firemaster - edilportale.com · curtains remain invisibly retracted until activated by an alarm or...
TRANSCRIPT
FireMasterAUTOMATIC FIRE CURTAINS
Fully retracted
Fully Protected
Architect Fire Design Solutions
Engineered, fully tested and certified for the latest fire regulations and building design technology -
Fully Fit For Purpose*
* Refer to ‘Don’t be liable!’ on the back page
Cl/Sfb (31.5) Fire Doors
DESIGN SOLUTIONS THAT WORK FOR YOU
MEANS OF ESCAPE - Curtains create protected routes
SHOP FRONTS - No need for expensive and noticeable fire-rated glass
STAIRWELLS - No need for fire-rated walls
OPEN SPACE - Virtual Fire Walls can be over 50m long for maximum visibility
Invisible
Partial descent for initial smoke containment Full protection
ATRIA - Curtains allow multi-floor concourse openings and large atria
ESCALATORS - No need for fire-rated walls
LIFTS - No need for lift lobby areas
BOUNDARY PROTECTION - Eliminate vertical and horizontal fire spread to other buildings
What are automatic fire curtains and how do they work?
Single Roller Assembly
Multiple Roller Assembly
Automatic fire curtains comprise technologically advanced fire-resistant fabric roller barriers encased in a compact steel housing. Curtains remain invisibly retracted until activated by an alarm or detector signal, at which time they descend safely to their operational position.
To be regulation compliant and to be fully Fit For Purpose they must be protected by total power failure Gravity Fail-Safe. Fire curtains will stop and control the spread of fire in a building and protect the means of escape.(See ‘Don’t be liable!’ on the back page)
Single roller assembly curtains for spans up to 5m as standard • **All curtains allow escape for occupants and entry for emergency services•
• Controlled Gravity Fail-Safe operation ensures safe rate of descent even following total power loss or wiring / system corruption on all curtains
Unique overlapping design with continuous, conjoined bottom bar• Multiple roller assembly curtains for spans over 5m• ** as standardFully synchronised intelligent drive system• Unlimited spans and drops of 4m• ** require only lightweight housings as small as 180mm x 340mm
Partial deployment
Partial deployment
1
** Coopers has a design solution for any size requirement - See the chart on the left for our standard range of sizes. For queries about special size requirements, please contact our technical department.
Single rollers Multiple roller
What are the standard headbox sizes?
FM 15/20 FM 18/22 FM 18/26 FM 18/34
Model No. Maximum CurtainWidth **
Maximum CurtainDrop **
FM 15/20 5 metres 4 metres
FM 18/22 5 metres 6 metres
FM 18/26 5 metres 8 metres
FM 18/34 54 metres 4 metres
2
There are many fixing options to suit all types of ceiling configurations. Curtains can be integrated with both solid and suspended ceilings, enabling total project design flexibility.
How are the headboxes installed?
I beamUnistrut and drop rods Face fixed Soffit fixed
3
(These are just our standard sizes)
Flush fit
Suspended ceiling with SLAT(Self Levelling Access Trim)
Suspended ceiling with recessed shadow gap
FireMaster curtain systems provide a range of ceiling interfaces and can even invisibly conceal the curtain in the ceiling whilst still allowing access for service and maintenance. All our systems remain totally concealed when non-operational.
How are the curtains concealed?
Removable access
Removable access
Removable access
How is the curtain accessed?(Remember, regular service and maintenance is mandatory.)
Side channels seal the curtain fabric and the building. Fire can cause extreme positive or negative pressures. Side guide channels are made from galvanised steel (available in standard RAL colours) that can be either surface mounted or recessed into the wall structure to give a flush finish. Coopers’ unique fabric locking system has been developed and proven over many years.
5 How do the curtain’sside channels interface with
the walls?
Face fixed RecessedEnd fixed
Post fixed Recessed withcosmetic trim
29
90 - 100Adjustable
4
MCU MCU MCUMCUMCUMCU
F
13A
A
F
13A
F
13A
F
13A
FireMaster (Standard) EFP 2/1000 and EFP 4/1000 are long established, high performance fire textile composite materials of a stainless steel reinforced woven glass fibre. The special EFP coating contains a micronised aluminium enriched polymer, which when exposed to fire, is absorbed into the surface of the curtain to provide high temperature performance.
Power Supply: 230V AC 50Hz dedicated supply via 13Amp un-switched fuse spur
Battery: 2 x 12V 12A/h lead acid batteries
Alarm Signal: Normally closed volt-free contacts. Open on activation
Test Facility: Key switch and Reset button on PZCP
Display: Power On, Alarm Active and Alarm Off
Power Supply Unit -Panel Size: 400mm(w) x 500mm(h) x 210mm(d)
Motor Control Unit -Panel Size: 300m(w) x 200mm(h) x 80mm(d)
Coopers Fire Limited, Edward House,Penner Road, Havant, Hampshire PO9 1QZ UK
Tel: +44(0) 23 9245 4405 | Fax: +44(0) 23 9249 2732email: [email protected] | web: www.coopers-uk.com
Does your system comply with fire regulations?Do not jeopardise your insurance or your Professional • Indemnity. Do not be fooled by systems which are not properly tested. This is a life safety product!
Compromise on safety and you compromise on life. • Demand to see full testing and cer tification.
Remember: Corporate & Personal Manslaughter Legislation•
Fabric specification
Controls specification
Testing
Coopers FireMaster systems are fully tested for 2 & 4 hour fire resistance to BS EN 1634-1 & BS 476-22-8 and are also tested to BS 476-6, 7, BS 7346-3, BS EN 12101-1:2006 and BSi PAS 121:2007.
Controls are custom made to be fully compatible with both existing alarm systems and the number of curtain units installed, whether single or multiple roller assemblies. When an alarm signal is detected, the control panel will automatically trigger all the curtain systems to deploy in a controlled descent under gravity.
Control OptionsSupply
5m maximum54m maximum
Single Multiple
AlarmPSU
MCU
300
400
500
200
“When used as part of a fire engineered design, fire curtain barrier assemblies become a critical element of that design. If fire curtain barriers do not deploy to their operational position, the [fire engineered] system will not perform as designed.
However, in the event that other elements of the fire protection system do not function, for example due to total power failure, the fire curtain barriers in the fire operational position will provide fire separation.
Active fire curtain barrier assemblies shall gravity fail-safe to their fire operational position in a controlled manner when all consumable primary and auxiliary power sources are removed, in the event of wiring or system corruption, or any combination thereof.”
DON’T BE LIABLE!
More importantly... Is it Fit For Purpose?Don’t buy a Chocolate Teapot!
Your fire curtain must comply with BSi PAS 121:2007 to be both tested & Fit For Purpose. You must insist on this.
BSi PAS 121:2007 states:-
210
80
Assessed to ISO 9001:2000Certificate number FM 22356