fire pump idiot proofing
DESCRIPTION
fireTRANSCRIPT
Fire protection systems control and extinguish fires without human intervention.
A fire sprinkler system is an active fire protection measure, consisting of a water supply system, providing adequate pressure and flowrate to a water distribution piping system, onto which fire sprinklers and fire hose are connected.
Fire protection system is not connected to FDAS. The only part of fire protection system that have a direct link to FDAS is the flow sensor
EXIT
FLOAT VALVE / BALL
BACK
An automatic valve whose opening and closing are controlled by a float at the end of a wire or lever
ISOLATION VALVE
BACK
It is a valve in a system that stops the flow of water to a given location, usually for maintenance or safety purposes.
FIRE PUMPIt is a part of a fire protection system. The pump intake is connected to the fire tank. The pump provides water flow at a higher pressure to the sprinkler system risers and hose standpipes.
FIRE PUMP
Example of burnt fire pump due to lack of water in the fire tank.
BACK
FIRE TANK
BACK
A water reservoir intended for the event of a fire.
JOCKEY PUMP
BACK
It is a small apparatus that works together with a fire pump as part of a fire-protection system. It is designed to keep the pressure in the system elevated to a specific level when the system is not in use, so that the fire pump doesn't have to run all the time.
GATE VALVE
BACK
A valve that either allows or prohibits the flow of hydraulic fluid. The gate valve consists of a plate-like obstruction that is raised and lowered into place to control the flow of hydraulic fluid.
FLEXIBLE CONNECTORIt provides for misalignment of the shafts or to introduce mechanical flexibility and to alter the vibration characteristics of the motor.
FLEXIBLE CONNECTOR
BACK
Damage flexible connector can cause harm to your pump.Also it can cause flooding in the pump room.
CHECK VALVE
BACK
It is a valve that normally allows fluid or gas to flow through it in only one direction.
PRESSURE RELIEF VALVE
BACK
It is a valve designed to open at a predetermined pressure value.
ALARM CHECK VALVE
BACK
A check valve located in the riser of fire protection system that sounds an alarm when water begins to pass through it.
SPRINKLER HEAD
An outlet on a sprinkler system which covers a radius of 3m. Each sprinkler head must have a maximum distance of 6m with each other.
SPRINKLER PRESSURE HEAD
Rule of thumb:1m=1.39psi
Formula:Pressure=height(1.39)+60psi
Note:60psi is the standard pressure inside the sprinkler system.
BACK
CROSS MAIN VALVE
BACK
It is a valve that normally allows or restrict fluid or gas to flow
SUPERVISORY and FLOW SWITCH
BACK
The function of a water flow switch is to detect water flow in the sprinkler system, usually during a fire event, to send a signal to FDAS to activate the alarm devices in the property
SIGHT GLASS
BACK
A sight glass or water gauge is a transparent tube through which the operator of a tank can observe the level of liquid contained within.
DRAIN VALVE
BACK
A drain valve is a mechanical device used to release excess or unwanted liquids from the pipe line.
BACK
STEP 1
Check and double check the fire Check and double check the fire pump system and everything pump system and everything surrounding it before doing surrounding it before doing anything else.anything else.
• Fire pump and motorFire pump and motor• Control PanelControl Panel• Piping systemPiping system• Fire Water Fire Water • Never test equipments without Never test equipments without
the knowledge of others.the knowledge of others.
STEP 2 Open the Open the BY-PASS VALVEBY-PASS VALVE. This . This valve is channeled back to the fire valve is channeled back to the fire tank.tank.
GOING TO TANK GOING TO TANK
BY-PASS BY-PASS VALVE-VALVE-always always
“NORMALLY “NORMALLY CLOSED” CLOSED” except except during during testingtesting
STEP 3 Close the Close the MAIN ISOLATION MAIN ISOLATION VALVEVALVE. This valve is located at . This valve is located at the alarm check valve.the alarm check valve.
MAIN MAIN ISOLATION ISOLATION VALVE VALVE
AUXIALIARY AUXIALIARY DRAINDRAIN
ALARM ALARM CHECK CHECK VALVEVALVE
STEP 4 Activate the fire pump by Activate the fire pump by pressing thepressing the START BUTTON START BUTTON. . This button is at the control panel.This button is at the control panel.
OPERATING OPERATING LEVERLEVER
START START BUTTONBUTTON
STOP STOP BUTTONBUTTON
STEP 5 Let the pump run for about 10 Let the pump run for about 10 minutes, observe parameters in the minutes, observe parameters in the DISPLAY PANELDISPLAY PANEL, if your panel does , if your panel does not have display, measure not have display, measure parameters manually. parameters manually.
DISPLAYDISPLAY
START BUTTONSTART BUTTON
OPERATING OPERATING LEVERLEVER
STOP BUTTONSTOP BUTTON
STEP 5 continued• Observe the motor for over-heating.Observe the motor for over-heating.• Observe excessive heating of Observe excessive heating of pump pump
shaft, pump casing and mechanical shaft, pump casing and mechanical seal or packing.seal or packing.
• Observe for unecessary leaks from Observe for unecessary leaks from the pumpthe pump..
MECHANICAL MECHANICAL SEAL / SEAL / PACKINGPACKING
IMPELLERIMPELLER
PUMP PUMP CASINGCASING
PUMP SHAFTPUMP SHAFT
SAFETY REMINDERS
Make sure that Make sure that CUT-INCUT-IN and and CUT-OFFCUT-OFF PRESSUREPRESSURE of pressure actuated equipments of pressure actuated equipments like fire and jockey pump, PRV’s and like fire and jockey pump, PRV’s and booster pump.booster pump.
STEP 6
To test To test PRESSURE RELIEF VALVEPRESSURE RELIEF VALVE, , gradually close the by-pass valve gradually close the by-pass valve until water passes through the PRV, until water passes through the PRV, observe the trip pressure if it is observe the trip pressure if it is same with the set pressure posted same with the set pressure posted on the PRV. Adjust if necessary .on the PRV. Adjust if necessary .
PRV PRV pressure pressure
gage gage reading reading
should be should be 0 if pump 0 if pump is not is not
running.running.
PRV pressure PRV pressure adjusting adjusting
knob, remove knob, remove cap to cap to adjust adjust settingsettingPRV PRV
discharge discharge pipe pipe
should be should be back to back to tanktank
SAFETY REMINDERS
PRV discharge pipe should be back PRV discharge pipe should be back to tankto tank, , if ever your PRV if ever your PRV discharge is directed to sump pit, discharge is directed to sump pit, discharge volume of PRV will discharge volume of PRV will SURELY flood your pump room of SURELY flood your pump room of sump pit. Consider re-directing sump pit. Consider re-directing PRV discharge back to tank.PRV discharge back to tank.
STEP 7 Shut-down the fire pump by Shut-down the fire pump by pressing the pressing the STOPSTOP BUTTONBUTTON at the at the control panel after 10 minutes.control panel after 10 minutes.
STEP 8 STEP 8
Record parameters and test results Record parameters and test results at at FIRE PUMP PM CHECKLIST.FIRE PUMP PM CHECKLIST.
STEP 9 STEP 9
Close BY-PASS VALVE and re-open Close BY-PASS VALVE and re-open the MAIN ISOLATING VALVE to put the MAIN ISOLATING VALVE to put the system in service.the system in service.
PREVENTIVE MAINTENANCE CHECKLIST
EQUIPMENT : FIRE PUMP
Pump #: ___________
Location:_____ Phase: ____ Horsepower Rating: _____ Voltage: ______ Size of wires: ________ Breaker Rating: __________
Cut-in Pressure: ________________________________
Cu-off Pressure: ________________________________
PRV Set Pressure: ______________________________
Work Description J F M A M J J A S O N D
MONTHLY
Clean and remove dirt of the pump and motor.
Clean motor control and electrical panels
Check all gate valves if functioning properly.
Check for pump overheating.
Check leak at packing seal.
Check leak at all gate valves and check valves.
INITIAL OF ATTENDING MAINTENACE
QUARTERLY
Grease and lubricate bearings.
Inspect and retighten all screws, holding, mounting nuts & bolts.
Lubricate moving parts (bearing, etc.)
Inspect and service all electrical controllers & components,
retightens setcrews, of circuit breakers and controls
Apply and spray cleaner to all contact surfaces.
Cleaning of float switch located at Overhead Tank.
Test and check for noise and vibration.
QUARTERLY ACTIVITIES
Voltage Reading
Line 1
Line2
Line 3
Ampere Reading
Line 1-2
Line 2-3
Line 1-3
Insulation Resistance of Motors.
Line1 - Line 2
Line 2 - Line 3
Record Cut-in Pressure
Record Cut-off Pressure
Record PRV Set Pressure
INITIAL OF ATTENDING MAINTENACE
Notes : Report to Property Engineer all abnormal findings and results.
Place Date of Inspection on space provided if there are no abnormal findings
Minimum Insulation Resistance Reading : 25 MΩ ( 250-599 volts), NETA 2009
SAFETY REMINDERS
If during major fire emergency and If during major fire emergency and fire pumps fails to activate, use fire pumps fails to activate, use EMERGENCY RUNEMERGENCY RUN..
The End!!!
STEP 1
Check and double check the fire Check and double check the fire pump system and everything pump system and everything surrounding it before doing surrounding it before doing anything else.anything else.
• Fire pump and motorFire pump and motor• Control PanelControl Panel• Piping systemPiping system• Fire Water Fire Water • Never test equipments without Never test equipments without
the knowledge of others.the knowledge of others.
STEP 2 Open the Open the BY-PASS VALVEBY-PASS VALVE. This . This valve is channeled back to the fire valve is channeled back to the fire tank.tank.
GOING TO TANK GOING TO TANK
BY-PASS BY-PASS VALVE-VALVE-always always
“NORMALLY “NORMALLY CLOSED” CLOSED” except except during during testingtesting
STEP 3 Close the Close the MAIN ISOLATION MAIN ISOLATION VALVEVALVE. This valve is located at . This valve is located at the alarm check valve.the alarm check valve.
MAIN MAIN ISOLATION ISOLATION VALVE VALVE
AUXIALIARY AUXIALIARY DRAINDRAIN
ALARM ALARM CHECK CHECK VALVEVALVE
STEP 4 Deactivate the Deactivate the JOCKEY PUMP JOCKEY PUMP CONTROLLERCONTROLLER, use either main , use either main switch or selector switch.switch or selector switch.
MAIN MAIN SWITCHSWITCHON/OFFON/OFF
SENSING LINE AND TEST DRAINSENSING LINE AND TEST DRAIN
SELECTOR SELECTOR SWITCHSWITCH
STEP 5 Decrease Decrease SYSTEM PRESSURE SYSTEM PRESSURE by by releasing water through the releasing water through the AUXIALIRY DRAIN AUXIALIRY DRAIN at the at the ALARM ALARM CHECK VALVECHECK VALVE, observe panel or , observe panel or pressure gauge until pressure pressure gauge until pressure reaches reaches CUT-INCUT-IN. Compare actual . Compare actual cut-in pressure to regular pressure cut-in pressure to regular pressure setting.setting.AUXILIARY AUXILIARY
DRAINDRAIN
STEP 5 continued Upon release of water, pressure Upon release of water, pressure decrease can be monitored through decrease can be monitored through the the CONTROL PANELCONTROL PANEL or or ALARM ALARM CHECK VALVECHECK VALVE..
SYSTEM SYSTEM PRESSUREPRESSUREGAUGE GAUGE PRESSUREPRESSURE
GAUGE – GAUGE – pressure pressure should be should be 0 if pump 0 if pump
is not is not running.running.
STEP 6 Based on the standard of Bureau of Based on the standard of Bureau of Fire (BFP) it is not practical to have Fire (BFP) it is not practical to have an automatic cut-off / shut-offan automatic cut-off / shut-off
A.A. MANUAL CUT-OFFMANUAL CUT-OFF– fire pump will – fire pump will NOT shut-off instantly upon NOT shut-off instantly upon reaching cut-off pressurereaching cut-off pressure
STEP 7 Fire pump can be shut-down by Fire pump can be shut-down by deactivating the deactivating the OPERATING LEVEROPERATING LEVER..
OPERATING OPERATING LEVERLEVER
STEP 8 STEP 8
Record parameters and test results Record parameters and test results at at FIRE PUMP PM CHECKLIST.FIRE PUMP PM CHECKLIST.
STEP 9 STEP 9
Close BY-PASS VALVE and re-open Close BY-PASS VALVE and re-open the MAIN ISOLATING VALVE to put the MAIN ISOLATING VALVE to put the system in service.the system in service.
PREVENTIVE MAINTENANCE CHECKLIST
EQUIPMENT : FIRE PUMP
Pump #: ___________
Location:_____ Phase: ____ Horsepower Rating: _____ Voltage: ______ Size of wires: ________ Breaker Rating: __________
Cut-in Pressure: ________________________________
Cu-off Pressure: ________________________________
PRV Set Pressure: ______________________________
Work Description J F M A M J J A S O N D
MONTHLY
Clean and remove dirt of the pump and motor.
Clean motor control and electrical panels
Check all gate valves if functioning properly.
Check for pump overheating.
Check leak at packing seal.
Check leak at all gate valves and check valves.
INITIAL OF ATTENDING MAINTENACE
QUARTERLY
Grease and lubricate bearings.
Inspect and retighten all screws, holding, mounting nuts & bolts.
Lubricate moving parts (bearing, etc.)
Inspect and service all electrical controllers & components,
retightens setcrews, of circuit breakers and controls
Apply and spray cleaner to all contact surfaces.
Cleaning of float switch located at Overhead Tank.
Test and check for noise and vibration.
QUARTERLY ACTIVITIES
Voltage Reading
Line 1
Line2
Line 3
Ampere Reading
Line 1-2
Line 2-3
Line 1-3
Insulation Resistance of Motors.
Line1 - Line 2
Line 2 - Line 3
Record Cut-in Pressure
Record Cut-off Pressure
Record PRV Set Pressure
INITIAL OF ATTENDING MAINTENACE
Notes : Report to Property Engineer all abnormal findings and results.
Place Date of Inspection on space provided if there are no abnormal findings
Minimum Insulation Resistance Reading : 25 MΩ ( 250-599 volts), NETA 2009
SAFETY REMINDERS
When activating When activating OPERATING LEVEROPERATING LEVER, , always make sure that the always make sure that the STOP STOP BUTTON BUTTON is pressed to prevent fire is pressed to prevent fire pump from activating.pump from activating.
STOP BUTTON is pressed upon activation of STOP BUTTON is pressed upon activation of OPERATING LEVEROPERATING LEVER
The End!!!
MANUAL MANUAL
Afterwards, record parameters and Afterwards, record parameters and test results at test results at JOCKEY PUMP PM JOCKEY PUMP PM CHECKLIST.CHECKLIST.
AUTOMATIC AUTOMATIC
Put selector switch of Jockey Pump Put selector switch of Jockey Pump into into HANDHAND, slightly release water to , slightly release water to avoid over pressure.avoid over pressure.
Put selector switch of Jockey Pump Put selector switch of Jockey Pump into into AUTOAUTO, slightly release water to , slightly release water to avoid over pressure.avoid over pressure...
The End!!!
PREPARED BY:
RENEGADE CUISON