Fire Pump Controller For Electric Motor Driven Fire Pumps MP300 Fire Pump Controller Across The Line Type Series MP300 − Combined Manual and Automatic Aquarius Fire Pump Controllers conform to the latest requirements of Chapter 10, National Fire Protection Association Pamphlet 20, Standard for Centrifugal Fire Pumps as adopted by Underwriters Laboratories and Factory Mutual. They are withstand rated and listed by Underwriters’ Laboratories and approved by Factory Mutual Research Corporation. Sizes range from 15 to 600 horsepower, 200 to 600 volts, 60 Hz. These controllers are for use on Across-the-Line type installations. Only the highest quality components, all UL listed or UL recognized, are used throughout to assure the best possible reliability. The cabinet is fabricated of heavy gauge reinforced steel with drip-proof hood. All field wiring and service connections may be made from the front, allowing the controller to be mounted flush against a wall. The controller is completely wired, assembled, and tested at the factory before shipment, and ready for immediate installation. TM Aquarius Fluid Products, Inc. Manufactured by Metron, Inc.

Upload: others

Post on 11-Sep-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Fire Pump Controller · 2015. 4. 2. · Manufactured by Metron, Inc. Standard and Optional Features All photographs and graphics are typical and may not represent actual product supplied

Fire Pump Controller For Electric Motor Driven Fire Pumps

MP300 Fire Pump Controller

Across The Line Type Series MP300 − Combined Manual and Automatic

Aquarius Fire Pump Controllers conform to the latest requirements of Chapter 10, National Fire Protection Association Pamphlet 20, Standard for Centrifugal Fire Pumps as adopted by Underwriters Laboratories and Factory Mutual. They are withstand rated and listed by Underwriters’ Laboratories and approved by Factory Mutual Research Corporation.

Sizes range from 15 to 600 horsepower, 200 to 600 volts, 60 Hz. These controllers are for use on Across-the-Line type installations.

Only the highest quality components, all UL listed or UL recognized, are used throughout to assure the best possible reliability. The cabinet is fabricated of heavy gauge reinforced steel with drip-proof hood. All field wiring and service connections may be made from the front, allowing the controller to be mounted flush against a wall.

The controller is completely wired, assembled, and tested at the factory before shipment, and ready for immediate installation.

TM

Aquarius Fluid Products, Inc.

Manufactured by Metron, Inc.

Page 2: Fire Pump Controller · 2015. 4. 2. · Manufactured by Metron, Inc. Standard and Optional Features All photographs and graphics are typical and may not represent actual product supplied

Standard and Optional Features

All photographs and graphics are typical and may not represent actual product supplied

Standard Features Operator Interface Device (OID) with LED Annunciator and Digital Display

• NEMA Type 2 drip proof metal freestanding enclosure

• Operator Interface Device (OID) with 4 lines by 20 character display with large character backlit Liquid Crystal Display (LCD) capable of being read in both direct sunlight or dark lighting conditions

• 10 pushbuttons for easy screen navigation, LED lamp test, alarm reset, controller test and horn silencing

• Removable labels to allow for easy field language changes

• All controller settings are programmable through the OID. All features are enabled or disabled through the OID, no jumpers or external wires are needed allowing easy field modification

• The system status data is displayed on the OID. The displayed items include: System pressure, Phase to Phase (AB, BC, AC) voltage, Phase current (A, B, C), Current time and date, System Events and Notifications such as Remote Start, Local Start etc., Number of starts, Total motor run hours, Time remaining on sequential motor start and motor stop timers, Status of automatic stop setting.

• Auxiliary alarm functions displayed on the OID LCD screen

• Audible horn with silence feature for silencable alarms

• Lamp test feature • Foreign languages selectable through the OID • Microprocessor based logic with real time/date

clock capable of running a minimum of 14 days without AC power connected to controller

• SD Memory card used to record pressure log, event and log, and auxiliary user programs. Pressure log is stored in separate comma delimited ASCII text files with each file containing data for one day. The SD card is removable and can be read by any PC equipped with an SD card reader.

• Input and output status LED's provide visual indication of each discrete input's or output's on/off status

• One RS485 Serial Port• MODBUS Communication Protocol via RS485 port • Service Entrance Rated

Standard Auxiliary alarms: The controller includes as standard six (6) discrete auxiliary inputs, nine (9) form 'C' auxiliary relay outputs. These auxiliary inputs and outputs are in addition to those mandated by NFPA 20. All auxiliary inputs, outputs, and OID Display can be field programmed through the OID.

Nine (9) of the following auxiliary alarms can be programmed and recorded in the event/alarm logs and annunciated on the OID display screen and/or output relay contact(s). These alarm conditions include:

LOW PUMP ROOM TEMP RESERVOIR LOW RESERVOIR EMPTY RESERVOIR HIGH FLOW METER ON RELIEF VALVE OPEN LOW SUCTION PRESSURE HIGH PUMP ROOM TEMPERATURE LOW FIREWATER PRESSURE LOW PURGE PRESSURELOW GEAR OIL PRESSURE HIGH GEAR OIL TEMPERATURE

TM

Aquarius Fluid Products, Inc.

Manufactured by Metron, Inc.

Page 3: Fire Pump Controller · 2015. 4. 2. · Manufactured by Metron, Inc. Standard and Optional Features All photographs and graphics are typical and may not represent actual product supplied

GAS DETECTION HIGH VIBRATION EMERGENCY POWER ON PUMP ROOM DOOR OPEN

Data logging:The controller includes two (2) separate data logs for storing system data that is readable through the OID or copied to a computer equipped with an SD card reader. The 2 data logs are as follows:

Pressure Log: The pressure log provides a continuous pressure record for 30 days. The pressure log samples shall be time and date stamped and stored in permanent non-volatile SD memory card. The pressure log can be searched by each sample, by minute, or by hour through the OID.

Event Log: The event log will store up to 300 of the most current events. These events can include, but is not limited to, any of the following events/alarms:

PUMP RUNNING POWER AVAILABLE PHASE REVERSAL MOTOR OVERLOAD REMOTE START LOCAL START PUMP ON DEMAND SYSTEM FAULT PRESSURE TRANSDUCER FAULT PUMP FAILED TO START LOW INTAKE SHUTDOWN ALARM SUPERVISORY POWER FAILURE LOW PRESSURE AUTO WEEKLY TEST START UNDER FREQUENCY OVER FREQUENCY LOW ZONE / HIGH ZONE CONTACTS HIGH DISCHARGE PRESSURE NO LOAD CONDITION

OptionsOption H: Space Heater If the ambient atmosphere is especially damp, a space heater rated at 100 watts may be supplied to reduce moisture in the cabinet. A thermostat is supplied as standard with this option. A humidistat may be substituted if specified. Option W: Omit Legs For systems where the controller is mounted on a common skid with the pump and motor, the legs of the controller may be omitted, 3” (76.2mm) channels or wall mounting brackets can be supplied. If specified, lifting eyes may also be supplied.

EnclosureThe following NEMA type enclosures are also available: 3R, 4, 4X (Painted Cold Rolled Steel), 4X (304 or 316 Stainless Steel), and 12

Manufactured by Metron, Inc.

TM

Aquarius Fluid Products, Inc.

Page 4: Fire Pump Controller · 2015. 4. 2. · Manufactured by Metron, Inc. Standard and Optional Features All photographs and graphics are typical and may not represent actual product supplied

Fire Pump Controller For Electric Motor Driven Fire Pumps

_____________________________________________________________________________________________________________ Aquarius Fluid Products, Inc. • 2585 Millennium Drive, Unit B • Elgin, IL 60124 • (800) 208.8181 • Fax (847) 289.9292 • www.aquariusfp.com

Bulletin MP300 05/10vØ

Model MP300 Across-the-line Start Microprocessor Electric Motor Fire Pump Controller

SpecificationsGeneral Controller Description

The Fire Pump Controller shall be factory

assembled, wired and tested as a unit and shall

conform to all requirements of the latest edition

of NFPA 20, NFPA 70 and be Third Party Listed

by Underwriters Laboratories (UL) and

Approved by Factory Mutual (FM). The

controller shall be available for 208, 230, 380-

415, or 480 volt three phase power.

Controller Equipment Features

The controller shall include the following

standard features:

• NEMA Type 2 drip proof metal freestanding

enclosure

• Operator Interface Device (OID) with 4 lines

by 20 character display with large character

backlit LCD capable of being read in both

direct sunlight or dark lighting conditions

• 10 pushbuttons for easy screen navigation,

system test, lamp test, alarm reset, and horn

silencing

• Multicolored LED's for alarm and mode

annunciation

• LEDs shall be labeled with removable labels

to allow for easy field modification of

language changes

• All controller settings shall be programmable

through the OID and shall be protected by two

password levels

• All features shall be enabled or disabled

through the OID, no jumpers or external wires

shall be needed or allowed to activate or de-

activate a feature

• The system status data shall be displayed on

the OID. The displayed items shall include:

System pressure, Phase to Phase (AB, BC,

AC) voltage, Phase current (A, B, C), System

Events and Notifications, Current time and

date, Number of starts, Total motor run hours,

Displayed countdown timers for: Sequential

motor start and motor stop, Status of

Automatic Stop Setting.

• Audible horn with silence feature for

silencable alarms

• Lamp test feature

• Foreign languages selectable through the OID

• Microprocessor based logic with real time/date

clock capable of running a minimum of 14

days without AC power connected to

controller and non-volatile flash memory to

permanently store the continuous pressure log,

event log, alarm log and all user changeable

set points and system data. Battery backup of

any kind not allowed.

• Input and output status LED's to provide visual

indication of each discrete input's or output's

on/off status

• One RS485 Serial Port

• MODBUS Communication Protocol via

RS485 port

• All wiring terminals on PCB's shall be

removable type

• Service Entrance Rated

Auxiliary alarms

As standard the controller shall include 6 discrete

auxiliary inputs, 9 form 'C' auxiliary relay

outputs. These auxiliary inputs and outputs are

in addition to those mandated by NFPA 20. All

auxiliary inputs, outputs, and OID screens shall

be field programmable through the OID. This

permits a multitude of customizable controller

configurations to meet each installations unique

needs without adding cost to the controller. The

use of jumpers, soldering, or other external

components are not allowed.

The user can select any 9 of the following

auxiliary alarms that can be programmed and

recorded in the event log and annunciated with

an OID screen and output relay contact for

conditions such as but not limited to:

LOW PUMP ROOM TEMP RESERVOIR LOW RESERVOIR EMPTY RESERVOIR HIGH FLOW METER ON RELIEF VALVE OPEN LOW SUCTION PRESSURE HIGH PUMP ROOM TEMPERATURE LOW FIREWATER PRESSURE LOW PURGE PRESSURE LOW GEAR OIL PRESSURE HIGH GEAR OIL TEMPERATURE GAS DETECTION HIGH VIBRATION EMERGENCY POWER ONPUMP ROOM DOOR OPEN

Data logging

The controller shall have separate data logs for

storing system data that is readable through the

OID.

Pressure Log: The controller shall have a

Pressure log with continuous pressure recording

of 30 days of data. The pressure log samples

shall be time and date stamped and stored on a

removable SD card memory. The pressure log

shall be searchable by each sample, by minute, or

by hour. Each days entries shall be stored in a

separate file on the SD card. SD memory shall be

readable by any PC equipped with an SD

memory card reader.

Event Log: The event log shall be capable of

storing no less than 3000 events. These events

shall include, but is not limited to, any of the

following events/alarms:

PUMP RUNNING POWER AVAILABLE PHASE REVERSAL MOTOR OVERLOAD REMOTE START LOCAL START PUMP ON DEMAND SYSTEM FAULT PRESSURE TRANSDUCER FAULT PUMP FAILED TO START LOW INTAKE SHUTDOWN ALARM SUPERVISORY POWER FAILURE LOW PRESSURE AUTO WEEKLY TEST START UNDER FREQUENCY OVER FREQUENCY LOW ZONE / HIGH ZONE CONTACTS HIGH DISCHARGE PRESSURE NO LOAD CONDITION

Each event or alarm recorded in the event log

shall have the following data recorded with the

event/alarm:

• Time and Date of Event or Alarm

• System Pressure

• Descriptive Text Message of the Event/Alarm

• Motor Running Status

• Phase to Phase Volts

• Phase Amps

The internal logic of the controller shall be

capable of operation in a temperature range of

4.4ºC to 40ºC and high, non-condensing,

humidity levels.

The controller shall be manufactured by Metron.

TM

Aquarius Fluid Products, Inc.

Page 5: Fire Pump Controller · 2015. 4. 2. · Manufactured by Metron, Inc. Standard and Optional Features All photographs and graphics are typical and may not represent actual product supplied

Fire Pump Controller For Electric Motor Driven Fire Pumps

MP700 Fire Pump Controller

Solid State Reduced Voltage Types Series MP700 Soft Start, Soft Stop

Fire Pump Controllers conform to the latest requirements of Chapter 10, National Fire Protection Association Pamphlet 20, Standard for Centrifugal Fire Pumps as adopted by Underwriters Laboratories and Factory Mutual.

Sizes range from 15 to 600 horsepower, 200 to 600 volts, 60 Hz. These controllers are used on reduced voltage type installations using a solid state starter for “Soft” starting and “Soft” stopping of electric motors.

Only the highest quality components, all UL listed or UL recognized, are used throughout to assure the best possible reliability. The cabinet is fabricated of heavy gauge reinforced steel with drip-proof hood. All field wiring and service connections may be made from the front, allowing the controller to be mounted flush against a wall.

The controller is completely wired, assembled, and tested at the factory before shipment, and ready for immediate installation.

TM

Aquarius Fluid Products, Inc.

Manufactured by Metron, Inc.

Aquarius

Page 6: Fire Pump Controller · 2015. 4. 2. · Manufactured by Metron, Inc. Standard and Optional Features All photographs and graphics are typical and may not represent actual product supplied

Standard and Optional Features

All photographs and graphics are typical and may not represent actual product supplied

Standard Features Function - The MP700 series Soft Start electric fire pump controllers utilizes a state of the art solid state motor controller. The motor voltage is raised to an initial torque value. This is an adjustable value of locked rotor torque. The motor voltage is gradually increased during the acceleration ramp time. The acceleration ramp time is set to 10 seconds as required by NFPA 20, but it is adjustable from approximately 3 to 30 seconds.

After a minimum run period and all starting causes have returned to normal, the solid state controller will initiate a stop sequence. This function will reduce surges in the pumping system during stopping of a centrifugal pump by smoothly decelerating the motor at a selectable rate. This will reduce the possibility of surges occurring in the system.

Operator Interface Device (OID) with LED Annunciator and Digital Display

• The solid state unit is supplied with the following protection features: Instantaneous Overcurrent

Detection; Shorted SCR Detection; Phase Loss Monitor; Heatsink Over Temperature Switch

• NEMA Type 2 drip proof metal freestanding enclosure • Operator Interface Device (OID) with 4 lines by 20

character display with large character backlit Liquid Crystal Display (LCD) capable of being read in both direct sunlight or dark lighting conditions

• 10 pushbuttons for easy screen navigation, LED lamp test, alarm reset, controller test and horn silencing

• Removable labels to allow for easy field language changes

• All controller settings are programmable through the OID. All features are enabled or disabled through the OID, no jumpers or external wires are needed allowing easy field modification

• The system status data is displayed on the OID. The displayed items include: System pressure, Phase to Phase (AB, BC, AC) voltage, Phase current (A, B, C), Current time and date, System Events and Notifications such as Remote Start, Local Start etc., Number of starts, Total motor run hours, Time remaining on sequential motor start and motor stop timers, Status of automatic stop setting.

• Auxiliary alarm functions displayed on the OID LCD screen

• Audible horn with silence feature for silencable alarms • Lamp test feature • Foreign languages selectable through the OID • Microprocessor based logic with real time/date clock

capable of running a minimum of 14 days without AC power connected to controller

• SD Memory card used to record pressure log, event and log, and auxiliary user programs. Pressure log is stored in separate comma delimited ASCII text files with each file containing data for one day. The SD card is removable and can be read by any PC equipped with an SD card reader.

• Input and output status LED's provide visual indication of each discrete input's or output's on/off status

• RS485 Communications Port • MODBUS Communication Protocol via RS485 port • Service Entrance Rated

Standard Auxiliary alarms: The controller includes as standard six (6) discrete auxiliary inputs, nine (9) form 'C' auxiliary relay outputs. These auxiliary inputs and outputs are in addition to those mandated by NFPA 20. All auxiliary inputs, outputs, and OID Display can be field programmed through the OID.

TM

Aquarius Fluid Products, Inc.

Manufactured by Metron, Inc.

Page 7: Fire Pump Controller · 2015. 4. 2. · Manufactured by Metron, Inc. Standard and Optional Features All photographs and graphics are typical and may not represent actual product supplied

Nine (9) of the following auxiliary alarms can be programmed and recorded in the event/alarm logs and annunciated on the OID display screen and/or output relay contact(s). These alarm conditions include:

LOW PUMP ROOM TEMP RESERVOIR LOW RESERVOIR EMPTY RESERVOIR HIGH FLOW METER ON RELIEF VALVE OPEN LOW SUCTION PRESSURE HIGH PUMP ROOM TEMPERATURE LOW FIREWATER PRESSURE LOW PURGE PRESSURE LOW GEAR OIL PRESSURE HIGH GEAR OIL TEMPERATURE GAS DETECTION HIGH VIBRATION EMERGENCY POWER ONPUMP ROOM DOOR OPEN

Data logging: The controller includes two (2) separate data logs for storing system data that is readable through the OID or copied to a computer equipped with an SD card reader. The 2 data logs are as follows:

Pressure Log: The pressure log provides a continuous pressure record for 30 days. The pressure log samples shall be time and date stamped and stored in permanent non-volatile SD memory card. The pressure log can be searched by each sample, by minute, or by hour through the OID.

Event Log: The event log will store up to 300 of the most current events. These events can include, but is not limited to, any of the following events/alarms:

PUMP RUNNING POWER AVAILABLE PHASE REVERSAL MOTOR OVERLOAD REMOTE START LOCAL START PUMP ON DEMAND SYSTEM FAULT PRESSURE TRANSDUCER FAULT PUMP FAILED TO START LOW INTAKE SHUTDOWN ALARM SUPERVISORY POWER FAILURE LOW PRESSURE AUTO WEEKLY TEST START UNDER FREQUENCY OVER FREQUENCY LOW ZONE / HIGH ZONE CONTACTS

HIGH DISCHARGE PRESSURE NO LOAD CONDITION

OptionsOption H: Space Heater If the ambient atmosphere is especially damp, a space heater rated at 100 watts may be supplied to reduce moisture in the cabinet. A thermostat is supplied as standard with this option. A humidistat may be substituted if specified.

Option W: Omit Legs For systems where the controller is mounted on a common skid with the pump and motor, the legs of the controller may be omitted, 3” (76.2mm) channels or wall mounting brackets can be supplied. If specified, lifting eyes may also be supplied.

EnclosureThe following NEMA type enclosures are also available: 3R, 4, 4X (Painted Cold Rolled Steel), 4X (304 or 316 Stainless Steel), and 12

TM

Aquarius Fluid Products, Inc.

Manufactured by Metron, Inc.

Page 8: Fire Pump Controller · 2015. 4. 2. · Manufactured by Metron, Inc. Standard and Optional Features All photographs and graphics are typical and may not represent actual product supplied

Fire Pump Controller For Electric Motor Driven Fire Pumps

_____________________________________________________________________________________________________________

Bulletin MP700 05/10 V Ø

Model MP700 Soft Start/Soft Stop Microprocessor Electric Motor Fire Pump Controller

Specifications

The Fire Pump Controller shall be factory

assembled, wired and tested as a unit and shall

conform to all requirements of the latest edition

of NFPA 20, NFPA 70 and be Third Party

Listed by Underwriters Laboratories (UL) and

Approved by Factory Mutual (FM). The

controller shall be available for 208, 230, 380-

415, or 480 volt three phase power.

Controller Equipment Features

The controller shall include the following

standard features:

• NEMA Type 2 drip proof metal freestanding

enclosure

• The controller shall be designed for Soft Start

starting and shall incorporate a special Pump

Control feature which eliminates excessive

acceleration torque problems (water hammer)

and related effects. The controller shall stop

the motor by reducing the speed in a manner

that prevents any sudden changes in torque

and minimizes surges in the system resulting

in a smooth deceleration to the pump

• Operator Interface Device (OID) with 4 lines

by 20 character display with large character

backlit LCD capable of being read in both

direct sunlight or dark lighting conditions

• 10 pushbuttons for easy screen navigation,

system test, lamp test, alarm reset, and horn

silencing

• Multicolored LED's for alarm and mode

annunciation

• LEDs shall be labeled with removable labels

to allow for easy field modification of

language changes

• All controller settings shall be programmable

through the OID and shall be protected by

two password levels

• All features shall be enabled or disabled

through the OID, no jumpers or external wires

shall be needed or allowed to activate or de-

activate a feature

• The system status data shall be displayed

on the OID. The displayed items shall

include: System pressure, Phase to Phase

(AB, BC, AC) voltage, Phase current (A,

B, C), System Events and Notifications,

Current time and date, Number of starts,

Total motor run hours, Displayed

countdown timers for: Sequential motor

start and motor stop, Status of Automatic

Stop Setting

• Audible horn with silence feature for

silencable alarms

• Lamp test feature

• Foreign languages selectable through the OID

• Microprocessor based logic with real

time/date clock capable of running a

minimum of 14 days without AC power

connected to controller and non-volatile flash

memory to permanently store the continuous

pressure log, event log, alarm log and all user

changeable set points and system data.

Battery backup of any kind not allowed

• Input and output status LED's to provide

visual indication of each discrete input's or

output's on/off status

• RS485 Communications Port

• MODBUS Communication Protocol via

RS485 port

• All wiring terminals on PCB's shall be

removable type

• Service Entrance Rated

Auxiliary alarms As standard the controller shall include 6

discrete auxiliary inputs, 9 form 'C' auxiliary

relay outputs. These auxiliary inputs and

outputs are in addition to those mandated by

NFPA 20. All auxiliary inputs, outputs, and

OID screens shall be field programmable

through the OID. This permits a multitude of

customizable controller configurations to meet

each installations unique needs without adding

cost to the controller. The use of jumpers,

soldering, or other external components are not

allowed.

The user can select any 9 of the following

auxiliary alarms that can be programmed and

recorded in the event log and annunciated with

an OID screen and output relay contact for

conditions such as but not limited to:

LOW PUMP ROOM TEMP RESERVOIR LOW RESERVOIR EMPTY RESERVOIR HIGH FLOW METER ON RELIEF VALVE OPEN LOW SUCTION PRESSURE HIGH PUMP ROOM TEMPERATURE LOW FIREWATER PRESSURE LOW PURGE PRESSURE LOW GEAR OIL PRESSURE HIGH GEAR OIL TEMPERATURE GAS DETECTION HIGH VIBRATION EMERGENCY POWER ONPUMP ROOM DOOR OPEN

Data logging The controller shall have separate data logs for

storing system data that is readable through the

OID.

Pressure Log: The controller shall have a

Pressure log with continuous pressure recording

of 30 days of data. The pressure log samples

shall be time and date stamped and stored on a

removable SD card memory. The pressure log

shall be searchable by each sample, by minute,

or by hour. Each days entries shall be stored in a

separate file on the SD card. SD memory shall

be readable by any PC equipped with an SD

memory card reader.

Event Log: The event log shall be capable of

storing no less than 3000 events. These events

shall include, but is not limited to, any of the

following events/alarms:

PUMP RUNNING POWER AVAILABLE PHASE REVERSAL MOTOR OVERLOAD REMOTE START LOCAL START PUMP ON DEMAND SYSTEM FAULT PRESSURE TRANSDUCER FAULT PUMP FAILED TO START LOW INTAKE SHUTDOWN ALARM SUPERVISORY POWER FAILURE LOW PRESSURE AUTO WEEKLY TEST START UNDER FREQUENCY OVER FREQUENCY LOW ZONE / HIGH ZONE CONTACTS HIGH DISCHARGE PRESSURE NO LOAD CONDITION

Each event or alarm recorded in the event log

shall have the following data recorded with the

event/alarm:

• Time and Date of Event or Alarm

• System Pressure

• Descriptive Text Message of the Event/Alarm

• Motor Running Status

• Phase to Phase Volts

• Phase Amps

The internal logic of the controller shall be

capable of operation in a temperature range of

4.4ºC to 40ºC and high, non-condensing,

humidity levels.

The controller shall be manufactured by Metron.

TM

Aquarius Fluid Products, Inc.

Aquarius Fluid Products, Inc. • 2585 Millennium Drive, Unit B • Elgin, IL 60124 • (800) 208.8181 • Fax (847) 289.9292 • www.aquariusfp.com

Page 9: Fire Pump Controller · 2015. 4. 2. · Manufactured by Metron, Inc. Standard and Optional Features All photographs and graphics are typical and may not represent actual product supplied

Fire Pump Controller For Electric Motor Driven Fire Pumps

MP430 Fire Pump Controller

Wye−Delta Reduced Current Types Series MP430 and Series MP435 − CombinedManual and Automatic Aquarius Fire Pump Controllers conform to the latest requirements of Chapter 10, National Fire Protection Association Pamphlet 20, Standard for Centrifugal Fire Pumps as adopted by Underwriters Laboratories and Factory Mutual. They are withstand rated and listed by Underwriters’ Laboratories and approved by Factory Mutual Research Corporation.

Sizes range from 15 to 700 horsepower, 200 to 600 volts, 60 Hz. These controllers are for use on Reduced Voltage type installations.

Only the highest quality components, all UL listed or UL recognized, are used throughout to assure the best possible reliability. The cabinet is fabricated of heavy gauge reinforced steel with drip-proof hood. All field wiring and service connections may be made from the front, allowing the controller to be mounted flush against a wall.

The controller is completely wired, assembled, and tested at the factory before shipment, and ready for immediate installation.

Manufactured by Metron, Inc.

TM

Aquarius Fluid Products, Inc.

Page 10: Fire Pump Controller · 2015. 4. 2. · Manufactured by Metron, Inc. Standard and Optional Features All photographs and graphics are typical and may not represent actual product supplied

Standard and Optional Features

All photographs and graphics are typical and may not represent actual product supplied

Standard Features Series MP430/MP435 Wye- Delta motors have all six leads brought out to the motor terminal box. These leads are connected by the controller first in the Wye configuration which draws only 33% of normal starting current and develops 33% of normal starting torque. After a short time delay, the controller then connects the motor winding in a Delta configuration, applying full voltage and drawing full load running current and developing full running torque.

With the MP430 open transition types, there is a very short period of time where no voltage is applied to the motor during transition from Wye to Delta connections. This condition can cause current surges or disturbances being fed back into the main power source. The magnitude of the surges is proportional to the phase difference between the voltage generated by the running motor and the power source. These transients can in some instances, affect other equipment which are sensitive to current surges.

The MP435 closed transition types provide a smoother transition from Wye to Delta by keeping the motor continuously energized during the transition period. This is accomplished by means of resistors which are connected in the circuit during the momentary period of transition from Wye to Delta.

Metron Wye-Delta Controllers incorporate a mechanical as well as electrical interlock to prevent the Wye connecting contactor from being energized at the same time as the Delta contactor.

An emergency start lever to close starting contactor independent of automatic control circuits. When used, this lever will bypass the reduced current start feature and start the motor with full inrush current drawn from the power source.

Operator Interface Device (OID) with LED Annunciator and Digital Display

• NEMA Type 2 drip proof metal freestanding enclosure • Operator Interface Device (OID) with 4 lines by 20 character

display with large character backlit Liquid Crystal Display (LCD) capable of being read in both direct sunlight or dark lighting conditions

• 10 pushbuttons for easy screen navigation, LED lamp test, alarm reset, controller test and horn silencing

• Removable labels to allow for easy field language changes • All controller settings are programmable through the OID. All

features are enabled or disabled through the OID, no jumpers or external wires are needed allowing easy field modification

• The system status data is displayed on the OID. The displayed items include: System pressure, Phase to Phase (AB, BC, AC) voltage, Phase current (A, B, C), Current time and date, System Events and Notifications such as Remote Start, Local Start etc., Number of starts, Total motor run hours, Time remaining on sequential motor start and motor stop timers, Status of automatic stop setting.

• Auxiliary alarm functions displayed on the OID LCD screen • Audible horn with silence feature for silencable alarms • Lamp test feature • Foreign languages selectable through the OID • Microprocessor based logic with real time/date clock capable of

running a minimum of 14 days without AC power connected to controller

• SD Memory card used to record pressure log, event and log, and auxiliary user programs. Pressure log is stored in separate comma delimited ASCII text files with each file containing data for one day. The SD card is removable and can be read by any PC equipped with an SD card reader.

• Input and output status LED's provide visual indication of each discrete input's or output's on/off status

• One RS485 Serial Port • MODBUS Communication Protocol via RS485 port • Service Entrance Rated

Standard Auxiliary alarms: The controller includes as standard six (6) discrete auxiliary inputs, nine (9) form 'C' auxiliary relay outputs. These auxiliary inputs and outputs are in addition to those mandated by NFPA 20. All auxiliary inputs, outputs, and OID Display can be field programmed through the OID.

Nine (9) of the following auxiliary alarms can be programmed and recorded in the event/alarm logs and annunciated on the OID display screen and/or output relay contact(s). These alarm conditions include:

LOW PUMP ROOM TEMP RESERVOIR LOW RESERVOIR EMPTY RESERVOIR HIGH FLOW METER ON RELIEF VALVE OPEN LOW SUCTION PRESSURE HIGH PUMP ROOM TEMPERATURE LOW FIREWATER PRESSURE LOW PURGE PRESSURE LOW GEAR OIL PRESSURE

Manufactured by Metron, Inc.

TM

Aquarius Fluid Products, Inc.

Page 11: Fire Pump Controller · 2015. 4. 2. · Manufactured by Metron, Inc. Standard and Optional Features All photographs and graphics are typical and may not represent actual product supplied

HIGH GEAR OIL TEMPERATURE GAS DETECTION HIGH VIBRATION EMERGENCY POWER ONPUMP ROOM DOOR OPEN

Data logging:The controller includes two (2) separate data logs for storing system data that is readable through the OID or copied to a computer equipped with an SD card reader. The 2 data logs are as follows:

Pressure Log: The pressure log provides a continuous pressure record for 30 days. The pressure log samples shall be time and date stamped and stored in permanent non-volatile SD memory card. The pressure log can be searched by each sample, by minute, or by hour through the OID.

Event Log: The event log will store up to 300 of the most current events. These events can include, but is not limited to, any of the following events/alarms:

PUMP RUNNING POWER AVAILABLE PHASE REVERSAL MOTOR OVERLOAD REMOTE START LOCAL START PUMP ON DEMAND SYSTEM FAULT PRESSURE TRANSDUCER FAULT PUMP FAILED TO START LOW INTAKE SHUTDOWN ALARM SUPERVISORY POWER FAILURE LOW PRESSURE AUTO WEEKLY TEST START UNDER FREQUENCY OVER FREQUENCY LOW ZONE / HIGH ZONE CONTACTS HIGH DISCHARGE PRESSURE NO LOAD CONDITION

OptionsOption H: Space Heater If the ambient atmosphere is especially damp, a space heater rated at 100 watts may be supplied to reduce moisture in the cabinet. A thermostat is supplied as standard with this option. A humidistat may be substituted if specified.

Option W: Omit Legs For systems where the controller is mounted on a common skid with the pump and motor, the legs of the controller may be omitted, 3” (76.2mm) channels or wall mounting brackets can be supplied. If specified, lifting eyes may also be supplied.

Enclosure The following NEMA type enclosures are also available: 3R, 4, 4X (Painted Cold Rolled Steel), 4X (304 or 316 Stainless Steel), and 12

TM

Aquarius Fluid Products, Inc.

Manufactured by Metron, Inc.

Page 12: Fire Pump Controller · 2015. 4. 2. · Manufactured by Metron, Inc. Standard and Optional Features All photographs and graphics are typical and may not represent actual product supplied

Fire Pump Controller For Electric Motor Driven Fire Pumps

_____________________________________________________________________________________________________________

Bulletin MP430/MP435 05/10vØ

Model MP430/435 Wye-Delta Start Microprocessor Electric Motor Fire Pump Controller

SpecificationsGeneral Controller Description

The Fire Pump Controller shall be factory

assembled, wired and tested as a unit and shall

conform to all requirements of the latest edition

of NFPA 20, NFPA 70 and be Third Party Listed

by Underwriters Laboratories (UL) and

Approved by Factory Mutual (FM). The

controller shall be available for 208, 230, 380-

415, or 480 volt three phase power.

Controller Equipment Features

The controller shall include the following

standard features:

• NEMA Type 2 drip proof metal freestanding

enclosure

• The controller shall be designed for Wye-Delta

starting and shall start the motor in the Wye

configuration drawing 33% of normal current,

then connect the motor in the Delta

configuration applying full voltage.

• Operator Interface Device (OID) with 4 lines

by 20 character display with large character

backlit LCD capable of being read in both

direct sunlight or dark lighting conditions

• 10 pushbuttons for easy screen navigation,

system test, lamp test, alarm reset, and horn

silencing

• Multicolored LED's for alarm and mode

annunciation

• LEDs shall be labeled with removable labels

to allow for easy field modification of

language changes

• All controller settings shall be programmable

through the OID and shall be protected by two

password levels

• All features shall be enabled or disabled

through the OID, no jumpers or external wires

shall be needed or allowed to activate or de-

activate a feature

• The system status data shall be displayed on

the OID. The displayed items shall include:

System pressure, Phase to Phase (AB, BC,

AC) voltage, Phase current (A, B, C), System

Events and Notifications, Current time and

date, Number of starts, Total motor run hours,

Displayed countdown timers for: Sequential

motor start and motor stop, Status of

Automatic Stop Setting.

• Audible horn with silence feature for

silencable alarms

• Lamp test feature

• Foreign languages selectable through the OID

• Microprocessor based logic with real time/date

clock capable of running a minimum of 14

days without AC power connected to

controller and non-volatile flash memory to

permanently store the continuous pressure log,

event log, alarm log and all user changeable

set points and system data. Battery backup of

any kind not allowed.

• Input and output status LED's to provide visual

indication of each discrete input's or output's

on/off status

• One RS485 Serial Port

• MODBUS Communication Protocol via

RS485 port

• All wiring terminals on PCB's shall be

removable type

• Service Entrance Rated

Auxiliary alarms

As standard the controller shall include 6 discrete

auxiliary inputs, 9 form 'C' auxiliary relay

outputs. These auxiliary inputs and outputs are

in addition to those mandated by NFPA 20. All

auxiliary inputs, outputs, and OID screens shall

be field programmable through the OID. This

permits a multitude of customizable controller

configurations to meet each installations unique

needs without adding cost to the controller. The

use of jumpers, soldering, or other external

components are not allowed.

The user can select any 9 of the following

auxiliary alarms that can be programmed and

recorded in the event log and annunciated with

an OID screen and output relay contact for

conditions such as but not limited to:

LOW PUMP ROOM TEMP RESERVOIR LOW RESERVOIR EMPTY RESERVOIR HIGH FLOW METER ON RELIEF VALVE OPEN LOW SUCTION PRESSURE HIGH PUMP ROOM TEMPERATURE LOW FIREWATER PRESSURE LOW PURGE PRESSURE LOW GEAR OIL PRESSURE HIGH GEAR OIL TEMPERATURE GAS DETECTION HIGH VIBRATION EMERGENCY POWER ONPUMP ROOM DOOR OPEN

Data logging The controller shall have separate data logs for

storing system data that is readable through the

OID.

Pressure Log: The controller shall have a

Pressure log with continuous pressure recording

of 30 days of data. The pressure log samples

shall be time and date stamped and stored on a

removable SD card memory. The pressure log

shall be searchable by each sample, by minute, or

by hour. Each days entries shall be stored in a

separate file on the SD card. SD memory shall be

readable by any PC equipped with an SD

memory card reader.

Event Log: The event log shall be capable of

storing no less than 3000 events. These events

shall include, but is not limited to, any of the

following events/alarms:

PUMP RUNNING POWER AVAILABLE PHASE REVERSAL MOTOR OVERLOAD REMOTE START LOCAL START PUMP ON DEMAND SYSTEM FAULT PRESSURE TRANSDUCER FAULT PUMP FAILED TO START LOW INTAKE SHUTDOWN ALARM SUPERVISORY POWER FAILURE LOW PRESSURE AUTO WEEKLY TEST START UNDER FREQUENCY OVER FREQUENCY LOW ZONE / HIGH ZONE CONTACTS HIGH DISCHARGE PRESSURE NO LOAD CONDITION

Each event or alarm recorded in the event log

shall have the following data recorded with the

event/alarm:

• Time and Date of Event or Alarm

• System Pressure

• Descriptive Text Message of the Event/Alarm

• Motor Running Status

• Phase to Phase Volts

• Phase Amps

The internal logic of the controller shall be

capable of operation in a temperature range of

4.4ºC to 40ºC and high, non-condensing,

humidity levels.

The controller shall be manufactured by Metron.