Ins tal lat ion An d Operat ing Ins t ruct ion s
For
A ux i l iary Contro l Uni t (ACU)
FIRESCAN ®
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 2/15
FIRESCAN ®
Page 2 of 15October, 2001
CONTENTS
1.0 INTRODUCTION
2.0 INSTALLATION PROCEDURES
2.1) SCHEMATICS DIAGRAM OF RCP AND ACU
3.0 SYSTEM OPERATION PROCEDURES
3.1) ICONS AND ITS FUNCTIONS
3.2) FIRE-ALERT!
3.2.1) FALSE ALARM
3.3) MAKING OUTGOING CALLS
3.4) RECEIVING IN-COMING CALLS
3.5) MAKING CALLS TO FIRESCAN ACU FOR REMOTE VIDEO SURVEILLANCE
4.0 TECHNICAL SPECIFICATION
5.0 SAFETY PRECAUTIONS
6.0 PERIODIC MAINTENANCE
7.0 TROUBLESHOOTING
8.0 AFTER -SALES CUSTOMER SUPPORT
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 3/15
FIRESCAN ®
Page 3 of 15October, 2001
1.0 INTRODUCTION
This manual describes the installation and operating instructions of FIRESCAN
Auxiliary Control Unit (ACU).
The Auxiliary Control Unit (ACU) is designed to interface with FIRESCAN Release
Control Panel (RCP) and or other type of Fire Detection and Suppression Release
Panels using a DSP (Digital Signal Processing) microprocessor to perform video
post-recording (record up to 3 cameras) of fire events and to provide remote video
surveillance of the protected premises with emergency auto dial-out ability to 3 pre-
programmed telephone numbers informing fire outbreak through pre- recorded
messages. The unit can be easily installed and connected to all types of Fire /
Release Control Panels.
When a fire event occurs, the ACU will receive an alarm signal from the Release
Control Panel and it will activate as follows:
a) Commence video recording of the respective fire zone for 30 seconds.
b) Commence emergency dail-out to 1st pre -programmed number and play pre -
recorded SOS voice messages twice when connection is through.
c) Repeat emergency dial-out for 2nd & 3rd pre-programmed numbers.
d) Wait for call in.
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 4/15
FIRESCAN ®
Page 4 of 15October, 2001
2.0 INSTALLATION PROCEDURES
Proper system installation requires the following steps (See Figure 2A for the Wiring
Diagram ): -
1. Connect the 24VDC (e.g. auxiliary power output from FIRESCAN RCP or othersFire Panel) to the ‘+24VDC’ and ‘-24VDC’ terminals (located at 6-way block
terminal) of the ACU.
2. Connect the ‘RS485’ terminal from FIRESCAN RCP to the ‘RS485 Terminal’
(located at 6 way Block Terminal) of the ACU, OR
3. Connect the ‘Normally Open Relay Contact Terminal’ from other type of Fire /
Release Control Panels to the ‘Relay Input’ terminal (located at 6 way Block
Terminal) of the ACU.
4. Connect the telephone line to the ‘LINE’ port of the ACU.
5. Connect the Coaxial/Video cable (from Camera) to the ‘V1’, ‘V2’ and ‘V3’ (located
at facial plate) of the ACU.
6. Connect the camera power of 12VDC to the ‘+12VDC PWR OUTPUT’ (located at
facial plate) of the ACU.
7. Connect the Video Cable (from Television/Monitor) to the ‘VIDEO OUT’ (locatedat facial plate) o f the ACU.
8. Connect the Pan/Tilt/Zoom Controller cable (from Dome Camera) to the ‘RS485’
terminal (located at 6 way Block Terminal) of the ACU. (Optional)
9. Connect the earphone with microphone to the ‘SPK’ and ‘MIC’ (located at facial
plate) of the ACU. (Optional)
10. Check all the connections against the Wiring Diagram (Figure 2A) to ensure
that all the wirings are correctly done.
11. Power ON the ACU and now you have completed your system set-up.
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 5/15
FIRESCAN ®
Page 5 of 15October, 2001
2.1 Wiring Diagram (Figure 2A)
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 6/15
FIRESCAN ®
Page 6 of 15October, 2001
3.0 SYSTEM OPERATION PROCEDURES
3.1 Icons and its functions
The definition of the basic icons and their functions is tabulated below.
NOTE: Use the ‘FUNC’ key on the keypad to get to the desired icon/function or use‘FUNC’ key to return to the previous icon/function).
Icon(TV display) LCD Display Redial:1 Set: ?
Functions - Press ‘1’ on keypad to redial. Phone number appears on screen.(If you have dialed the wrong number, press ‘CLR’ to reset the system.)
- Press ‘ ? ’ to enter into Settings Menu.
Icon(TV display) LCD Display
Pickup:1 Fire:2Key:3 C:4 B:5
Functions Settings Menu:-- Press ‘1’ for Incoming Call Setting- Press ‘2’ for Fire Alert Emergency Dial -out Number and Message- Press ‘3’ for Password Setting- Press ‘4’ for Contrast Select- Press ‘5’ for Brightness Select
Icon(TV display) LCD Display
Auto: ? Manual:#[ ]
Functions Incoming Cal l Setting:-- Press ‘ ? ’ for auto answer - Press ‘#’ for manual answer
Icon(TV display) LCD Display Tel No.:1 2 3Record:4
Functions Set Fire Alert Emergency Dial-out Number and Message:-- Press ‘1’, ‘2’ or ‘3’ to indicate the first, second or third party to call out
upon emergency.- Press ‘4’ to record message. When the “ ” icon appears, speak into
the earphone to record the message for 20 seconds. (Remember tospecify your site address and the state of emergency)
Icon(TV display) LCD Display Change
PasswordFunctions Password Setting:-
- Use the keypad to enter any 4- digit number.- After entered the password the “ ” icon appears on thescreen. The new password is now automatically saved.
- You should not reveal your password to unauthorized person.
(Note: the password is used when dialing in to ACU for auto connection.)
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 7/15
FIRESCAN ®
Page 7 of 15October, 2001
Icon(TV display)
LCDDisplay
Contrast12345678[ ]
Functions Contrast Select:-- To adjust color contrast of picture.- Press ’8’ for highest contrast.
Icon(TV display) LCD Display
Brightness:12345678 [ ]
Functions Brightness Select:-- To adjust brightness of picture.- Press ’8’ for maximum brightness.
Icon(TV display) LCD Display
Sensor:ON: ? OFF:# [ ]
Functions Turning ON/OFF the Sensor Circuitry:-- Press ‘ ? ’ to turn ON the sensor circuitry. The red LED situated on facial
plate of ACU will illuminate and the system now is activated.- Press ’#’ to turn OFF the sensor circuitry. The red LED will turn-off.
System shall not respond to any fire alert.
Icon(TV display) LCD Display
Select Camera:1 2 3 [ ]
Functions Select Camera:-- When performing remote surveillance or CCTV, a camera may be
selected.- Select desired camera by indicating its number ‘1’, ‘2’, or ‘3’.- Once power on the system, its default setting is always camera ‘1’.
Icon(TV display) LCD Display
View:1&2 Fz:3&4
Play:5 Stop:6 [ ]Functions Set Large/Small View, Freeze/Unfreeze & Recorded Video Playback:-
- Press ‘1’ for Large view, ‘2’ for small view.- Press ‘3’ to freeze picture and ‘4’ to unfreeze.- Press ‘5’ for recorded video playback and ‘6’ to stop during local mode.
Icon(TV display) LCD
DisplayCamera PTZ: L4R6U2 D8 ?5 O0 [ ]
Functions Camera PAN/TILT/ZOOM (where camera focus can be physically shifted):-- Press ‘4’ on keypad to pan left, ‘6’ to pan right, ‘2’ to tilt up and ‘8’ to tilt
down.- In addition, press ‘5’ and ‘0’ to zoom in and zoom on the subject.- Adjust the speed of camera by pressing ‘ ? ’ to increase or ‘#’ to decrease.
- The “ ” icon appears on the screen and the 2 x 16
- LCD will display “ Speed 1234567”; press ‘1’ for lowest speed and ‘7’ for highest speed.
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 8/15
FIRESCAN ®
Page 8 of 15October, 2001
Icon(TV display) LCD
DisplayDigital PTZ: L4R6U2 D8 ?5 O0 [ ]
Functions Digital PAN/TILT/ZOOM (of screen view):-- Press ‘4’ to pan left, ‘6’ to pan right, ‘2’ to tilt up and ‘8’ to tilt down, press
‘5’ and ‘0’ to zoom in and zoom on the subject.
Icon(TV display) LCD Display
Quality:12345678Password ? [ ]
Functions Quality Select:-- During video mode, user is able to select video quality, press ‘8’ for
maximum quality.- Higher video quality results in slower frame speed, i.e. slower picture
movement than real time.- Press ‘ ? ’ to change the password of remote site during video mode.
- Use keypad to enter the old password when the “ “icon appears on the screen.
- After entered the old password, the “ “icon appears on the screen. Now enter the new password with any 4 -digit number.
- After entered the new password the “ ” icon appears onthe screen. The new password is now automatically saved.
Icon
(TV display)LCDDisplay
LoadVideo:1 ? # [ ]ViewVideo:2 ? # [ ]
Functions Download Recorded Video & Review Video:-- During video mode, user is able to review the recorded video.- Press ‘1’ followed by ‘ ? ’ to start download video or press ’#’ to stop. The
“ ” icon appears on the screen to indicate that
ACU is downloading the recorded video.
The “ ” icon appears to indicate the video
has been received & auto -saved.
- Press ‘2’ followed by ‘ ? ’ to review the recorded video or ‘#’ to stop.
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 9/15
FIRESCAN ®
Page 9 of 15October, 2001
3.2 Fire Alert!
The following process occurs when 1 st Alarm or Manual Release Station of the FireControl Panel is activated.
1 s Alarm / Manual Release Station
Auxil iary Control Unit will record event for 20-30 second.- For Single C hannel: only record event of 1 st camera- For Two Channels: parallel recording event of 1 st and 2 nd camera- For Three Channels: parallel recording event of 1 st , 2 nd and 3 r d camera
Auxiliary Control Unit receives signal to dial out to three preset telephonenumbers (1, 2 and 3) consecutively
First party (e.g. factory owner) receivescall and pre-recorded SOS voicemessages twice. ACU will auto-reset.
Second party (e.g. fire brigade) receivescall and pre-recorded SOS voicemessages twice. ACU will auto -reset.
Third party (e.g. relatives) receives calland pre-recorded SOS voice messagetwice.
Owner can dial out to ACU to view theprotected premises toascertain situation.
1 st Call
During this period, owner can dial in to ACU to viewthe protected premises toascertain situation.
2 n Call
3 rd Call
Auxiliary Control Unit resets i tsel f
20-sec Interval
20-sec Interval
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 10/15
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 11/15
FIRESCAN ®
Page 11 of 15October, 2001
3.4 Receiving In-coming Calls
1. The receiver presses the ‘ANS’ key to answer the call.
2. To enter into video conferencing, either party presses the ‘FUNC’ key.
3. The ‘ ’ icon appears on the TV screen and ‘VideoConnecting ’ appear on the 2 x 16 LCD display. The waiting time is approximately10 to 20 seconds, depending on the line speed.
4. When the ‘ ’ icon appears, the TV screen will display thevideo image of both parties.
5. To select screen preference or change video quality, refer to icons in section 3.1.
6. To cancel or disconnect the video function, either party presses the ‘CLR’ key tocut off. FIRESCAN ACU may be used as a standard telephone set.
3.5 Making Calls to FIRESCAN ACU For Remote Video Surveillance
1. Using a CyberEye Transceiver or a Spartadial or another ACU from another site,the caller presses the “Dial” key to enter the phone number of the desired ACUand wait for the activation of the unit (if you have dialed the wrong number, press‘CLR’ to reset the system).
2. The ACU will automatically be activated after 5 ringing tones and 2 beepsthereafter to indicate successful connection.
3. Press ‘FUNC’ key immediately to enter into video mode.
4. The ‘ ’ icon appears on the TV screen and ‘Video Connecting ’
appear on the 2 x 16 LCD display. The waiting time is approximately 10-20seconds, depending on the line speed.
5. The unit will request for password authorization on the screen.
6. Enter the password in order to activate video mode.
7. Upon keying the correct password, the ‘ ’ icon appears, the ACU will enter into video mode.
8. To select camera or adjust video quality, refer to icons in section 3.1.
9. To cancel or disconnect the video function, press the ‘CLR’ key to terminate theline connection.
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 12/15
FIRESCAN ®
Page 12 of 15October, 2001
4.0 TECHNICAL SPECIFICAT ION
* 3 Video Inputs (for camera)
* 1 Relay Input – Normally Open Relay Contact (from Alarm Relay Output of other
type of Fire / Release Control Panel)
* 1 RS485 Connector (to FIRESCAN Release Control Panel & Pan/Tilt/Zoomcamera)
Video Input OutputChannel : 3 1
(one active channel per view) (active channel only)
Scanning system : PAL/NTSC PAL/NTSCcomposite color composite color
Input impedance : 75 ohm 75 ohm
Signal amplitude : 1 Vp-p 1 Vp-p
Line OutputPhysical media : POTS line
Line : 1
Data rate : 33.6 kbps
Data format : H.324 (include H.263, G.723, H.223, H.245)
Video FormatData format : H.263
Resolution : 352 x 288(CIF), 176 x 144 (QCIF)
Frame rate : Up to 15 fps for QCIF
Audio Input OutputChannel : 1 1
Audio Input* Condenser Microphone* Frequency : 50~6300 Hz
Audio Output* Impedance : 32 Ohms* Frequency : 100~6200 Hz
Power Requirement* Input Voltage : [email protected]* Output Voltage : [email protected], [email protected]
Dimensions : (L) 380mm x (W) 250mm x (H) 100mm
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 13/15
FIRESCAN ®
Page 13 of 15October, 2001
5.0 SAFETY PRECAUTIONS
1. Make sure the installation is always secured and well connected.Improper installation or connection to the devices may resul t in a short- circuit,causing a fire or equipment damage!
2. Keep the FIRESCAN Auxiliary Control Unit away from water.If FIRESCAN Auxiliary Control Unit is drenched, shut down the power supplyand replace with a new ACU.
3. Terminate power supply in case of irregular functioning.Turn off the power supply if smoke or unfamiliar smell is observed. Continualusage of the FIRESCAN Auxiliary Control Unit under irregular conditions maycause damage and result in injury.
4. Treat connection cables wit h care .Do not cut or change the cables, handle cables abruptly or place weights onthe cable. Avoid exposing cables to high temperature.
5. Do not try to service the ACU by removing the cover.Mishandling the system may cause short-circuit, a fire or equipment damage.
6. Do not mount the ACU near flammables. Flammable gases or objects near the camera may cause fi re and severeinjury.
7. Do not handle power connections with damp or wet hands.May result in short circuit or electrical shock.
6.0 PERIODIC MAINTENANCE
1. Weekly - Reset the power supply.
2. Yearly - Contact WILLIAMSON & KING -trained and authorizeddistributors for a complete system checkout and service.
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 14/15
7/27/2019 Fire Protection Installation and Operation Manual
http://slidepdf.com/reader/full/fire-protection-installation-and-operation-manual 15/15
FIRESCAN ®
Page 15 of 15October, 2001
8.0 AFTER-SALES CUSTOMER SUPPORT
In case of trouble, please contact WILLIAMSON & KING-trained and authorizeddistributors at: -
WILLIAMSON & KING PTE LTD81 LOYANG WAYSINGAPORE 508767
TEL : (65) 6545-1188FAX : (65) 6545-2139
Website: www.williamsonking.comEmail: [email protected]