B wiring from a FACP
![Page 25: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/25.jpg)
Stand Alone OperationMore Power
What’s the max. current that the Model 5495 can supply with 4 the outputs? What’s the max. current that the Model 5499 can supply with 4 the outputs?
![Page 26: FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps](https://reader036.vdocuments.us/reader036/viewer/2022062519/5697c0211a28abf838cd2da2/html5/thumbnails/26.jpg)
Stand AloneDoor Holder Operation
FACP 5495 or 5499
Normally ClosedAlarm Relay
What’s the max. current that the Aux. Power output can supply???