fire services at data centre. fm200 training course
TRANSCRIPT
![Page 1: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/1.jpg)
FIRE SERVICES AT DATA CENTRE
![Page 2: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/2.jpg)
FM200 TRAINING COURSE
![Page 3: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/3.jpg)
INTRODUCTION OF FM 200
![Page 4: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/4.jpg)
THE PROPERTIES OF FM-200®
![Page 5: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/5.jpg)
WHAT IS FM-200® ?
C C C
F F F
F F
F FH
ASHRAE Designation = HFC227eaASHRAE Designation = HFC227ea
![Page 6: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/6.jpg)
Fire TriangleFuel, oxygen, heat
What is fire?A series of highly exothermic chain-branching free radical reactions
Removal of any element of fire triangle results in suppression
THE PHYSICS OF FIRE
![Page 7: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/7.jpg)
Removes heat, so fire can’t sustain itself
FAST & EFFICIENT PERFORMANCE
![Page 8: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/8.jpg)
FM-200® CHEMICAL/PHYSICALEXTINGUISHING MECHANISM
Physical
Chemical
80%
Physical
Chemical 20%
80%
20%
Halon 1301 FM-200®®
![Page 9: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/9.jpg)
Cup Burner Conc. [Heptane] - 5.8%
Use Concentration [Minimum] - 7.5% for ISO compliance
Maximum Discharge Time limited to 10 Seconds
HOW IS FM-200® APPLIED?
![Page 10: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/10.jpg)
Compact storage space requirements
FAST & EFFICIENT PERFORMANCE
Halon 1301
CO
Inert Gas
![Page 11: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/11.jpg)
FM-200® iscompletely safe for use in occupiedspaces.
HUMAN SAFETY
![Page 12: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/12.jpg)
Reaches extinguishing concentration within 10 seconds
Provides ACTIVE Fire Protection
FM-200® IS FAST & EFFECTIVE
![Page 13: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/13.jpg)
FM-200® ENGINEERED SYSTEMS
![Page 14: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/14.jpg)
14
ENGINEERED CENTRAL STORAGE FM-200® SYSTEM
Raised Floor
Distribution PipeDischarge Nozzles
Smoke Detectors
Manual Station
Containers
![Page 15: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/15.jpg)
Computer Rooms
PRIMARY APPLICATIONS
![Page 16: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/16.jpg)
3M™ Novec™ 1230 Fire Protection Fluid
Novec 1230 fluid has distinct environmental benefits Ozone depletion potential (ODP) of
0
5 day atmospheric lifetime
Global Warming Potential (GWP) of 1
THE NEW CLEAN AGENT
![Page 17: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/17.jpg)
FM200 CONTROL EQUIPMENT
![Page 18: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/18.jpg)
Kentec Panel Kentec lock off
FM200 CONTROL EQUIPMENT
![Page 19: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/19.jpg)
Kidde Panel Kidde Panel
FM200 CONTROL EQUIPMENT
![Page 20: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/20.jpg)
Chubb Panel Viking & Notifier Panel
FM200 CONTROL EQUIPMENT
![Page 21: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/21.jpg)
Thorn Panel
FM200 CONTROL EQUIPMENT
![Page 22: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/22.jpg)
FM200 CYLINDER
![Page 23: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/23.jpg)
Kidde FM200
FM200 CYLINDER
![Page 24: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/24.jpg)
Chemetron FM200
FM200 CYLINDER
![Page 25: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/25.jpg)
ThornFM200
FM200 CYLINDER
![Page 26: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/26.jpg)
Fike FM200
FM200 CYLINDER
![Page 27: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/27.jpg)
Siemens FM200
FM200 CYLINDER
![Page 28: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/28.jpg)
SIGNAGE BOX AND PRESSURE SWITCH
Signage Box Pressure Switch for Fed-back Signal
![Page 29: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/29.jpg)
AUTO-MANUAL Mode Selection Provided Next to the Panel Outside the Room
When Personal Before Enter the Room:
- Switch the Auto-Manual Switch to “MANUAL” - “System Inoperative” Signal Box Flash - Switch Back to “AUTO” when Leave the Room
MODE SELECTION
![Page 30: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/30.jpg)
Two Detection Zones for Each SystemCross Zone OperationActivating Anyone Zone:
- Alarm Sound - “Do Not Enter” Sign Flash, Don’t Enter the Room
FM200 OPERATION IN AUTO MODE
![Page 31: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/31.jpg)
Two Zones Activated:
- Two-Tone Sounder Raised - “Evacuate” Sign Flash, Evacuate Room
Immediately - A/C in the Room Will Shunt Down - System Start Count Down for 30 Sec. - Gas Discharge to Room After Count Down
FM200 OPERATION IN AUTO MODE
![Page 32: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/32.jpg)
When Personal Working inside the Room:One Zone of Alarm Activated and Alarm
Sound: - Check Any Fire Happened in Room - Inform Others to Leave the Room if Fire Happened - Go out of the Room, Push the “Manual Release”
Switch to Discharge Gas Two Zone Activated: - Evacuate Room Immediately - Go out of the Room, Push the “Manual Release”
Switch to Discharge Gas
FM200 SYSTEM OPERATION IN MANUAL MODE
![Page 33: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/33.jpg)
Check Smoke Detectors- Corrosion- Dirty
- Generate False Alarm FrequentlyCheck Modules
- Simulate Tests to Check the Modules
Working Properly
MAINTENANCE OF AFA AND FM200 SYSTEMS
![Page 34: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/34.jpg)
Monthly & Annual
- To Be Carried-Out By FS Contractor
MAINTENANCE
![Page 35: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/35.jpg)
What is VESDA…
INTRODUCTION OF VESDA SYSTEM
Aspirating Smoke Detection吸气式烟雾探测
![Page 36: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/36.jpg)
THEINTRODUCTION OF VESDA SYSTEM VESDA ADVANTAGE…
![Page 37: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/37.jpg)
VESDA Panel VESDA Panel
INTRODUCTION OF VESDA SYSTEM
![Page 38: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/38.jpg)
Kidde HSSD Panel Kidde HSSD Panel
INTRODUCTION OF HSSD SYSTEM
鐳射探測器主機板
風機
![Page 39: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/39.jpg)
Kidde HSSD Sampling Point
INTRODUCTION OF HSSD SYSTEM
![Page 40: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/40.jpg)
Pre-action System
INTRODUCTION OF PRE-ACTION SYSTEM
![Page 41: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/41.jpg)
Pre-action System
INTRODUCTION OF PRE-ACTION SYSTEM
![Page 42: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/42.jpg)
THANK YOU
![Page 43: FIRE SERVICES AT DATA CENTRE. FM200 TRAINING COURSE](https://reader033.vdocuments.us/reader033/viewer/2022061420/56649f2c5503460f94c46f3b/html5/thumbnails/43.jpg)
END