Pneumatic Actuated with Local Reset Deluge Valve
Deluge Systems
ADVANTAGES
CHARACTERISTICS
The FDV is a Fire Protection control valve for Deluge fire sprinkler systems, designed for installations in hazardous environments. The FDV-DP0 Deluge system is actuated pneumatically and resets locally. When the pneumatic dry pilot detection line is exposed to flame heat, its automatic fire sprinklers shatter-open, while venting the air pressure from the FDV-DP0’s actuator, commanding the deluge valve to open.The Deluge system incorporates an emergency valve, bypassing the fire detection systems for manual operation.Designed for vertical or horizontal installation, a globe pattern, line pressure operated FDV-DP0 valve features a direct elastomeric diaphragm seal. It has no balancing spring or internal metallic wet components in the valve body. The hydrodynamic pattern design, ensures high flow rates with minimum head loss.
Only three parts: body, diaphragm & cover plate. No wet metal spring inside the control chamber Full bore unobstructedSimple manual reset of the valve to standby position without draining or opening the valve itself, neither closing OS&Y or other valves in the systemOpen fail safe valve, maintained in stand-by closed positionLow maintenance cost: the valve is serviced in-line with only one replaceable part which is long life elastomeric diaphragm Conforms with inspection, testing and maintenance standard of water-based fire protection systems, NFPA 25
Hydro-dynamic pattern design ensures high flowrates with minimum head lossThe valve trips open automatically upon a gradual release of water pressure from its control chamber. The trip is actuated by Dry Pilot Line’s pneumatic pressure release due to its exposure to flame heatSoft closing upon pressurization of the valve’s control chamber, by line pressure or other independent water source, prevents surges
•
••
•
•
•
•
•
•
FDV - DP0Fire
Pro
tect
ion
M A R K E T S
T E C H N I C A L D ATA
Commercial Residential
21
The FDV-DP0 resets to stand-by close position by pressurizing the Dry Pilot Line and manually operating the PSA device.
FLUID:Water, Brackish water, Sea water, Foam SIZE RANGE:40mm to 250mm (1½’’ to 10”)AVAILABLE CONNECTIONS ENDS:Flange*Flange, Groove*Groove, Flange*Groove, Groove*Flange,Thread*ThreadPRESSURE NOMINAL:250 psi (17.2 bar)
Marine
A P P R O VA L S
P.O.G. Industry
Schematic drawing
OPERATION
SET positionPressurized water in the valve’s control chamber (DL) is trapped by the closed PSA (PA), the closed PA-PTC actuator (PC) and by the closed emergency valve (EU), maintaining the FDV Deluge valve (DL) closed.
FIRE situationWhen some of the Dry Pilot detection line’s automatic fire sprinklers are subjected to flames heat and shatter-open, the pilot detection line depressurizes the PA-PTC control chamber. The PA-PTC (PC) opens and drains the deluge valve’s control chamber.The FDV deluge valve opens and admits water to the spray sprinklers line.
RESET positionSystem reset requires the replacement of all the Dry Pilot detection Line’s shattered-open automatic fire sprinklers.The detection line is then pressurizing together with the PA-PTC actuator, to reset it to closed position.The PSA (PS) push button should be pressed to enable the control chamber filling, closing the FDV deluge valve.
Set position Fire position
Fire
Pro
tect
ion
TALI
S FP
RAN
GE
22
BF - Butterfly valveDL - FDV Deluge valveAL - Acoustic & Electric alarmsTS - Trim supply valve
SR - “Y” strainerCV - Check valvePS - PSA – Pressure Supply ArrestorMA - MADV – Man/Auto Drain Valve
TV - Alarm test valveEU - Emergency Manual UnitPC - PA-PTC – PneumaticActuator-Pressure to Close
Fire
Pro
tect
ion
23
FDV - DP0Typical installation
MD
PC
PS
CVSRTV
TS
AL
DL
EU
BF
BF - Butterfly valveDL - FDV Deluge valveAL - Acoustic & Electric alarmsTS - Trim supply valve
SR - “Y” strainerCV - Check valvePS - PSA – Pressure Supply ArrestorMA - MADV – Man/Auto Drain Valve
TV - Alarm test valveEU - Emergency Manual UnitPC - PA-PTC – PneumaticActuator-Pressure to Close
Fire
Pro
tect
ion
TALI
S FP
RAN
GE
24
Dimensions Table
Vertical
A 314 384 300 11.8 327 12.9268 231 220
630.8 296 11.7
94 84 2.5 61 2.4
12.4 15.210.5 93.7 3.38.8 12.84.6 2.66.5 76.740.7
7.968
224 325 462 18.2 580 22.8117 66 -164 180 230 9 254 1017018.5
20030.8
3952447340040
20624047.7
30266.2
11.9146
335105.8
13.2233.3
15.59.62.915.81.68.19.5
105.2
BCDEFG
Kg/lb
Size1 1/2” 2” 3”
mm mm mm mm mmInch Inch Inch Inch Inch
4” 6” 8”
Size1 1/2” 2” 3”
mm mm mm mm mmInch Inch Inch Inch Inch
4” 6” 8”
Horizontal
A 314 381 420 16.5 398189 201 240
-9.5 268
- 31 - -
12.4 157.4 7.9- 1.2
8.8 12.85 1.9
6.5 78.242
9.468
224 325 462 18.2 580127 47 - - -164 180 231 9 25720919
23930.8
395215-
40013
20727847.7
34166.4
13.4146.5
374105.7
15.710.5
-228
-10.214.7
223.2
15.68.5-
15.80.58.510.9105.2
BCDEFG
Kg/lb
PIPING & TUBING:
Stainless Steel 316
Copper/Brass
Cupro-Nickel
Monel®
FITTINGS:
Stainless Steel 316
Brass
Super Duplex
Cupro-Nickel
Monel®
ACCESSORIES:
Brass Nickel plated
Nickel Aluminium bronze
Stainless steel CF8M
Monel®
Cupro-Nickel
TRIM
•
•
•
•
•
•
•
•
•
•
•
•
•
•
BODY & COVER
Ductile iron
Cast Steel WCB
Stainless Steel CF8
Stainless Steel CF8M
Nickel Aluminum Bronze
ELASTOMERS:
NBR, 3 layer reinforced natural rubber
EPDM, 3 layer reinforced
COATING:
Rilsan Polyamide based (Nylon 11)
Polyester based EPC
High built Epoxy FBE
Vitreous Enamel (internal only)
MAIN VALVE:
Factory Standard
•
•
•
•
•
•
•
•
•
•
•
Working Media
Ambiental conditions
Min/Max operating flow
Min/Max operating pressure
Energize to Open/Close valve
Pneumatic working pressure
System installation orientation
Additional accessories needed
PLEASE SPECIFY
•
•
•
•
•
•
•
•
For more detailed technical information, please refer to chapter Engineering Data.