FIRE FIGHTER’S GUIDE 1. VIEW NEXT/PREVIOUS ALARM Press "NEXT" key once - - The LCD will display the next alarm. Press “PREV” key once - - The LCD will display the previous alarm. 2. ACKNOWLEDGE DISPLAYED ALARM Press "ACK" key once. - LCD will display "ACKD" for the displayed alarm. - If all alarms are acknowledged, the ALARM LED will go steady. 3. RESET DISPLAYED ALARM Press "RESET" key once. - LCD will display “PRESS ACKNOWLEDGE TO CONFIRM RESET”. - Press the ACK key within 10 seconds to reset the alarm. - If the final alarm is reset the LCD will exit FF mode. 4. ISOLATE DISPLAYED ALARM Press "ISOLATE" key once. - LCD will display “PRESS ACKNOWLEDGE TO CONFIRM ISOLATE”. - Press the ACK key within 10 seconds to isolate the zone. - The isolated LED will turn on. - If the final alarm is isolated, the LCD will give an option to view isolated alarms. 5. ISOLATE/DE-ISOLATE EXTERNAL BELL - Press the "EXTERNAL BELL ISOLATE” key once. If the “External Bell Isolate” LED is off it will turn on steady. The External Bell will turn OFF if it is on. - If the "External Bell Isolate" LED is on, it will turn off. If any un-isolated alarms exist, the External Bell will ring. 6. ISOLATE/DE-ISOLATE WARNING SYSTEM - Press the "WARNING SYSTEM ISOLATE” key once. If the “Warning System Isolate” LED is off it will turn on steady. The Warning System will turn OFF if it is on. - If the " Warning System Isolate" LED is on, it will turn off. If any un-isolated alarms exist, the Warning System will sound.

Upload: others

Post on 18-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

FIRE FIGHTER’S GUIDE

1. VIEW NEXT/PREVIOUS ALARM Press "NEXT" key once -

- The LCD will display the next alarm.

Press “PREV” key once - - The LCD will display the previous alarm.

2. ACKNOWLEDGE DISPLAYED ALARM Press "ACK" key once.

- LCD will display "ACKD" for the displayed alarm. - If all alarms are acknowledged, the ALARM LED will go

steady.

3. RESET DISPLAYED ALARM Press "RESET" key once.

- LCD will display “PRESS ACKNOWLEDGE TO CONFIRM RESET”. - Press the ACK key within 10 seconds to reset the alarm. - If the final alarm is reset the LCD will exit FF mode.

4. ISOLATE DISPLAYED ALARM Press "ISOLATE" key once.

- LCD will display “PRESS ACKNOWLEDGE TO CONFIRM ISOLATE”. - Press the ACK key within 10 seconds to isolate the zone. - The isolated LED will turn on. - If the final alarm is isolated, the LCD will give an option to view isolated alarms.

5. ISOLATE/DE-ISOLATE EXTERNAL BELL - Press the "EXTERNAL BELL ISOLATE” key once.

If the “External Bell Isolate” LED is off it will turn on steady. The External Bell will turn OFF if it is on. - If the "External Bell Isolate" LED is on, it will turn off. If any un-isolated alarms exist, the External Bell will ring.

6. ISOLATE/DE-ISOLATE WARNING SYSTEM - Press the "WARNING SYSTEM ISOLATE” key once.

If the “Warning System Isolate” LED is off it will turn on steady. The Warning System will turn OFF if it is on. - If the " Warning System Isolate" LED is on, it will turn off. If any un-isolated alarms exist, the Warning System will

sound.

Page 2: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

THIS PAGE INTENTIONALLY LEFT BLANK

Page 3: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200

AS4428.1 OPERATOR'S MANUAL

F3200 PRODUCT MANUAL DOCUMENT: LT0251 (A4 Loose)

DOCUMENT: LT0250 (A5 Bound)

Issue 1.08; 30 June 2016

- A P P R O V A L S -

AS4428.1 1998 - ActivFire Listing Number afp789 AS/NZS CISPR 22 : 2006 AS/NZS 60950.1 : 2015

The F3200 Fire Indicator Panel is a product of

Tyco Fire Protection Products 17 Mary Muller Drive Christchurch 8022 NEW ZEALAND

Telephone : +64 3 3895096 Fax : +64 3 3895938

NOTICE Information contained in this document is copyright, and shall not be reproduced in any form whatsoever, or its contents disclosed to any third party, without the written consent of Tyco Fire Protection Products (The Company). Information contained in this document is believed to be accurate and reliable, however the company reserves the right to change the content without prior notice.

COPYRIGHT (C) 2000, 2002, 2009, 2016 TYCO FIRE PROTECTION PRODUCTS

Page 4: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250

Page ii 30 June 2016 Issue 1.08

INSTALLATION DETAILS

For your reference please complete the following information on the F3200 Fire Indicator Panel supplied.

F3200 FIP SUPPLIED BY

F3200 FIP INSTALLATION LOCATION

CONTRACT/JOB NUMBER

F3200 SERIAL NUMBER

F3200 SYSTEM AS INSTALLED DRAWING NUMBER

ISSUE:

F3200 SYSTEM PARAMETERS DRAWING NUMBER

ISSUE:

DATE PANEL MANUFACTURED

DATE PANEL INSTALLED

DATE PANEL COMMISSIONED

MAINTENANCE COMPANY

TELEPHONE B.H. A.H.

SERVICE CONTACT

SITE CONTACT OR REGISTERED USER (INCLUDE TITLE)

COMPANY / ADDRESS

TELEPHONE B.H.

F3200 SID NUMBER (IF NETWORKED)

Page 5: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual

Issue 1.08 30 June 2016 Page iii

TABLE OF CONTENTS

Installation Details .......................................................................................................... .ii End User Liability Disclaimer .......................................................................................... vii Amendments …………………………………………………………………………………..viii

1 INTRODUCTION ......................................................................................... 1-1

1.1 SCOPE .............................................................................................................................. 1-2

1.2 ATTACHMENTS ............................................................................................................... 1-3

1.3 ASSOCIATED DOCUMENTATION .................................................................................. 1-4

1.4 GLOSSARY OF ABBREVIATIONS ................................................................................. 1-5

1.5 GLOSSARY OF TERMINOLOGY .................................................................................... 1-6

1.6 HOW TO USE THIS MANUAL ......................................................................................... 1-6

2 SYSTEM DESCRIPTION ............................................................................ 2-1

2.1 BASIC PRINCIPLES OF A FIRE ALARM SYSTEM ........................................................ 2-2

2.2 F3200 SYSTEM DESCRIPTION ....................................................................................... 2-4

3 SYSTEM SPECIFICATIONS ....................................................................... 3-1

3.1 GENERAL ......................................................................................................................... 3-2

3.2 MECHANICAL SPECIFICATIONS ................................................................................... 3-5

3.3 ELECTRICAL SPECIFICATIONS .................................................................................... 3-6

3.4 INPUT SPECIFICATIONS ................................................................................................ 3-8

3.5 OUTPUT SPECIFICATIONS ............................................................................................ 3-8

3.6 SERIAL COMMUNICATIONS ........................................................................................ 3-10

4 GENERAL DISPLAY & KEYPAD OPERATION ......................................... 4-1

4.1 INTERPRETING THE LEDS ............................................................................................. 4-2

4.2 LCD BASE DISPLAY & MENU STRUCTURE ................................................................. 4-4

4.3 RESPONDING TO ALARMS ............................................................................................ 4-7

4.4 DEALING WITH FAULTS ................................................................................................. 4-8

5 OPERATING INSTRUCTIONS - BRIGADE FUNCTIONS ......................... 5-1

5.1 INTRODUCTION TO BRIGADE FUNCTIONS ................................................................. 5-2

5.2 SILENCING THE INTERNAL SOUNDER ........................................................................ 5-4

Page 6: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250

Page iv 30 June 2016 Issue 1.08

5.3 ACKNOWLEDGE ZONE IN ALARM ................................................................................ 5-5

5.4 RESET ACKNOWLEDGED ZONE IN ALARM ................................................................ 5-6

5.5 ISOLATE ACKNOWLEDGED ZONE IN ALARM ............................................................ 5-7

5.6 ISOLATING/DE-ISOLATING EXTERNAL BELL ............................................................. 5-8

5.7 ISOLATING/DE-ISOLATING WARNING SYSTEM ......................................................... 5-9

5.8 EXITING FF MODE ......................................................................................................... 5-10

5.9 RECALLING ALARMS ................................................................................................... 5-11

5.10 BRIGADE FUNCTIONS ON NETWORK SYSTEMS ..................................................... 5-12

6 OPERATING INSTRUCTIONS - SYSTEM FUNCTIONS ........................... 6-1

6.1 BATTERY TEST & PSU FAULT INHIBIT ........................................................................ 6-2

6.2 EXTERNAL BELL TEST .................................................................................................. 6-4

6.3 WARNING SYSTEM TEST ............................................................................................... 6-5

6.4 LCD/LAMP (LED) TEST ................................................................................................... 6-6

6.5 SYSTEM TEST ................................................................................................................. 6-7

6.6 RECALL SYSTEM FAULTS ............................................................................................. 6-9

6.7 BUZZER TEST ................................................................................................................ 6-14

6.8 RECALL HISTORY ......................................................................................................... 6-14

6.9 SET SYSTEM TIME ........................................................................................................ 6-15

6.10 SET SYSTEM DATE ....................................................................................................... 6-16

6.11 ANCILLARY, WARNING SYSTEM, EXTERNAL BELL AND PLANT ISOLATE ......... 6-16

6.12 PRINT FUNCTIONS ........................................................................................................ 6-17

6.13 RZDU STATUS DISPLAY .............................................................................................. 6-18

6.14 RECALL DATABASE CRC ............................................................................................ 6-19

6.15 BRIGADE TEST .............................................................................................................. 6-20

6.16 ERROR AND EVENT MESSAGES ................................................................................ 6-21

6.17 BUZZER RESOUND TEST............................................................................................. 6-26

7 OPERATING INSTRUCTIONS - ZONE FUNCTIONS ................................ 7-1

7.1 ZONE ALARM OR FAULT TEST ..................................................................................... 7-2

7.2 ZONE ISOLATE OR DE-ISOLATE .................................................................................. 7-4

7.3 ZONE RESET ................................................................................................................... 7-5

Page 7: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual

Issue 1.08 30 June 2016 Page v

7.4 ZONE IN-SITU TEST MODE ............................................................................................ 7-6

7.5 ZONE STATUS RECALLS ............................................................................................... 7-8

8 OPERATING INSTRUCTIONS - RELAY/OUTPUT FUNCTIONS .............. 8-1

8.1 INTRODUCTION ............................................................................................................... 8-2

8.2 MODULE RELAY STATUS RECALL .............................................................................. 8-4

8.3 MODULE RELAY ISOLATE/DE-ISOLATE ...................................................................... 8-5

8.4 MODULE RELAY RESET SUPERVISION FAULT .......................................................... 8-6

8.5 MODULE RELAY TEST ................................................................................................... 8-7

8.6 ANCILLARY RELAY STATUS RECALL ......................................................................... 8-8

8.7 ANCILLARY RELAY ISOLATE/DE-ISOLATE ................................................................. 8-9

8.8 ANCILLARY RELAY RESET SUPERVISION FAULT ................................................... 8-10

8.9 ANCILLARY RELAY TEST ............................................................................................ 8-11

8.10 OPEN COLLECTOR STATUS RECALL OR TEST ....................................................... 8-12

8.11 WARNING SYSTEM STATUS RECALL ........................................................................ 8-13

8.12 EXTERNAL BELL STATUS RECALL ........................................................................... 8-14

9 PLACING INTO OPERATION ..................................................................... 9-1

9.1 GENERAL ......................................................................................................................... 9-2

9.2 POWER-UP ....................................................................................................................... 9-2

9.3 COMMISSIONING CHECKLIST ....................................................................................... 9-3

10 SYSTEM TESTING & MAINTENANCE ................................................. 10-1

10.1 SYSTEM TESTING & FAULT FINDING ......................................................................... 10-2

10.2 MODULE REMOVAL ...................................................................................................... 10-3

10.3 SYSTEM MAINTENANCE .............................................................................................. 10-4

10.4 AS 1851 TESTING REQUIREMENTS ............................................................................ 10-4

10.5 PREVENTION OF FALSE ALARMS ............................................................................ 10-12

11 NETWORK SYSTEMS ........................................................................... 11-1

11.1 INTRODUCTION ............................................................................................................. 11-2

11.2 NDU - NETWORK DISPLAY UNIT ................................................................................. 11-4

11.3 LCD TOTALS, LEDS, OUTPUTS & BUZZER OPERATION ........................................ 11-5

Page 8: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250

Page vi 30 June 2016 Issue 1.08

11.4 EXTERNAL BELL/WARNING SYSTEM ISOLATE/SILENCE ....................................... 11-7

11.5 NETWORK FIP & ZONE NUMBERING ......................................................................... 11-8

11.6 SYSTEM FAULT RECALL/NET PANEL STATUS RECALL ....................................... 11-9

11.7 NETWORK COMMAND RESPONSES & EXCEPTION MESSAGES ......................... 11-12

11.8 NETWORK SYSTEM COMMANDS ............................................................................. 11-14

11.9 REMOTE RELAY & OPEN COLLECTOR OPERATION & ZONE MAPPING ........... 11-18

11.10 NETWORK ZONE RECALLS & COMMANDS ............................................................ 11-19

11.11 POINT RECALLS & COMMANDS ............................................................................... 11-26

APPENDIX A COMPATIBLE ACTUATING DEVICES (DETECTORS) ……..A-1

Page 9: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual

Issue 1.08 30 June 2016 Page vii

TYCO FIRE PROTECTION PRODUCTS END USER LIABILITY DISCLAIMER

The F3200 Fire Indicator Panel has a configuration programming facility which may be accessed from the keypad by using a password. This programming facility allows the user to define in detail the operation of the F3200 System. It is possible for the user to program operational features that prevent the installed FIP from meeting statutory requirements. Tyco Fire Protection Products does not accept responsibility for the suitability of the functions programmed by the user.

CISPR 22 NOTICE

WARNING: This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

Page 10: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250

Page viii 30 June 2016 Issue 1.08

AMENDMENTS

ISSUE DATE AMENDMENT ECN

1.00 31/10/00 ORIGINAL ISSUE 3041

1.01 29/07/02 Prefix, Appendix A and Pages 2-5, 3-8, 6-10….6-13, 6-17, 8-11, 11-2

3322

1.02 01/03/05 Item 18 inserted into Section 6.6.3 & 6.16.3. Appendix A2 – add 614CH, 614I & 614P

3635

1.03 28/10/05 Appendix A – added System Sensor detector 885WP-B ECS 1181

1.04 24/03/06 Appendix A – add 614T 3731

1.05 23/07/08 Revise AS 1851.8 to 1851, replace Section 10.3 and other minor edits to Sections 6.1.4, 6.6., 6.16

ECS 1303

1.06 23/01/09 Corresponds to software V5.xx. Sections 3.1.4, 4.1.2, 11.8.5, 11.8.6, 11.9, 6.14 updated. Section 11.8.9 added.

3997

1.07 18/01/13 Section 3.5.3 – add MAF relay rating for Rev 11. Add Section 6.17. Fix Table 10.4.7 – volts. Revised Section 10 for AS 1851-2012.

4443

1.08 30/06/16 Added RCM details. Revised PSU current down from 3A/6A.

4925

Page 11: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Introduction

Issue 1.08 30 June 2016 Page 1-1

1 INTRODUCTION

Page 12: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Introduction

Page 1-2 30 June 2016 Issue 1.08

1.1 SCOPE

This manual describes the operation of an F3200 fire panel or NDU running software V5.00 or later. The F3200 Fire Indicator Panel (FIP) has an Operator Display Panel with an alphanumeric "Liquid Crystal Display" (LCD) and a keypad. The keypad has numeric keys (0 to 9) and specific control keys (e.g. External Bell Isolate, Reset, etc). The operator controls the FIP by pressing the appropriate control keys. The FIP, in turn, prompts the operator by displaying messages on the LCD. Where appropriate, the FIP will provide the operator with options, numbered from 1 up. The operator selects the desired option by pressing the appropriate key on the numeric keypad. Control of the FIP is therefore intuitive to an operator familiar with the basic principles of a fire alarm system. Such an operator may well perform all desired functions without reference to this manual. This manual is intended as a guide to an unfamiliar operator and a reference for the more experienced operator. It is recommended that the building owner's representative who is responsible for the fire alarm system, becomes familiar with the FIP operation by practice and by reference to this manual. The unfamiliar operator should learn the basic principles described in Chapter 2, and become familiar with the F3200 system structure and controls. With appropriate hardware and cabling F3200 panels may be networked to form a system of inter-connected panels and network devices. This manual describes the operation of both non-networked and networked F3200 panels that comply with AS4428.1, and also describes the operation of the NDU (Network Display Unit) which is essentially a networked F3200 without any alarm zone modules or relay modules. This manual also covers operation of an F3200 panel with an older style AS1603.4 keyboard that has been upgraded to use AS4428.1 compliant software. Some differences in operation are covered in Section 4.2.5. A separate manual, LT0119, covers operating an F3200 panel that complies with AS1603.4. An NDU may be programmed to operate in “New Zealand mode” for use in New Zealand. New Zealand mode is not available for an F3200 Fire Panel. Section 1.6 describes how this manual should be used according to the type of panel being operated. The Manual is structured in chapters as follows: Chapter 1: Introduction: An introduction to this manual, other F3200 Product

manuals and the standards relating to fire alarms. Chapter 2: System Description; A description of the F3200 system features and

functions. Chapter 3: Specifications; A summary of F3200 system specifications.

Page 13: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Introduction

Issue 1.08 30 June 2016 Page 1-3

SCOPE (CONTINUED) Chapter 4: General Display & Keypad Operation; A description of display

indications, menu structure and key functions.

Chapter 5: Operating Instructions - Brigade Functions; A detailed description of

the operation and function of keys for FIRE FIGHTER'S USE provided on the F3200 ("ACK", "RESET", "ISOLATE", "EXTERNAL BELL ISOLATE", “WARNING SYSTEM ISOLATE”, “PREV”, and "NEXT").

Chapter 6: Operating Instructions - System Functions; A description of the

operation and function of keys provided on the F3200 FIP for system testing and operation. For example, System Test, External Bell Test, and Recall History. Also included are the system faults and event messages that can be generated.

Chapter 7: Operating Instructions - Zone Functions; A detailed description of the

operation and function of keys provided on the F3200 FIP for zone tests and functions.

Chapter 8: Operating Instructions - Relay/Output Functions; A description of the

operation of keys provided on the F3200 FIP for relay and output test and functions.

Chapter 9: Placing Into Operation; A description of how to place a system into

operation. Also included is a System Commissioning Checklist. Chapter 10: System Testing & Maintenance; A description of fault finding, routine

testing and system maintenance. Chapter 11: Network System Operation; Operation of a networked panel or NDU. Appendix A: Compatible Actuating Devices (Detectors); A list of detectors approved

for use with F3200.

1.2 ATTACHMENTS

A FIRE FIGHTER'S GUIDE is fixed inside the front cover for quick reference in emergencies. Your installation company should install the following documents inside the panel: (a) An "AS INSTALLED" fire detection system diagram and/or summary, describing

the installed layout of your F3200 System. (b) Other "AS INSTALLED" information, such as System configuration parameters. (c) A Maintenance Log-Book.

Page 14: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Introduction

Page 1-4 30 June 2016 Issue 1.08

1.3 ASSOCIATED DOCUMENTATION

1.3.1 PRODUCT RELATED

The following manuals for the F3200 are available: F3200 Operator’s Manual For F3200 panels that comply with

AS1603.4. LT0119 is in A5 bound form. LT0120 is in A4 loose leaf form. F3200 AS4428.1 Operator's Manual This manual LT0251 is in A4, loose leaf form. LT0250 is in A5, bound form. F3200 Technical Manual Provides technical information for system

designers and service staff. Part number LT0121.

F3200 AS4428.1 Installation & Provides information for personnel Configuration Manual responsible for system design, installation

and commissioning. Part number LT0255. F3200 AS4428.1 Programming Manual Provides information for panel

programmers. Part number LT0256.

1.3.2 STANDARDS RELATED

This manual makes reference to the following Australian and combined Standards: AS1603.4 Automatic Fire Detection and Alarm Systems Part 1 - Control and Indicating Equipment. AS4428.1 Automatic Fire Detection and Alarm Systems Part 1 - Control and Indicating Equipment. AS1670.1 Automatic Fire Detection and Alarm Systems- System Design, Installation and Commissioning. AS1851 Maintenance of Fire Protection Systems and Equipment AS/NZS 60950.1 Information Technology Equipment – Safety AS/NZS CISPR22 Information Technology Equipment – Radio Disturbance Characteristics This manual makes reference to the following New Zealand standards. NZS4512 Automatic Fire Alarm Systems in Buildings.

Page 15: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Introduction

Issue 1.08 30 June 2016 Page 1-5

1.4 GLOSSARY OF ABBREVIATIONS

The following abbreviations and terminology are used in this manual: AC Alternating Current "ALM" Display abbreviation for ALARM AS Ancillary Supervision AVF Alarm Verification, or check alarm. AZC Alarm Zone Circuit, commonly referred to as "Detection Zone" AZF Alarm Zone Facility, commonly referred to as "GROUP" CIE Control and Indicating Equipment DC Direct Current EEPROM Electrically Erasable Programmable Read Only Memory EOL End Of Line device EPROM (U.V.) Erasable PROM F Flashing LED indicator FF Fire Fighter's Facilities, AS4050 (INT) FIP Fire Indicator Panel "FLT" Display abbreviation for FAULT FRC Flat Ribbon Cable "ISO" Display abbreviation for ISOLATED LCD Liquid Crystal Display LED Light Emitting diode (Visual Indicator) MAF Master Alarm Facility MCP Manual Call Point (break glass switch) No Number O/C Open Circuit PCB Printed Circuit Board PROM Programmable Read-Only Memory PSU Power Supply Unit RAM Random Access Memory RF Rapid Flashing LED indicator RZDU Remote Zone Display Unit S/C Short Circuit SF Slow Flashing LED indicator SID System Identification Number for a Network Device VB Battery Backed Voltage VBF Fused Battery Backed Voltage VNB Non-Battery Backed Voltage VNBF Fused Non-Battery Backed Voltage 8RM 8 Relay Module 8ZM 8 Zone Module

Page 16: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Introduction

Page 1-6 30 June 2016 Issue 1.08

1.5 GLOSSARY OF TERMINOLOGY

The following terminology is used throughout this manual: Ancillary Equipment : Equipment external to Fire Alarm system Ancillary Relay : Relay in FIP which operates Ancillary equipment Auxiliary Output : Output for driving additional LEDs/relays Baud : Bits per second Brigade : Fire Brigade, or any other authority which receives the FIP alarm signals Control Output : Output from FIP to other equipment Detector : Alarm Detection Device FF Mode : The LCD is displaying the alarms list. Limited key entry permitted as per AS4428.1 Global : A function that may affect more than one zone In-Situ : A test mode for one person testing of detectors MAF Zone : Any zone, Alarm or Ancillary Relay, that is configured to signal the brigade in the event of an alarm or fault Mapping : Programmable causal relationship between inputs and outputs Zone : Fire searchable area of building

1.6 HOW TO USE THIS MANUAL

This manual describes the operation of both non-networked and networked F3200 panels and also describes the operation of the NDU (Network Display Unit), which is essentially a networked F3200 without any alarm zone modules or relay modules. It also covers operation of an F3200/NDU that has an AS1603.4 compliant keyboard that has been upgraded to use AS4428.1 software (V3.XX or higher). Some differences in operation are covered in Section 4.2.5. Operation of AS1603.4 compliant F3200 panels and NDU is covered in LT0119. Chapters 1 to 10 apply to non-networked panels, networked panels and NDUs, except that NDUs do not have 8 zone modules or 8 relay modules, and may not have a MAF module. In Chapters 1 to 10 if a particular detail or command differs between non-networked and networked panels, then either the appropriate information for networked systems is also described or the user is directed to Chapter 11. Chapter 11 contains information specifically for users of networked F3200 panels and NDUs and does not contain any information relevant to users of non-networked F3200s. It is recommended that operators of networked panels or NDUs read the Introductory sections of Chapter 11. An NDU may be programmed to operate in “New Zealand” mode for use in New Zealand. Any differences in operation between New Zealand mode and Australian mode for the NDU, are described, where applicable, throughout this manual.

Page 17: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Description

Issue 1.08 30 June 2016 Page 2-1

2 SYSTEM DESCRIPTION

Page 18: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Description

Page 2-2 30 June 2016 Issue 1.08

2.1 BASIC PRINCIPLES OF A FIRE ALARM SYSTEM

2.1.1 DETECTORS & ALARM ZONE FACILITY

A fire alarm system has sensors (electric transducers) which detect the presence of fire. These include heat detectors (thermals), product of combustion detectors (smoke and CO), sprinkler system water flow switches, manual call points (break glass switches), and others. The building being protected is divided into areas of limited size called zones. The detectors in each zone are connected to an electric circuit called an Alarm Zone Circuit (AZC). The portion of the FIP which controls the AZC is called the Alarm Zone Facility (AZF). In F3200 the 8 Zone Module does this. When a detector detects fire (i.e. operates) it changes the electrical condition on the AZC and the AZF senses this (zone alarm). The detector remains in the operated state (latches) until the AZF temporarily removes the voltages to it (resets it). N.B. some detectors, e.g. flow switches, are non-latching. As well as sensing when a detector has operated the AZF can sense a fault in the AZC wiring (zone fault), e.g. due to removal of a detector from its base. The zone isolate function prevents a zone alarm or fault being registered by the Master Alarm Facility (MAF). Refer to Fig 2.1.1.

2.1.2 ALARM VERIFICATION

When programmed (by the installer) to do so, the AZF may perform a verification function on sensed alarms. This Alarm Verification (AVF) functions as follows: When an AZF senses that a detector has operated, it does not register alarm immediately but delays for a period of time and then resets the detector (typical total delay is 15 seconds). If that, or another detector on the same AZC operates within the next 150 seconds (or similarly programmed period) then the AZF recognises that as a verified alarm, and generates alarm to the MAF.

2.1.3 DISPLAY

There is a display of zone status which allows the operator to see if a particular zone is normal or is in alarm or fault, and if it is isolated. There is also a separate display of common status which shows if any zone in the system is in alarm, fault, or is isolated. The display can be a liquid crystal display (LCD) and/or individual LED indicators.

Page 19: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Description

Issue 1.08 30 June 2016 Page 2-3

KEY AZC = Alarm Zone Circuit AZF = Alarm Zone Facility MAF = Master Alarm Facility ACF = Ancillary Control Facility FIP = Fire Indicator Panel = End of Line (circuit) Device = Detector FIG 2.1.1 BASIC FIRE ALARM SYSTEM

ACF

AZF MAF

Operator Controls

Power

Signal to Brigade

Warning System

Ancillary Control Outputs (e.g. Air Conditioning shutdown)

Visual Indication of Status

AZC n

FIP

AZC 1

AZC 2

External Bell

Page 20: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Description

Page 2-4 30 June 2016 Issue 1.08

2.1.4 MASTER ALARM FACILITY

The MAF receives zone status (normal, alarm, fault) and transmits it (via Alarm Signalling Equipment (ASE)) to the Brigade. It also operates the warning system (part of the fire alarm system or a separate warning system) to warn people to evacuate the building, and the External Bell (strobe and/or bell) to advise the Fire Brigade of the location of the fire alarm panel. Individual (or blocks of) zones can be isolated, the External Bell output and Warning System output can be isolated, but the MAF (i.e. Brigade signalling) cannot be isolated. In F3200 it is possible to have zones which are not "mapped" to the MAF, External Bell, and/or warning system i.e. when in alarm, do not cause a Brigade signal, External Bell or warning system operation.

2.1.5 ANCILLARY CONTROL FACILITY

The ancillary control facility consists of relays (electrically controlled switches) which can be used to switch equipment which is not directly part of the Fire Alarm System. Examples include shutting down air-conditioning plant, returning lifts to a certain floor, and releasing fire stop doors held open by electric door holders.

2.1.6 NETWORKING

A fire panel may be part of a network of devices such as other fire panels, display and control devices, and colour graphic displays. This builds larger, more flexible systems, and also allows the display and control of the system to be provided at multiple locations throughout a building or group of buildings. It is possible that the brigade signalling would be done by only one panel on the network, with the other panels transmitting alarm/fault, etc, to the common panel for signalling to the brigade.

2.2 F3200 SYSTEM DESCRIPTION

2.2.1 GENERAL

The F3200 is a self-contained, modular, intelligent Fire Indicator Panel (FIP) which performs the functions of the Control and Indicating Equipment (CIE) as specified by the Australian Standard AS4428.1 Automatic Fire Detection and Alarm Systems. It has a high degree of flexibility and expendability, catering for medium to very large buildings. A single panel may have up to 64 zones and a network system may have up to 64 panels.

2.2.2 DETECTOR CIRCUITS

The F3200 detector circuits cater for a wide range of detectors, including various types which have high alarm current requirements. It also interfaces to:

Intrinsically safe circuit barriers/isolators (hazardous areas). Long line circuits e.g. from a sub-indicator FIP. Tamper-proof circuit e.g. for water valve supervision.

A full range of compatible detectors is listed in Appendix A.

Page 21: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Description

Issue 1.08 30 June 2016 Page 2-5

2.2.3 DISPLAYS

The primary display of the F3200 is a 2 line by 40 character LCD on which the status messages and prompts are shown. The LCD has backlight illumination which is turned on when there is an alarm or operator interaction. Refer Fig 2.2.1. Common conditions are displayed on 9 LEDs adjacent to the LCD. The display panel composed of the LCD common, LEDs and keypad is called the Operator Display panel. The portion within the red border is called the Fire Fighter's Facility (FF). It includes the common status LEDs for ALARM, ISOLATED and FAULT. As an optional extra, individual zone status (ALARM, ISOLATE and FAULT) can be displayed on LEDs by fitting the appropriate number of 16 Zone LED Display boards. By default Zone 1 corresponds to the top row of LEDs (3) on the left most display, Zone 2 to the row below it, etc, (top to bottom, left to right). Display bds may also annunciate Relay status. Alarm LED on <-> relay energised, Isolated LED on <-> relay isolated, Fault LED on <-> relay wiring fault (i.e. supervision fault). The relay LEDs simply follow the zone LEDs in the same order that they occur in the FIP. For example, a system with 3 x 8 Zone Modules, 2 x 8 Relay Modules, would require 3 Display bds. Relay 1 will be annunciated on the 25th row of LEDs and the last 8 rows will be unused. Mapping zones and relays to LEDs in other patterns is programmable. The F3200 electronics includes, as standard, an open collector transistor output for each zone which can be used to drive an internal or remote mimic display. An NDU in New Zealand mode may have an additional 3 system status indicators on the NZ Display Extender board: Fire, Defect, Normal.

Page 22: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Description

Page 2-6 30 June 2016 Issue 1.08

FIG 2.2.1 F3200 - FRONT VIEW

Page 23: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Description

Issue 1.08 30 June 2016 Page 2-7

2.2.4 OUTPUTS

The F3200 MAF/PSU Module provides 7 relays as standard. These are used for signalling to the Brigade and for switching alarm bells and ancillary equipment such as door holders or air-conditioning shutdown. Where more than 7 relays are required, additional sets of 8 are available by fitting an 8 Relay Module. All outputs are individually programmable with a logic equation of zone and FIP status. For a networked system it is possible for the brigade signalling to be done by only one panel by combining the status received from the other panels.

2.2.5 POWER SUPPLY

The F3200 has a 3 Amp battery charger as standard. There is adequate room for large batteries. A version with a 6 Amp battery charger is also available. Fuse protected battery backed and non-battery backed dc voltage supplies are available to power external loads such as bells, illuminated signs, interposing relays or gas release solenoids.

2.2.6 REMOTE DISPLAYS

A serial port is included in the F3200 to provide a 3 or 4 wire link to one or more Remote Display Units (RDUs, with some earlier variants called Remote Zone Display Units RZDUs). Up to 8 replying RDUs may be connected to one F3200. Several versions of F3200 RDU are available. The most commonly used versions have small, attractive cabinets (flush and surface mounting) not much larger than the F3200 display-keyboard which is fitted on them. They receive power from the F3200 FIP. Other versions look like an F3200 FIP, have their own power supply, and may have LED Display Boards fitted to them. Additional mimic-only devices can be connected to the RDU output to monitor the F3200 zone status. For example, IO-NET can be used to provide floor mimic panels, AS1668 interfaces or remote outputs for evacuation panels. For a networked system, an RDU can display (and control) only the zones and relays of the FIP to which the RDU is connected. With appropriate programming, such an RDU could be used to isolate the warning system of that FIP, and hence isolate the warning system across the entire network. Refer to Section 11.4.

Page 24: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Description

Page 2-8 30 June 2016 Issue 1.08

2.2.7 LOGGING PRINTER

A serial printer may be connected to F3200 to provide a log of events and operator actions, and also to print the programmed database. Events which are printed include: (i) Zone Events, e.g. Alarm, Fault;

(ii) Zone Commands, e.g. Reset, Isolate;

(iii) System events, e.g. communication failures, battery faults, etc. The printout includes the time and date, the cause of the event (e.g. Zone, Relay, RZDU or FIP), and the event type. Events and commands for zones and relays that have a text name programmed also have the name printed. F3200 is able to store at least 100 events for printing, being the first 100 events to occur. As events are printed, more events are able to be put into the list. If events cannot be put into the list because it is full, the FIP keeps a count of those events it has had to discard. When the FIP is next able to put more events into the list, it prints out the number of events it had to discard. For a networked system, with appropriate programming, an F3200 panel (or NDU) may print events and accumulate history for some or all of the other panels on the network.

2.2.8 NETWORKING CAPABILITIES

A number of F3200 fire panels, NDUs (Network Display Unit) and other Vigilant Panel-link compatible devices may be connected together to form a large distributed system. Chapter 11 describes networking operation. The NDU is essentially a networked F3200 without any 8 zone or 8 relay modules. Two types are available - one a slimline unit without a MAF module and similar to the RDU, the second exactly like an F3200 panel but without any zone or relay modules. The F3200 System supports the addition of colour graphics display and control terminals on the network. These units can be programmed to show graphical displays on zone alarm or fault conditions. The operator can use function keys or the optional touch screen to generate commands to the F3200 and thus have remote control of it.

2.2.9 CONFIGURATION

An F3200 FIP is configured by the system designer and installation staff to suit a particular customer's requirements.

** PLEASE NOTE **

If your building or occupancy requirements change, then the F3200 FIP may require reprogramming, so please consult your installation or maintenance company.

Page 25: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Specifications

Issue 1.08 30 June 2016 Page 3-1

3 SYSTEM SPECIFICATIONS

Page 26: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Specifications

Page 3-2 30 June 2016 Issue 1.08

3.1 GENERAL

3.1.1 FIP PART NUMBER & DESCRIPTION

FP0780, F3200 AS4428 FIP, NO CARDFRAME, 24 ZONE MAX, 1931-95 FP0782, F3200 AS4428 FIP, NO CARDFRAME, 24 ZONE MAX, 1931-95, 6A PSU Includes: Full size cabinet Controller/Display with Operator Display & Keypad MAF/PSU (includes 7 relays, 3A/6A Battery Charger) 1 x 8 Zone Module with standard EOLRs Modules fit to cabinet rear wall (up to 3 modules max) FP0781, F3200 AS4428 FIP, C/W CARDFRAME, 64 ZONE MAX, 1931-95 FP0783, F3200 AS4428 FIP, C/W CARDFRAME, 64 ZONE MAX, 1931-95, 6A PSU Includes: Full size cabinet Controller/Display with Operator Display & Keypad MAF/PSU (includes 7 relays, 3A/6A Battery Charger) Cardframe (can house up to 8 modules) 1 x 8 Zone Module fitted in cardframe includes standard EOLRs FP0784, F3200 AS4428 FIP, SMALL CABINET, 1931-71 Includes: Small size cabinet Controller/Display with Operator Display & Keypad MAF/PSU (includes 7 relays, 3A Battery Charger) 1 x 8 Zone Module with standard EOLRs Modules fit to cabinet rear wall (up to 4 modules max)

3.1.2 SYSTEM EXPANSION

Expansion of the base F3200 panel is by adding 8 way modules. FP0553, F3200 8 ZONE INPUT EXPANSION KIT Includes: 8 Zone Module, FRC, 8 x EOLR (std) FP0554, F3200 8 RELAY EXPANSION KIT Includes: 8 Relay Module, FRC, 8 x Minijump links (for supervision selection)

3.1.3 CONTROLS

KEYPAD Type : Polyester Membrane Keypress : Buzzer gives short "beep" for valid keypress Number : 36 FF Keys : EXT.BELL ISOL.; WARNING SYS. ISOL; PREV; NEXT; ACK; RESET; ISOL 4x4 Keypad : Digits 0-9; Clear/Esc; Enter; 4 x Logic Keys

Page 27: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Specifications

Issue 1.08 30 June 2016 Page 3-3

CONTROLS (CONTINUED) Zone Functions - Alarm and Fault Test - Isolate, Reset, Recall - In-Situ Test Mode Ancillary Functions - Test, Isolate, Reset, Recall Relay Functions - Test, Isolate, Reset, Recall KEYPAD FUNCTIONS System Functions - Battery Test, Buzzer Test, Display Test - System Test - Bell Test, External Bell Isolate, Warning System Isolate - Recall : Alarms, Faults, Isolates, System Faults, History - Set time and date - Program and view parameters - Print and save database Brigade Functions - Acknowledge Alarms - View alarms (Next & Prev) - Reset acknowledged zone in alarm - Isolate acknowledged zone in alarm - Brigade Test (via menu) BUZZER (INTERNAL SOUNDER) Mounted on Controller/Display pcb Tone Steady : Fault, System Fault Unisolated zone (note 1) or relay supervision fault (note 2) Sounder re-sounds 8 hours after silence. Pulsing 2Hz : Unisolated zone alarm (note 1) Slow Pulse : Door closed with Database Write Enabled (Lk7) or zones in alarm

test or fault test. Cadence : Zone or In-Situ Test failed (note 3) Short Pulse : Valid keypress Long Pulse : Invalid keypress Notes: 1. For zones not mapped to MAF (status only) the buzzer does not turn on

(dependent also on programming of FF). 2. For relay supervision not mapped to MAF the buzzer does not turn on. 3. Cadence is repeated fast pulses with a pause.

Page 28: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Specifications

Page 3-4 30 June 2016 Issue 1.08

CONTROLS (CONTINUED) NDU NZ MODE KEYSWITCHES Brigade Functions - Trial Evacuation - Silence Alarms - Services Restore

3.1.4 DISPLAYS

Standard Operator Display Includes : LCD; FF LEDs; System Status LEDs Panel Size : 19", 4U FF Type : 3 (common indicators & common controls) Standard : Complies with AS4428.1 LCD Size : 2 Lines of 40 characters 5.5mm (H) x 3.2mm (W) per character Site Name : 40 Characters max. Zone Name : 30 Characters max. Relay Name : 30 Characters max. FF LEDs : ALARM (red); ISOLATED (yellow); FAULT (yellow); EXTERNAL BELL ISOLATE (yellow); WARNING SYSTEM ISOLATE (yellow) System Status LEDs : MAINS ON (green); CHGR/BATT FAULT (yellow); SYSTEM

FAULT (yellow); AIF ATTENDED (yellow) Internal : Mains On (green), Fuse Blown (yellow) on MAF/PSU pcb. Status LEDs Optional Additional LED Display (3 columns of LEDs) Requires 1 x ME0060 plus 1 x FZ3031 plus 1-3 x FP0475 as required. ME0060, MECH ASSY, 1901-79, F4000 RAC, EXT INNER DOOR (19", 7U, mounts up to 4 of 16 LED Display Bd) FZ3031 KIT, F3200, 16 ZONE LED DISPLAY, LHS POSITION FP0475, FP, F4000 DISPLAY EXTENDER KIT, 1901-26 Includes : 1 x 16 LED Display Bd (16 zone parallel LED display); FRC;

Power leads; zone name label. Format : 7U Parallel LED display mounts directly below the standard 4U

LCD. Zone LEDs : ALARM (red); FAULT (yellow); ISOLATED (yellow) Name Space : 10mm x 60mm per zone on paper label. E.g. 2 lines of 23 characters at 10 per inch. Optional Additional LED Display (2 columns of LEDs) Requires: 1 x ME0457 4U Ext Inner Door 1 to 5 x FP1002 16 Zone LED Board (includes 200mm FRC) 1 x LM0092 Controller to First Display 1 x LM0295 (FRC 26W 700mm) is required for each additional door Format: 4U Door – capacity 80 zones, parallel LED display

Page 29: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Specifications

Issue 1.08 30 June 2016 Page 3-5

DISPLAYS (CONTINUED) Zone LEDs: Alarm (red); Fault/Isolate (amber) Name Space: 10mm by 46mm per zone on paper label (use LT0369 from Web site) NDU New Zealand Mode Display Extender Board Status LEDs: NORMAL (green), DEFECT (yellow), FIRE (Red)

3.1.5 ENVIRONMENTAL

Operating Temperature : -5°C to 45°C (Ambient) Relative Humidity : 95% maximum @ 40°C (non-condensing)

3.2 MECHANICAL SPECIFICATIONS

CABINET Style : Wall mounting Hinged outer door with large window (hinges to left) Accepts 19" rack mounting equipment 4U Display on hinged inner door (hinges to right) Construction : Welded steel Material : 1.6mm mild steel Size : 750mm (H) x 550mm (W) x 210mm (D) * * MCP is an additional 20mm. Finish : Powdercoat BFF-998-CW Cream Wrinkle (Iron Phosphate pre-treat) Weight : Unpackaged Packaged FP0780 21kg 24kg FP0781 25kg 28kg FP0782 23kg 26kg FP0783 25kg 29kg FP0784 17kg 19kg

Page 30: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Specifications

Page 3-6 30 June 2016 Issue 1.08

3.3 ELECTRICAL SPECIFICATIONS

3.3.1 MAINS SUPPLY

Voltage : 240Vac +6% -10% Current : 0.5A Frequency : 50Hz

3.3.2 BATTERY CHARGER & PSU

Input Voltage : 31Vac rms (Transformer sec) PSU Voltage : 27.3Vdc (nominal at 20°C) Temperature : -36mV per °C nominal Compensation Non-Battery Backed : 28.0 nominal Voltage Supervision : Charger High 28.1V nominal Charger Low 26.6V nominal Max Charger Current : 3Adc (FP0780/781/784) 6Adc (FP0782/783) Max Total Load : 2.8Adc (FP0780/781/784) (Continuous - exclude 4.7Adc (FP0782/783) charging)

3.3.3 BATTERY

Battery Voltage : 24Vdc nominal (2 x 12Vdc) Compatible Makes : Sonnenschein A200 series Sonnenschein A300 series Powersonic PS12 series Yuasa NP series Capacity : 6 to 50 Ahr (dependent on load and configuration) Space : Up to 220H, 440W, 150D

Page 31: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Specifications

Issue 1.08 30 June 2016 Page 3-7

3.3.4 FUSES

Location : MAF/PSU PCB Number Name Size Rating Type F1 +VBF1 5 x 20mm 2A Glass Cartridge, Std F2 +VBF2 5 x 20mm 6A Glass Cartridge, Std F3 +VNBF 5 x 20mm 2A Glass Cartridge, Std F4 +VE 5 x 20mm 2A Glass Cartridge, Std F5 Mains In 5 x 20mm 6A Glass Cartridge, Std F7 +VBELLS 5 x 20mm 2A Glass Cartridge, Std

3.3.5 QUIESCENT & ALARM CURRENTS

At 24Vdc battery supply, nominal currents: Quiescent Alarm (2 Zone) Base Panel (notes 1 & 2) 130mA 275mA 8 Zone Module - all AZCs disabled 4mA - all AZCs enabled (notes 2-6) 82mA 97mA Current per enabled AZC (note 3) 10mA 8 Relay Module - all supervision disabled 4mA - all supervision enabled 6mA Current per relay on 11mA RS485 Communication Board 20mA Notes 1. The base panel includes Controller/Display, MAF/PSU and 1 x 8ZM with all AZCs

enabled and with EOLRs (2K7 for mode 1 or 2). 2. Quiescent current for enabled AZC is for modes 1 or 2 (standard or high current)

and includes the 2K7 EOL, but not the detector current (up to 4mA detector current per AZC).

3. The alarm current shown is for mode 1. Refer to the Technical or Installation

manual for detail on other modes. 4. The 8 Zone Modules are supplied from the fused battery supply (+VE) via the

22V regulator which has a maximum rating of 800mA. 5. The 8 Relay Modules are supplied from the fused battery supply. 6. Quiescent and alarm currents do not include external loads e.g. door holders,

bells, etc.

Page 32: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Specifications

Page 3-8 30 June 2016 Issue 1.08

3.4 INPUT SPECIFICATIONS

AZCs Number : 8 AZCs per 8 Zone Module. 64 max per system. Voltage : 20V nominal. Detector Current : 4mA max. Compatible Detectors Refer to Appendix A. End of Lines (EOLs) Mode EOL 1 Standard 2k7, 5%, 400mW resistor 2 High Current 2k7, 5%, 400mW resistor 3 Low Current 10k, 5%, 400mW resistor 4 Tamper EOL002Z active EOL 5 Disabled None MAF Door Switch 5V, 0.5mA Unsupervised 4 Way .1" pcb header, J6 MCP 5V, 1mA Supervised 2k7 EOLR 4 Way .1" pcb header, J6

3.5 OUTPUT SPECIFICATIONS

3.5.1 8 ZONE MODULE OUTPUTS

Type Darlington open collector switch to 0V Voltage Rating 28.5V max, "off" state 1V max @ 30mA, "on" state, 1.1V max at 100mA Current Rating 100mA max per O/P, 1A max per FIP Operation Programmable Default O/C 1 = Zone 1 Alarm; O/C 2 = Zone 2 Alarm, etc.

Page 33: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Specifications

Issue 1.08 30 June 2016 Page 3-9

3.5.2 8 RELAY MODULE OUTPUTS

Form 1 Pole changeover contacts Voltage-free when unsupervised Rating 30V, 2Adc resistive; 30V, 1Adc inductive Operation Programmable Supervision Programmable 400 Ohm - 10k Ohm (less than 400 Ohm requires series diode)

3.5.3 MAF/PSU OUTPUTS

Brigade Relays Number/Type 4 relays, 1 pole changeover contacts Standby Normally energised De-energises on battery fail or panel fail or in program mode. Fault, Isolated, Normally de-energised Alarm Energise on active state Rating 30V, 5A DC resistive; 30V, 3A DC inductive (Rev 1-10) 30V, 2A DC resistive; 30V 1A DC inductive (Rev 11 onwards) Isolation 1500V rms contact to coil Anc 1, Anc 2 1 Pole changeover contacts; Voltage-free Rating 30V, 2A DC resistive; 30V, 1A DC inductive Operation Programmable – default is operate on any unisolated alarm Supervision Separate terminal, 2 modes, programmable (refer to Technical or Installation manual) Anc 3 1 relay, 2 pole; Link selectable function Standard Format Polarity reversal switched 24Vdc output; 2 terminals, Bells +, - Rating 24V, 1.5A Inductive Supervision Programmable, requires diode at each device Number of Circuits Resistor End of Line (each circuit) 1 3k3 2 6k8 3 10k

Page 34: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Specifications

Page 3-10 30 June 2016 Issue 1.08

3.6 SERIAL COMMUNICATIONS

RZDU Comms Tx, Rx, 0V 3 Wire (+VBF2 also available). Terminals on MAF/PSU. Transmission 1200 Baud, Vigilant F4000 RZDU Protocol. Printer/Programmer Port Form Pseudo RS232 Rx, Tx, 0V signals only Transient Protection Allows external wiring Transmission 9600 Baud (programmable) ASCII Xon, Xoff Protocol Termination 4 Way .156" male molex (J1 on Controller/Display). Standard cables with miniature D connectors available.

Page 35: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual General Display & Keypad Operation

Issue 1.08 30 June 2016 Page 4-1

4 GENERAL DISPLAY & KEYPAD OPERATION

Page 36: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 General Display & Keypad Operation

Page 4-2 30 June 2016 Issue 1.08

4.1 INTERPRETING THE LEDS

4.1.1 OPERATOR DISPLAY LEDS

The description of LED states in this section applies to both non-networked and networked F3200 panels and also to the NDU. The 9 LEDs on the Operator Display Panel indicate status as follows: LED off (unlit) for function off; LED on (steady) for function on; The ALARM, CHGR/BATT FAULT, EXTERNAL BELL ISOLATE and WARNING

SYSTEM ISOLATE LEDs indicate further information by flashing; All LEDs (except MAINS ON) flash rapidly for 2 seconds on FIP power up, and at 1Hz for LED Test. For Fire Alarm System normal only the MAINS ON LED should be on: LED State Interpretation ALARM Flashing Unacknowledged alarm in FF alarm queue. Steady If there are no unacknowledged alarms; and the alarms

total on the base display is not zero (includes isolated zones).

ISOLATED Steady The isolates total on the base display is not zero. FAULT Steady The faults total on the base display is not zero. MAINS ON Steady Mains power is present. CHGR/BATT Flashing 2HZ Battery test failed (battery capacity less than 45%), or FAULT battery low, or battery connection fault. Also flashes if mains is failed (after 8 hours). Flashing 5HZ The charger LED flashes rapidly when a battery test is in progress. Steady Battery charger voltage is too high or low. SYSTEM Steady System Fault, e.g. electronics faulty, internal module FAULT unplugged, network fault or all zones isolated. Flashing 2Hz Tandem LCD to LCD is active (refer Section 11.8.9) AIF Steady Not implemented. ATTENDED EXTERNAL Steady External Bell output is locally isolated. BELL Flashing The External bell output is silenced due to ISOLATE network silence. Refer to Section 11.4. WARNING Steady Warning system is locally isolated. SYSTEM Flashing The Warning System is silenced due to network ISOLATE silence. Refer to Section 11.4.

Page 37: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual General Display & Keypad Operation

Issue 1.08 30 June 2016 Page 4-3

4.1.2 16 ZONE LED DISPLAY BOARDS

When these boards are fitted they provide 2 or 3 LEDs per local zone, local module relay or network zone. Any of the LEDs on the first four display boards may be controlled by an output logic equation, in which case the behaviour of the LED depends on how it is programmed. There are two types of LED display boards. One type has two columns of LEDs (red and amber) and the other type has three columns of LEDs (one red column and two amber columns). On the three column board, the red column is used to display alarm states, the middle amber column displays fault states and the right hand amber column displays isolate states. On a two column board, the red LED shows alarm, and the amber LED can be configured to show isolate states only, or both fault (flashing) and isolate (steady). Three column board LED cadences 1. Unacknowledged alarm - alarm LED 2 Hz flash 2. Acknowledged alarm - alarm LED on steady 3. Fault - middle amber LED on steady 4. Isolate - right-hand amber LED on steady 5. Partial isolate - right-hand amber LED 2.5 seconds on, 0.5 seconds off 6. Auto-reset mode (in-situ) - right-hand amber LED flashes at 2 Hz Two column board LED cadences 1. Unacknowledged alarm - alarm LED 2 Hz flash 2. Acknowledged alarm - alarm LED on steady 3. Fault - amber LED 2 Hz flash 4. Isolate - amber LED on steady 5. Fault and isolate - amber LED 2 Hz for 1 second then 1.5 on, 0.5 off

(2 short, one long) 6. Fault and partial isolate - amber LED 2 Hz for 1 second then 1 Hz for 2 seconds

(2 short, 2 long) 7. Partial isolate - amber LED 2.5 seconds on, 0.5 seconds off 8. Auto-reset mode (in-situ) - amber LED flashes at 2 Hz An alarm LED that is mapped to by a module relay is on when the relay is operated.

4.1.3 NDU NEW ZEALAND MODE DISPLAY EXTENDER BOARD LEDS

NORMAL LED - on steady means normal - off means fire, defect or abnormal condition is present FIRE LED - flashing means alarm present, otherwise off DEFECT LED - normally off - flashing for defect present

Page 38: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 General Display & Keypad Operation

Page 4-4 30 June 2016 Issue 1.08

4.2 LCD BASE DISPLAY & MENU STRUCTURE

4.2.1 GENERAL

The menu structure of the F3200 takes the form of an inverted tree, with a display screen for every branch. Each screen provides the status being searched for, a message, or a menu of options. Menu options are normally presented with numbers, and the desired choice is made by pressing the appropriate digit (0 to 9), or by pressing a specific control key e.g. "ACK" (Acknowledge), "RESET", "ALARM TEST", etc. Each choice takes the display down a level in the menu tree. Generally, control functions result in a message requesting operator confirmation for the function. For example: "Press ACK to reset zone". Pressing "ACK" then initiates the function. The "CLEAR ESC" (Escape) key is used to return up levels in the menu tree. To get from a function or status message in one branch of the tree to a function or status message in another branch of the tree, generally "CLEAR ESC" must be repeatedly pressed until the menu option gives the choice of the two branches. If "CLEAR ESC" is pressed enough times, the display returns to the trunk of the tree with one of two screens being displayed. These two screens are termed the base display.

FIG 4.2.1 MENU STRUCTURE

4.2.2 BASE DISPLAY

When the system is normal (no faults, alarms, isolates) then the base display has the site name on the top line, with software version, date and time on the bottom line. For example:

LISBORN DAIRY FACTORY F3200 V3.00 08/11/00 2:09:36

BASE DISPLAY

Page 39: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual General Display & Keypad Operation

Issue 1.08 30 June 2016 Page 4-5

BASE DISPLAY (CONTINUED) When any event has left the FIP in a non-normal state, the base display has the totals of the non-normal conditions under 4 headings. An example of a system with two zones or relays isolated, and one zone or relay fault follows.

Alarms : 0 Isol : 2 Fault : 1 Other : 0 Press the RECALL key to view

For a networked F3200 or NDU the totals may include totals received from other devices on the network. The totals are as follows: Alarms Includes alarms on all zones including isolated zones. Isol Includes all isolated zones and relays (module and ancillary). Faults Includes all zone faults, and module/ancillary relay supervision faults

(whether isolated or un-isolated). Others Includes all system faults, Plant Isolated, network faults and conditions not

associated with a zone. Pressing the RECALL key from the base display gives a menu of options which allow searching for and displaying of off normal zones and system fault conditions. The menu options given are: Alarms, Isolates, Faults and Others, plus FF, History and "more". Selecting more, (or pressing "RECALL" again) gives a second menu of recall options and repeatedly pressing RECALL cycles around the recall menus. If an alarm occurs on any un-isolated zone which is mapped to the FF then the display will switch from the base display (or wherever it was) to the FF mode (i.e. display the alarm, refer to Chapter 5). Once all alarms are acknowledged, the display can be returned to the "totals" base display by pressing "CLEAR ESC".

4.2.3 SELECTIVE FUNCTIONS

System Functions Menus for system functions can be selected by pressing "RECALL", "SYSTEM", "SET", "TEST" or "PRINT". Direct acting (non-menu) functions are "EXTERNAL BELL ISOL" and "WARNING SYSTEM ISOL". Refer to Chapter 6. Zone Functions Zone functions can be selected directly by pressing "ZONE", or indirectly by pressing "RESET", "ISOLATE", "TEST", "ALARM TEST" or "FAULT TEST". Refer to Chapter 7. Relay Functions Relay functions can be selected directly by pressing "RELAY POINT", or indirectly by pressing "RESET", "ISOLATE" or "TEST". Refer to Chapter 8.

Page 40: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 General Display & Keypad Operation

Page 4-6 30 June 2016 Issue 1.08

4.2.4 ZONE NUMBERING

An F3200 panel maps its inputs and outputs to zones so that they may be accessed and controlled over a network. Zones 1-64 - Alarm zones 1-64 Zones 65-128 - Module relays 1-64 Zones 129-192 - Open collector outputs 1-64 Zone 194 - Ancillary relay 1 Zone 195 - Ancillary relay 2 (External Bell*) Zone 196 - Ancillary relay 3 (Warning System*) Zone 197 - Plant isolate Zone 198 - Warning System Zone 199 - External Bell When the status of a relay or open collector is being shown on the LCD, the display shows both the zone number and the relay or open collector number. This mapping scheme means that there are often two ways of doing the same thing. For example, to display the status of module relay 1 it is possible to use either the ZONE key (and select zone 65) or the RELAY key (and select module relay 1). * By default Zone 195, Ancillary 2, is the External Bell output and Zone 196, Ancillary 3, is the Warning System output. This might not apply if the programming has been changed from the default.

4.2.5 OPERATING AN F3200 WITH AS1603.4 KEYBOARD

The AS4428.1 software (V3.xx) can be installed in an older F3200/NDU that has an AS1603.4 front panel, and the panel is operated as described in this manual but with the following differences. In normal mode the Bells Isol key is used to perform External Bell Isolate/de-isolate functions and the Bells Isol LED shows the External Bell Isolate status. In New Zealand mode the Bells Isol key and LED correspond to the Warning System and the External Bell is not used. Warning System isolate/de-isolate functions can be performed by pressing the Ancil Isol key from the base display and selecting the Warning System option from the menu. This menu also displays the current isolate/de-isolate status of the Warning System. If the Warning System is isolated or silenced by network Warning System silence, then the Ancillary Isolate LED will be on steady. The Ancillary Isolate LED is also on steady if any of the local Ancillary or module relays or Plant are isolated. On a network system, the Warning System and External Bell on a remote panel can be accessed (i.e. isolated, de-isolated, tested) as described in the networking chapter of this manual and the Warning System and External Bell of this panel can be accessed from other panels. The Brigade Test key may be used to directly perform a brigade test if this is enabled with programming. If the daily 40 minute battery test is enabled then the battery test resistors on the MAF/PSU module must be removed. The hourly battery test runs for a duration of 60 seconds (instead of 90 seconds) and the manual battery test runs for 60 seconds instead of 40 minutes.

Page 41: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual General Display & Keypad Operation

Issue 1.08 30 June 2016 Page 4-7

4.3 RESPONDING TO ALARMS

WHEN THE FF ALARM LED INDICATOR IS FLASHING AND THE LCD IS DISPLAYING AN UNACKNOWLEDGED ALARM, PROCEED AS FOLLOWS: STEP 1 DO NOT PRESS "ACK", "RESET", "ISOLATE", "EXT BELL ISOL",

OR "WARNING SYSTEM ISOL" KEYS ON THE PANEL until the Fire Brigade arrives. The "NEXT" key can be pressed to view the next zone alarm in the list if there is more than one alarm present. If the "NEXT" key is pressed, the internal sounder will silence, but the External Bell and warning system will continue to sound.

STEP 2 INVESTIGATE THE ALARM (if possible by Fire Safety Crew), and

implement appropriate fire control and extinguishing measures. The FIRE SEARCH AREA (zone) will be indicated by the zone text

displayed on the LCD (and by the flashing zone "ALM" LED where the LED display is fitted).

STEP 3 Evacuate the areas if necessary. STEP 4 ADVISE THE BRIGADE of real fires and false alarms. STEP 5 KEEP A MEMBER OF THE FIRE SAFETY CREW ON STANDBY to

direct fire fighters to the source(s) of alarm and inform them of measures already taken.

STEP 6 RECORD ALL EVENTS IN THE LOG BOOK PROVIDED.

** PLEASE NOTE **

The above procedure should be executed by a trained fire officer, and may need to be modified in accordance with any special conditions applying to the particular F3200 FIP installation.

Page 42: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 General Display & Keypad Operation

Page 4-8 30 June 2016 Issue 1.08

4.4 DEALING WITH FAULTS

4.4.1 WHAT IS A FAULT?

A fault is any situation which prevents the fire alarm system from performing its functions correctly. Possible faults include defects in wiring to the detectors, faulty detectors, removed detectors, component failures, prolonged mains failure and faulty battery charger.

4.4.2 RESPONDING TO FAULT SIGNALS

For a networked system, refer also to Section 11.6. When a fault occurs, the fault sounder operates (steady tone). If the fault exists on a zone or relay then the FF "FAULT" LED will be ON. If a system fault exists, the "SYSTEM FAULT" LED will be ON. If a Battery/Charger fault exists, the "CHGR/BATT FAULT" LED will be ON or FLASHING. The screen will show a message indicating a fault is present and what action to take (usually to call the service company). The "CLEAR ESC" key or "ACK" key may be pressed in order to silence the panel's fault sounder until a service technician arrives. If a fault or other off-normal condition exists, the LCD will display the number of Alarms, Faults, Isolates and Other off-normal conditions. To determine the source of the fault conditions, use the following keypad commands, i.e. press Recall from the base display and select the appropriate menu option: Recall Faults Recall More, System Faults Recall History Recall Other These commands allow an operator to quickly determine the fault condition(s). Note that the Recall Faults command will show all zones and relays that have faults, regardless of the Isolate status. The Recall History command can help to determine the sequence of fault conditions as the events are ordered chronologically.

** PLEASE NOTE **

(a) Subsequent faults will re-start the fault sounder. (b) RECORD ALL EVENTS IN THE LOG BOOK PROVIDED.

Page 43: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual General Display & Keypad Operation

Issue 1.08 30 June 2016 Page 5-1

5 OPERATING INSTRUCTIONS - BRIGADE FUNCTIONS

Page 44: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 General Display & Keypad Operation

Page 5-2 30 June 2016 Issue 1.08

5.1 INTRODUCTION TO BRIGADE FUNCTIONS

5.1.1 GENERAL OPERATION & DISPLAY

When an alarms occurs, the FIP switches from the base (or other) display to FF mode and displays the alarm. The keys that can be used are then limited to those within the Firefighters Facility (FF), plus "CLEAR ESC”. The FF is the area of the keypad within the red border, as shown in Figure 5.1.

FIG 5.1 EXAMPLE FIREFIGHTER'S FACILITY (FF) The FF operates as follows: Each zone alarm is displayed on the LCD and must be individually acknowledged by pressing the "ACK" key when the alarm is displayed. Each alarm can then be reset or isolated by pressing the "RESET" or "ISOLATE" keys respectively, followed by the “ACK” key. The “NEXT” and “PREV” keys can be used to step around multiple alarms if they exist. All alarms must be acknowledged before the display can exit from the FF mode. The "EXTERNAL BELL ISOLATE" key may be used at any time to isolate or de-isolate the External bell (strobe and/or bell). The “ WARNING SYSTEM ISOLATE” key may be used at any time to isolate or de-isolate the warning system.

Page 45: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual General Display & Keypad Operation

Issue 1.08 30 June 2016 Page 5-3

5.1.2 FF OPERATION

When the FIP is displaying an alarm the LCD display includes the following information: (i) The time at which the alarm occurred. (ii) The zone alarm type. (iii) Whether the alarm is acknowledged or not (Figure 5.1 shows an unacknowledged

alarm). (iv) The total number of alarms and the sequence number of the currently displayed

alarm. (v) The zone number and location. (vi) For network systems the “AND.” or “RELAY/POINT” key may be used to display

additional information. The F3200 FIP maintains a list of alarms in the order in which they occurred. In the absence of operator intervention, the LCD display will show the first alarm. All alarms in the list can be viewed, one by one, by pressing the "NEXT" or "PREV" keys. Each alarm can be individually acknowledged when it is displayed by pressing the "ACK" key. The text "ACKD" appears on the display whenever an acknowledged alarm is viewed. Once an alarm has been acknowledged, it can be removed from the alarms list by: (i) Pressing the "RESET" key and then the “ACK” key within 10 seconds. The

indicated alarm is RESET and removed from the list; or (ii) Pressing the "ISOLATE" key and then the “ACK” key within 10 seconds. The

indicated alarm is ISOLATED and removed from the list; or (iii) The alarm condition being cleared from a non-latching detector on a non-latching

zone. Once all alarms have been acknowledged, stepping past the end (or the beginning) of the alarm list will include any isolated alarms. On pressing “NEXT” at the most recent alarm, or “PREV” at the oldest alarm, a display will show the number of isolated alarms present and a prompt to search for these. Pressing “NEXT” will start a recall of isolated alarms from the beginning (these are shown in numerical order), while “PREV” will start from the end. Pressing “CLEAR/ESC” at this prompt will go back to the first alarm in the alarm list. After all alarms have been acknowledged, pressing the "CLEAR ESC" key will exit from the FF alarm list display even if there are still zones in alarm. After exiting, the FF alarm list display can be recalled by using the RECALL FF command from the base display.

Page 46: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 General Display & Keypad Operation

Page 5-4 30 June 2016 Issue 1.08

5.2 SILENCING THE INTERNAL SOUNDER

5.2.1 FUNCTION

Pressing any key will silence the internal sounder, ie, cancel the pulsing alarm tone, steady fault tone, or rapid pulsing test fail tone. Note that the key pressed will still be processed as if the sounder was not on. Therefore, it is safest to use the "CLEAR ESC" key to silence the sounder and not to use the "ACK" key for faults or other states which are not automatically displayed. Note: The alarm bell is silenced by the "EXTERNAL BELL ISOLATE" key.

5.2.2 OPERATING SEQUENCE

Press "CLEAR ESC" key once. - The internal sounder silences. NOTE: If a key sequence was being entered, it may be necessary to re-enter number information or the last command as the "CLEAR ESC" key will, in addition to silencing the buzzer, either step back through the menu or clear any number entry sequence that has been started. If all zone alarms are acknowledged, pressing the "CLEAR ESC" key will result in the LCD exiting FF mode. It can be re-entered by use of the Recall FF command by pressing the "RECALL" key when the base display is shown and selecting the FF option (option 1).

Page 47: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual General Display & Keypad Operation

Issue 1.08 30 June 2016 Page 5-5

5.3 ACKNOWLEDGE ZONE IN ALARM

5.3.1 FUNCTION

In FF mode, pressing the "ACK" key performs the following functions: (a) The displayed alarm is acknowledged. (b) The pulsing internal sounder is silenced. (c) For a network system: (i) For a local zone an FF acknowledge indication may be sent to other

devices on the network;

(ii) For a remote zone, an acknowledge command may be sent to the panel originating the alarm.

5.3.2 OPERATING SEQUENCE

Press "ACK" key once: - Internal sounder will be silenced. - LCD displays "ACKD" for the currently displayed alarm. - If there are no more unacknowledged alarms in the system, the ALARM LED goes steady. - Where fitted, the flashing red "ALM" LED indicator for the zone goes steady. NOTES: (a) Subsequent non-isolated zone ALARMS or FAULTS on the system will re-

operate the indicators, and sounder, as appropriate. (b) If an unacknowledged FAULT condition existed before the alarm the sounder will

still be silenced. However, the FAULT LED will be ON, indicating the presence of a zone or relay fault in the system.

(c) For a network system, if the alarm being acknowledged is from a zone on a

remote panel, then the event in the local FF will be "ACKD" and, depending on programming, an ACK command may be sent to the panel originating the alarm, which in turn may result in the alarm being acknowledged at all devices on the network.

(d) For an alarm on a local zone, depending on programming, the alarm may be

acknowledged at an RZDU which may result in the alarm being acknowledged at the FIP (and hence, for a network system, at other devices on the network).

Page 48: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 General Display & Keypad Operation

Page 5-6 30 June 2016 Issue 1.08

5.4 RESET ACKNOWLEDGED ZONE IN ALARM

5.4.1 FUNCTION

In FF mode, pressing the "RESET" and then the “ACK” key within 10 seconds performs the following: (a) RESETS the indicated zone. (b) Silences the internal sounder. (c) Aborts zone test if the zone is under test. (d) If no more un-isolated alarms exist, the External Bell, warning system, ancillary

relays and Brigade Alarm relay turn OFF, if they were ON. (e) The acknowledged zone alarm is removed from the alarm list. (f) For a network system: (i) For local zones, a return to normal indication may be sent to other

network devices to allow the alarm to be removed from their FF list. (ii) For remote zones, depending on programming, a reset command may be

sent to the originator of the alarm. The alarm remains in the FF list of the local panel until the originator of the alarm indicates the alarm has been reset.

5.4.2 OPERATING SEQUENCE

Press "RESET" key once: - LCD displays "Press acknowledge to confirm reset". - Press the “ACK” key within 10 seconds. - The displayed zone in the alarm list will be reset. - If fitted, the red alarm LED indicator for the zone will be turned

OFF. - If there are no more unisolated zones in alarm, then the External

Bell, Warning System and Brigade alarm relay will be turned off. - The internal sounder will be silenced. NOTES: (a) If the alarm condition on the zone input has not been removed, then a new alarm

will be generated after the appropriate filtering time delay. (b) If a fault condition exists in a zone that also has an alarm condition, FF Reset will

not clear the fault. To Reset the fault condition, the Operator must first exit FF mode. (Refer to Sections 5.7 and 7.3).

Page 49: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual General Display & Keypad Operation

Issue 1.08 30 June 2016 Page 5-7

5.5 ISOLATE ACKNOWLEDGED ZONE IN ALARM

5.5.1 FUNCTION

In FF mode, pressing the "ISOLATE" key and then the “ACK” key within 10 seconds performs the following: (a) ISOLATES the indicated zone. (b) Silences any internal sounder condition. (c) If all alarms are isolated, then the External Bell, Warning System, Brigade alarm

relay and any ancillary relays turn off. (d) The acknowledged local zone alarm is removed from the alarm list. (e) For a network system: (i) For local zones, an isolate condition may be sent to other network devices

to allow the alarm to be removed from their FF list. (ii) For remote zones, depending on programming, an isolate command may

be sent to the originator of the alarm. The alarm remains in the FF list of the local panel until the originator of the alarm indicates the alarm can be removed.

5.5.2 OPERATING SEQUENCE

Press "ISOLATE" key once: - The LCD displays “Press acknowledge to confirm isolate”. - Press “ACK” within 10 seconds. - The displayed zone in the alarm list will be isolated - shown by

the corresponding amber "ISOLATED" LED indicator turning ON.

- If all alarms are isolated then the External Bell, Warning

System, Brigade Alarm relay and any ancillary relays will turn off.

- The internal sounder, if on, will be silenced. NOTES: (a) Subsequent non-isolated zone ALARMS on the system will re-operate the alarm

indications, alarm sounder and local bells. (b) Subsequent non-isolated zone FAULTS on the system will operate the fault

indication and steady fault sounder. (c) To DE-ISOLATE alarm zones, FF mode must be exited and the zone selected for

de-isolation. Refer to the Exiting FF mode section in this chapter and the Zone Isolating/De-Isolating section in Chapter 7.

Page 50: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 General Display & Keypad Operation

Page 5-8 30 June 2016 Issue 1.08

5.6 ISOLATING/DE-ISOLATING EXTERNAL BELL

5.6.1 FUNCTION

For a network system, refer also to Section 11.4. The isolate status of the External Bell (strobe and/or bell) can be changed at any time during FF alarm display by pressing the "EXTERNAL BELL ISOLATE" key. The isolate status of the EXTERNAL BELL is shown on the " EXTERNAL BELL ISOLATE" LED. If it is ON the bell is isolated and will not sound. If the LED is OFF the bells will sound when an un-isolated alarm is present on any zone which is programmed (mapped) to operate the bell. Isolating the External Bell can serve as a method to silence the bell whilst un-isolated alarms still exist. De-isolating the External Bell allows the bell to turn on for subsequent alarms occurring, and can serve to immediately turn the bell on again if any un-isolated zone alarm condition exists for zones which are mapped to the bell.

5.6.2 OPERATING SEQUENCE

Press the "EXTERNAL BELL ISOLATE" key once: - If the bell was un-isolated: - The " EXTERNAL BELL ISOLATE " LED turns ON steady. - The bell, if ON, turns OFF. - If the bell was isolated: - The " EXTERNAL BELL ISOLATE " LED turns either OFF, or slow flashes. - If any un-isolated alarm condition exists on a zone mapped

to the External Bell, then the External Bell turns ON, unless the External Bell isolate LED is flashing.

NOTE: If any subsequent alarm occurs, the External Bell will turn ON only if the External Bell is un-isolated.

Page 51: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual General Display & Keypad Operation

Issue 1.08 30 June 2016 Page 5-9

5.7 ISOLATING/DE-ISOLATING WARNING SYSTEM

For a network system, refer also to Section 11.4. The isolate status of the Warning System can be changed at any time during FF alarm display by pressing the "WARNING SYSTEM ISOLATE" key. The isolate status of the WARNING SYSTEM is shown on the " WARNING SYSTEM ISOLATE" LED. If it is ON the Warning System is isolated and will not sound. If the LED is OFF the Warning System will sound when an un-isolated alarm is present on any zone which is programmed (mapped) to operate the Warning System. If the LED is flashing the Warning System is silenced by network silence, or NZ Silence Alarms, and will not sound. Isolating the Warning System can serve as a method to silence the Warning System whilst un-isolated alarms still exist. De-isolating the Warning System allows the Warning System to turn on for subsequent alarms occurring, and can serve to immediately turn the Warning System on again if any un-isolated zone alarm condition exists for zones which are mapped to the Warning System.

5.7.1 OPERATING SEQUENCE

Press the "WARNING SYSTEM ISOLATE" key once: - If the Warning System was un-isolated: - The " WARNING SYSTEM ISOLATE " LED turns ON

steady. - The Warning System, if ON, turns OFF. - If the Warning System was isolated: - The " WARNING SYSTEM ISOLATE " LED turns either off or slow flashes. - If any un-isolated alarm condition exists on a zone mapped

to the Warning System, then the Warning System turn ON, unless the Warning System isolate LED is flashing.

NOTES: If subsequent alarm occurs, the Warning System will turn ON only if the Warning System is un-isolated. If the Warning System is a standalone Evacuation System then isolating the Warning System on the F3200 may not silence the Evacuation System. In this case it is necessary to operate the Evacuation System directly to silence the Warning System. For an NDU in New Zealand mode the Warning System Isolate LED flashes (at 2HZ) if a Silence Alarms keyswitch has been turned on, and flashes more slowly (at 1HZ)) if the Warning System is silenced by network Warning System silence.

Page 52: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 General Display & Keypad Operation

Page 5-10 30 June 2016 Issue 1.08

5.8 EXITING FF MODE

5.8.1 FUNCTION

While in FF mode, access to all other functions and displays is prevented. On occasion it may be necessary to recall an Isolated Alarm, de-isolate a zone or perform some other function. To do so, FF mode must be exited. FF mode can be exited only when ALL alarms in the list have been acknowledged. When FF mode is exited, the LCD shows the base display (totals). At this point, the required functions can be performed e.g. Recall Zone.

5.8.2 OPERATING SEQUENCE

Press the "CLEAR ESC" key once: - If all alarms are acknowledged, FF mode is exited and the LCD

shows the totals. - If any alarms are NOT acknowledged, the sounder will produce

an error tone, and FF mode will not be exited. It is necessary to acknowledge all alarms before FF mode can be exited.

NOTE: To re-enter FF mode to view the list of alarms, use the Recall FF command sequence. Refer to Section 5.8 Recalling Alarms.

Page 53: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual General Display & Keypad Operation

Issue 1.08 30 June 2016 Page 5-11

5.9 RECALLING ALARMS

5.9.1 FUNCTION

It is possible for there to be un-isolated, acknowledged alarms present in the FF queue, but the display NOT be in FF mode. The FF can be recalled, and thus put the display into FF mode.

5.9.2 OPERATING SEQUENCE

Press the "CLEAR ESC" key until the base display is shown. Press the "RECALL" key followed by the "1" key to show the FF alarms list. The display will start at the first alarm in the alarm list. If there are no alarms in the FF alarm queue, then the LCD will briefly display "There are no (more) alarms" and revert to the base display.

5.9.3 NON-FF ALARMS

It is possible to have zones not mapped to the FF (i.e. display only zones, e.g. flow switch). These might be displayed on LEDs only. If such a zone goes into alarm the buzzer will not sound, the LCD will not automatically display the zone, but the FF ALARM LED will be on and the Alarms total will be non-zero. The zone can be found by Recall Alarms (RECALL 4). It is also possible to have "status only" zones which do not appear in the totals at all. These may only be recalled by pressing "Zone", followed by the zone number.

Page 54: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 General Display & Keypad Operation

Page 5-12 30 June 2016 Issue 1.08

5.10 BRIGADE FUNCTIONS ON NETWORK SYSTEMS

All of the brigade functions and commands operate exactly as described in Chapter 5, Sections 5.1 to 5.9. I.e. the FF alarm list operation, acknowledging, resetting, or isolating alarms, etc. is the same for network systems, but the following additional details apply to network systems. FF Alarm List Operation Depending on programming, the FF alarm list may contain alarms received from other devices on the network. Local Alarms Local alarms may always be acknowledged, reset, or isolated. Depending on programming, they may also be acknowledged, reset, or isolated from other network devices or from local RZDUs. With programming, it is possible to inhibit the acceptance of acknowledgements from other network devices or RZDUs and force all alarms to be acknowledged at each device. Remote Alarms Alarms received from remote devices may always be locally acknowledged in the local FF alarm list and this will cause an acknowledge command to be sent to the remote device that originated the alarm. Depending on its programming, the remote device may accept this command, and in turn cause all devices on the network to receive an acknowledge indication for the alarm. Depending on programming, alarms originating from remote devices may also be reset or isolated from the "local" FF display. I.e. when a reset or isolate function is carried out the appropriate command will be sent to the remote device originating the alarm. If this function is disabled, the FF Reset or FF Isolate functions will not send a reset or isolate command to the remote device, and further, the remote device may reject the command with an exception message. "Point" Key Operation When a remote alarm is being displayed on the FF display, either the

OR

key may be pressed (and held) to show additional information about the source of the alarm.

Page 55: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-1

6 OPERATING INSTRUCTIONS - SYSTEM FUNCTIONS

Page 56: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-2 30 June 2016 Issue 1.08

6.1 BATTERY TEST & PSU FAULT INHIBIT

6.1.1 FUNCTION

For a network system: to test the local battery follow this section; to test the battery at a remote panel refer to Section 11.8.2. A battery test will disable the battery charger and place the panel load onto the battery for 40 minutes.

6.1.2 OPERATING SEQUENCE

From the base display press the "BATT TEST" key. - The message "Press ENTER to initiate battery test" will appear. Press the "ENTER" key to initiate the battery

test, or "CLEAR ESC" to exit. When the battery test is initiated the display will show "40 minute battery test in progress - press RESET to abort", along with the time (minutes : seconds) that the test has been running for.

The charger LED will flash rapidly while the test is in progress.

TO STOP THE BATTERY TEST WHEN RUNNING - Press the "RESET" key.

THE TEST PASSES - If at the completion of the test the battery voltage is still

within specification, then the test will terminate and the LCD displays “Battery test passed. Pres ACK”.

- Press the “ACK” key and the LCD will return to the base

display.

THE TEST FAILS - If during the test a battery low is detected, the test will terminate and the LCD will display "Battery test failed. Press ACK", and a Battery Test Fail event will be logged to history. No fault will be generated.

- Press the "ACK" key to exit back to the base display. - Perform another battery test after 24 hours and if this fails

as well contact your service company. - If it is known that the battery needs recharging then battery

and power supply faults can be inhibited as described in Section 6.1.3.

NOTE: While the 40 minute battery test is in progress, the keypad and LCD may be used to do other things. Pressing CLEAR will leave the 40 minute battery test running and return to the base display. Pressing BATT TEST from the base display when the battery test is in progress will show the status of the test and the RESET key can be used at this point to terminate the test. If the battery test status screen is not displayed at the time the test finishes, then the result of the test is not shown on the LCD. However, an event is logged to the history indicating whether the test passed or failed.

Page 57: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-3

6.1.3 PSU FAULT INHIBIT

When a flat battery is connected to a panel, it may take some time before the battery voltage rises above the battery low threshold or for the battery connection test to pass. To allow a service person to clear/inhibit these faults temporarily (for 24 hours) a PSU Fault Inhibit command is provided. From the base display press:

The message “Press ACK to inhibit PSU faults for 24 hours” will appear. Press the

Key and the message “PSU faults inhibited for 24:00 h:m, Press RESET to cancel” will appear. After PSU fault inhibit has been enabled, the CLEAR Key can be used to return to the base display. From the base display, pressing the key sequence:

will show the remaining time that PSU faults will be inhibited for. When the PSU fault inhibit command is entered any existing battery capacity or battery connection faults are cleared. While the PSU fault inhibit timer is running any battery low conditions or charger faults do not signal fault to the brigade but will still flash the charger LED and appear in the system fault recall. A fault resulting from 8 hours of mains fail is not cleared by the PSU fault inhibit. The logic tokens BFT, CGF and BLO return false while the PSU fault timer is running, so any outputs driven by these conditions will be disabled. When the PSU fault inhibit timer elapses, or is RESET, any battery low, battery connection or charger faults will be signalled to the brigade and logged to history etc, and automatic battery tests will resume at their scheduled times.

6.1.4 AUTOMATIC BATTERY TEST

The F3200 can be programmed to carry out automatic battery capacity tests on the hour (lasts 60 seconds) and at the same time as the automatic system test (lasts 40 minutes). If there is no automatic system test, then the automatic battery test is done at 9:00am on working days.

Page 58: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-4 30 June 2016 Issue 1.08

6.2 EXTERNAL BELL TEST

6.2.1 FUNCTION

To operate the External Bell Output of this panel for a period of five (5) seconds follow this section. To test the External Bell Output at a remote panel refer to Section 11.8.5.

6.2.2 OPERATING SEQUENCE

From the base display press: For a non-network panel: For a networked panel:

The LCD will show "Press ACK to activate external bell for 5 seconds”. Press the "ACK" key to initiate the test. The External Bell output will then operate for 5 seconds. It can be stopped at any time by pressing the "ACK" key.

6.2.3 NOTES

The action that occurs when an External Bell Test is done depends on the programming of the panel. When an External Bell Test is initiated, the EBT logic token is set true for 5 seconds. Outputs that include EBT in their logic equation will then operate for five seconds. The default programming is for the Ancillary 2 relay to operate when an External Bell Test is done.

Page 59: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-5

6.3 WARNING SYSTEM TEST

6.3.1 FUNCTION

To operate the Warning System Output of this panel for a period of five (5) seconds follow this section. To test the Warning System Output at a remote panel refer to Section 11.8.6.

6.3.2 OPERATING SEQUENCE

From the base display press: For a non-network panel: For a networked panel:

The LCD will show “Press ACK to activate warning system for 5 seconds”. Press the “ACK” key to initiate the test. The Warning System output will operate for 5 seconds. It can be stopped at any time by pressing the “ACK” key.

6.3.3 NOTES

The action that occurs when an Warning System Test is done depends on the programming of the panel. When an Warning System Test is initiated, the WST logic token is set true for 5 seconds. Outputs that include WST in their logic equation will then operate for five seconds. The default programming is for the Ancillary 3 relay to operate when an Warning System Test is done.

Page 60: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-6 30 June 2016 Issue 1.08

6.4 LCD/LAMP (LED) TEST

6.4.1 FUNCTION

To momentarily flash all LED indicators to visually inspect that they are working correctly, and to test operation of the LCD.

6.4.2 OPERATING SEQUENCE

From the base display, press: For a non-network panel: For a networked panel:

A number of different test patterns are displayed on the LCD. At the same time as the LCD test pattern is shown the LED indicators on the front panel (except the “MAINS ON” LED) will be flashed on for half a second, off for half a second, for 5 seconds. After the front panel LEDs and LCD have been tested, the zone (and relay) LED display boards will be tested, one board (16 zones) at a time. Each display board will be tested for about 3 seconds and all 48 LEDs on the board will be turned on and off simultaneously with half a second on and half a second off. The testing of the LED display boards can be terminated by pressing "RESET". The test can be paused and resumed at a particular display board by using the "ISOLATE" key. The test can be stepped to the next display board by using the "ACK" key. The "ACK" key can be used to step to the next display board when the test is in pause mode. NOTE: For an NDU in New Zealand mode a Lamp Test can also be started by momentarily shorting the LAMP TEST input on the Display Extender board to 0V.

Page 61: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-7

6.5 SYSTEM TEST

6.5.1 FUNCTION

For a network system to perform a local system test follow this section; to initiate a system test at a remote panel refer to Section 11.8.1. The System Test checks the integrity of the system hardware and software. It applies simulated alarm and fault conditions to each circuit to check that the conditions are detected and processed correctly. It also checks the Controller RAM and EPROM and checks the database EEPROM checksum.

6.5.2 OPERATING SEQUENCE

From the base display, press:

or

A system test cannot be initiated when any of the following conditions are present: (a) Database EEPROM checksum error. (b) Module configuration fault. (c) Battery very low. (d) Shift register bus fault. (e) Any zone currently being reset or in zone test or In-Situ mode. (f) Auto-test currently in progress. If none of the above conditions are present, a system test will be initiated and the LCD will show "System test in progress - press RESET to abort". The test may be terminated prematurely at any point by pressing the "RESET" key. If the test fails for any reason, a test fail cadence will sound on the buzzer and an error message will appear on the display. The system test will perform memory tests concurrently with circuit fault and alarm tests. Output logic execution continues to run during system test. If a circuit test fails, the brigade fault relay and "SYSTEM FAULT" LED will turn on.

Page 62: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-8 30 June 2016 Issue 1.08

6.5.3 TEST DESCRIPTION

6.5.3.1 Controller Tests

If the Controller RAM or EPROM test fails, then the Brigade standby relay will de-energise and the "SYSTEM FAULT" LED will turn on but processing of circuit alarms and faults will continue. If the database EEPROM checksum test fails then all circuit alarm and fault processing will stop and the panel will become in-operational and the standby relay will de-energise. After this fault occurs, it is not possible to perform another system test to re-check the EEPROM database. To recover, do the following. First, power the panel off and on again which will check the database EEPROM and start processing if the checksum is correct. If the fault does not clear then enter program mode using the "SET" key and entering the password. Then exit program mode which will calculate and save the checksum of the database and then re-check the checksum. It is advisable to do a printout of the entire database and re-check all of the programmed data. Alternatively, upload a new database into the F3200 panel by entering program mode and loading a previously saved database.

6.5.3.2 Circuit Tests

Circuit fault tests are done first followed by circuit alarm tests. The system will NOT test a circuit if any of the following is true: 1. The circuit is disabled. 2. The zone is isolated. 3. The zone is latched in fault or alarm. 4. The zone is a Status Only zone. 5. The circuit input is in B1 band (short circuit) and B1 is programmed to be normal. 6. The 8 Zone Module has been unplugged (partial module configuration fault, see

Chapter 6.6.3). A circuit fault test is done on all odd numbered circuits simultaneously - first (1, 3, 5 ....) taking 4 to 8 seconds, depending on whether any tamper circuits are being tested, followed by all even numbered circuits (2, 4, 6 ....) taking a further 4 to 8 seconds. After the fault tests, circuit alarm tests are done. All circuit modules are tested simultaneously but only one circuit per module is tested at a time. E.g. if there are 16 zones (two modules) then circuits 1 and 9 will be tested simultaneously, followed by circuits 2 and 10, etc, up to circuits 8 and 16. Each circuit alarm test takes 2 seconds making a total of 16 seconds for the entire circuit alarm tests. If a circuit test fails or an unexpected alarm or fault occurs, then the circuit tests will stop immediately, a test fail cadence will sound on the buzzer and the "BRIGADE FAULT" relay will turn on.

Page 63: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-9

6.6 RECALL SYSTEM FAULTS

6.6.1 FUNCTION

Allows an operator to view on the LCD the current causes of a "SYSTEM FAULT" indication. It also displays the status of any RZDU that has an off-normal condition, including those which do not cause System Fault, and some conditions that don’t cause System Fault (e.g. Mains Fail).

6.6.2 OPERATING SEQUENCE

For both networked and non-networked systems, from the base display, press: OR

If there are no system faults, a brief message is displayed saying so, and the LCD reverts to the base display. If a system fault exists, the LCD will display it. To view the next fault, press:

To view the previous fault, press:

6.6.3 LIST OF SYSTEM FAULTS

A system fault recall shows additional network fault information described in Section 11.6.1 NETWORK SYSTEM FAULT RECALL. Some of this information also applies to non-networked panels and appears in a system fault recall as a sequence of “pages” with the heading “System Status Summary”. If any connected RZDU has an off-normal condition present, then an RZDU status display is included for that RZDU. Refer Section 6.13 RZDU STATUS DISPLAY. Faults which can be displayed in a system fault recall are as follows. 1. Mains fail.

This indicates that mains is currently failed. When mains has been failed continuously for 8 hours, a system fault may be generated, depending on programming.

2. Flash database checksum error. The panel is non-operational if this fault is present.

3. Flash database version error. This occurs if the database checksum is correct but the database is an incompatible version with a format that cannot be used. Alarm processing is disabled when this fault is present and the panel is non-operational.

Page 64: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-10 30 June 2016 Issue 1.08

LIST OF SYSTEM FAULTS (CONTINUED) 4. Ram database reloaded after corruption

This occurs if the database in RAM is corrupted or fails to verify. The database is stored in both flash memory and RAM and is copied from flash to RAM at startup. The Controller continually checks that the database in RAM is identical to the copy in flash. If a mismatch is detected, and the checksum of the database in flash is correct, then the database is re-loaded into RAM, which may result in this fault self-clearing a short time later.

5. Module configuration mismatch This fault occurs when the number of Zone or Relay Modules installed does not match the programmed number of modules required to be present. The display indicates whether processing is enabled or disabled. On detection of a module mismatch, processing is disabled and the panel is non-operational. Modules can be temporarily selected as "not present" using the "Bds present" option accessed by pressing the SET from the base display. This is a temporary measure which allows alarm processing to continue until the full complement of modules is installed.

6. Keypad disconnected. The keypad has been disconnected or there is a hardware fault associated with the two keypad membranes connected to the Controller board. Processing of circuit inputs and alarms continues.

7. LED display board fault There is a fault with a zone or relay LED display board. This can occur if the wrong number of display boards is installed or the termination link on the last board is missing.

8. LCD display fault A fault has occurred with the 80 character LCD. This can occur at startup or during an LCD test.

9. EPROM CRC error A checksum calculation of the firmware in flash memory has failed. This can occur during System and Auto Test.

10. RAM write read fault A write read test of main RAM has failed. This can occur during System and Auto Test.

11. Charger [high/low/normal] Raw value = [high/low/normal] This message indicates the battery charger voltage is high, low or normal. The “Raw” high/low/normal value indicates the actual current sate of the charger voltage monitoring input. The first high/low/normal value (“Charger”) indicates the “signalling” state, where the signalling state is the raw value subject to some filtering delays as follows. A raw charger high (or normal) condition must be present continuously for 5 seconds before becoming the signalling state. A raw charger low condition must be present continuously for 60 seconds before becoming the signalling state, plus a raw charger low condition is ignored for 30 minutes after an automatic or manual battery capacity test. During a battery test, the “raw” value will normally be low because the charger is inhibited, but a charger low will not be signalled for this. If the charger signalling state is high or low, a brigade fault will be signalled (subject to programming of charger fault to signal brigade fault).

Page 65: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-11

LIST OF SYSTEM FAULTS (CONTINUED) 12. Fuse blown

There are several fuses on the MAF module that can be blown. Refer to section 3.3.4 FUSES.

13. Clock chip RAM fault Clock chip RAM is used to store all the isolate data (zone and relay isolate status, etc) plus temporary "board present" settings. The isolate data and board present data is read from clock chip RAM at startup and this fault means the clock chip RAM has not saved the data correctly and will probably not be read correctly at startup.

14. All MAF zones isolated This fault occurs if all zones (mapped to MAF) are isolated. This can be inhibited with an option in programming.

15. Supply failed This fault means that both mains has failed and the battery voltage has fallen to 21 volts or below. The standby relay is de-energised and all processing of circuit inputs stops.

16. Output logic exec error nn An error has occurred with output logic execution and output logic execution is suspended. The error numbers have the following meaning. 1. Corruption in output logic data. Conflicting information has been found in the

output logic.

2. Invalid opcode An invalid token has been encountered in a logic equation.

3. Range error This occurs when an out of range value is found such as a timer number greater than 64 or an ancillary relay number greater than 3.

4. Stack error. The logic execution stack in RAM has overflowed or underflowed. This error should never occur as it is checked for at programming time.

5. Link error An invalid value has been found in a link field in a logic equation.

6. Invalid data.

7. NA (New Alarm) function RAM limit exceeded. This error should never occur as it is checked for at programming time.

8. Netvar SID not present This error occurs if a network variable in the output logic specifies a SID which is not present in the SID list of this panel. Every SID for which netvars are to be accessed must be entered into the SID list of this panel.

9. Zone command range error An equation to isolate/deisolate or reset a zone or range of zones had an invalid zone number.

10. BEL/BLI logic token present This indicates the output logic contains the BEL or BLI tokens, which are not valid in V3.XX or later software.

Page 66: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-12 30 June 2016 Issue 1.08

LIST OF SYSTEM FAULTS (CONTINUED) 17. System/Auto Test circuit test fail

A circuit test failed during System or Auto Test or an unexpected fault or alarm occurred during the test. The Brigade fault relay is turned on when this fault is present. The fault will be cleared by a successful System or Auto Test. Isolating the faulty circuit & performing a System Test should allow the test to pass & clear the fault.

18. Shift register bus fault This error indicates a fault with the bus connecting the Controller with the MAF/PSU, zone modules and relay modules. It may be caused by a break or short in the flat ribbon cable (e.g. bd unplugged), by temporary noise, or by a circuit board fault. When this fault occurs all outputs will be held in their current state and all processing of inputs will stop until the fault clears. If the fault does clear, processing of outputs and inputs will resume automatically. This error can also be generated at start up.

19. RZDU x This displays the current status of any RZDU which has an off-normal condition. Refer to Section 6.13 RZDU STATUS DISPLAY for a description.

20. Net msg discard This fault occurs only with network systems. The local system discarded a message that was being sent to another device on the network because no acknowledgement has been received after multiple attempts to send. This can occur if the target device is offline or the network is overloaded or there is a hardware or wiring fault.

21. Net port fault This indicates a hardware fault with the network serial port on the Controller board.

22. Clock crystal timebase check fail This error message occurs only at startup and indicates the frequency of the clock chip on the Controller is out of tolerance to the microprocessor. The Controller will restart after 5 seconds and try the test again.

23. Clock register write read fail A test of the Controller time/date clock registers has failed. The Controller will restart after 5 seconds and try the test again.

24. Clock chip RAM write read fail A read/ write test of the Controller’s clock chip RAM has failed. The Controller will restart and try the test again.

25. Shift reg clocking fault This is the same fault as “Shift register bus fault” above. However, this fault occurs only at startup or on exit from programming mode when the panel is trying to determine what modules are present.

26. Invalid BEL/BLI logic tokens This message indicates that the output logic in the database in Flash contains either the BEL or BLI logic token. These tokens are valid with V2.XX (AS1603) software but not with V3.XX (AS4428) software. This fault can occur if V3.XX software is installed in a panel containing a database created with V2.XX software that has not been updated.

Page 67: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-13

LIST OF SYSTEM FAULTS (CONTINUED) 27. Battery is low

This message indicates the battery voltage is low. When PSU faults are inhibited for 24 hours, this message will still appear in a system fault recall if the voltage is low even though it is not creating a system fault.

28. Battery connection fail This message indicates the battery is not connected, but may occur with the battery connected if the battery is faulty or has a low charge. When PSU faults are inhibited for 24 hours, this message will still appear in a system fault recall if the battery appears to be not connected even though a system fault is not being signalled.

29. Battery capacity low This message indicates an automatic battery test failed, i.e. the battery has a low charge.

30. External defect This fault occurs only on an NDU in New Zealand mode and indicates the External Defect input on the N.Z. Display Extender board is active.

31. External evac defect This message indicates the External Evac defect input on the N.Z. Display Extender board is active.

32. Silence alarms This message indicates the Silence Alarms input on the N.Z. Display Extender board is active.

33. Trial evac This message indicates the Trial Evac input on the N.Z. Display Extender board is active.

34. Services restore This message indicates the Services Restore input on the N.Z. Display Extender board is active.

35. Brigade iso/test This message indicates the Brigade Iso/Test input (dual purpose) on the N.Z. Display Extender board is active.

36. U3 Flash Memory Fail This error occurs when non-volatile history process attempts to write or erase the flash memory used to store history. This most likely indicates a fault on the Controller board, requiring a board replacement but it can also be caused by temporary electromagnetic interference. It is possible that replacing the flash chip in the U3 socket will fix this error. Re-starting the panel may also fix this fault. After re-starting the panel, check that non-volatile history is enabled as follows. From the base display press RECALL 2 (history) then press the SET key and check that the display shows “non-volatile history is enabled”. If there is no flash memory installed in the U3 socket then the panel will store its history in RAM and the history will be lost if the panel is powered down.

Page 68: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-14 30 June 2016 Issue 1.08

LIST OF SYSTEM FAULTS (CONTINUED) 37. Too many SIDs in database.

Zone LED database error. Storage limit . Error in LED mapping database. These errors indicate the information in the zone to LED mapping database is invalid. This can occur if the database has been corrupted. Re-starting the panel might clear the fault, otherwise the database may need re-initialising and re-programming.

6.7 BUZZER TEST

6.7.1 FUNCTION

To test the buzzer for both loud and quiet operation. (The buzzer has loud operation for when the FIP door is closed, and quiet for when the door is open).

6.7.2 OPERATING SEQUENCE

From the base display, press: For a non-network panel: For a networked panel:

The buzzer will turn on "loud" for 2-3 seconds, followed by "quiet" for 2-3 seconds.

6.8 RECALL HISTORY

6.8.1 FUNCTION

The FIP keeps a list of at least the last 100 events in chronological order. The RECALL HISTORY command allows an operator to view the latest event stored, and to move forwards and backwards through the list. When either end of the list is reached, the LCD automatically shifts to the other end of the list and displays whether the event is the newest (latest) or oldest (earliest). For networked systems the history will include events from other network panels for which event logging is enabled at this panel. Refer to section 6.16.4 HISTORY OR PRINTER EVENTS for a list of event types relating to faults.

6.8.2 OPERATING SEQUENCE

From the base display, press:

The display will show the most recent history event.

Page 69: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-15

OPERATING SEQUENCE (CONTINUED) To access the event that occurred before the event displayed, press:

If the "PREV" key is pressed when the event displayed is the oldest event, the LCD will briefly display a message indicating that the event to be displayed is the most recent event and then it displays that event. To access the event that occurred after the event displayed, press:

If the "NEXT" key is pressed when the event displayed is the most recent event, the LCD will briefly display a message indicating that the event to be displayed is the oldest event on record, and then displays it.

6.9 SET SYSTEM TIME

6.9.1 FUNCTION

Allows an operator to set the time in the real-time clock within the FIP. For network systems, the new time may also be sent on the network to set the time at other devices (depending on programming). In this situation, it is best to set the date first then, the time, and for the time to be entered with the seconds set to 00 and the Enter key pressed at the start of that minute.

6.9.2 OPERATING SEQUENCE

To set the time, press:

The current time is displayed. Enter the new time, in 24 hour format, i.e. the hours value is 00 to 23 where 01 is 1am and 23 is 11pm. Hours, minutes and seconds may be entered. E.g. to set the time to 1:52:40pm, press: "135240 ENTER".

Page 70: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-16 30 June 2016 Issue 1.08

6.10 SET SYSTEM DATE

6.10.1 FUNCTION

Allows an operator to set the date in the real-time clock within the FIP. For network systems, the new date may also be sent on the network to set the date at other devices (depending on programming).

6.10.2 OPERATING SEQUENCE

To set the date, press:

The current date is displayed. Enter the new date. E.g. To set the date to 21 November 2001, press: "211101 ENTER".

6.11 ANCILLARY, WARNING SYSTEM, EXTERNAL BELL AND PLANT ISOLATE

6.11.1 FUNCTION

To individually isolate or de-isolate local Ancillary 1, Ancillary 2, Ancillary 3, Warning System, External Bell, and the plant, or to provide a global isolate of all allowable local relays.

6.11.2 OPERATING SEQUENCE

From the base display, press:

A menu with 5 options will appear, with a further menu with more options available by pressing:

The current isolate status of each of the relays is shown. To change the isolate status of any ancillary output use the indicated numeric key 1 to 6. Ancillary, External Bell, Warning System and Plant Isolate: Pressing numeric keys 1, 2, 3, 4 and 5 + further menu Key 1 allows isolating or

de-isolating of the ancillary relays, External Bell, Warning System, and plant individually. The current isolate state of the selected item will be shown. Press the "ACK" key to change the isolate status.

Page 71: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-17

OPERATING SEQUENCE (CONTINUED) Press the "CLEAR ESC" key to exit without changing. Note each relay can be

programmed to have the isolate/deisolate command disabled. Attempting to isolate/deisolate such a relay will display “This relay may not be isolated”.

Global Isolate: Pressing numeric key 2 of the second menu will select a global isolate of

allowable ancillary outputs (except External Bells and Warning System). Each ancillary output is programmable as to whether it can be isolated or not.

Note: there is no global de-isolate facility i.e. the relays must be de-isolated

individually or in blocks. Press the "ACK" key followed by the "ENTER" key to initiate the global isolate.

Press the "CLEAR ESC" key to exit without doing the global isolate. NOTE: The PLANT isolate status affects the PLI token in output logic and the "Others"

total on the base display. It does not affect the Brigade isolate relay or LED. The PLI token is true if the plant is isolated and false if not isolated. This token may be programmed to disable the ancillary relays, module relays or open collector outputs.

6.12 PRINT FUNCTIONS

6.12.1 FUNCTION

The PRINT key is used from the base display to access functions for printing the history, the system status, the database or to save the database in binary format. The output can be printed on a printer or captured on a portable computer. Note that the printer serial port is normally used for printing events. While a print function is in progress, events will not be printed but will be held in a queue of at least 100. Event printing automatically restarts when the printout is finished.

6.12.2 OPERATING SEQUENCE

From the base display press:

A menu with 5 options will be shown. Press a numeric key "1" to "5" to select the appropriate option or press the "CLEAR ESC" key to return to the base display. Options 3 to 5 are not normally used by an operator and require a password. They are described in the F3200 Programmer’s manual.

Page 72: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-18 30 June 2016 Issue 1.08

OPERATING SEQUENCE (CONTINUED) The valid options are: 1. History This will initiate a printout of the current history from newest to oldest. These

events are the same as those shown for Recall History (Section 6.8). 2. System Status This option can be used to print the current status of the FIP. This includes all

zones and relays together with their text names and any off-normal status, plus any system faults.

While a print function is in progress the display will show: "Print in progress. Press RESET to cancel". Pressing the "RESET" key will terminate the printout immediately. Pressing the "CLEAR ESC" key while the printout is in progress will return to the base display and the printout will continue.

6.13 RZDU STATUS DISPLAY

Up to 8 Remote Zone Display Units (RZDU) or Remote LCD Units (RDU) may be connected to an F3200 FIP. These units are monitored for various abnormal conditions, which (in most cases) will generate a System Fault condition if they are detected. Also each RZDU or RDU may have an MCP mounted on it. This may be mapped (by programming at the F3200) to a zone in the FIP. Operation of the MCP, or a fault on its wiring, will cause an alarm or fault indication on the zone. These are displayed, recalled and logged similarly to other zone alarms and faults, but are also logged as RZDU events. If an RZDU (or RDU) has any abnormal condition then its status can be viewed on the FIP LCD by initiating a System Fault Recall as described in Section 6.6. The RZDU display shows the RZDU number plus any of the following conditions if they exist. BatLo Battery Voltage Low ChgrF Charger Fault MainF Mains Fail BatFl Battery Voltage Fail DispF LED Display Bd Fault Forgn Foreign RZDU i.e. particular RZDU not configured in FIP McpAl MCP Alarm i.e. on MCP on RZDU McpFt MCP Fault i.e. on MCP on RZDU Scan Scan Fail i.e. no reply from RZDU (e.g. power off or cable fault) StstF Self Test Fail CMDef Hardware fault at RDU SupFt Relay supervision fault at RDU Fuse Fuse blown at RDU The first three conditions are logged on the printer and displayed, but they do not cause a system fault condition on the FIP.

Page 73: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-19

RZDU STATUS DISPLAY (CONTINUED) The other off-normal conditions (except MCP Alarm and Fault) cause a FIP system fault. That is, they turn on the System Fault LED, buzzer and Brigade Fault relay, and add to the "Others" total on the base display. All conditions are non-latching, i.e. turn off when the condition returns to normal.

6.14 RECALL DATABASE CRC

6.14.1 FUNCTION

Allows an operator to view on the LCD the software version, Database CRC and the time and date the database was last changed. This information can be used as part of an AS1851 testing schedule, and to provide for detection of tampering with the system configuration. For network systems refer to Section 11.8.4.

6.14.2 OPERATING SEQUENCE

For a non-networked system, from the base display press:

The LCD will display on the top line the software version and on the bottom line the database CRC, and the time and date that the database was last altered. NOTE: Any changes made to the database will change the numbers displayed in this

recall. Thus, if the database is changed, the new numbers should be recorded in the log

book and the service company advised.

Page 74: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-20 30 June 2016 Issue 1.08

6.15 BRIGADE TEST

6.15.1 FUNCTION

The Brigade Test function turns on the Brigade alarm relay (if programmed to) i.e. signals alarm to the Brigade and turns on the "ALARM" LED. For a network system, the brigade signalling may be at a remote panel in which case a command is sent across the network to operate the alarm relay, but the local alarm LED will still turn on after "BRIG TEST" key has been held for 2 seconds.

6.15.2 OPERATING SEQUENCE

Press the “CLEAR ESC” key until the base display is shown. Press the “TEST” key to select the LOCAL TEST display page, then press and hold the “6” key for at least 2 seconds. - If so programmed the MAF alarm relay and common “ALARM”

LED will turn on. - “Activated” is shown on the bottom line of the LCD to indicate

that the test has been activated. Release the "6" key. After a short period: - The MAF alarm relay will de-activate and the "ALARM" LED

will turn off unless there are other alarms present. NOTE: That the MAF alarm relay operation of the "Brigade Test" function key can be disabled via system programming. If so disabled, pressing the "TEST", “6” keys will not result in an alarm signal to the brigade, but an event will be logged to the history and printer. However, it is possible for the FIP to be programmed to generate brigade alarm via other means when the Brigade Test is activated. The exact test sequence may be different in this case.

Page 75: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-21

6.16 ERROR AND EVENT MESSAGES

6.16.1 ERROR MESSAGES ON STARTUP

The following error messages can be shown on the display during start up. 1. "Main RAM write read fail"

This message is shown on the display at startup if the RAM test fails. The Controller will attempt to restart after five seconds. No events are logged. If this problem occurs repeatedly, the Controller board should be replaced.

2. "Firmware checksum fail"

This message is shown on the display at startup if the firmware (software in flash memory) CRC/ checksum test fails. The Controller will attempt to restart after five seconds. An "EPROM CRC TEST FAIL" event will be logged to the printer and history. If this problem occurs repeatedly, the Controller board should be replaced.

3. “Clock crystal timebase check fail”, “Clock register write read fail”, “Clock

startup fault” These messages occur only at startup and indicate a hardware fault on the Controller board. The Controller will attempt to restart after five seconds and will also log a "CLOCK CHIP FAULT" event to the printer and history. If this problem occurs repeatedly, the Controller board should be replaced.

4. “Clock chip ram write read fail”

This message is shown on the display at startup and indicates that the clock chip is faulty because its initialization is failing i.e. it was found to initially have no valid data and an attempt to write valid data to it failed to verify. An "ISOLATE DATA LOST" event will be logged to the printer and history. The Controller will attempt to restart after 5 seconds. If this problem occurs repeatedly, the Controller board should be replaced.

5. "Isolate Data Lost"

"Isolate data lost" is an event that is logged at startup when the isolate data cannot be successfully read from the clock chip. "Isolate data" refers to zone and relay isolate states. At startup, the message "Reading clock chip ram" may or may not appear on the display. Normally, this message doesn't appear but if the data in the clock chip is invalid, the "Reading clock chip ram" message will be shown and the Controller will try repeatedly to read the isolate data from RAM. If the isolate data cannot be read successfully then the "ISOLATE DATA LOST" event is logged to the printer and history and zones and relays are set to "all isolated". If the "all zones isolated signals fault" option is enabled in programming, then the panel will signal Brigade Fault when this occurs. The Controller does not restart for this condition.

6. "LCD ram read test fail."

This fault can occur at startup or during a "displays test" that can be initiated from the keypad. It indicates a fault on the LCD driver board and F3200 signals Brigade Fault for it. The panel is still operational but the LCD display may not be readable. The event logged for this is "LCD DDRAM READ FAIL".

Page 76: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-22 30 June 2016 Issue 1.08

ERROR MESSAGES ON STARTUP (CONTINUED) 7. “Shift reg clocking fault”

“Invalid # shift regs.Total # regs=xxx # input regs=xxx” These messages indicate a hardware fault with the shift register bus that connects the Controller, MAF/PSU, 8 Zone, and 8 Relay modules. The fault could be on the Controller, the interconnecting FRCs or any of the connected boards. Try connecting just the MAF/PSU on its own and with different cables to isolate the problem. If this fault occurs during startup, the Controller attempts to restart after 5 seconds. If this fault occurs on exit from program mode, the Controller signals Brigade Fault but doesn't restart. An event "SHIFT REG BUS FLT" is logged to the printer and history.

8. “Shift reg driver fault”

This message indicates a problem with the software driver for the shift register bus. It is unlikely this fault will ever occur but it could be caused by a fault in the firmware flash memory or RAM and is probably not a fault with the shift register bus itself. If this fault occurs during startup, the Controller attempts to restart after 5 seconds.

9. "Database checksum fault. No processing."

If the database checksum is invalid at startup, this message will appear for 2 to 3 seconds on the display and an event "DBASE CHKSUM ERROR" is logged.

10. "Incorrect modules"

This message can appear for 2 to 3 seconds on the display during startup if the number of zone and relay modules that are connected does not match the values assigned in the database. An event MODULE CONFIG ERROR is logged and Brigade Fault is signalled.

11. "WARNING programmed number of azc & relay modules is invalid. Please

reprogram asap" This message can appear for 2 to 3 seconds at startup and indicates that the values in the database for the number of modules are invalid e.g. they exceed the maximum number of allowed modules. The "incorrect modules" message will appear before this message, and Brigade Fault will be signalled.

12. "Incorrect display boards"

This message can appear for 2 to 3 seconds at startup and indicates that the number of connected display boards is incorrect. An event LED DISPLAY BDS FLT is logged and Brigade Fault is signalled.

6.16.2 ERROR MESSAGES THAT CAN OCCUR ON ENTRY TO PROGRAM MODE

1. "Flash database version error Must reinit or reload database." This message appears on entry to program mode and indicates that the database was created with a different version of software and cannot be used. This message does not appear if the database checksum is incorrect so it indicates the database is valid but incompatible with this software version. F3200 is able to convert some older versions of database to the latest version when a database is loaded so it may be that saving and re-loading the database will result in the database being converted.

2. "WARNING-the database in flash is invalid. Recommend save->PC before save to flash" This message appears on entry to program mode if the database checksum is incorrect.

Page 77: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-23

6.16.3 ERROR MESSAGES THAT CAN OCCUR ON EXIT FROM PROGRAM MODE

1. "Flash database checksum fail. Processing is disabled." This indicates the database checksum is invalid and the panel is non-operational. A "DBASE CHKSUM ERROR" is also logged.

2. "History queue is being cleared" This indicates that the size of the history queue

has been decreased to enable the print queue. This occurs when the programmable option to enable or disable event printing is changed from disable to enable. When event printing is disabled, the history queue uses the memory normally used for event printing.

3. “Shift reg clocking fault”

“Invalid # shift regs.Total # regs=xxx # input regs=xxx” “Shift reg driver fault” This indicates a hardware fault of some kind. Refer to the information for these messages in the earlier section on startup faults.

4. "Processing disabled." If a shift register fault occurs (as listed above), then this

message will also appear to indicate the panel is non-operational. 5. "Not all modules present." This message indicates that some modules have

temporarily been configured as "not present". This is a configuration setting that is not part of the configuration database and is selected using the "Bds present" menu accessed by pressing the SET key from the base display. The panel is partially operational .

6. "Display module mismatch." This indicates the number of connected display

boards does not match the database configuration parameter. A Brigade Fault is signalled.

7. "Module error. Processing halted." This indicates the wrong number of zone and

relay modules is connected. The panel is non-operational. 8. "WARNING programmed number of azc & relay modules is invalid." This

indicates that the values in the database for the number of modules are invalid e.g. they exceed the maximum number of allowed modules. The panel is non-operational.

6.16.4 HISTORY OR PRINTER EVENTS

The following additional fault events can be logged to the history or event printer. Refer also to section 6.6.3 LIST OF SYSTEM FAULTS. 1. RZDU DISPLAY DEFECT

This indicates a general hardware fault at an RDU. The specfic type of fault can be determined by using a System Fault Recall command at the RDU.

2. RZDU REMOTE COMMAND This indicates a command such as zone isolate or zone reset has been received from an RDU.

3. RZDU BATTERY LOW The battery voltage at the specified RZDU is low.

Page 78: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-24 30 June 2016 Issue 1.08

HISTORY OR PRINTER EVENTS (CONTINUED) 4. RZDU FOREIGN

A message (reply) has been received from an RZDU device that has not been configured in the database.

5. LED DISPLAY BDS FAULT This indicates the wrong number of LED display boards are installed or there is a hardware problem associated with the LED display board bus or there is no "termination link" fitted on the last display board.

6. SHIFT REG BUS FAULT This event indicates there is a hardware fault associated with the bus that connects Controller to the MAF module and the zone and relay modules. It may be caused by a break or short in the flat ribbon cable (e.g. board unplugged), by temporary noise, or by a circuit board fault. Check cables, connections, and for faulty boards.

7. ISOLATE DATA LOST "Isolate data lost" is an event that is logged at startup when the isolate data cannot be successfully read from the clock chip.

8. LCD DDRAM READ FAIL There is a fault with the RAM on the LCD display module. If the fault is persistent, the LCD module may need replacing. A displays test using the TEST key from the base display) may be able to clear the fault.

9. DBASE CHKSUM ERROR The checksum of the database is invalid and the panel is non-operational. The preferred method of fixing this fault is to re-load the database or to re-initialize and re-program.

10. ISOLATE RAM FAIL This indicates the RAM in the clock chip that holds the isolate states associated with zones and relays is failing to verify the data that has been written to it. If this occurs at startup, all zones and relays are set to the isolated state.

11. KEYPAD DISCONNECT The keypad has been disconnected or there is a hardware fault associated with the two keypad membranes connected to the Controller board.

12. SUPPLY FAILED This fault means that both mains has failed and the battery voltage has fallen to 21 volts or below. The standby relay is de-energised and all processing of circuit inputs stops.

13. PSU FAULTS INHIBITED This event is logged when an operator initiates the 24 hour PSU faults inhibit period using the keypad command accessed through the SET key menu.

14. EPROM CRC TEST FAIL System or auto test has failed because the firmware checksum check failed. If this fault was caused by a temporary electrical disturbance then it may clear automatically, or it may be cleared by turning the panel off and back on. Ideally, the Controller board should be replaced if there is no obvious explanation for this fault.

Page 79: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - System Functions

Issue 1.08 30 June 2016 Page 6-25

HISTORY OR PRINTER EVENTS (CONTINUED)

15. PROCESSING STOPPED This event occurs on entry to program mode because normal alarm processing is suspended while in program mode.

16. DBASE REINITIALIZE This event occurs when the database is re-initialized at startup.

17. OUTPUT LOGIC ERROR nn An error has occurred in the execution of output logic and the error number is nn. A list of these errors is given in section 6.6.3 LIST OF SYSTEM FAULTS.

18. CLOCK CHIP FAULT This event occurs only at startup and indicates a problem with the clock chip. The Controller may need replacing.

19. NET PORT HW FAULT This event occurs only for networked panels and indicates that the network serial driver chip failed to initialize correctly. Turning the panel off and on may clear the fault, otherwise the Controller board needs replacing.

20. NET MSG DISCARD This event occurs only for networked panels and indicates that the panel failed to receive an acknowledge to a message it sent on the network. This might occur on busy systems if there is a hardware fault somewhere, or if the device that is programmed to send the acknowledgement is powered down or faulty.

21. MODULE CONFIG ERROR This error indicates that the software was unable to shift a sequence of data around the shift register bus and thus determine what modules (MAF/PSU 8 Zone and 8 Relay boards) were present.

22. NET SCAN FAULT CHA / CHB This event occurs only for network systems and indicates that link integrity checking data has not been received from the specified SID on the specified channel within the desired time period, indicating either a broken connection or failure of the SID .

23. RAM DATABASE CORRUPT This event occurs if the database in RAM is corrupted or fails to verify. The database is stored in both flash memory and RAM and is copied from flash to RAM at startup. The Controller continually checks that the database in RAM is identical to the copy in flash. If a mismatch is detected, and the checksum of the database in flash is correct, then the database is re-loaded into RAM, which may result in this fault self-clearing a short time later.

24. U3 FLASH MEM FAIL Non-volatile history flash memory has failed. Refer to system faults Section 6.6.3.

Page 80: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - System Functions

Page 6-26 30 June 2016 Issue 1.08

25. DATABASE ERROR, DATABASE ERROR 2, ZONE STATUS STORAGE These faults indicate that information in the database is invalid or corrupt even though the database checksum is correct. Try performing a System Test to check the database checksum. If the database checksum is correct, try re-starting the panel. If the fault persists, the database may have to be re-initialised or re-programmed.

6.17 BUZZER RESOUND TEST

This tests the functionality of the AS 4428 requirement to resound the panel buzzer for Faults and Isolates after 8 hours. This test temporarily shortens the resound period to two minutes. To run the test, create a fault on an alarm zone circuit, and acknowledge it to silence the buzzer. Press the TEST key and the 7 key. When instructed, press the ACK key. The display briefly shows a message “Don’t press keys for 1-2 minutes” and then returns to the test menu screen. Note the time and do not touch any keys on the panel. After two minutes, the fault sounder should resound, indicating that the panel is operating correctly.

Page 81: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - Zone Functions

Issue 1.08 30 June 2016 Page 7-1

7 OPERATING INSTRUCTIONS - ZONE FUNCTIONS

Page 82: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - Zone Functions

Page 7-2 30 June 2016 Issue 1.08

7.1 ZONE ALARM OR FAULT TEST

7.1.1 FUNCTION

To test the circuit input of a selected alarm zone or group of zones and to send test alarm signals to the Brigade. Two tests can be performed: (a) A fault simulation test, or (b) An alarm simulation test. WARNING: This test performs a true zone test, time delays operate, and, unless the

zone is isolated, all outputs operate, including External Bell (strobe and/or bell), Warning System and the Brigade Alarm.

For network systems: to test a local zone follow this section; to test a remote zone refer to Section 11.10.6.

7.1.2 OPERATING SEQUENCE

SUGGESTION: To prevent mapped outputs from operating, ISOLATE the zone(s) first.

- Refer to "Zone Isolate or De-Isolating" section 7.2. From the base display, press:

OR

where n n is the number of the zone to test. Alternatively, from the zone status recall display for the zone to be tested, press:

OR

FOLLOWED BY

To apply a zone alarm test or zone fault test to the range of zones nn to mm inclusive, from the base display press:

OR

The relevant test signal is applied to the circuits.

Page 83: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - Zone Functions

Issue 1.08 30 June 2016 Page 7-3

OPERATING SEQUENCE (CONTINUED) Once a circuit has gone into the required test state, the relevant status LED and buzzer are turned on if that zone is not isolated. For alarm test, FF mode will be entered if the zone is mapped to the MAF and the alarm must then be acknowledged. When the zone status is displayed, the message: "Test-Fault. Press ACK to stop" or "Test-Alarm. Press ACK to stop" will be shown. Pressing the "ACK" key stops the test at any point but does not reset the zone. Pressing "RESET" followed by "ACK" will stop the test and reset the zone. If the circuit does not enter the correct state in response to the test signal then the buzzer sounds its "TEST FAIL" cadence and the LCD displays a test fail message. Resetting the zone will terminate the test.

7.1.3 ABORT ZONE TEST

Press the "ACK" key at any time to stop the ZONE TEST for the displayed zone. This will NOT reset the zone. Press the "RESET" key followed by "ACK" to stop the zone test and reset the circuit of the displayed zone. It is recommended to always reset a zone at the completion of a zone test. A zone range reset command will terminate the zone test on each zone being reset (but will leave zone tests running on any zones not being reset).

7.1.4 NOTES

(a) An Alarm detected on the zone under test when one is not expected (eg during the FAULT test) is processed as a real alarm. Similarly a fault during the ALARM test is processed as a real fault. (After the appropriate first condition tone on the buzzer is silenced, the second condition tone occurs).

(b) All alarm processing delays (AVF sequences, etc) are still active so the

alarm response time will depend on the circuit type and the programmed delays for each circuit.

(c) An AVF delay sequence initiated by a zone alarm test continues if the

zone test is aborted by the "ACK" key before the test has passed (i.e. before the zone goes into alarm). That is, a second alarm test on the same zone within 150 sec will give an instant alarm.

(d) A zone alarm or fault test will be automatically terminated 5 to 6 minutes

after starting. (e) It is not possible to start a zone test if the zone is already in test, in In-Situ

mode, or if the circuit is disabled.

Page 84: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - Zone Functions

Page 7-4 30 June 2016 Issue 1.08

7.2 ZONE ISOLATE OR DE-ISOLATE

7.2.1 FUNCTION

To isolate or de-isolate a zone or range of zones. For network systems: to isolate/de-isolate a local zone follow this section; to isolate/de-isolate a remote zone refer to Section 11.10.4.

7.2.2 OPERATING SEQUENCE - SINGLE ZONE

To isolate or de-isolate zone n n, from the base display press:

To isolate the zone shown on a zone status recall display, press:

followed by

The LCD displays the current isolate status of the zone. Pressing the "ACK" key changes the isolate state. Pressing the "CLEAR ESC" key aborts the Isolate command.

7.2.3 OPERATING SEQUENCE - ZONE RANGE

To isolate or de-isolate a range of zones, from the base display press:

The LCD will display the selected range of zones, i.e. zone n n to zone m m inclusive, plus the options to isolate or de-isolate the range.

To isolate the range of zones, press:

To de-isolate the range of zones, press:

7.2.4 NOTES

(a) Isolated zone(s) will register and indicate alarm and fault, but are prevented from entering FF mode or operating system outputs.

(b) If the zone is in In-Situ mode, the zone may still be isolated and de-isolated but

will remain in In-Situ mode. A zone which is in In-Situ mode and is isolated will not operate the bells for 2 seconds when an alarm occurs.

(c) Any zones which are currently in alarm or fault will not be de-isolated by a zone

range command and will remain isolated. They must be de-isolated by a single zone de-isolate command.

Page 85: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - Zone Functions

Issue 1.08 30 June 2016 Page 7-5

7.3 ZONE RESET

7.3.1 FUNCTION

A Zone Reset command performs the following: - Applies an electronic reset to the AZC to reset latched detectors. - Clears latched ALARM and FAULT conditions and indications. - Silences the alarm and fault sounder. - Cancels any zone test in progress on that zone. - Returns the Zone from In-Situ mode to normal operation. A single zone or a continuous range of zones may be reset with a single command. For network systems: to reset a local zone follow this section; to reset a remote zone or zone range refer to Section 11.10.5.

7.3.2 OPERATING SEQUENCE

To reset one zone only: To reset zone number n n, from the base display press:

From a zone status display, to reset the displayed zone, press: The LCD will query if this is the zone to be RESET. Press "ACK" to reset, or "CLEAR ESC" to abort. The zone’s red alarm LED and amber fault LED (if fitted) will turn off, and the common alarm and fault LEDs will turn off if there are no other zones in alarm or fault respectively. To reset a range of zones: From the base display press:

The LCD will display the range of zones selected. Press the "ACK" key to initiate the reset of zones nn to mm inclusive or press the "CLEAR ESC" key to abort with no reset. NOTES: (a) If a detector or circuit is still in alarm or fault, then after the zone reset delay and

the circuit input delay the zone will return to alarm or fault. (b) If the amber fault indicator reappears, then isolate the zone and call the service

company.

Page 86: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - Zone Functions

Page 7-6 30 June 2016 Issue 1.08

7.4 ZONE IN-SITU TEST MODE

7.4.1 FUNCTION

In-Situ test mode allows testing of all detectors on an Alarm Zone Circuit without the need for a second person resetting alarms at the FIP. It isolates the zone from its outputs, and automatically resets detectors in alarm on the circuits being tested. When the zone goes into alarm the Warning System is operated for 2 seconds, unless the Warning System is isolated, or the zone is not mapped (programmed) to operate the Warning System or the zone is isolated. For a network system, to In-Situ test a remote zone on another panel, refer to Section 11.10.6. To In-Situ test a local zone, follow this section.

7.4.2 OPERATING SEQUENCE

To put a single zone into In-Situ mode To In-Situ test Zone nn, from the base display press:

From a zone status display, to In-Situ test the displayed zone press:

followed by

To put a range of zones into In-Situ test mode, from the base display press:

Then press the "ACK" key to put the range of zones into In-Situ test mode, or press the "CLEAR ESC" key to abort.

7.4.3 TEST OPERATION

When a zone is put into In-Situ test mode a reset command is applied to the zone so that any latched alarm and faults are cleared. On operation of a detector (and after the 2 second transient suppression delay) the zone will go into the alarm condition and the Warning System will sound for 2 seconds. After 17 seconds of alarm, usually sufficient time for the detector LED and any remote indicator to be checked, the detector circuit is reset for 6 seconds to allow smoke or heat to clear. To assist with identification of the detectors wired to the AZC the current voltage band of the AZC is continuously displayed on the LCD. B1 (0-3V) is short circuit, B2 (3-13V) is detector operated, B3 (13-17.5V) is programmable, B4 (17.5-21V) is normal and B5 (21-22V) is open circuit. The zone status (alarm, resetting, etc) is also shown, with a count of the number of alarms detected.

Page 87: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - Zone Functions

Issue 1.08 30 June 2016 Page 7-7

TEST OPERATION (CONTINUED) When fitted, the zone alarm indicator latches, flashing when an alarm condition is present on the circuit and steady on the removal of the alarm condition. If a fault occurs on a zone in In-Situ test mode then the Zone Fault LED latches on steady until the end of the test, even if the zone is programmed as non-latching. Resetting the zone will cancel the In-Situ Test mode for the zone. But as a fusible link detector may have been permanently operated, check that the zone status is normal before resetting. Otherwise a real alarm may be generated.

7.4.4 NOTES

(a) Multiple zones can be put into In-Situ test mode at the same time. (b) If any zone is in In-Situ test mode then it is not possible to perform a

System or Auto test. (c) All programmed input time delays (e.g. alarm verification) are overridden

to allow operation of the detectors to be tested quickly. (d) The internal sounder (buzzer) is not operated by a zone in In-Situ test

mode. (e) All zones in In-Situ test mode will automatically return to normal operation

after ONE HOUR from the last alarm received on any such zone or from the last initiation of In-Situ mode on any zone. A reset command will be applied to any such zone but the zone isolate/de-isolate status will not be altered. (Zones should be manually reset and de-isolated for tea breaks, lunch breaks, and when testing is finished).

(f) A zone may be isolated or de-isolated while it is in In-Situ test mode and

will remain in In-Situ test mode. An isolated zone will not operate the Warning System when an alarm occurs.

(g) When a zone range reset command is used to reset a range of zones all

zones in the range will be reset and any which were in In-Situ mode will return to normal operation.

(h) A zone recall command may be used to step through zones which are in

In-Situ mode by selecting the testing option (option 4) from the recall zone display (i.e. "RECALL", "ZONE", "4").

(i) The outer door of the panel may be closed while one or more zones are in

In-Situ mode without causing a slow beeping cadence on the buzzer.

Page 88: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - Zone Functions

Page 7-8 30 June 2016 Issue 1.08

7.5 ZONE STATUS RECALLS

7.5.1 FUNCTION

Allows an operator to recall the status of a specific zone, or to, search for those zones meeting a specified criteria, e.g. in fault or alarm. For network systems: this section may be used to search for local zones; for searching or displaying remote zones refer to Section 11.10.1.

7.5.2 OPERATING SEQUENCE - ZONE STATUS

To recall the status of zone n n, from the base display press:

To view the status of other zones, press: to view the status of the next zone, or to view the status of the previous zone. Press the "ZONE" key to select a different zone, or press "CLEAR ESC" to return to the base display. The first line of the LCD displays the zone number and any zone name programmed for that zone. The second line displays the zone alarm type text for that zone, followed by its status. The status consists of any of the following: normal - the zone is not in alarm or fault alarm - the zone is in alarm. fault - the zone is in fault. isolated - the zone is isolated. deisolated - (or deiso) the zone is de-isolated. FIP MCP - the FIP MCP maps to this zone. Status Only - the zone is a status-only type. disabled - the circuit is disabled but the zone may still have the FIP MCP

mapped to it. Thus it can still produce alarms and faults, and signal the Brigade but alarms and faults will never be produced by the detector circuit on the AZC module.

Page 89: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - Zone Functions

Issue 1.08 30 June 2016 Page 7-9

OPERATING SEQUENCE – ZONE STATUS (CONTINUED) If the zone is currently in zone alarm test, zone fault test, In-Situ mode or is being reset, then the zone name on the top line of the display will be replaced by one of the following messages. "resetting" - If the zone is currently being reset. "Test-alarm. Press ACK to stop" - If a zone alarm test is in progress. "Test-alarm failed. Press ACK" - If a zone alarm test has failed. "Test-fault. Press ACK to stop" - If a zone fault test is in progress "Test-fault failed. Press ACK" - If a zone fault test has failed. "In-Situ Test Bn" - If the zone is in In-Situ mode. Bn is one of

B1, B2, B3, B4 or B5 depending on the current voltage applied to the circuit input.

7.5.3 OPERATING SEQUENCE - ZONE SEARCHES

The zone search functions allow an operator to query the F3200 for zones meeting specified status criteria, e.g. in alarm. To start a search, from the base display press:

Then select the option required. Note Status-Only zones do not appear in the alarms, faults or isolate recalls. Valid options are: "1" all off normal Searches for any zones in alarm, fault or isolated, or in zone test or In-Situ mode. "2" alarms - Searches for any zones in alarm, whether or not they

are isolated. "3" faults - Searches for any zones in fault, whether or not they

are isolated or mapped to MAF. "4" testing - Searches for any zones in zone alarm test, zone fault

test or In-Situ mode (independent of zone type and mapping).

"5" isolated - Searches for any zones that are isolated or in In-Situ

mode. "6" status - Prompts for a zone number and displays the status of

that zone as described in Section 7.5.2. When an option has been selected, the FIP searches for a zone starting from Zone 1 up to the programmed maximum zone that meets the specified criteria.

Page 90: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - Zone Functions

Page 7-10 30 June 2016 Issue 1.08

OPERATING SEQUENCE – ZONE SEARCH (CONTINUED) Once a zone is found that meets the specified criteria, the LCD display reverts to a zone status display for that zone. When the "NEXT" or "PREV" key is pressed, the search continues for the next or previous zone respectively, that meets the original search criteria. If no zones matching the criteria are found, the LCD briefly displays a message saying so, and reverts to the base display.

Page 91: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - Relay/Output Functions

Issue 1.08 30 June 2016 Page 8-1

8 OPERATING INSTRUCTIONS - RELAY/OUTPUT FUNCTIONS

Page 92: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - Relay/Output Functions

Page 8-2 30 June 2016 Issue 1.08

8.1 INTRODUCTION

For networked systems local outputs may be accessed as described in this section; outputs on remote panels may be accessed as zones with zone commands as described in Section 11.10. There are several types of output in the panel whose status may be viewed on the display - module relays, ancillary relays, open collector outputs, External Bell and Warning System. The functions which can be applied to these outputs include isolate/de-isolate, reset and test. Each of these outputs has a unique zone number but it is not necessary to know the zone number to recall the status of the output. The status of MAF relays (Alarm, Fault, Isolate and Standby) cannot be viewed on the display and cannot be tested (except Brigade Test tests Alarm). There are eight open collector outputs on each AZC module and these may be tested (i.e. operated for 5 seconds) but cannot be isolated or reset.

8.1.1 WARNING SYSTEM & EXTERNAL BELL

The purpose of the Warning System is to evacuate people from the building when an alarm occurs. The purpose of the External Bell is to allow the Fire Brigade to locate the fire panel where an alarm has occurred. The External Bell and Warning System can be isolated and tested, and their status can be recalled. When the Warning System is activated, one or more physical outputs may operate according to output logic programming. By default the Ancillary 3 relay is programmed to operate when the Warning System is activated. By default the Ancillary 2 relay is programmed to operate when the External Bell is activated. Any of the physical outputs on the panel may be programmed to operate when the Warning System or External Bell is activated. WARNING SYSTEM OPERATION By default the Warning System is activated when any non-isolated zone mapped to the Warning System is in alarm, or when the Warning System is tested, or when there is an alarm on a zone that is mapped to the Warning System and is in In-Situ Test mode. When the Warning System is activated or tested, the physical outputs controlled by the Warning System will operate if the Warning System is not isolated and the physical output itself is not isolated. When a supervision fault occurs on any of the outputs controlled by the Warning System, the Warning System is also put into fault. When the fault has been fixed, a reset command must be applied to the physical output to clear the latched fault. By default, the Ancillary 3 Relay cannot be isolated or tested “directly” because these functions are achieved with a Warning System Test or isolate command. However, this can be changed with programming.

Page 93: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - Relay/Output Functions

Issue 1.08 30 June 2016 Page 8-3

WARNING SYSTEM & EXTERNAL BELL (CONTINUED)

For an NDU in New Zealand mode the Warning System is activated when a Trial Evacuation Keyswitch is operated and the Warning System is inhibited when a Silence Alarms Keyswitch is operated. EXTERNAL BELL OPERATION By default the External Bell is activated when any non-isolated Zone mapped to the External Bell is in alarm or when the External Bell is tested. When the External Bell is activated or tested, the physical outputs controlled by the External Bell will operate if the External Bell is not isolated and the physical output itself is not isolated. When a supervision fault occurs on any of the outputs controlled by the External Bell, the External Bell is also put into fault. When the fault has been fixed, a reset command must be applied to the physical output to clear the latched fault. By default, the Ancillary 2 output cannot be isolated or tested “directly” because these functions are achieved with an External Bell isolate or test command. However, this can be changed with programming.

8.1.2 MODULE RELAYS

Relays on the 8 Relay Module are controlled by output logic that has been specifically programmed. They may also be activated for 5 seconds during a relay test.

8.1.3 ANCILLARY RELAYS

The Ancillary relays 1, 2 and 3 are located on the MAF board. Each of these relays is controlled by an output logic equation. For the Ancillary 1 relay, there is no default equation but the relay will operate when any non isolated zone mapped to the Ancillary 1 relay is in alarm. If an output logic equation is programmed for the Ancillary 1 relay, then the relay operates according to the equation and ignores any zones specifically mapped to it – i.e. an alarm on a zone mapped to the Ancillary 1 relay does not cause the Ancillary 1 relay to operate when the relay is controlled by an output logic equation (this saves having to de-map all zones from the Ancillary 1 relay). By default, all alarm zones are programmed to map to the Ancillary 1 relay, the External Bell (Ancillary 2 relay) and the Warning System (Ancillary 3 relay).

8.1.4 OPEN COLLECTOR OUTPUTS

There are 8 open collector outputs on each 8 Zone Module, i.e. one open collector output for each alarm zone circuit. Each output may be controlled by a logic equation. If an open collector output has no logic equation then the output will be on whenever the corresponding zone is in alarm and is not isolated.

Page 94: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - Relay/Output Functions

Page 8-4 30 June 2016 Issue 1.08

8.2 MODULE RELAY STATUS RECALL

8.2.1 FUNCTION

To display the status of a local module relay. For network systems, to display the status of a relay on a remote panel you need to use the zone number associated with the relay and a zone recall command. Refer to Section 11.10.

8.2.2 OPERATING SEQUENCE

To display the status of a local module relay n n, from the base display press:

to select module relays, then press:

The status display will show the relay number, zone number and name on the top line and information on the bottom line as follows: deactivated - if the relay is de-energised activated - if the relay is energised normal - no supervision fault fault - supervision fault open circuit - supervision fault short circuit - supervision fault isolated de-isolated unsupervised The "RESET", "ISOLATE" and "TEST" keys may be used from this display and "NEXT" and "PREV" may be used to step through the module relays.

Page 95: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - Relay/Output Functions

Issue 1.08 30 June 2016 Page 8-5

8.3 MODULE RELAY ISOLATE/DE-ISOLATE

8.3.1 FUNCTION

To isolate or de-isolate a single module relay or continuous range of module relays. Whenever a relay is isolated the relay will always be de-energised. A supervision fault on an isolated relay mapped to the MAF will NOT activate the brigade fault relay. For network systems to isolate a relay on a remote panel, use a zone command - refer to Section 11.10.

8.3.2 OPERATING SEQUENCE

To isolate or de-isolate a local module relay or range of relays, from the base display press:

To isolate/de-isolate module relay n n press:

To isolate/de-isolate the range of module relays n n to m m press:

Then press numeric key "1" to isolate relays n n to m m or numeric key "2" to de-isolate them, or press "CLEAR ESC" to abort.

8.3.3 NOTES

Depending on programming, an isolate command may not be allowed on particular relays, in which case the message “This relay may not be isolated” will appear when an attempt is made to isolate it.

Page 96: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - Relay/Output Functions

Page 8-6 30 June 2016 Issue 1.08

8.4 MODULE RELAY RESET SUPERVISION FAULT

8.4.1 FUNCTION

To reset a latched supervision fault on a single module relay or a continuous range of relays. Each module relay may be programmed to be latching/non latching and mapped/not mapped to the MAF. If a module relay is programmed as latching then when a supervision fault occurs on the output wiring the fault will remain after the supervision fault is physically cleared. For network systems, to reset a relay on a remote panel use a zone reset command - refer to Section 11.10.

8.4.2 OPERATING SEQUENCE

To reset a local module relay, from the base display press:

to select module relays, then press either:

to reset relay nn or:

to reset the range of relays nn to mm inclusive.

Press

To confirm the reset, or “CLEAR ESC” to abort.

If the fault is still physically present on the output wiring then the relay will remain latched in fault.

Page 97: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - Relay/Output Functions

Issue 1.08 30 June 2016 Page 8-7

8.5 MODULE RELAY TEST

8.5.1 FUNCTION

To briefly turn on a relay output (i.e. for five seconds). If the relay is isolated the test command will not energise the relay. If the relay is already energised (because an output logic equation requires it to be on) then it will remain energised and is not affected by the test. For network systems, to test a relay on a remote panel use a zone operate test command - refer to section 11.10.

8.5.2 OPERATING SEQUENCE

To test a local module relay, from the base display press:

to select module relays, then press

to test relay nn or

to test the range of relays nn to mm inclusive. Press

to apply the test, or “CLEAR ESC” to abort.

The relays will be energised (if not isolated) for five seconds, or until "ACK" is pressed, and then de-energised.

8.5.3 NOTES

Depending on programming, a test command may not be allowed on particular relays, in which case, the message “This relay may not be tested” will appear when an attempt is made to test it.

Page 98: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - Relay/Output Functions

Page 8-8 30 June 2016 Issue 1.08

8.6 ANCILLARY RELAY STATUS RECALL

8.6.1 FUNCTION

To display the status of a local ancillary relay. For network systems, to display the status of an ancillary relay on a remote panel use a zone recall command. Refer Section 11.10.

8.6.2 OPERATING SEQUENCE

To display the status of a local ancillary relay, from the base display press:

to select ancillary relays

then press numeric key "1", "2" or "3" followed by the ENTER key to select the desired ancillary relay. The programmed name for the relay will be show on the top line and the status of the relay will be shown on the bottom line of the display as follows: deactivated - if the relay is de-energised activated - if the relay is energised normal - no supervision fault fault - supervision fault open circuit - supervision fault short circuit - supervision fault isolated de-isolated unsupervised The "RESET", "ISOLATE" and "TEST" keys may be used from this display and "NEXT" and "PREV" may be used to step through the three ancillary relays.

Page 99: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - Relay/Output Functions

Issue 1.08 30 June 2016 Page 8-9

8.7 ANCILLARY RELAY ISOLATE/DE-ISOLATE

8.7.1 FUNCTION

The local Ancillary 1, Ancillary 2, and Ancillary 3 relays may be individually isolated/de-isolated (depending on programming). This may be done by using the "ANCIL ISOL" key (described in section 6.11) or from an ancillary relay status display as follows. For network systems to isolate/de-isolate an ancillary relay on a remote panel, use a zone isolate/de-isolate command. Refer to Section 11.10.

8.7.2 OPERATING SEQUENCE

To isolate/de-isolate a local ancillary relay, from the base display press:

to select ancillary relays,

then press numeric key “1”, “2” or “3” followed by the ENTER key to select the desired ancillary relay. Then press:

to change the current isolate status of the relay.

8.7.3 NOTES

De-isolating an ancillary relay may cause the relay to turn on and isolating a relay will cause the relay to turn off if it was on. De-isolating a relay may cause the Brigade Fault relay to turn on if there is a latched supervision fault on the ancillary relay and the ancillary relay is mapped to the MAF. Depending on programming, an isolate command may not be allowed on particular relays. In which case the message “This relay may not be isolated” will appear when an attempt is made to isolate it.

Page 100: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - Relay/Output Functions

Page 8-10 30 June 2016 Issue 1.08

8.8 ANCILLARY RELAY RESET SUPERVISION FAULT

8.8.1 FUNCTION

To reset a latched supervision fault on a local ancillary relay. For network systems, to reset a latched supervision fault on an ancillary relay on a remote panel, use a zone reset command. Refer Section 11.10.

8.8.2 OPERATING SEQUENCE

To reset a latched supervision fault on a local ancillary relay, from the base display press:

to select ancillary relays

then press numeric key "1", "2" or "3" followed by the ENTER key to select the desired ancillary relay. Then press:

to reset the fault.

If the fault is still physically present on the relay wiring then the relay status will remain in fault.

Page 101: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - Relay/Output Functions

Issue 1.08 30 June 2016 Page 8-11

8.9 ANCILLARY RELAY TEST

8.9.1 FUNCTION

To briefly turn on a local ancillary relay output for five seconds. If the relay is isolated the test command will not energise the relay. If the relay is already energised before the test starts then the test command will have no effect on the relay and will not de-energise it. For network systems, to test an ancillary relay on a remote panel use a zone operate test command. Refer to Section 11.10.

8.9.2 OPERATING SEQUENCE

To test a local ancillary relay, from the base display press:

to select ancillary relays, then press

The relay will be energised for five seconds or until "ACK" is pressed again.

8.9.3 NOTES

Depending on programming, a test command may not be allowed on particular relays. In which case, the message “This relay may not be tested” will appear when an attempt is made to test it.

Page 102: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - Relay/Output Functions

Page 8-12 30 June 2016 Issue 1.08

8.10 OPEN COLLECTOR STATUS RECALL OR TEST

8.10.1 FUNCTION

To view the state of a local open collector output. A test command may be used to turn on an open collector output for five seconds if not already on. For network systems, to recall or test an open collector output on a remote panel use a zone recall command or a zone operate test command. Refer to Section 11.10.

8.10.2 OPERATING SEQUENCE - STATUS RECALL

To recall a local open collector output, from the base display press:

to select open collector outputs, then press

to recall open collector output nn status.

The display will show the open collector number on the top line and on the bottom line either activated or deactivated according to whether the output is currently on or off. The

and

keys may be used to step through the open collector outputs. Press the "CLEAR ESC" key to return to the base display.

8.10.3 OPERATING SEQUENCE - OPEN COLLECTOR TEST

From an open collector status recall selected as described above, press:

to turn the open collector output on for five seconds or " CLEAR ESC" to abort.

If the open collector output is already on it will not be affected by the test. If an open collector output is controlled by the default logic of zone alarm, then the output can be turned off, if it is on, by isolating the corresponding zone.

Page 103: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Operating Instructions - Relay/Output Functions

Issue 1.08 30 June 2016 Page 8-13

8.11 WARNING SYSTEM STATUS RECALL

The status of the Warning System can be shown on the LCD. This shows whether the Warning System is activated, isolated or in fault. OPERATING SEQUENCE From the base display press

In F3200, the Warning System has a unique zone number which is 198. Other types of panels may not associate a zone number with the Warning System. Zone numbering is more significant on networked systems and the full list of zone numbers used in F3200 is shown in Section 11.9. The Warning System status recall includes the following: activated - if the Warning System is activated deactivated - if the Warning System is not activated fault - if there is a supervision fault on any of the Warning System

outputs isol - if the Warning System is isolated deisol - if the Warning System is de-isolated SilAlms - For New Zealand operation, this will be shown if the Silence

Alarms Keyswitch is operated NetSil - For a networked system this is shown if the local Warning System

is inhibited (Silenced) by a Warning System isolate on another panel.

From the Warning System status recall display the

key can be used to operate the Warning System for 5 seconds,

the

key can be used to isolate or de-isolate the Warning System.

The

or

keys can be used to show the next or previous zones. Zone 199 is the External Bell and zone 197 is Plant.

Page 104: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Operating Instructions - Relay/Output Functions

Page 8-14 30 June 2016 Issue 1.08

8.12 EXTERNAL BELL STATUS RECALL

The status of the External Bell can be shown on the LCD. This shows whether the External Bell is activated, isolated or in fault. OPERATING SEQUENCE From the base display press

In F3200, the External Bell has a unique zone number which is 199. Other types of panels may not associate a zone number with the External Bell. Zone numbering is more significant on networked systems and the full list of zone numbers used in F3200 is shown in Section 11.9. The External Bell status recall includes the following: activated - if the External Bell is activated deactivated - if the External Bell is not activated fault - if there is a supervision fault on any of the External Bell outputs isol - if the External Bell is isolated deisol - if the External Bell is de-isolated NetSil - For a networked system this is shown if the local External Bell is

inhibited (Silenced) by an External Bell isolate on another panel. From the External Bell status recall, the

key can be used to operate the External Bell for 5 seconds,

the

key can be used to isolate or de-isolate the External Bell.

The

and

keys can be used to show the next or previous zones. Zone 198 is the Warning System and zone 197 is Plant.

Page 105: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Placing Into Operation

Issue 1.08 30 June 2016 Page 9-1

9 PLACING INTO OPERATION

Page 106: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Placing Into Operation

Page 9-2 30 June 2016 Issue 1.08

9.1 GENERAL

This chapter describes the procedure to place an F3200 FIP into operation. It assumes that the mains and other field wiring has been connected, but that the battery has not. Note that all electronic modules were tested and adjusted in the factory and should need no further adjustment. Before switching on power, inspect the cabinet and internals. Check that all equipment is securely mounted, and that all cables are connected at the appropriate points. The factory checklist is included. The "MAINS ISOLATE SWITCH" is located at the top right hand side of the cabinet rear, to the left of the mains transformer, behind the inner display door. This controls the mains power to the FIP, charger and power supply, and should be left on once the FIP is operational. NOTE: The Battery is not disconnected by the "MAINS ISOLATE SWITCH".

9.2 POWER-UP

To place the F3200 FIP into operation, perform the following steps: STEP 1 Ensure that the Mains Isolate Switch is OFF. STEP 2 Ensure that 240 VAC is connected to the panel from the mains distribution

switchboard. STEP 3 Turn the Mains Isolate Switch ON. STEP 4 Check that the buzzer sounds and all LEDs on the Operator Display panel

flash for 2 seconds (except Mains On). STEP 5 Check that the green "MAINS ON" LED indicator is on. The Controller performs tests on its memory, electronics, and the LCD.

Refer to Section 6.6 for a list of faults that may occur. STEP 6 Check that the LCD has good visibility. The LCD displays the FIP pcb

configuration before showing the Base Display. STEP 7 Install and connect the batteries. Take care not to short the battery leads when connecting. STEP 8 De-isolate all normalised zones and perform a System Test. (This takes

almost one minute and includes a fault and alarm test of each zone). STEP 9 Perform a Battery Test. If Battery Test fails check the battery

connections, leave for 24 hours and retest. STEP 10 Perform a Test of the External Bell and Warning System. A full commissioning test should be performed as per AS1670.1.

Page 107: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Placing Into Operation

Issue 1.08 30 June 2016 Page 9-3

9.3 COMMISSIONING CHECKLIST

The following checklist should have been completed and supplied by the manufacturer. It should be placed with other System Configuration Information. Commissioning staff should check the installed FIP against it. (Note that all pcbs are electronically tested and adjusted before being fitted to the FIP). 1. CABINET & GENERAL

A) Cabinet colour - Standard Cream Wrinkle (BFF 998 CW)

- Other:

B) Cabinet undamaged (Paint OK)

C) Door aligned correctly

D) Window undamaged and fitted correctly

E) MCP fitted and undamaged

F) Cabinet Door locks firmly, operates microswitch

G) Lock - 003 Type & key supplied

H) Door seals fitted to top and sides

I) Display Keypad and 4U door fitted & aligned correctly

J) Cardframe fitted correctly ..(FP0781/3 only)

K) Standoffs fitted to cabinet rear (none missing)

L) Operator Manual and battery leads included

M) VIGILANT label completed

2. PCBS & WIRING

A) MAF/PSU Fitted securely on standoffs

B) Controller/Display fitted securely

C) 8ZM fitted securely, earth screw fitted

D) FRC Looms fitted correctly

E) MCP & door switch wires fitted to J6 of MAF/PSU, secured

F) Earth wire fitted to display door

G) All 3 modules earth to cabinet metal

Page 108: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Placing Into Operation

Page 9-4 30 June 2016 Issue 1.08

COMMISSIONING CHECKLIST (CONTINUED) 3. POWER SUPPLY

A) Mains Wired correctly, MOV, cap fitted

B) "Mains Isolate Switch" and "NAE" label fitted

C) Mains Earth wired to stud, good contact

D) All 6 fuses fitted to MAF/PSU

E) Mains Switch neon off/on for switch off/on

F) MAF/PSU Mains On LED on, Fuse Blown LED off

G) VRECT at DC IN tab 40-42Vdc

H) Charger Voltage 27.3-27.4V warm, 27.5-27.6V cold

4. OPERATION

A) LEDs bright through window, "MAINS ON" LED on

B) Correct modules are configured and found on Init

C) Buzzer louder with microswitch operated

D) Controller LK7 in "Protect" position

E) LCD contrast correct for front view

F) De-isolate zones, system test pass on all zones

G) FIP MCP Programmed to Zone 1; Other: OK

H) "ALM" LED flashes & buzzer pulses for MCP operation

I) Acknowledge silences buzzer, Zone Resets

SERIAL NUMBER TEST PASSED

DATE: SIGNATURE

Page 109: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Testing and Maintenance

Issue 1.08 30 June 2016 Page 10-1

10 SYSTEM TESTING & MAINTENANCE

Page 110: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Testing and Maintenance

Page 10-2 30 June 2016 Issue 1.08

10.1 SYSTEM TESTING & FAULT FINDING

The F3200 has various test and diagnostic facilities to check functionality of the system and assist fault finding. Self Testing includes checking: Controller memory; real time clock; I/O bus communications; modules present; and LCD module operation. Should the Controller discover a fault it will annunciate a System Fault and take appropriate action. For example, for a module failure such that the Controller can no longer clock data to/from it, the Controller will display "Shift Register Clocking Fault", turn on the System Fault LED, de-energise the Standby relay and stop processing AZC status. Auto Test operates on a daily basis (holidays excluded) and includes Fault testing and Alarm testing (programmable) of all AZC's. Operator controlled tests include AZC (zone) Fault and Alarm tests, battery test, output tests (e.g. Test Relay), and a System Test. It is strongly recommended that the System Test is performed at the end of each monthly test and at the end of each service call. Refer to Section 6.5 for instructions. The supervision facility on AZCs, ancillary outputs and relay wiring allows detection of field wiring faults. Routine testing should include checking the operation of the FIP and various outputs. The cause of any faults within the system can be found as per Section 4.4.

Should a fault occur within the FIP electronics or system wiring, the operator should call a service person to check functionality and establish which facilities do not operate. Only a suitably trained technician should attempt to repair wiring or replace suspect modules.

Once it is established which particular module has a fault, the FIP should be de-powered (mains and battery) and the module replaced. (Refer to Chapter 10.2).

Faulty electronic modules should be returned to the factory for repair and testing. It is not recommended that service staff repair electronic failures on site.

All faults and alarms should be recorded in the system log book, with time and date of occurrence.

Page 111: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Testing and Maintenance

Issue 1.08 30 June 2016 Page 10-3

10.2 MODULE REMOVAL

10.2.1 GENERAL

Modules should only be unplugged and plugged in with both the Mains off and the battery disconnected. Faulty modules should be replaced by good ones at the earliest possible time. Should a spare module not be available at the time a module is diagnosed as faulty and removed, it is possible to reconnect the other modules and run the system with a module missing. The FIP must be told which of its modules are missing to assign the correct inputs/outputs to the modules which are present.

WARNING Suitable precautions should be made to check for fire in any unprotected areas, and to manually operate ancillary equipment which would otherwise be automatically operated.

NOTE When fitting modules ensure that the single screw which connects the module to the cardframe (FP0781) or the cabinet (FP0780) is fitted firmly, as it earths the module.

10.2.2 CONFIGURATION

On power up with a module removed, the Brigade Standby relay remains de-energised, the FIP does not process input/outputs and the System Fault LED turns on. Pressing "RECALL" "7" (Recall others) will display the appropriate fault message. From the base display (totals) press "SET" "5" to view both modules configured and present e.g. "relay = 1/0" implies that one 8RM is configured, but none are plugged in. Press "ENTER" then cursor along to the module which has been removed. Press

to toggle between P (present) and N (not present).

Press "ACK" to save the correct temporary configuration. The F3200 then checks the temporary configuration is correct and prompts the operator to press "ACK" to confirm the temporary configuration. Subsequently the Standby relay energises but the System Fault LED remains on.

WARNING If the FRCs to the Controller/Display are unplugged they must be replugged in with care. The FRC from the MAF must be plugged into the correct connector (J14 I/O Bus OUT) on the Controller. The FRC from a LED Display must only be plugged into the top connector (J13 LED Display). Swapping these may cause damage to the electronics.

Page 112: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Testing and Maintenance

Page 10-4 30 June 2016 Issue 1.08

10.3 SYSTEM MAINTENANCE

The F3200 and NDU are designed for high reliability and minimum maintenance. In Australia, however, in order to comply with the requirements of AS1851, the owner/occupier (or a nominated representative) must carry out system tests on a regular basis. In New Zealand, regular testing must be carried out to comply with NZS4512 parts 602 and 603. This is normally carried out by approved fire alarm contractors.

10.4 AS 1851 TESTING REQUIREMENTS

10.4.1AS 1851 TESTING - GUIDE FOR F3200 – SUGGESTED TEST METHODS

The F3200 and its associated equipment must be tested at regular intervals. Test criteria, service intervals, and record keeping requirements are specified in the appropriate Standard, the latest being AS 1851-2012. The following sections suggest how service persons may perform some of the required inspections and tests, where the method may not be immediately obvious or where special operations for particular features will be required. The references in the tables to “AS 1851 Item Number” refer to Table 6.4.1.2 through 6.4.1.5 in AS 1851-2012. References to just Section x.y refer to sections in this manual. Note; this is not intended to be used as a complete list of AS 1851 service requirements, nor as a complete test schedule. It is strongly recommended that the F3200 System Test is performed at the end of each monthly test and at the end of each service call. Refer to Section 6.5 for instructions.

10.4.2 MONTHLY TESTS

FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD MANAGEMENT SYSTEMS AS 1851 Item No

Description Action required and pass/fail criteria Test Facility, Procedure, Notes

1.4 Fire Alarm SIMULATE an alarm condition and confirm that all required common or general visual and audible indications operate and the external alarm is activated. Where the system is monitored ensure the alarm has activated the alarm signalling equipment. Where CIE is a sub-indicator panel, confirm that the alarm condition is indicated at the FIP.

Refer Section 7.1. Failure of the alarm relay should be treated as a critical defect – refer AS 1851-2012, Section 1.5.6.

1.5 Occupant warning system

SIMULATE an alarm and confirm the alarm initiates the occupant warning system including any visual warning devices (VWD).

Alarm Test as per Item 1.4, or Warning System Test as per Section 6.3. Failure should be treated as a critical defect – refer AS 1851, Section 1.5.6.

Continued…

Page 113: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Testing and Maintenance

Issue 1.08 30 June 2016 Page 10-5

AS 1851 Item No

Description Action required and pass/fail criteria Test Facility, Procedure, Notes

1.6 Isolate/Disable INITIATE an isolate/disable condition at the fire indicator panel and confirm that all required common or general visual and audible indications operate. Where the system is monitored, ensure the isolate is received by the monitoring service provider alarm signalling equipment. Where the panel is an SIP, confirm that the isolate/disable condition is indicated at the FIP as either a fault or isolate/disable.

Refer Section 7.2. Failure of the isolate relay should be treated as a non-critical defect – refer AS 1851-2012, Section 1.5.6.

10.4.3 SIX-MONTHLY TESTS

FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS

AS 1851 Item No

Description Action required and pass/fail criteria Test Facility, Procedure, Notes

2.4 Local control station (LCS) discharge inhibit switch

TEST the operation of each inhibit or auto/manual switch and confirm that: (a) It prevents the automatic discharge of

suppression system. (b) Stops and resets the normal system

discharge sequence. (c) Causes the illumination of a visual

indicator at the LCS and the system FIP. (d) Causes an audible indication. (e) Does not override the operation of the

manual discharge switch.

Refer Section 10.4.10 for suggested test procedure.

2.5 Local control station (LCS) manual initiate switch

TEST the operation of the manual initiate switch and confirm normal system discharge sequence, including fire and evacuation alarms, time delays equipment shutdowns, and that it overrides the LCS discharge inhibit switch.

Refer Section 10.4.10 for suggested test procedure.

2.6 System inoperative visual warning device (VWD)

CONFIRM the system inoperative VWD operates for: (a) Operation of a service switch (discharge

initiating circuit electrical isolation). (b) Fault in the discharge actuator circuit. (c) Operation of a lock-off valve (where

fitted). (d) Operation of a manual inhibit switch

(where fitted). (e) Isolation or fault in any part of the fire

detection or control system that prevents the automatic or electrical manual discharge of the suppression system.

Refer Section 10.4.10 for suggested test procedure.

2.7 System operation and logic

TEST the system logic (e.g. dual detector operation or dependency on more than one alarm) and confirm that the operation of • VWDs • audible alarms • directional valve signal/output • equipment fire mode signal/output • HVAC fire mode signal/output • system discharge actuator • system discharge actuator • system discharge actuator • door and damper release and • ancillary controls is in accordance with the approved design.

Refer to the baseline data and test appropriately.

Continued…

Page 114: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Testing and Maintenance

Page 10-6 30 June 2016 Issue 1.08

AS 1851 Item No

Description Action required and pass/fail criteria Test Facility, Procedure, Notes

2.8 Actuator circuit faults

TEST each supervised actuator circuit to ensure a fault is registered at the FIP.

Refer Section 10.4.10 for suggested test procedure.

2.9 Actuator TEST the function of each actuator and ensure that each actuator operates correctly. Ensure that each actuator has been mechanically isolated or temporarily removed from the suppressant supply to prevent unintended discharge. For non-resettable actuators (e.g. pyrotechnic types) substitute the actuator with a load of equivalent value and CONFIRM the operating current is in accordance with baseline data.

Refer to the actuator manufacturers documentation for test instructions.

10.4.4 ANNUAL TESTS

Before proceeding with Annual Tests, check that the installed F3200 software is up to date (refer Section 6.14). If it is not, consider installing the current version of software. Also check the site specific configuration details are up to date and in the log book. Use the Database CRC Recall function – refer to Sections 6.14 and 11.8.4. If these do not match the database most recently commissioned and recorded in the log book – then ascertain why and correct as necessary. FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS

AS 1851 Item No

Description Action required and pass/fail criteria Test Facility, Procedure, Notes

3.5 Panel switches and keypads

TEST the operation of each control. Refer Section 10.4.9.

3.6 Visual indicators TEST the operation of each visual indicator and alphanumeric displays.

Display Test as per Section 6.4.

3.7 Battery MEASURE system quiescent and maximum alarm currents in accordance with Appendix F. Calculate the required battery capacity and CHECK the nominal capacity of the installed batteries is not less than the calculated capacity. Verify that the measured currents are the same as recorded in the baseline data.

The F3200 battery test functions do not meet the requirements of this test. A separate test method must be used. Refer Section 10.4.6.

3.8 Fire Detectors TEST detectors as specified in Appendix G and confirm correct alarm zone indication. Where the detectors are used as part of special hazards systems 100% of the detectors shall be functionally tested yearly.

Zone in-situ test mode may be used to speed up testing of devices in a zone. Refer Sections 7.4 and 10.4.8.

Continued…

Page 115: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Testing and Maintenance

Issue 1.08 30 June 2016 Page 10-7

AS 1851 Item No

Description Action required and pass/fail criteria Test Facility, Procedure, Notes

3.9 Audibility TEST the occupant warning system and check the signals are distinctly audible in all areas of the building. NOTE: In order to reduce the disturbance to occupants an acceptable means of conducting this test is to provide an audio signal other than the warning signal at a reduced sound pressure level. Where the FIP is connected to a sound systems and intercom systems for emergency purposes (AS 1670.4) or EWIS (AS 2220.2) test in accordance with Table 6.4.3.2.

If a T-GEN 50 is used to generate the alert tone you can either select the low level test tone or play background music via the background music input.

3.15 Service life Inspect detectors, equipment or other items having a defined service life and report where the service life is exceeded or will be exceeded before the next scheduled service.

Unless accurate records have been kept of the installed detectors, their location and manufacture date, CO detectors will require manual inspection to determine their expiry date. Refer to manufacturer’s data.

3.18 Interfaced system initiation

Simulate alarm(s) to verify that each interface transmission path initiates the corresponding interfaced system(s) in accordance with the approved design

Referring to the baseline data check that a test alarm (refer Section 7.1) on each appropriate zone activates the required output device.

SMOKE HAZARD MANAGEMENT SYSTEMS—ADDITIONAL ACTIVITIES CAUTION: TAKE PRECAUTIONS TO PREVENT UNACCEPTABLE VENTILATION SYSTEM CHANGES

AS 1851 Item No

Description Action required and pass/fail criteria Test Facility, Procedure, Notes

3.19 FFCP latching and reset

CHECK that after initiation by a signal from the FIP, the FFCP remains operating in the fire mode until reset by the reset switch on the FFCP.

Trigger the FFCP with zone alarm test on the FIP. Then reset the FIP and check the FFCP is still operating in fire mode. Press FFCP fire mode reset to clear.

3.20 Manual override controls

CHECK that manual override ON-AUTO-OFF control operates.

NOTE: Manual override should function in normal mode and fire mode.

Check operation between the FFCP and the field equipment.

3.21 Airflow fault indicator

CHECK the operation of the airflow fault indicator

3.22 Open-circuit fault indicator

CHECK the operation of the air-handling equipment interconnecting cable open-circuit fault indicator.

3.23 Closed-circuit fault indicator

CHECK the operation of the air-handling equipment interconnecting cable closed-circuit fault indicator.

3.24 Electrical CHECK the operation of the electricity phase-fail fault indicator.

3.25 Fan-running indicator

CHECK the operation of the fan-running indicator.

3.26 Fan-stopped indicator

CHECK the operation of the fan-stopped indicator.

3.27 Fan fault indicator CHECK the operation of the fan-fault indicator.

Page 116: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Testing and Maintenance

Page 10-8 30 June 2016 Issue 1.08

SPECIAL HAZARD SYSTEMS—ADDITIONAL ACTIVITIES CAUTION: TAKE PRECAUTIONS TO PREVENT THE DISCHARGE OF THE SYSTEM DURING THESE TESTS

AS 1851 Item No

Description Action required and pass/fail criteria Test Facility, Procedure, Notes

3.28 Status monitoring TEST the each suppression system status monitored function (e.g. container level, pressure switches, pump controllers, isolation valves) and CHECK each monitored function indicates at the suppression system control panel.

Replace the actuator with a test actuator (with indicator) during testing. The discharge time delay can be measured during the Special Hazard Test (refer Section 10.4.10 step 5).

3.29 Suppression system directional valves

SIMULATE the system operation and confirm that each electrical directional valve operates according to the approved design.

3.30 Discharge time delay

TEST and RECORD the system discharge sequence and confirm the time delay period is in accordance with the approved design.

3.31 Agent release indication

TEST the agent release detection device (e.g. pressure switch) and confirm the operation of the agent release is indicated at the FIP.

10.4.5 FIVE-YEARLY TESTS

FIRE DETECTION AND ALARM SYSTEMS

AS 1851 Item No

Description Action required and pass/fail criteria Test Facility, Procedure, Notes

4.2 Supervised circuits TEST each input and output supervised circuit for any condition that prevents the transmission of the required signal and ensure a fault is registered at the FIP.

Apply o/c and s/c faults on the field wiring where appropriate and verify faults are generated at the FIP.

4.3 Fault SIMULATE a circuit fault condition at the FIP and confirm that all required common or general visual and audible indications operate. Where such faults are monitored, ensure the fault has activated the alarm signalling equipment. Where the panel is an SIP confirm that the fault condition is indicated at the FIP.

Refer Section 7.1. Failure of the fault relay should be treated as a non-critical defect – refer AS 1851-2012, Section 1.5.6.

4.5 Power supply supervision

Where the system is monitored, REDUCE the CIE operating voltage to trigger a power supply supervision fault and CONFIRM that it is received by the monitoring service provider. Where the panel is an SIP or a distributed power supply, confirm that the power supply supervision fault condition is indicated at least as a fault at the FIP.

This test requires equipment external to the F3200. Refer Section 10.4.7.

4.7 Interface and control test

CONDUCT a functional test with each system interface in accordance with the building’s systems interface diagram and CHECK that each interfaced system responds to the signal in accordance with the approved design. See Appendix D.

Refer to the baseline data for details. See Appendix D of AS 1851-2012.

Continued…

Page 117: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Testing and Maintenance

Issue 1.08 30 June 2016 Page 10-9

As 1851 Item No

Description Action required and pass/fail criteria Test Facility, Procedure, Notes

4.9 Monitoring connection

Where the system is monitored, TEST that the loss of each of the monitoring links is indicated at the monitored site.

For networked systems break/short each communication line between a sub FIP to the main FIP and check that a fault is indicated at each FIP. If the FIP is fitted with an ASE consult the monitoring company regarding testing the fault monitoring of the ASE’s communication links.

4.10 Alarm verification facility

TEST one detector of each type per circuit with alarm verification facility enabled to check that it functions in accordance with the approved design.

To test AVF put the detector into alarm using appropriate test apparatus (e.g., test smoke/gas or Solo in-situ tester) and check the following: i) The detector’s indicator turns on ii) The indicator turns off for at least 5 seconds iii) The indicator turns on again within 60 seconds and the FIP goes into alarm.

10.4.6 BATTERY LOAD DISCHARGE TESTING (AS 1851 ITEM 3.7)

The F3200 Fire Alarm panel has no provision for load discharge testing of the battery at the levels required for yearly testing to AS 1851-2012. Refer to AS1851-2012 Appendix F for the battery capacity test method.

10.4.7 PSU SUPERVISION (AS 1851 ITEM 4.5)

F3200 does not include built-in facilities to carry out this test. A suitably rated bench power supply connected to the F3200 battery terminals with mains power turned off may be used instead. Ensure the panel is normal – i.e., no faults and no system conditions that cause the Standby relay to be de-energised are present. Reduce the bench power supply output voltage to below the minimum operating voltage and check the Standby relay de-energises. Refer Table 10.4.7. If the PSU supervision signal is monitored, confirm that it is received at the monitoring service, or for an SIP at the main CIE. The status of the PSU/Batt can be observed in the Recall System Faults (refer Section 6.6). This will indicate a Supply Failed condition when the system voltage is below the minimum operating voltage.

Table 10.4.7 Standby Relay Dropout Voltage

Temperature Min. Nominal Max.

40ºC 30ºC 20ºC 10ºC 0ºC

20.9V 21.2V 21.5V 21.8V 22.1V

21.4V 21.7V 22.0V 22.3V 22.6V

21.9V 22.2V 22.5V 22.8V 23.1V

Page 118: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Testing and Maintenance

Page 10-10 30 June 2016 Issue 1.08

10.4.8 DETECTOR SENSITIVITY TEST (AS 1851 ITEM 3.8)

Item 3.8 of the yearly test of AS 1851-2012 (detailed in Appendix G of AS 1851-2012) requires that the functionality of a sample of all detectors be in-situ tested each year. Additionally the sensitivity of each detector needs to be tested at specific service intervals. The yearly functional test will usually be conducted using test smoke/gas/heater or other approved apparatus (e.g., Solo in-situ tester). Auto-Reset mode (see Section 7.4) should be enabled for each zone as its detectors are being tested to speed up operation. If no suitable in-situ sensitivity test is available and the detectors do not report “out-of-sensitivity” at the FIP (as is the case for many conventional detectors), then the detectors need to be replaced with new, or cleaned and calibrated, detectors at the specified time.

10.4.9 KEYBOARD TEST

Usually pressing keys on the F3200 keyboard will cause things to happen to the panel. The following sequence can be used to test the keyboard without affecting anything. Press each key in order and check a beep is heard (it may be short or long) for each keypress.

Page 119: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual System Testing and Maintenance

Issue 1.08 30 June 2016 Page 10-11

10.4.10 SPECIAL HAZARD TEST

The following test procedure may be adapted to carry out the six-monthly service schedule for special hazard systems items 2.4 -2.6. 1. Take whatever precautions are necessary to prevent the system from accidental

discharge. 2. Replace the actuator with a test actuator that includes an activation indicator (e.g.,

LED). 3. Put the LGCS INHIBIT GAS RELEASE switch in to the INHIBIT position and check

that the LGCS sounder and GAS INHIBITED LED turn on. 4. Place the two automatic fire detection zones into test alarm (refer Section 7.1) on the

FIP and check that the GAS INITIATED LED on the FIP remains off. 5. Test activate the LGCS GAS RELASE MCP and check that the GAS INITIATED LED

on the FIP turns on. 6. Measure the time delay from the GAS INITIATED LED turning on to the test actuator

activating. Check that the delay period is correct. Note that this is required as part of the annual test (refer item 3.30).

7. Verify that the required equipment is shut down. 8. Place the LGCS GAS RELEASE MCP and the INHIBIT switch in the normal position

and reset the FIP. Check the LGCS GAS ISOLATED and GAS INHIBITED LEDs are off, the FIP goes back to normal and the test actuator deactivates.

9. Place the GAS DISCHARGE ISOLATE switch in the ISOLATE position. Check that: (a) the GAS ISOLATED LED on the LGCS turns on, (b) the GAS ISOLATED LED on the FIP turns on, (c) the SYSTEM INOPERATIVE LED on the FIP turns on, (d) the SYSTEM INOPERATIVE AVI turns on (if installed). Return the GAS DISCHARGE switch to the NORMAL position. Check that the panel returns to normal.

10. Disconnect the test actuator. Check items 9a-9d. Reconnect the test actuator and reset the FIP. Check that the panel returns to normal.

11. Activate the lock-off valve (if fitted). Check items 9a-9d. Deactivate the lock-off valve and reset the FIP. Check that the panel returns to normal.

12. Isolate one of the two automatic fire detection zones. Check items 9a-9d. Deisolate the automatic fire detection zones. Check that the panel returns to normal.

13. Place one of the two automatic fire detection zones in to test fault (refer Section 7.2). Check items 9a-9d. Return the automatic fire detection zone to normal. Check that the panel returns to normal.

14. Restore all circuits and panel switches to normal. Finally reconnect the actuator and reset any latched faults.

Page 120: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 System Testing and Maintenance

Page 10-12 30 June 2016 Issue 1.08

10.5 PREVENTION OF FALSE ALARMS

Fire detection systems rely on sensors to identify atmospheric or environment changes brought about by the presence of fire. They employ various types of sensors to monitor specific conditions. These devices signal a warning when an abnormal condition exists, indicating either the presence of a fire or the immediate likelihood of an outbreak. There are detectors to monitor heat, flame, water pressure or the presence of combustion products such as smoke or gases. However, some or all of these conditions may appear in different locations when there is no fire present. For example: (a) HEAT SOURCES; The sudden increase in local temperature when a furnace

door is opened can trigger heat sensors. (b) DRAUGHTS, DUST, STEAM, CHEMICALS; Wind-induced surges of dust,

release of steam or chemicals can cause smoke detectors to generate an alarm signal.

(c) ENVIRONMENT CHANGES; Changes to wall partitions, Air-Duct position or air

velocity can cause detectors to be forced into continuous alarm. (d) CONSTRUCTION AND MAINTENANCE ACTIVITIES; Portable welding units

can activate flame detectors, while spray-painting 'drift' can trigger smoke detectors.

It is therefore highly recommended that the service company be notified of any proposed physical, environmental or occupancy changes.

Page 121: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-1

11 NETWORK SYSTEMS

Page 122: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-2 30 June 2016 Issue 1.08

11.1 INTRODUCTION

This chapter describes the operation of networked systems and is not relevant to users of non-networked F3200 panels. Multiple F3200 fire panels and NDUs (Network Display Units) along with other devices, may be connected together to form a network. Some of the devices which may be part of the network include: 1. F3200 fire panels. 2. NDU - network display/printer unit. 3. PTM - Protocol Translation Module for interface to XL colour graphics or for event

printing. 4. Network LED display unit (NLDU) for display of network zone states on LEDs. 5. Panel-link Modbus Bridge (PMB), which provides a Modbus output of network

states for connection to colour graphics systems (e.g. Overview) or building management system (BMS) that support the Modbus protocol.

Except where otherwise stated, the commands and information in Chapters 1 to 10 of this manual apply to networked F3200s and to NDUs. The operation of an NDU is almost identical to the operation of a networked F3200 and is described in Section 11.2. Networking allows F3200 fire panels to share: (i) Alarm information for display and control of alarms on the LCD. Alarms on one

FIP can be displayed at other FIPs and Colour Graphics displays. Alarms can be acknowledged, reset and isolated from the FIPs and Colour Graphics displays.

(ii) Output logic status, allowing status and controls generated by the Output Logic at

one FIP to be used by the Output Logic at another FIP, e.g. for extended AS1668 Fan Controls.

(iii) MAF Status, so that one FIP can be a common brigade interface point for a

number of FIPs elsewhere on site. (iv) Event Information for status monitoring and network event printing. An F3200

FIP may be programmed to perform system wide event printing and event history. (v) Control for activating, isolating and silencing the External Bell and Warning

System on remote FIPs as a result of alarms or operator controls on the local FIP.

(vi) For an NDU in New Zealand mode, the Trial Evac and Silence Alarms keyswitches can affect all panels on the network and allow the system to be controlled from a single point.

Page 123: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-3

INTRODUCTION (CONTINUED) Network Zone Functions 1. Recall the status of a specific zone on a remote FIP. 2. Search for zones of a specific condition on remote FIPs. 3. Send reset, isolate, de-isolate, alarm test, fault test, abort test, and operate test

commands on a single zone or range of zones to a remote FIP. Network System Functions System functions which may be sent to or from network panels are: 1. System Test 2. System Fault Reset 3. Battery Test 4. Set Time/Date 5. External Bell / Warning System Isolate / De-Isolate / Test 6. Recall Database CRC 7. For an NDU in New Zealand mode Trial Evacuation and Silence Alarms 8. Silence sounders on all network panels Network Event Logging Networked FIPs can be programmed to transmit their events onto the network for use by network printers, colour graphic systems, etc. An F3200 FIP or NDU may be used as a system-wide history/event printer and may be programmed to print events for selected FIPs on the network, and to log events for those selected FIPs into the event history. LCD Totals, LEDs and Outputs Depending on the programming of the FIP the state of these may include, or be affected by, data received from other devices on the network.

Page 124: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-4 30 June 2016 Issue 1.08

11.2 NDU - NETWORK DISPLAY UNIT

An NDU can be thought of as an F3200 FIP without any alarm zone modules or relay modules. An NDU also has an option of MAF board present/not present. An NDU without a MAF board is physically quite small, convenient to use, and is powered from an external source. An NDU with a MAF board may perform brigade signalling functions and also has ancillary and bell relays. Even though an NDU does not have any 8 zone or 8 relay modules, it does have 16 alarm zones. The local MCP (or connected RDU MCP), if any, may be mapped to any one of these 16 zones. Each of the 16 zones may be isolated, de-isolated, or reset, but cannot be tested. Each zone can be programmed as latching/non-latching, MAF/non-MAF, etc. Even though an NDU zone which does not have an MCP mapped cannot go into alarm, it may be useful as an object which can be isolated or de-isolated (as this state can be sent to other panels on the network). Otherwise an NDU will perform all the functions of an F3200 panel, including sending/receiving network zone commands, network event printing, and FF alarm display. An NDU may be programmed with output logic, the same as F3200, and may send and receive network logic variables on the network. An NDU without a MAF board may still perform the functions of External Bell, Warning System, and/or or Ancillary Relay Isolate / De-Isolate / Test, and the output logic tokens associated with these may be used so that these conditions can be accessed from other panels. The keypad on an NDU without a MAF board is physically accessible all the time, but when the cabinet is locked the NDU disables the keypad even though the keypad is physically accessible. It is possible to program selected keys to be operational when the NDU cabinet is locked. Section 4.1.1 describes the interpretation of the front panel LEDs on an NDU. If an NDU is programmed to use the totals sent by another device on the network, then the NDU will turn its buzzer on if a new MAF fault, Standby condition or new System fault occurs on the remote device. NDU in New Zealand Mode An NDU can be programmed to operate in either New Zealand mode or Australian mode. New Zealand mode operation is not available on an F3200 panel.

Page 125: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-5

11.3 LCD TOTALS, LEDs, OUTPUTS & BUZZER OPERATION

For a networked F3200 or NDU, the interpretation of the front panel LEDs is described in Section 4.1.1. However, the operation of the Off-Normal totals, buzzer, MAF relays, and Ancillary relays may be affected by states coming from other panels on the network, depending on programming.

11.3.1 LCD TOTALS

The totals shown on the LCD display may include totals received from other devices on the network. A recall net SID status function is provided to show the individual totals local to this panel and the totals currently being received from any other device on the network (from the base display press RECALL RECALL 3 - refer to Section 11.6.2). Refer also to Section 4.2.2 (Base Display).

11.3.2 BUZZER OPERATION

The buzzer turns on: Steady: For a local fault or system fault, or a MAF fault, standby condition

or System fault received from another network device for which this panel has been programmed to include the totals of.

Pulsing: For a new alarm being put into the FF list or a new MAF alarm on

the local panel. Rapid Pulsing: For a local test failure, e.g. system test. The buzzer is turned off: 1. Whenever a key is pressed on the keypad. 2. When there are no more unisolated alarms or faults. 3. When a system fault reset command is received from another device on the

network. 4. When the buzzer is turned off at another device on the network (depends on

programming). 5. When a “silence all network sounders” command is received from another panel

on the network.

Page 126: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-6 30 June 2016 Issue 1.08

11.3.3 MAF RELAYS

The MAF states received from another device on the network will be used by this panel to drive its MAF outputs (if any) if this panel has been programmed to use the MAF states of the other device. MAF Alarm Relay Energised for a local MAF alarm or for a MAF alarm state received from another device. (For an NDU in New Zealand mode, the MAF alarm relay is normally energised and de-energises for alarm). MAF Fault Relay Energised for a local MAF fault or System fault or for a MAF fault, standby condition or system fault state received from another device. MAF Isolate Relay Energised for a local MAF isolate condition or for a MAF isolate state received from another device. MAF Standby Relay De-energised for a local "Standby Fault". It does not de-energise for a Standby condition received from another device. Ancillary Relays Unless controlled by output logic, this relay is not affected by states from other network devices and operates for a local alarm on a zone mapped to it. Ancillary 2 Relay For both networked and non-networked panels, this relay is controlled by an output logic equation, for which the default operation is that the relay operates when the External Bell is activated. Ancillary 3 Relay For both networked and non-networked panels, this relay is controlled by an output logic equation for which the default operation is that the relay operates when the Warning System is activated. External Bell The activation of the External Bell is controlled by an output logic equation, for which the default operation is that the External Bell is activated when: 1. Any local zone mapped to the External Bell is in alarm. 2. The External Bell is tested.

Page 127: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-7

MAF RELAYS (CONTINUED) Warning System The activation of the Warning System is controlled by an output logic equation, for which the default operation is that the Warning System is activated when: 1. Any local zone mapped to the Warning System is in alarm. 2. The Warning System is tested. 3. There is an alarm on a zone in In-Situ test mode that is mapped to the Warning

System. For an NDU in New Zealand mode the Warning System is usually programmed to operate for Trial Evacuation.

11.4 EXTERNAL BELL/WARNING SYSTEM ISOLATE/SILENCE

11.4.1 WARNING SYSTEM

The Warning System can be isolated locally or it can be silenced by a Warning System Silence state received from other devices on the network. For New Zealand mode, the Warning System can also be silenced by activation of a Silence Alarms keyswitch. Depending on programming, when the Warning System is isolated locally, this panel may send a Warning System Silence state onto the network which may cause the Warning System to be silenced (inhibited) at other panels on the network, depending on their programming. Hence when the key is used to Isolate the Warning System at one panel on

the network, it can result in the Warning System being silenced at other panels on the network.

The Warning System Isolate LED indicates whether the Warning System is isolated or silenced as follows, in order of priority. Warning System Isolate LED Flash at 2Hz : A Silence Alarms Keyswitch is activated (NZ only) Slow flash : Warning System inhibited by network silence On steady : Warning System locally isolated Off : None of the above i.e. the Warning System outputs will operate for

alarm For an NDU without its own Warning System output, the information shown on the Warning System Isolate LED is still useful because it shows the network Warning System silence status.

Page 128: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-8 30 June 2016 Issue 1.08

11.4.2 EXTERNAL BELL

The External Bell can be isolated locally or it can be silenced by a External Bell Silence state received from other devices on the network. Depending on programming, when the External Bell is isolated locally, this panel may send a External Bell Silence state onto the network which may cause External Bell to be silenced (inhibited) at other panels on the network, depending on their programming. Hence when the key is used to Isolate the External Bell at one panel on the

network, it can result in the External Bell being silenced at other panels on the network.

The External Bell Isolate LED indicates whether the External Bell is isolated or silenced as follows, in order of priority. External Bell Isolate LED Slow flash : External Bell inhibited by network silence On steady : External Bell locally isolated Off : None of the above i.e. the External Bell outputs will operate for

alarm For an NDU without its own External Bell output, the information shown on the External Bell Isolate LED is still useful because it shows the network External Bell silence status.

11.5 NETWORK FIP & ZONE NUMBERING

When F3200 FIPs are networked together there must be a way to identify each FIP and the zones on that FIP. In this manual, reference is made to "local" and "remote" panels. A local panel is the panel at which the operator is at. Remote panels are all other panels on the network. This applies even if a number of networked panels are co-located. When a networked FIP is configured, it is programmed with a unique number between 1 and 254. This is its System Identification Number, or SID. The SID is used to: (a) Identify a specific FIP. (b) Identify a zone on a specific FIP, by combining the SID and Zone number as

detailed below. For a networked FIP, zone numbers and zone ranges fall into 3 formats: (i) Zone number(s) less than 1000 are local zones, ie. specific to the panel at which

the number is being entered or displayed, eg. Z57, Z135.189. (ii) Zone number(s) greater than, or equal to, 1000 are network zones, eg. Z32105 or

Z17001.17095. The SID of the FIP that has the zone is the network zone number divided by 1000. The actual zone number on that FIP is the remainder after dividing by 1000.

Eg. Z1057 is Zone 57 on FIP number 1. Z35218 is Zone 218 on FIP number 35. Note that all zeros must be entered, eg. for Zone 1 on Panel 2, the entry must be

2001, ie. the intermediatory 0s are necessary.

Page 129: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-9

NETWORK FIP & ZONE NUMBERING (CONTINUED) (iii) Zone numbers less than 1000 preceded by the SID of the FIP that has the

zone(s) and separated by a : or double points “..”. ,eg. (a) Z57:1 - Zone 1 on Panel 57. (b) Z2:135.208 - Zones 135 to 208 on Panel 2. (c) Z61..72 - Zone 72 on Panel 61. (d) Z85..24.154 - Zones 24 to 154 on Panel 85. A colon is entered using the SYSTEM key. Double points are entered by pressing

the AND. key twice. For F3200, zone numbers can be entered in any of the above formats. However, any zone range that extends across more than one FIP, eg. Z35097.36002 is illegal. F3200 always displays network zones in format (ii), and event printing uses format (iii). If a zone number or range is entered in formats (i) or (ii), and the SID is that of the local FIP, then the zone number(s) may be converted back to format (i) for local processing. When alarm events are sent from one FIP to another on the network, the zone number is sent as network zone format (ii) for display on the LCD.

11.6 SYSTEM FAULT RECALL/NET PANEL STATUS RECALL

As described in Section 6.6.2, a RECALL SYSTEM command can be used to recall all system faults. As well as the faults listed in Section 6.6.3, a system fault recall (or network device status recall) will display up to 5 "pages" of information for each device on the network, beginning with the local panel. The "pages" are numbered 0 to 4, and the information shown is described in Section 11.6.3.

11.6.1 NETWORK SYSTEM FAULT RECALL

This is the same as described in Section 6.6.2. From the base display, press:

Use NEXT and PREV keys to step through the faults. The system faults shown are listed in Section 6.6.3 plus the additional faults listed in Section 11.6.3 below.

Page 130: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-10 30 June 2016 Issue 1.08

11.6.2 NETWORK PANEL STATUS RECALL

The five pages of panel status listed in Section 11.6.3 may be recalled by a panel status recall command. From the base display, press:

Then press 1, 2 or 3 to select the desired option as follows: 1. All net SIDs. 2. Select SID. 3. All off normal SIDs. Option 1: All net SIDs, will step through all panels on the network that are in the SID list of this panel, starting with the local panel. Option 2: Select SID, will prompt for the entry of a SID number and will start the recall from the selected SID, and is otherwise the same as Option 1. Option 3: All off normal SIDs, will display only those SIDs that have off normal conditions or have non-zero totals.

11.6.3 NETWORK PANEL STATUS

The network panel status is shown as a sequence of pages containing fault and status information. For a non-networked panel this information appears with the heading “System Status Summary”. Network Panel Status Page 0 ScanF - The Local Panel is not receiving any data from the Remote Panel. LnkIA - The Local Panel is not receiving Channel A test data from the Remote

Panel. LnkIB - The Local Panel is not receiving Channel B test data from the Remote

Panel. SysFlt - The Remote Panel has a system fault. NetFlt - The Remote Panel has a network fault. Stdby - The Remote Panel has generated a standby condition. Network Panel Status Page 1 Abnml - The Remote Panel has an Abnormal status present. BellI - The Remote Panel's bells are isolated. (See note 1) TEvac - The Remote Panel is asserting Trial Evacuation. SilAlm - The Remote Panel is asserting Silence Alarms (Silence Bells). (See note

1). BrigT - The Remote Panel is asserting Brigade Test. SysFRcl - The Remote Panel has information that should be recalled on its own LCD

display using the System Fault recall command.

Page 131: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-11

NETWORK PANEL STATUS (CONTINUED) Network Panel Status Page 2 MafAlm - The panel has a MAF alarm condition. MafFlt - The panel has a MAF fault condition. MafIso - The panel has a MAF isolation condition. NMAlm - The panel has a non-MAF alarm condition. NMFlt - The panel has a non-MAF fault condition. NMIso - The panel has a non-MAF isolate condition. Network Panel Status Page 3 CmnPtI - Common point isolate. SysTst - A system/auto-test is in progress. TstFlI - Test fail indication. A zone/system/auto-test has failed and the test fail buzzer is currently active. PSUFlt - Indicates a Power Supply or battery fault e.g. mains fail, charger low,

battery low, battery connection or battery capacity. LatBVLO - For New Zealand mode, this indicates a latched Battery Very Low Alarm. BSR - For New Zealand mode, indicates Building Services Restore keyswitch

activated. Network Panel Status Page 4 WOpr - The Warning System at the panel is operated. WIso - The Warning System at the panel is isolated. WSil - The panel is sending Warning System silence. WAlm - There is a non-isolated zone mapped to the Warning System in alarm at

the panel. BOpr - The External Bell at the panel is operated. BIso - The External Bell at the panel is isolated. BSil - The panel is sending External Bell silence. BAlm - There is a non-isolated zone mapped to the External Bell in alarm at the

panel. Network Panel Status Page 5 Page 5 shows the 4 totals being transmitted onto the network by the panel - alarm, fault, isolate, other. For the local panel the page 5 totals only show the off normal conditions being generated by this panel - these may not be the same as the values shown on the base display because the base display may show combined totals from multiple panels. NOTE 1: The BellI and SilAlm status in Page 1 are meaningful only for a panel running

AS1603.4 type software. When a network system has a mixture of older AS1603.4 panels and new AS4428 type panels, the older panels don’t have a Warning System or External Bell. However, their Bells/Bells Isolate state normally correspond to the External Bell on the AS4428 panels and will interact with the AS4428 panels as if it were an External Bell. Hence when the BellI status is shown in Page 1, the BIso status will also appear in Page 4 as they represent the same state.

The mapping of Bell states on an older panel to External Bell on a newer panel is programmable, and for New Zealand operation the Bell states on an older panel actually map to the Warning System on a newer panel.

Page 132: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-12 30 June 2016 Issue 1.08

11.7 NETWORK COMMAND RESPONSES & EXCEPTION MESSAGES

Whenever a network command or status recall is initiated with the keypad, the display will show a variety of information or response messages listed in Section 11.7.1. When a network command is received by a remote device, the device may take from several seconds to several minutes to carry out the command (e.g. System Test). When the command or test is completed the device may send an exception message to indicate the result of the test. Exception messages are listed in Section 11.7.2.

11.7.1 NETWORK COMMAND RESPONSES

1. "Sending Command" The command is now being sent across the network. 2. "Command Accepted" The command arrived successfully at the remote device and is now being

processed. 3. "Command NOT Accepted" The command arrived successfully at the remote device, but is not able to be

executed for one of the following reasons: (i) Invalid zone number. (ii) Invalid command type - e.g. alarm test on relay zone. (iii) Command not supported. (iv) Panel busy - e.g. system test already in progress. 4. "Command Timeout. No response" The command did not arrive successfully at the remote device and was not

acknowledged by that device. 5. "Command NOT accepted. Try Again" The command arrived successfully at the remote device but was not able to be

executed at the present time but may be able to be at some future time. This could occur if the panel was in program mode.

6. "Data Retrieve Timeout. Retrying" This indicates that the remote panel is not responding with some status

information when requested - such as for a zone status recall. The local panel will automatically retry every few seconds (programmable time) to get the information.

7. "Net Command Tx Disabled for SID" The local panel has not been programmed to allow the sending of commands

to the specified SID. The local panel needs to be programmed with the list of SID's that it is allowed to send commands to.

8. "Illegal or Invalid Command" This could occur for the reasons listed in item 3 above, such as invalid zone

number.

Page 133: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-13

NETWORK COMMAND RESPONSES (CONTINUED) 9. "Network Panel Not Processing" The remote panel is in program mode and cannot accept commands. 10. "Retrieve Timeout. No Response" The Remote Panel did not acknowledge a request for information. 11. "Unable to Access Network" This indicates a hardware fault such as a break or short circuit on the network

cabling. 12. "Local Net Transmit Queue Full" All commands initiated are entered into a queue until the network driver is able

to send them. It is only in extreme or fault situations that the queue would become full.

In a fault situation it may be that the queue remains full until the fault clears.

The command should be retried.

11.7.2 EXCEPTION MESSAGES

When an exception message is received from a remote device, it is immediately shown on the display, temporarily interrupting whatever is being shown on the display at the time. The display shows the number of the SID which sent the exception message. The pressing of any key will clear the exception message and restore the display. Exception messages which may be shown are: "Not All Zones De-Isolated" The zone range de-isolation command processed did not de-isolate one or

more zones because they were in alarm or fault. "Zxxxxx Test Passed" "Zxxxxx Test Failed" "Zxxxxx Test Aborted" "Zxxxxx Test Time Out" The previous Zone test command issued to zone xxxxx had the indicated

result. "System Test Passed" "System Test Failed" "System Test Aborted" The previous System test command had the indicated result. "Battery Test Passed" "Battery Test Failed" "Battery Test Aborted" The previous Battery test command had the indicated result.

Page 134: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-14 30 June 2016 Issue 1.08

11.8 NETWORK SYSTEM COMMANDS

11.8.1 NETWORK SYSTEM TEST

To initiate a system test on a remote device, from the base display press:

Then enter the SID number 1 to 254 using the numeric keys 0 to 9, followed by the ENTER key. The top line of the display then shows the name of the selected SID and the bottom line gives a list of options 1 to 3 as follows: 1:System 2:Zone 3:Battery Select option 1 (system), then press the ACK key to initiate the test. The display will indicate if the command was accepted by the remote device. The remote device may send an exception message to indicate if the test passed or failed.

11.8.2 NETWORK SYSTEM BATTERY TEST

To initiate a battery test on a remote device, from the base display press:

Then enter the SID number 1 to 254 using the numeric keys 0 to 9, followed by the ENTER key. The top line of the display then shows the name of the selected SID and the bottom line gives a list of options 1 to 3 as follows: 1:System 2:Zone 3:Battery Select Option 3 to initiate a battery test at the remote device. The display will indicate if the command was accepted by the remote device. The remote device may send an exception message to indicate if the test passed or failed.

Page 135: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-15

11.8.3 NETWORK SYSTEM FAULTS RESET

To send a system fault reset command to a remote device, from the base display press:

Then enter the SID number 1 to 254 using the numeric keys 0 to 9, followed by the ENTER key. The top line of the display then shows the name of the selected SID and the bottom line gives options 1 to 4 as follows: 1:System Test 2:Faults Reset 3:Warning System 4:External Bell. Select option 2: Faults Reset, i.e. press numeric key 2.

11.8.4 NETWORK RECALL DATABASE CRCs

It is possible to recall the database CRC from a remote F3200 or NDU. This information can be used as part of an AS1851 testing schedule. From the base display, press:

then press: 1. For all panels (SIDs). 2. Local panel. 3. A selected panel. For Option 1, the LCD will first display the database CRC for the local panel. The NEXT and PREV keys may then be used to step to the next or previous panel in the system. Some devices on the network may not support the remote database CRC recall function, in which case an error message will be displayed and an option given to retry (ACK key) or to step to the next panel (NEXT key). To exit from the recall at any time, press the CLEAR key. NOTE: Any changes made to the database will change the numbers displayed in

this recall. Thus, if the database is changed, the new numbers should be recorded in the log book and the service company advised.

Page 136: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-16 30 June 2016 Issue 1.08

11.8.5 NETWORK EXTERNAL BELL ISOLATE/DE-ISOLATE/RECALL/TEST

To isolate, de-isolate, test or recall the status of the External Bell at a remote device, from the base display press:

Then enter the SID number 1 to 254 using the numeric keys 0 to 9 followed by the ENTER key. The top line of the display then shows the name of the selected SID and the bottom line gives options 1 to 4 as follows: 1:System Test 2:Faults Reset 3:Tandem 4:more Select option 4:more. The display then shows 1:Warning System 2:External Bell Select Option 2:External Bell The display will then show the current External Bell isolate state of the selected SID and a list of options as follows: 1. Test . 2. Isolate. 3. De-Isolate. Press numeric key 1, 2 or 3 to select the desired option, then press the ACK key when prompted to initiate the command. An External Bell test will result in the External Bell output at the remote device turning on for a few seconds and then automatically turning off (if not previously on).

11.8.6 NETWORK WARNING SYSTEM ISOLATE/DE-ISOLATE/RECALL/TEST

To isolate, de-isolate, test or recall the status of the Warning System at a remote device, from the base display press:

Then enter the SID number 1 to 254 using the numeric keys 0 to 9 followed by the ENTER key. The top line of the display then shows the name of the selected SID and the bottom line gives options 1 to 4 as follows: 1:System Test 2:Faults Reset 3:Tandem 4:more Select option 4:more. The display then shows 1:Warning System 2:External Bell Select Option 1:Warning System

Page 137: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-17

NETWORK WARNING SYSTEM ISOLATE/DE-ISOLATE/RECALL/TEST (CONTINUED) The display will then show the current Warning System isolate state of the selected SID and a list of options as follows: 1. Test. 2. Isolate. 3. De-Isolate. Press numeric key 1, 2 or 3 to select the desired option, then press the ACK key when prompted to initiate the command. A Warning System test will result in the Warning System output at the remote device turning on for a few seconds and then automatically turning off (if not previously on).

11.8.7 NETWORK SET TIME/DATE

Section 6.9 describes how to set the local time/date. If programmed to, setting the local time/date will also cause the new time/date to be sent on to the network to set the time/date at other devices. If programmed to, this panel may also set its local time/date whenever it receives time/date from the network. If programmed to, a device will automatically transmit time/date onto the network every 12 hours at 11:30am and 11:30pm and also when the time is changed due to a daylight saving time change.

11.8.8 SILENCE ALL NETWORK SOUNDERS

If enabled with programming, there is a command that can be used to silence the sounders of all panels on the network (depending on their programming). From the Base display press:

The message “Sending network sounder silence” will be shown.

11.8.9 TANDEM LCD TO LCD

It is possible to take control of a remote panel on the network and operate it as if you were standing in front of it. Keypresses are sent across the network to the remote panel and display updates are sent back to be displayed locally. The common LEDs on the local front panel always show the status of the local panel and do not show the status of the remote panel. It is only the content of the LCD from the remote panel that is shown on the local panel. From the base display press:

Then enter the SID number 1 to 254 using the numeric keys 0 to 9 followed by the ENTER key.

Page 138: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-18 30 June 2016 Issue 1.08

TANDEM LCD TO LCD (CONTINUED) The top line of the display then shows the name of the selected SID and the bottom line gives options 1 to 4 as follows: 1:System Test 2:Faults Reset 3:Tandem 4:more Select option 3:Tandem and if prompted for a password, enter the local panel’s tandem mode LCD password (6 digits). The display will then prompt you to confirm that you want to make a tandem connection to the remote panel. Select option 1 (yes) if you wish to proceed. You will then be connected to the remote panel and the System Fault LED will start flashing and remain flashing while the tandem connection is present. During this time, all keypresses are sent to the remote panel, and display updates come from the remote panel. To exit the Tandem connection, press and hold the CLEAR key for approximately one second and select option 1 (yes) when prompted. Also, if no keys are pressed for 4 minutes, a prompt is given to maintain the connection. If no key is pressed then the connection is cleared after 10 seconds. If a new unacknowledged FF alarm occurs while tandem mode is active, the tandem connection is terminated automatically and the FF alarm list is displayed.

11.9 REMOTE RELAY & OPEN COLLECTOR OPERATION & ZONE MAPPING

An F3200 panel maps its inputs and outputs to zones as follows so that they can be accessed across the network using the zone number. Zones 1-64 - Alarm zones 1-64 Zones 65-128 - Module relays 1-64 Zones 129-192 - Open collectors 1-64 Zone 193 - Invalid Zone 194 - Ancillary relay 1 Zone 195 - Ancillary relay 2 (External Bell*) Zone 196 - Ancillary relay 3 (Warning System*) Zone 197 - Plant isolate Zone 198 - Warning System Zone 199 - External Bell For example, to recall the status of module relay 3, a recall of zone 67 would be done. When a recall command is done to search for zones in a particular condition, the recall includes a search of all the above zones except for open collectors which are never included in zone searches. Local module relays, open collectors and ancillary relays are also accessible by pressing the RELAY key from the base display. This requires the entry of an actual relay number rather than a zone number. Module relays and ancillary relays on a remote F3200 panel (or NDU) may be recalled, isolated, de-isolated, reset or tested using a zone recall, isolate, de-isolate, reset or test command (as described in Section 11.10) with the appropriate zone number determined from the mapping above. To test a remote relay or open collector, use a zone operate test command, (option 3 from the test menu), as described in Section 11.10.6, using a zone number determined from the mapping above.

Page 139: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-19

REMOTE RELAY & OPEN COLLECTOR OPERATION & ZONE MAPPING (CONTINUED)

* By default zone 195, Ancillary 2, is the External Bell output, and Zone 196, Ancillary 3,

is the Warning System output. This might not apply if the panel’s programming is changed from the default. Recalling pseudo relay status It is valid to have a logic equation for a relay for which there is no corresponding physical relay in the system. Relays in the range 1 to 64 for which there is no physical relay are referred to as "pseudo relays" and the states generated by these logic equations are sent on the network by the Status Transfer application as zones 65 to 128. The status of a pseudo relay can be viewed on the local panel by pressing the RELAY key on the base display, then selecting option 1 Module relays, and entering the relay number 1 - 64. The NEXT PREV keys can be used to step through the relays one by one. The up-arrow (fault test) and down-arrow (batt test) keys can be used to step through only those relays for which there are logic equations, i.e., skipping relays for which there is no logic equation. If there are no physical module relays and no "pseudo relay logic equations", the status of module relays cannot be viewed on the LCD.

11.10 NETWORK ZONE RECALLS & COMMANDS

11.10.1 ZONE RECALLS

Section 4.2.2 describes how to recall alarms, faults, isolates, and "others". For a network panel this will search all programmed devices on the network as well as the local panel. Network zones may also be recalled and searched as described in the following sections.

11.10.2 LOCAL OR NETWORK ZONE STATUS RECALL

To recall a specific zone's status, press:

where nnnnn is a network zone number. The first line of the LCD displays the zone number and any zone name programmed for that zone. Note that there may be a delay between requesting a network zone status and display of the true status, due to network delays. In this case, the panel will display default text, ie. just the network zone number, until the data is received. The display will update with the zone name and status when it is received. The second line displays the zone alarm type text for that zone, followed by its status.

Page 140: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-20 30 June 2016 Issue 1.08

LOCAL OR NETWORK ZONE STATUS RECALL (CONTINUED) The status consists of any of the following: Alarm - the zone is in alarm. Operate - the ACZ is operated. Fault - the zone is in fault. Isolate - the zone is isolated. Test - the zone is currently being tested. ARst - the zone is currently being auto reset tested. Normal - the zone is normal. To view other zones in the same condition press the NEXT or PREV keys.

11.10.3 NETWORK ZONE SEARCHES

The zone search functions allow an operator to search the local FIP and other network FIPs for zones meeting specified status criteria, e.g. in alarm. From the base display press:

Then press numeric key 1, 2, or 3 to search: 1: All SIDs. The local panel plus all programmed remote devices. 2: Local SID only Local panel only. 3: Select SID Prompts for the entry of a SID number - enter the SID number with the numeric keypad followed by ENTER, to start the search at a particular device on the network. A further set of options 1 to 6 will be given as follows: 1: All off normal 2: Alarms 3: Faults 4: Testing 5: Isolated 6: Status Press numeric keys 1 to 6 to select the desired option. When an option has been selected, the FIP searches for the first zone that meets the specified criteria. If there are no local zones that meet the criteria, the FIP then polls the other FIPs on the network to determine whether they have any zones that meet the criteria. Once a zone is found that meets the criteria specified, the LCD display reverts to a zone status display for that zone. When the NEXT or PREV key is pressed, the search continues for the next or previous zone, respectively, that meets the original search criteria. While the panel is determining the next or previous zone that meets the criteria the LCD displays "Searching".

Page 141: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-21

NETWORK ZONE SEARCHES (CONTINUED) If no zones matching the criteria are found, the LCD briefly displays a message saying so, and reverts to the base display. Note that due to network and remote panel delays a zone search command may take some time to complete, especially for larger systems with no zones that match the search criteria.

11.10.4 NETWORK ZONE ISOLATE OR DE-ISOLATE

To isolate or de-isolate a zone or range of zones on a network panel. If the network zone(s) entered are on the local panel, then the command is implemented locally as if the command had not used the network numbering format.

11.10.4.1 Operator Sequence - Single Network Zone

To isolate or de-isolate network zone n n n n n. From the base display, press:

The LCD will display the selected network zone, plus the options to isolate or de-isolate it. The status of the zone is retrieved from across the network. There may be a small delay before this is displayed. The display will also show options 1:Isolate and 2:De-isolate. Select the desired option. The LCD will display the network zone with a message saying "Sending Command". After a brief period the message should change to "Command Accepted". Refer to Section 11.7 for more detail on these and other possible LCD display messages.

11.10.4.2 Operator Sequence - Network Zone Range

To isolate a range of network zones, from the base display press:

The LCD will display the selected range of zones, i.e. zone n n n n n to zone m m m m m inclusive, plus the options to isolate or de-isolate the range.

Page 142: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-22 30 June 2016 Issue 1.08

Operator Sequence - Network Zone Range (Continued) Then press:

To isolate the range of zones, or

To de-isolate the range of zones.

A prompt is then given to select the type of zones to isolate/de-isolate. Press 1. to isolate/de-isolate only alarm zones. 2. to isolate/de-isolate only ancillary zones. 3. to isolate/de-isolate all zones. The LCD will display the network zone range with a message saying "Sending Command". After a brief period, the message should change to "Network Command Accepted". Refer to Section 11.7 for more details on these and other possible LCD display messages. Note that if the remote panel is unable to de-isolate all of the zones due to some having an alarm or fault status, then a exception message will be received indicating this. Refer to Section 11.7 for Exception Messages.

11.10.4.3 Notes

(i) The effect of the isolate/de-isolate command is dependent upon the remote FIP type, eg. which zones will be isolated/de-isolated, how a zone is affected by isolation/de-isolation, and so forth.

(ii) Refer to Section 7.2.4 for information on how an F3200 panel processes a

zone isolate/de-isolate command.

11.10.5 NETWORK ZONE RESET

11.10.5.1 Function

A Network Zone Reset command sends a Reset Zone(s) command to the remote FIP that has the zone(s). If the network zone(s) are on the local FIP, the command is implemented as a local zone(s) reset.

11.10.5.2 Operating Sequence - Single Network Zone

From the base display press:

to reset network zone number n n n n n. Press ACK to initiate the reset command. The LCD will display the network zone with a message saying "Sending Command". After a brief period the message should change to "Command Accepted". Refer to Section 11.7 for more details on these and other possible LCD display messages. If an exception occurs at the remote FIP, then an exception display may be received indicating the type of exception. Refer to Section 11.7 for Exception Messages.

Page 143: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-23

11.10.5.3 Operating Sequence - Network Zone Range

From the base display press:

to reset network zone numbers n n n n n to m m m m m. Press ACK to initiate the reset command. The LCD will display the network zones with a message saying "Sending Command". After a brief period the message should change to "Command Accepted". Refer to Section 11.7 for more details on these and other possible LCD display messages. If an exception occurs at the remote FIP, then an exception display may be received indicating the type of exception. IMPORTANT The range of zones entered must be limited to zones on a single

networked FIP, i.e. the range cannot encompass zones on more than one FIP. For an F3200 panel the zones must be all of the same type, i.e. all alarm zones or all relay zones, etc.

11.10.6 NETWORK ZONE TESTS

11.10.6.1 Function

To initiate a test of a zone at a remote FIP. The zone tests can: · Test the circuit inputs of the selected alarm zone; · Send test signals to the Brigade; · Operate test an ancillary control zone, relay or open collector output. · In-situ test an alarm zone, as if the test was initiated by an operator at the remote FIP. Tests at the remote FIP can also be aborted. If the network zone to be tested is on the local FIP, the test menus continue as if a local zone number had been entered. Refer to Section 7.1 for details on testing of local alarm zones, and Sections 8.5, 8.9 and 8.10 for testing of relays and open collectors.

Page 144: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-24 30 June 2016 Issue 1.08

11.10.6.2 Testing a Single Zone

SUGGESTION: To prevent mapped outputs from operating, "ISOLATE" the zone first. Refer Section 11.10.4.

From the base display, press:

Where nnnnn is the number of the network zone to be tested. If nnnnn is a network zone, a list of options is displayed, prompting for the type of test to be performed: Press 1: for alarm test (alarm zones) 2: for fault test (alarm zones) 3: for operate test (ancillary control zones, relays or open collector zones) 4: for In-Situ test (alarm zones) 5: to abort a test in progress (all zone types) Then press ACK to initiate the command. The command will be sent to the FIP with the selected zone on it. The LCD will display the network zone with a message saying "Sending Command". After a brief period the message should change to "Command Accepted", and the test will begin. Refer to Section 11.7 for a description of these and other possible LCD messages. If an exception occurs at the remote FIP, eg. a test failed, then an exception message may be received indicating the reason. Refer to Section 11.7 for a description of Exception Messages.

11.10.6.3 Notes

(i) The effect of the test command is dependent upon the receiving FIP type, eg. how the zones will be tested, how other zones/FIPs, etc, are affected by the test, and so forth.

(ii) A test on a remote zone may be aborted with an abort test command (option 5

from the menu described in Section 11.10.6.2). (iii) If the network zone number(s) entered correspond to local zone(s), the

LCD/keypad test menu continues as if local zone number(s) had been entered. Refer to Sections 7.5, 8.5, 8.9 and 8.10 for details on local tests.

Page 145: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-25

11.10.6.4 Testing a Range of Network Zones

To test a range of network zones, from the base display press:

The display will show the selected range of zones, i.e. zone nnnnn to zone mmmmm inclusive, plus a list of options as follows: 1: Alarm Test 2: Fault Test 3: Operate Test 4: In-Situ Test 5: Abort Test Press numeric key 1 to 5 to select the test and then press the ACK key to initiate the command. All zones in the range must be of the same type, i.e. all alarm zones, or all relay zones, etc. Alarm Test, Fault Test, and In-Situ Test, may be applied only to alarm zones. Operate Test may be applied to relay zones and open collector zones. The abort test command may be applied to any type of zone. Not all types of FIP support test commands for a range of zones.

Page 146: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-26 30 June 2016 Issue 1.08

11.11 POINT RECALLS & COMMANDS

If any devices on the network support analogue addressable points then they can be accessed from an F3200 panel or NDU (if so programmed). The status of a remote point can be recalled, and commands of isolate, de-isolate, point reset, reset tracking or reset history may be initiated. The common isolate LED on the operator display panel will flash at 2Hz if there are any isolated points on a remote SID. When the status of a remote SID is being displayed (by recall system faults - Sections 11.6.1 and 11.6.2) the text CmnPtl will be shown on Page 3 of the list if the remote SID has any isolated points. Refer to the Operator Manual for the remote panel to determine the meaning of point values and numbering.

11.11.1 POINT STATUS RECALL

There are four different status displays which may be selected for a point. These are: 1. Point Status; showing Normal, Fault, Alarm, Isol, Node Fault, Pre-Alarm,

Maintenance Alert.

2. Analogue values; showing CV, TV, HH, HL.

3. Analogue levels; showing current level (CL), pre-alarm sensitivity (PS), alarm sensitivity (AS).

4. Dirty Detectors; shows the % dirty value as a percentage plus the tracked value (TV), clean air max (CM), the upper tracking limit (UT) and the alarm sensitivity (AS) of the detector. To recall the status of a specific point, from the base display press:

If the panel does not have a “RELAY/POINT” key then the RELAY key should be used. Depending on the type of panel, either a menu of options will appear or the operator will be prompted to enter a point number. If a menu appears, select option 6: Network point, and then enter a point number. Entering a Point Number A point number is entered as three numeric values (SID.Responder.Point) with the

key being used to enter the separator. Press the ENTER key after entering 0, 1, 2 or 3 numeric values. If the ENTER key is pressed without entering any numeric values then the first point on the first SID programmed in the local SID list will be recalled. If a SID number is entered but no responder or point number, then the first point on that SID will be recalled (even if the SID does not appear in the local SID list).

Page 147: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Network Systems

Issue 1.08 30 June 2016 Page 11-27

POINT STATUS RECALL (CONTINUED) If a SID number and responder number are entered, but no point number, then the first point on the selected responder will be recalled. The name and number of the selected point will be shown on the display plus a menu of options. 1: Status 2: Analogue Values 3: Analogue levels 4:%Dirty Press numeric key 1, 2, 3 or 4 for the desired display or press NEXT or PREV keys to step to the next or previous point. When the status, analogue values or analogue levels or %Dirty of the point is/are being displayed, the

key may be pressed to bring up the menu of: 1: Status 2: Analogue Values 3: Analogue levels 4:%Dirty Or press numerical keys 1, 2, 3 or 4 to go directly to the relevant menu. At any of the four status displays, the

OR

keys may be pressed to initiate reset or isolate/de-isolate commands to the point. The NEXT or PREV keys may be used to step to the next point.

11.11.2 OFF-NORMAL POINT RECALL

Remote devices on the network may be searched for points with a particular off-normal condition. From the base display press:

A menu of options will then be shown. Press numeric key 1 to 6 to select as follows: 1. Status - this allows the status of a specific point to be displayed.

2. Off Normal - searches for points with any off-normal condition.

3. Alarms - searches for points in alarm.

4. Pre-Alarms - searches for points in pre-alarm.

5. Faults - searches for points in fault. 6. %Dirty – will search for points that have %Dirty greater than a percentage you will be asked to enter.

Page 148: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Network Systems

Page 11-28 30 June 2016 Issue 1.08

OFF-NORMAL POINT RECALL (CONTINUED) > More - this selects a second menu of options as follows:

1. Isolates - searches for isolated points. 2. Scan Fail - searches for scan failed points. 3. Maint Alerts - searches for points in maintenance alert. 4. Operated - searches for operated points. > More - selects the first menu again.

After the type of search has been selected a prompt is given for the SID.Responder.point to start the search from. If no SID, responder or point are entered then the search will start with the first point on the first SID. If a SID number and no responder/point numbers are entered, then the search starts with the first point on that SID. If a SID number and responder number are entered, then the search starts with the first point on that responder. If a SID, responder and point are all entered, then the search starts at that point.

11.11.3 POINT ISOLATE, DE-ISOLATE OR RESET

From the base display press:

If the panel does not have a “RELAY/POINT” key, then the RELAY key should be used. Depending on the type of panel, either a menu of options will appear or the operator will be immediately prompted to enter a point number. If a menu appears, select option 6: Network Point and then enter a point number. Three numeric values for SID.Responder.Point should then be entered, followed by either the:

OR

Isolate/De-Isolate The name and number of the selected point will be shown along with options of: 1: Isolate 2: De-isolate. Press numeric key 1 or 2 and the display will show “Sending Command” and after a brief period, “Command Accepted” or an error message. Reset The name and number of the selected point will be shown along with options of: 1: Point 2: History 3: Tracking Press numeric key 1, 2 or 3 and the display will show “Sending Command” and after a brief period, “Command Accepted” or an error message.

Page 149: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Appendix A

Issue 1.08 30 June 2016 Page A-1

APPENDIX A

COMPATIBLE ACTUATING DEVICES (DETECTORS)

The following detectors are compatible with the F3200 System. The maximum number of detectors per circuit is indicated by the columns 4mA and IS, for Standard and Intrinsically Safe applications respectively. For details on Intrinsically Safe applications refer to the F3200 Installation Manual LT0255.

DETECTORS CERTIFIED WITH F3200 FIP MAX NO.

TYPE DESCRIPTION BASE 4mA IS

614P PHOTOELECTRIC SMOKE DETECTOR 5B/M614 38

-

614I IONISATION SMOKE DETECTOR 5B/M614 40 -

614CH CARBON MONOXIDE & HEAT DETECTOR 5B/M614 40 -

614TA HEAT DETECTOR TYPE A 5B/M614 40 -

614TB HEAT DETECTOR TYPE B 5B/M614 40 -

614TC HEAT DETECTOR TYPE C 5B/M614 40 -

614TD HEAT DETECTOR TYPE D 5B/M614 40 -

MD614A HEAT DETECTOR TYPE A 5B/M614 40

-

MD614C HEAT DETECTOR TYPE C 5B/M614 40

-

MF614 IONISATION SMOKE DETECTOR 5B/M614 40

-

MR614 PHOTOELECTRIC SMOKE DETECTOR 5B/M614 40

-

MR614T PHOTOELECTRIC SMOKE DETECTOR 5B/M614 40*1 -

MU614 CO FIRE DETECTOR 5B/M614 40

-

T614A or T614A Mk2 HEAT DETECTOR TYPE A 5B/M614 40 -

T614B or T614B Mk2 HEAT DETECTOR TYPE B 5B/M614 40 -

T614C or T614C Mk2 HEAT DETECTOR TYPE C 5B/M614 40 -

T614D or T614D Mk2 HEAT DETECTOR TYPE D 5B/M614 40 -

MF301Ex x IONISATION SMOKE DETECTOR M300 40

40

MR301Ex x PHOTOELECTRIC SMOKE DETECTOR M300 40

40

MR301TEx x PHOTOELECTRIC SMOKE DETECTOR M300 40

40

MS302Ex x INFRA-RED FLAME DETECTOR M300 40

40

MD601Ex HEAT DETECTOR 5BEx 40 40

MDU601Ex HEAT & CO DETECTOR 5BEx 40 40

MF601Ex IONISATION SMOKE DETECTOR 5BEx 40 40

MR601TEx HPO PHOTOELECTRIC SMOKE DETECTOR 5BEx 36 36

MU601Ex CO DETECTOR 5BEx 40 40

601FEx FLAME DETECTOR 5BEx 6 6

S111 x INFRA-RED FLAME DETECTOR (IS) - 40 35

S121 x INFRA-RED FLAME DETECTOR (IS) - 40 35

S131 x INFRA-RED FLAME DETECTOR (IS) - 40 35

S231i+ x INFRA-RED FLAME DETECTOR (IS) - - 11

S231i+ INFRA-RED FLAME DETECTOR AND ZAU401 - 5 5

S231f+ INFRA-RED FLAME DETECTOR AND ZAU401 - 5 -

S261f+ INFRA-RED FLAME DETECTOR - 40 -

SU0600 15V MCP - 40 -

*1 For ambient temp < 30°C. Max Qty is 34 otherwise

Table I MINERVA/THORN/TYCO Detectors

Page 150: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Appendix A

Page A-2 30 June 2016 Issue 1.08

DETECTORS CERTIFIED WITH F3200 FIP MAX NO.

TYPE DESCRIPTION 4mA

DCA-B-60R HEAT DETECTOR TYPE A 40

DCA-B-90R HEAT DETECTOR TYPE C 40

DCD-A HEAT DETECTOR TYPE A WITH YBO – R/4A BASE 40

DCD-C HEAT DETECTOR TYPE C WITH YBO – R/4A BASE 40

DFE-60B (DFB-60B) HEAT DETECTOR TYPE B 40

DFE-90D (DFB-90B) HEAT DETECTOR TYPE D 40

DFJ-60B HEAT DETECTOR TYPE B WITH YBO – R/4A BASE 40

DFJ-90D HEAT DETECTOR TYPE D WITH YBO – R/4A BASE 40

SIJ-ASN IONISATION SMOKE DETECTOR WITH YBO – R/4A BASE 40

SLR-AS PHOTOELECTRIC SMOKE DETECTOR WITH YBO – R/4A BASE 40

SIF-AM IONISATION SMOKE DETECTOR 40

SIH-AM IONISATION SMOKE DETECTOR 40

SLK-A PHOTOELECTRIC SMOKE DETECTOR 40

SLG-AM PHOTOELECTRIC SMOKE DETECTOR 40

HF-24A ULTRAVIOLET FLAME DETECTOR 18

WITH YBC-RL/4AH4, YBF-RL/4AH4 OR YBF-RL/4AH4M BASES

Table II HOCHIKI Detector Range

DETECTORS CERTIFIED WITH F3200 FIP

MAX NO.

TYPE DESCRIPTION BASE 4mA IS

B111B # BEAM SMOKE DETECTOR (NOTE 7) - 40 0

B21B BEAM SMOKE DETECTOR - 1 0

C23B *& IONISATION SMOKE DETECTOR Z23 40 0

C23BEx *x IONISATION SMOKE DETECTOR (IS) Z23 40 35

C24B IONISATION SMOKE DETECTOR *1 40 0

C29B IONISATION SMOKE DETECTOR *1 40 0

C29BEX x IONISATION SMOKE DETECTOR (IS) Z94C 40 40

DL01191A BEAM DETECTOR - 1 -

FW81B HEAT DETECTOR CABLE FW68, FW105 (IS) - 1000m 1000m

P24B PHOTOELECTRIC SMOKE DETECTOR *1 40 0

P29B PHOTOELECTRIC SMOKE DETECTOR *1 36 0

P61B * PHOTOELECTRIC SMOKE DETECTOR (REV J) - 40 0

P76B PHOTOELECTRIC SMOKE DETECTOR NON-LATCHING

Z72 10 0

P136 DUCT SAMPLING UNIT - 8 -

R23B & INFRARED FLAME DETECTOR - 36 0

R24B DUAL SPECTRUM INFRARED FLAME DETECTOR

- 8 0

R24BEX +x DUAL SPECTRUM INFRARED FLAME DETECTOR (IS)

- 8 7

T54B +x# PROBE TYPE E HEAT DETECTOR (IS OR FLAMEPROOF)

- 40 40

T56B x HEAT DETECTOR TYPES A, B, C, D (IS WITH Z55, Z56N or Z500N BASE)

*1 40 40

V41B +x# ULTRAVIOLET FLAME DETECTOR - 40 40

V42B +x# ULTRAVIOLET FLAME DETECTOR SLAVE - N/A N/A

V44B +x# ULTRAVIOLET FLAME DETECTOR - 40 40

- SHORT CIRCUIT DEVICE - 40 40

*1 = Z54, Z54 MK2, Z55B, Z56, Z500 BASES

Table III OLSEN Detector Range

Page 151: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

Document No: LT0250 F3200 AS4428.1 Operator's Manual Appendix A

Issue 1.08 30 June 2016 Page A-3

DETECTORS CERTIFIED WITH F3200 FIP

MAX NO.

TYPE DESCRIPTION 4mA

SERIES 60 APOLLO HEAT DETECTOR TYPES A, B, C, D 40

SERIES 60 APOLLO PHOTOELECTRIC SMOKE DETECTOR 40

SERIES 60 APOLLO IONISATION SMOKE DETECTOR 40

ALL WITH 45681-200 BASES

MK VIII * FLAMEGUARD HEAT DETECTOR TYPE A 22

MK VIII * FLAMEGUARD HEAT DETECTOR TYPE C 11

MK5, MK6 * INTERTEC HEAT DETECTOR TYPES A, B, C, D 22

(NOTE 9) DETECTOR HAS INTEGRAL LED & TERMINALS

885WP-B ^@ WEATHERPROOF HEAT DETECTOR TYPE B 40

Table IV OTHER Detectors

SIMPLEX RANGE MAX NUMBER

TYPE DESCRIPTION Iq uA WITH EOL

4098-9618EA Type A Heat Detector 100 40

4098-9619EA Type B Heat Detector 100 40

4098-9621EA Type D Heat Detector 100 40

4098-9601EA Photoelectric Smoke Detector 100 40

4098-9603EA Ionisation Smoke Detector 100 40

4098-9612 Fixed Temperature Heat Detector 100 40

4098-9613 Fixed Temperature + Rate of Rise Heat Detector 100 40

4098-9614 Fixed Temperature Heat Detector 100 40

4098-9615 Fixed Temperature + Rate of Rise Heat Detector 100 40

All with Simplex 4098-9788EA base except 4098-9612 to 4098-9615 with 4098-9788 base.

Table V SIMPLEX Detectors

Page 152: FIRE FIGHTER’S GUIDEF3200 AS4428.1 Operator's Manual Document No: LT0250 Page ii 30 June 2016 Issue 1.08 INSTALLATION DETAILS For your reference please complete …

F3200 AS4428.1 Operator's Manual Document No: LT0250 Appendix A

Page A-4 30 June 2016 Issue 1.08

ACTUATING DEVICE COMPATIBILITY NOTES

1) The maximum number of detectors per AZC allowed by the standard is 40. 2) Those detectors shown in brackets have the same characteristics as the

current models. 3) Detectors indicated by a "x" may be used in INTRINSICALLY SAFE AREAS in

conjunction with approved and compatible, intrinsically safe adaptors. The number allowed in a particular circuit may be less than the maximum shown. Refer to the Installation Manual for details.

V41/42/44B detectors have flameproof enclosures. 4) Detectors indicated by a "+", which are used in HOSTILE CLIMATIC

ENVIRONMENTS, may be directly connected to the panel, if they are not required to be intrinsically safe.

5) Detectors indicated by a "*", are not current models and should not be used for

new installations. 6) Detectors indicated by an "&", normally use an incandescent lamp which will

have a low intensity when used in mode 1. The lamp can be replaced with an LED kit - contact supplier. 7) The B111B beam and V41B/V42B/V44B flame detectors require power from

the fused +24 VDC supply. 8) Hard Contact devices are indicated by a “#”. Where an AZC has only hard

contact devices circuit resistance must be less than 150 Ohms (i.e. reduce line voltage to less than 2.5V), to distinguish instant alarms (B1) from alarms (B2) (e.g. to override AVF).

9) The Intertec detectors require a series diode to be fitted for compatibility.

Consult manufacturer for detail. 10) The Olsen FW81B code for fire wire has been replaced by FW followed by the

temperature rating in °C, eg. FW68, FW105. Only FW68 is currently approved and listed.

11) Detectors indicated by a “^” have not been SSL/CSIRO accessed for compatibility.

12) Detectors indicated by a “@” cannot have their remote indicator outputs wired in common with Tyco 614 series or the Minerva M614 series (and most other Tyco/Olsen detectors).