FIRE FIGHTING COURSE Prepared by Eng/ Magid elithyrevised by Eng / Sayed Abd el Hamied
![Page 3: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/3.jpg)
3
TABLE OF CONTENTS
Overview of Firefighting Single Line Diagram Pumps & Pump Room Sprinklers Systems
![Page 4: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/4.jpg)
4
OVERVIEW OF FIREFIGHTING
Fire Triangle parameters :-
1. Air ( Oxygen )
2. Fuel ( Flammable Material )
3. Heat ( sufficient heat to raise
the material to its ignition temperature )
![Page 5: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/5.jpg)
5
OVERVIEW OF FIREFIGHTING
Fire Fighting methods :-
, by creating a barrier using foam for instance and prevent oxygen getting to the fire By applying water you can lower the temperature below the ignition temperature
![Page 6: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/6.jpg)
6
OVERVIEW OF FIREFIGHTING
Fire Fighting Systems
Manual
Manual extinguish
erCabinet Siamese
connection Fire
hydrant
Automatic
Sprinklers SYS
![Page 7: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/7.jpg)
7
OVERVIEW OF FIREFIGHTING
Materials ( Manual & Automatic )
Water FM20
0 Co2 Halon Dry Chemical powder
Foam
![Page 8: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/8.jpg)
8
SINGLE LINE DIAGRAM
Single Line Digram 2.dwg
Pump Room
Tank
Manual Systems
Automatic systems
Siamese connectio
n
Cabinet
Sprinklers
First Water source
Second Water
source
![Page 9: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/9.jpg)
9
Pump Room
![Page 10: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/10.jpg)
10
PUMP ROOM
Delivered water from tank to firefighting systems
Pump Room
Tank
Cabinet
Sprinklers
![Page 11: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/11.jpg)
11
PUMP ROOM
Types of Pumps
Centrifugal
Horizontal & Vertical
Positive displacement
Horizontal & Vertical
![Page 12: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/12.jpg)
12
PUMP ROOM
Horizontal Centrifugal Pump Vertical centrifugal pump
![Page 13: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/13.jpg)
13
Centrifugal pump
OverhungImpeller between bearing
![Page 14: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/14.jpg)
14
CENTRIFUGAL PUMPS
The main purpose is to convert energy of a mover (Electric motor ) first to velocity (kinetic energy ) and then into pressure energy ( Static energy )
Energy chance occur by two main parts 1-Impeller ( Rotating part that convert driver energy into kinetic energy ) 2-The Volute or Diffuser ( Stationary part that convert the kinetic energy to static energy (Pressure energy))
Working mechanism of centrifugal pump
![Page 15: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/15.jpg)
15
GENERATION OF CENTRIFUGAL FORCE
The liquid enter the suction nozzle and then
into eye of impeller
When the impeller rotates it spins the liquid sitting
in the cavities between the vanes outward and provides
centrifugal acceleration
As liquid leaves the eye of the impeller a low –
pressure area is created causing more liquid to flow
towards the inlet First Step :
Conversion Motor Energy Into Kinetic
Energy
![Page 16: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/16.jpg)
16
GENERATION OF CENTRIFUGAL FORCE
Resistance to the flow : the first resistance to the flow
is created by the pump casing ( Volute ) that catches the liquid and
slow it down ………..
Its velocity converted to pressure according to Bernoulli's equation
Second Step :
Conversion Kinetic Energy Into Pressure
Energy
![Page 17: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/17.jpg)
17
FORMULA :-
This head can also be calculated from the readings on the pressure gaugesattached to the suction and discharge lines
![Page 18: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/18.jpg)
18
FACTOne fact that must always be remembered: A pump does not create pressure, it only provides flow. Pressure is a just an indication of the amount of resistance to flow.
![Page 19: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/19.jpg)
19
Centrifugal pump has two main component
1-Rotating components comprised of an impeller and the shaft
2-Stationary components comprised of a casing and bearing
![Page 20: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/20.jpg)
STATIONARY COMPONENTS
CASING
Volute casing Circular casing
Volute casing increase the area to the discharge port , as the area of the cross section increase the volute reduce the speed of the liquid and increase the
pressureVolute casing : build HIGH head ,
Circular casing are used for LOW head and HIGH capacity
Have a stationary diffusions vanes surroundings the impeller periphery
that convert velocity energy into pressure energy
![Page 21: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/21.jpg)
21
casing
Spilt casing Solid Casing
A design in which the entire casing including the discharge nozzle is all contained in one casting or fabricated piece
Two or more parts are fastened together. When thecasing parts are divided by horizontal plane, the casing is described as horizontally split or axially split casing. When the split is in a vertical plane perpendicular to the rotation axis, the casing is described as vertically split or radially split casing.
![Page 22: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/22.jpg)
22
SUCTION AND DISCHARGE NOZZLE
End suction Top
Discharge
Top suction Top
Discharge
Side suctionSide
Discharge
The suction nozzle is located at the end of, and concentric to, the shaft while the discharge nozzle is located at the top of the case perpendicular to the shaft
The suction and discharge nozzles are located at the top of the case perpendicular to the shaftalways a radially split case pump
The suction and discharge nozzles are located at the sides of the case perpendicular to the shaft. This pump can have either an axially or radially split case type.
![Page 23: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/23.jpg)
23
ROTATING COMPONENTS
Impeller
direction of flow
suction type
mechanical construction
Radial flowAxial flow
Mixed
flow
Single-suctionDouble-suction
ClosedOpen
![Page 24: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/24.jpg)
24
CENTRIFUGAL PUMP PARAMETERS
Capacity :- Defi nition :-Capacity means the fl ow rate with which l iquid is moved or pushed by the pump to the desired point in the process. It is commonly measured in either gallons per minute (gpm) or cubic meters per hour (m3/hr). The capacity usually changes with the changes in operation of the process.
1 ( m3/Hr ) = 3.66 (GPM)
![Page 25: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/25.jpg)
25
The capacity depends on a number of factors like:
1-Process liquid characteristics i.e. density, viscosity
2-Size of the pump and its inlet and outlet sections
3-Impeller size 4-Impeller rotational speed RPM 5-Size and shape of cavities
between the vanes 6-Pump suction and discharge
temperature and pressure conditions
![Page 26: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/26.jpg)
26
FORMULA :-
![Page 27: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/27.jpg)
27
CENTRIFUGAL PUMP PARAMETERS (HEAD)
HEAD:- Signifi cance of using the “head” term instead of the “pressure” term
The pressure at any point in a l iquid can be thought of as being caused by a verticalcolumn of the l iquid due to its weight. The height of this column is called the static head and is expressed in terms of feet of l iquid.
![Page 28: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/28.jpg)
28
CENTRIFUGAL PUMP PARAMETERS (HEAD)
The same head term is used to measure the kinetic energy created by the pump.In other words, head is a measurement of the height of a l iquid column that the pumpcould create from the kinetic energy imparted to the l iquid
![Page 29: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/29.jpg)
29
CENTRIFUGAL PUMP PARAMETERS (HEAD)
The main reason for using head instead of pressure to measure a centrifugal pump's energy is that the pressure from a pump will change if the specifi c gravity (weight) of the l iquid changes, but the head wil l not change. Since any given centrifugal pump can move a lot of diff erent fl uids, with diff erent specifi c gravities, it is simpler to discuss the pump's head and forget about the pressure.
![Page 30: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/30.jpg)
30
FACT A given pump with a given impeller diameter and speed will raise a liquid to a certain height regardless of the weight of the liquid.
![Page 31: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/31.jpg)
31
FORMULA :-
liquids have specific gravities typically ranging from 0.5 (light) to 1.8 (heavy).
Water is a benchmark, having a
specific gravity of 1.0.
![Page 32: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/32.jpg)
32
DEFINITION :-
1-Static Suction Head, hS 2-Static Discharge Head, hd Total Static Head 3-Friction Head, hf 4-Vapor pressure Head, hvp 5-Velocity Head, hv 6-pressure head hp 7-Total Suction Head HS 8-Total Discharge Head Hd 9-Total Differential Head HT 10-Net Positive Suction Head Required NPSHr 11-Net Positive Suction Head Available NPSHa
![Page 33: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/33.jpg)
33
DEFINITION :-
1-STATIC SUCTION HEAD, HS
Head resulting from elevation of the l iquid relative to the pump center l ine. If the l iquid level is above pump centerline, hS is positive. If the l iquid level is below pump centerline, hS is negative
. Negative hS condition is commonly denoted as a “suction l ift” condition
![Page 34: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/34.jpg)
34
DEFINITION :-
2-STATIC DISCHARGE HEAD, HD
the vertical distance between the pump centerline and the surface of the
l iquid in the destination tank .
![Page 35: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/35.jpg)
35
DEFINITION :-
What is Static Head? In a pumping system, this head
represents the energy required to raise the l iquid from the pump centerline to the point in the pipe that the l iquid needs to be raised
![Page 36: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/36.jpg)
36
DEFINITION :-
3-FRICTION HEAD, HF
This is the loss needed to overcome that is caused by the resistance to fl ow in the pipe and fi ttings. It is dependent on size, condition and type of pipe, number and type of pipe fi ttings, fl ow rate, and nature of the l iquid.
![Page 37: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/37.jpg)
37
![Page 38: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/38.jpg)
38
DEFINITION :-
4-VAPOR PRESSURE HEAD, HVP
![Page 39: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/39.jpg)
39
DEFINITION :-
5-VELOCITY HEAD, HV
It is the equivalent head in feet through which the water would have to fall to acquire the same velocity,
![Page 40: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/40.jpg)
40
DEFINITION :-
6-PRESSURE HEAD HP
Suction Pressure Head existsbecause the suction tank is undera pressure other than atmospheric.It is the pressure acting on the surfaceof the liquid in the suction tank.This pressure can be positive (aboveatmospheric) or negative (vacuum).
![Page 41: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/41.jpg)
41
DEFINITION :-
7-TOTAL SUCTION HEAD HS This i s ca l led Tota l Sys tem Suct ion Head . Th is
i s a l so somet imes ca l led Tota l Dynamic Suct ion Head .
The equat ion to ca lcu la te th is head requirement
.Suct ion s ta t ic head i s pos i t i ve when there i s a fl ooded suct ion and negat ive when there i s a suct ion l i f t .
Pressure head i s zero i f the tank i s a tmospher ic . I t i s added when above zero gauge pressure and subtracted when under vacuum.
Ve loc i ty head theoret ica l l y i s par t o f the Sys tem Suct ion Head equat ion . In pract ica l app l ica t ion , i t i s rare ly cons idered as i t s va lue i s min imal
![Page 42: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/42.jpg)
42
DEFINITION
8-TOTAL DISCHARGE HEAD HD
![Page 43: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/43.jpg)
43
DEFINITION :-
9-TOTAL DIFFERENTIAL HEAD HTTOTAL HEAD SYSTEM TOTAL DYNAMIC HEAD
HT=HD-HS
![Page 44: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/44.jpg)
44
PUMP PERFORMANCE CURVE
Total dynamic Head
Capacity
Increasing capacity decreasing Head
![Page 45: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/45.jpg)
45
1 0 - N E T P O S I T I V E S U C T I O N H EA D R EQ U I R E D ( N P S H R )
As liquid enters the pump, there is a reduction of pressure and subsequent head. This head reduction is a function of the specific pump and is determined by laboratory testing to be stated by the pump manufacturer on a pump curve.
Net Positive Suction Head Required (NPSHR) is the measurement of this head reduction to determine the minimum suction head condition required to prevent the liquid from vaporizing in the pump.
![Page 46: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/46.jpg)
46
1 0 - N E T P O S I T I V E S U C T I O N H EA D R EQ U I R E D ( N P S H R )
Notice on the NPSHR curve below, as the pump capacity increases and head decreases, more NPSHR is required to prevent cavitation from occurring.
![Page 47: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/47.jpg)
47
DEFINITION
Efficiency
Efficiency is power output of a mechanical device, such as a pump, divided by power input to the device. Pump efficiency is the ratio of liquid power (also known as water power) divided by the power input to the pump shaft,(also known as brake power
![Page 48: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/48.jpg)
48
DEFINITION Best Efficiency point
![Page 49: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/49.jpg)
49
DEFINITION
Power Requirements
![Page 50: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/50.jpg)
50
![Page 51: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/51.jpg)
51
PUMP SELECTION
pss.jnlp
![Page 52: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/52.jpg)
52
PUMP OPERATIONS
Pumps operates by : -
Electric Engines
Diesel Engines
![Page 53: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/53.jpg)
53
PUMP ROOM CONTENTS
Pump Room
Electric pump
Jockey Pump
Diesel pump
![Page 54: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/54.jpg)
54
PUMP ROOM OPERATIONS
![Page 55: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/55.jpg)
55
PUMP ROOM SPECIFICATIONS
Any pump can be used to be Firefighting pumps as long as matching :-
1. NFPA (National Fire Protection Association)
2.LPC (Loss Prevention Council )
Manufacturing of pumps should be according to
1. American specs ANSI (American National Standards Institute )
2. British specs BS (British Standard )
3. Germany specs DIN (Diameter Nominal )
![Page 56: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/56.jpg)
56
PUMP ROOM SPECIFICATIONS
It should delivered with pumps test certification from manufacturer states about testing the pumps with its control panels
If the pump according American specs it should be UL or FM certification states about testing the pump according American specs
![Page 57: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/57.jpg)
57
NFPA (NATIONAL FIRE PROTECTION ASSOCIATION )
NFPA 20 (Installation of Stationary Pumps for Fire Protection )
1.3.1 This standard shall apply to centrifugal single-stage and multistage pumps of the horizontal or vertical shaft design and positive displacement pumps of the horizontal or vertical shaft design.
![Page 58: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/58.jpg)
58
NFPA (NATIONAL FIRE PROTECTION ASSOCIATION )
5.1.2 Other Pumps shall be limited to capacities of less than 1892 L/min (500 gpm).
The meaning of (SHALL) in nfpa code : Indicates a mandatory
requirement
![Page 59: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/59.jpg)
59
NFPA 20
The pump is required to demonstrate its ability to achieve 65% of rated pressure when flowing at 150% of rated capacity
Shut-off head will range from a minimum of 101% to a maximum of 140% of head
![Page 60: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/60.jpg)
60
![Page 61: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/61.jpg)
61
NFPA20
Gallon per minute according to NFPA20
![Page 62: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/62.jpg)
62
INSTALLATION OF PUMP
Pump Room Components
![Page 63: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/63.jpg)
63
INSTALLATION OF PUMP ROOM
1-Pump & Engine
![Page 64: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/64.jpg)
64
INSTALLATION OF PUMP ROOM
Suction Line Discharge Line Check Line
![Page 65: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/65.jpg)
65
INSTALLATION OF PUMP ROOM
Pump Room Connection
![Page 66: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/66.jpg)
66
![Page 67: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/67.jpg)
67
![Page 68: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/68.jpg)
68
INSTALLATION OF PUMP ROOM
pump room.dwg Pump Room 2.dwg
AutoCAD Drawings Pump Room (Electric ).dwg pump Room (Diesel ).dwg Pump Room 3d.dwg
![Page 69: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/69.jpg)
69
GALLERY
Gallery
![Page 70: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/70.jpg)
70
Concentric reducer
![Page 71: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/71.jpg)
71
Check Valve
![Page 72: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/72.jpg)
72
Diesel pump fuel tank
![Page 73: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/73.jpg)
73
Air Vent on discharge line
![Page 74: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/74.jpg)
74
Concentric & eccentric reducers
![Page 75: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/75.jpg)
75
Sprinklers Systems
![Page 76: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/76.jpg)
76
There are 4 main types of systems :-
Wet Pipe Dry Pipe Pre-Action Deluge
![Page 77: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/77.jpg)
77
WET PIPES SYSTEM
Wet pipe sprinkler systems contain water in the riser and piping at all times. As soon as a sprinkler head activates due to the heat of a fire, water is immediately discharged through the open head .
![Page 78: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/78.jpg)
78
![Page 79: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/79.jpg)
79
WET PIPE SYSTEM COMPONENTS MAIN CONTROL VALVE
Butterfly ValveOBJECTIVE :-Shut down system for service
![Page 80: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/80.jpg)
80
WET PIPE SYSTEM COMPONENTS
CONTROL VALVE
![Page 81: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/81.jpg)
81
When the fire protection system is initially being pressurized, water will flowinto the system until the water supply and system pressure become equalized, and the torsion Spring closes theClapper in the Alarm Check Valve. Once the pressures have stabilized
![Page 82: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/82.jpg)
82
Leakage in
System
Flow Inlet < Flow Outlet (1)
Flow Inlet > Flow Outlet (2)
Restriction
Assembly INLET
OU
TL
ET
2
1
![Page 83: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/83.jpg)
83
FIRE,FIRE
ALARM
![Page 84: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/84.jpg)
84
![Page 85: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/85.jpg)
85
CHECK VALVE SYMBOL CHECK VALVE
CHECK VALVE BLOCK Check Valve Block.dwg
![Page 86: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/86.jpg)
86
WET PIPE SYSTEM COMPONENTS
Friction Loss Chart ( Check Valve )
![Page 87: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/87.jpg)
87
![Page 88: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/88.jpg)
88
![Page 89: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/89.jpg)
89
![Page 90: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/90.jpg)
90
![Page 91: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/91.jpg)
91
![Page 92: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/92.jpg)
92
![Page 93: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/93.jpg)
93
DRY PIPES SYSTEM
Dry pipe sprinkler systems contain air (or sometimes nitrogen) in the riser and piping at all times. The air (or nitrogen) is under pressure and this pressure maintains a "differential dry pipe valve" in the closed position
![Page 94: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/94.jpg)
94
DRY PIPES SYSTEM
. When a sprinkler head activates, the air (or nitrogen) is exhausted through the open head, thus allowing the differential dry pipe valve to open and water to be admitted to the riser and piping.
![Page 95: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/95.jpg)
95
DRY PIPES SYSTEM
Some dry pipe systems are equipped with quick opening devices (QOD's) which assist in exhausting the air or nitrogen from the system thus allowing water to reach the open head more quickly. Dry pipe systems are installed where there is a danger of freezing.
![Page 96: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/96.jpg)
96
![Page 97: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/97.jpg)
97
![Page 98: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/98.jpg)
98
PROCEDURE
When one or more automatic sprinklers operate in response to a fire, air pressure within the system piping is relieved through the open sprinklers.
When the air pressure is sufficiently reduced, the water pressure overcomes the differential holding the Clapper Assembly closed and the Clapper Assembly swings clear of the water seat,
This action permits water flow into the system piping and subsequently to be discharged from any open sprinklers. Also, with the Clapper Assembly open, the intermediate chamber is pressurized and water flows through the alarm port.
![Page 99: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/99.jpg)
99
PROCEDURE
After a valve actuation and upon subsequent closing of a system main control valve to stop water flow, the Clapper Assembly will latch open Latching open of the DPV-1 will permit complete draining of the system through the main drain port. During the valve resetting procedure and after the system is completely drained, the external reset knob can be easily depressed to externally unlatch the Clapper Assembly
. As such, the Clapper Assembly is returned to its normal set position to facilitate setting of the dry pipe sprinkler system, without having to remove the Hand hole Cover.
![Page 100: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/100.jpg)
100
![Page 101: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/101.jpg)
101
![Page 102: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/102.jpg)
102
PREACTION PIPES SYSTEM A Preaction System is a sprinkler
system employing closed automatic sprinklers connected to a piping system that contains air or nitrogen that may or may not be pressurized. A supplemental detection system (release line) is installed in the same area as the sprinklers
![Page 103: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/103.jpg)
103
NFPA 13 DEFINES THREE BASIC TYPES OF PREACTION SYSTEMS: Single Interlocked: Admits water to
sprinkler piping upon operation of detection devices only.
Double Interlocked: Admits water to sprinkler piping upon operation of both the detection devices and automatic sprinklers
![Page 104: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/104.jpg)
104
PREACTION SYSTEMS:
Non-Interlocked: Admits water to sprinkler piping upon either operation of detection devices or automatic sprinklers.
![Page 105: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/105.jpg)
105
PREACTION SYSTEMS:
The supplemental detection system is commonly electric or pneumatic or a combination of both. Detection systems used with electric release systems are commonly actuated by manual pull stations, fixed-temperature heat detectors, rate-of-rise heat detectors, smoke detectors or other means determined
![Page 106: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/106.jpg)
106
PREACTION SYSTEMS:
In accordance with NFPA 13, the preaction sprinkler system piping and fire
detection devices shall be automatically supervised where there are more than 20 sprinklers on the systems. This is accomplished with air or nitrogen gas under pressure within the sprinkler piping. If the integrity of the sprinkler piping is compromised, the pressure will be reduced activating a supervisory pressure switch that transmits the signal to the release control panel and/or fire alarm panel.
![Page 107: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/107.jpg)
107
PREACTION SYSTEMS:
Single Interlocked
![Page 108: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/108.jpg)
![Page 109: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/109.jpg)
![Page 110: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/110.jpg)
![Page 111: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/111.jpg)
![Page 112: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/112.jpg)
![Page 113: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/113.jpg)
![Page 114: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/114.jpg)
114
PREACTION SYSTEMS:
Double Interlocked
![Page 115: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/115.jpg)
115
PREACTION SYSTEMS:
. The double interlock preaction system utilizes a detector system and pressurized air or nitrogen in the sprinkler system piping. This system is arranged so that the deluge valve will open only when both pressure is reduced in the sprinkler piping and the detection system operates.
![Page 116: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/116.jpg)
116
PREACTION SYSTEMS:
If the detection system operates due to damage or malfunction, the valve will not open, but an alarm will sound. If the sprinkler piping is damaged or sprinkler is broken, the valve will not open but a supervisory alarm will sound. The operation of both a sprinkler and a detector (or release) is required before the valve will open, allowing water to enter the system piping.
![Page 117: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/117.jpg)
![Page 118: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/118.jpg)
![Page 119: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/119.jpg)
![Page 120: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/120.jpg)
![Page 121: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/121.jpg)
![Page 122: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/122.jpg)
![Page 123: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/123.jpg)
![Page 124: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/124.jpg)
![Page 125: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/125.jpg)
![Page 126: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/126.jpg)
126
DELUGE SYSTEMS:
A deluge system is similar to a pre-action system except the sprinkler heads are open and the pipe is not pressurized with air. Deluge systems are connected to a water supply through a deluge valve that is opened by the operation of a smoke or heat detection system. The detection system is installed in the same area as the sprinklers. When the detection system is activated water discharges through all of the sprinkler heads in the system. Deluge systems are used in places that are considered high hazard areas such as power plants, aircraft hangars and chemical storage or processing facilities. Deluge systems are needed where high velocity suppression is necessary to prevent fire spread
![Page 127: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/127.jpg)
127
DELUGE SYSTEMS:
Deluge System with Electric actuated
![Page 128: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/128.jpg)
![Page 129: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/129.jpg)
![Page 130: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/130.jpg)
![Page 131: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/131.jpg)
![Page 132: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/132.jpg)
![Page 133: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/133.jpg)
![Page 134: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/134.jpg)
134
DELUGE SYSTEMS:
Deluge System with wet pilot actuated
![Page 135: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/135.jpg)
![Page 136: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/136.jpg)
![Page 137: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/137.jpg)
![Page 138: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/138.jpg)
![Page 139: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/139.jpg)
![Page 140: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/140.jpg)
![Page 141: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/141.jpg)
141
DELUGE SYSTEMS:
Deluge System with Dry pilot actuated
![Page 142: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/142.jpg)
![Page 143: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/143.jpg)
![Page 144: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/144.jpg)
![Page 145: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/145.jpg)
![Page 146: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/146.jpg)
![Page 147: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/147.jpg)
![Page 148: Fire Fighting Course](https://reader038.vdocuments.us/reader038/viewer/2022102519/545f3e3ab1af9f82438b4974/html5/thumbnails/148.jpg)
148
ZONE CONTROL VALVE ( FLOOR C V )