final tech. specification

Upload: mahnooranjum

Post on 06-Apr-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/3/2019 Final Tech. Specification

    1/12

    1. STEEL REINFORCEMENT

    1.1 a. This section shall apply to round bars 19 mm or smaller in

    diameter with strength of SR 235 to SR 295 and deformed bars

    D41 or smaller in nominal diameter with strength of SD 295 to SD390. Fabrication and placement of reinforcement of types,

    diameters and strength levels not covered by this section shall beas specified in the Special Provisions.

    b. The bar types, diameters scope of applications, as well as the

    number, shapes and dimensions of bars shall be as specified in theSpecial Provisions. All longitudinal bars shall be deformed bars.

    c. The types and diameters of weld mesh and reinforcement gridshall be in accordance with the Special Provision.

    d. Splicing of reinforcement shall be lap slices, gas pressure

    welding splices or special splices and shall be in accordance withthe Special Provisions. Unless specified in the Special Provisions,

    the Contractor shall determine the method of splicing subject to

    approval by the Architect/Engineer. Deformed bars with adiameter D35 or larger shall as a rule have no lap splices.

    e. Reinforcement bars shall site-assembled or preassembled andshall be placed in accordance with the Special Provisions. Unless

    specified in the Special Provisions, the Contractor shall determine

    the placement method subject to approval by the

    Architect/Engineer.

    f. The Contractor shall formulate a construction plan and shop

    drawings based on the Special Provisions and submit them to theArchitect/Engineer for approval.

    GENERAL

    FABRICATION AND

    PLACEMENT OF

    REINFORCEMENT.

    1.2 a. Reinforcing bars to be used shall conform to JIS G 3112 (SteelBars for Reinforced Concrete Structures)

    b. Weld mesh and reinforcement grid shall conform to JIS G3551 (Weld Mesh and Reinforcement Grid).

    REINFORCINGBARS AND WELD

    MESH

    1.3 a. Deleteriously bent or defective bars shall not be used.

    b. Reinforcing bars in coils shall be used after passing through a

    straightener. Bars shall not be damaged during the straightening

    process.

    FABRICATION OFREINFORCEMENT

    1 of 12

  • 8/3/2019 Final Tech. Specification

    2/12

    2. CONCRETE PLAIN AND REINFORCED

    2.1

    2.2

    2.3

    2.4

    2.5

    2.6

    This specification shall apply to cast-in-place reinforce concrete work,

    including reinforced work for such structure as steel-framed reinforcement

    concrete structures, and unreinforced concrete work.

    Concrete work shall conform to all requirements of building works with

    Japanese Architectural Standard specification (JASS 5, 2004).

    Concrete shall be composed of Portland cement, water fine and coarse

    aggregate and any admixtures as and when specified.

    The concrete mixtures will be designed by the engineer who will determine

    the required quality of the concrete for the structures covered by these

    specifications. The desired strengths of concrete for various parts of theproject have been shown on the drawing.

    Cement shall conform to the Standard specifications, as provided here under;

    All cement shall be ordinary Portland Cement confirming to the requirementsof JIS R 5210 (Portland Cement).

    Aggregates for normal concrete shall conform standard specification to JASS5 Section 4, (Concrete Material).

    The maximum size of course aggregate shall be 25 mm, 20 mm or 15mm.

    Aggregates for reinforced concrete should comply with JISS 5, 2004. The maximum

    size of course aggregate is given in following Table.

    Table 2.1 Maximum size of Course Aggregate Classified by Member Group (mm)

    Member Gravel

    Crushed stone,

    blast-furnace slag

    coarse aggregate

    Recycled

    aggregate

    Columns,

    beans, floor

    slabs, walls

    20,25 20 20,25

    Foundations 20,25,40 20,25,40 20,25

    Normal-weight aggregate shall be in accordance with (1) through (3) below:

    Gravel and sand shall possess the qualities specified in Tables 2.1 and 2.2.

    However, gravel and sand with an oven-dry density of 2.4g/cm3 or larger and

    a water absorption of 4.0% or less and sand with a chloride content between

    0.04% and 0.1% may be used in accordance with the Special Provisions,provided that the concrete containing such aggregates is proven to possess

    the specified qualities.

    SCOPE

    SPECIFICATIONS

    COMPOSITION

    PORTLAND

    CEMENT

    AGGREGATES

    GRADING

    2 of 12

  • 8/3/2019 Final Tech. Specification

    3/12

    2.7

    Table 2.2 Quality of Gravel and Sand

    Type

    Oven-dry

    specific

    density

    (g/cm3)

    Water

    absorption

    (%)

    Clay

    lumps

    (%)

    Volume

    lost by

    wash test

    (%)

    Organic

    impurities

    Chlorides

    (NaCl)

    equivalent

    (%)

    Gravel 2.5 3.0 0.2 1.0 - -

    Sand 2.5 3.5 1.0 3.0

    Lighter in

    color than

    standardsolution

    or sample

    color

    0.04(1)

    Note: (1) 0.02 (%) for the long-term planned service life class.

    Table 2.3 Standard Grading of Gravel and SandPercentage passing each sieve, by mass (%)

    Nominal Sievesize (mm)

    50 40 30 25 20 15 10 5 2.5 1.2 0.6 0.3 0.15

    Gravel(Max.

    size,mm)

    40mm 10095-100

    - -35-70

    -10-30

    0-5 - - - - -

    25mm - - 100

    95-

    10

    0

    - 30-

    70

    - 0-

    10

    0-5 - -- - -

    20mm - - - 100

    90-

    100

    - 20-

    55

    0-

    10

    0-5 - - - -

    Sand- - - - - - 100 90-

    100

    80-

    10

    0

    50-

    90

    25-

    65

    10-

    35

    2-

    10(1)

    Note: (1) When using com bin at io ns of crushed sand and slag sa nd, the

    percentage passing a 0.15-mm sieve shall be 15%.(2) Crushed stone and crushed sand shall conform to JIS A 5005

    (Crushed Stone and Crushed Sand for Concrete), and slag

    aggregate shall conform to JIS A 5011 (Slag Aggregate forConcrete).

    (3) Recycled aggregates shall conform to Table 4.2 and 4.3, and

    shall contain not more than 1.0% in weight of the grains thatfloat in the liquid of the density of 1.95(g/cm3).

    (4) When using combinations of different types of aggregates, each

    aggregate shall meet the quality requirements before blending

    specified in (1), (2) or (3) above, respectively. However, thechloride content and grading shall meet the requirements of

    Tables 2.2 and 2.3 after blending.

    d. When chemical or physical unsoundness of aggregate is suspected,

    the use of it and method of use shall be subject to approval by the

    Architect/Engineer.e. Aggregates for concrete portions requiring exceptionally high fire

    resistance shall be in accordance with the Special Provisions.

    f. Lightweight aggregates shall be in accordance with Section 16

    Lightweight Concrete.

    a. Specified mixture proportions of concrete shall be determined to provide

    the required workability, strength, Youngs modulus, durability.

    MIX

    PROPORTION

    3 of 12

  • 8/3/2019 Final Tech. Specification

    4/12

    2.8

    b. Specified mixture proportions shall as a rule is established on the basis oftrail mixtures. However, when JIS A 5308 conformed ready-mixed

    concrete is to be employed, the trail mixing process may be omitted.

    c. The age for strength control of concrete in structure shall be within 91days and as specified in the Special Provisions. Unless specified in the

    Special Provisions, it shall be 28 days.

    d. The curing method of control specimens for the strength of concrete in

    structure shall be in accordance with the Special Provisions. Unless specified

    in the Special Provisions, the method shall be water curing under fieldconditions or standard curing when the designated age for strength control is

    28 days and seal curing under field conditions when the designated age is

    older than 28 days.

    a. Proportioning strength shall be expressed as the 28-days old compressive

    strength of standard-cured specimens, and shall be in accordance with (1) or(2) below depending on the designated age for strength control of concrete in

    structure.

    (1) Where the age for strength control of concrete in structure is 28 days, the

    proportioning strength shall be the larger of the values calculated by Eqs.

    (5.1) and (5.2).

    F = Fq + T + 1.73 (N/mm2) (5.1)

    F = 0.85 (Fq + T) = 3 (N/mm2) (5.2)

    (2) Where the age for strength control of concrete in structure is n days(28

  • 8/3/2019 Final Tech. Specification

    5/12

    2.9

    respectively:

    (1) T shall be determined using Table 5.1 according to the type of

    cement and anticipated mean air temperature range. Where cement

    other than those indicated in Table 5.1 is employed, T shall be asspecified in the Special Provisions.

    (2) Tn shall be determined using Table 5.2 according to the type ofcement and anticipated mean air temperature range. Where cement

    other than those indicated in table 5.2 is employed, Tn shall be as

    specified in the Special Provisions.

    Table 5.1 Standard Values of Correction Value T for concrete Strength

    Type of cementRange of anticipated mean air temperature, t,

    during 28 days after concrete placement (C)

    Normal Portland

    Cement 16 8 t < 16 3 t < 8

    Correction value T

    for concrete strengthin terms of air

    temperature

    (N/mm2).

    0 3 6

    Table 5.2 Standard Values of Correction Value Tn for Concrete Strength

    Type of cement

    Age n

    (days)

    Range of anticipated mean air

    temperature, t, during 28 days after

    concrete placement

    Normal Portland

    cement

    42 8 4 t < 8 2 t < 4

    56 4 2 t < 4 -

    91 2 - -

    Correction value Tn for

    concrete strength in terms ofair temperature (N/mm2)

    0 3 6

    c. The standard deviation of the strength of concrete employed, shall be

    established based on records at the ready-mixed concrete plant. Where no

    record is available, it shall be the larger of 2.5 N/mm2 and 0.1 Fq.

    a. The workability of concrete shall be such that the concrete can be placed

    densely in all corners of forms and around reinforcing bars with minimum

    bleeding and segregation under the conditions of portions to be placed and

    methods of deposition compaction to be employed.

    b. The slump of concrete with a quality standard strength of 33 N/mm2 orhigher shall be 21 cm at the highest. It shall be 18 cm at the highest for

    concrete with a quality standard strength of less than 33 N/mm2. However,

    the slump of lightweight concrete, plasticized concrete, high fluidityconcrete, high strength concrete, mass concrete and concrete placed

    underwater shall be in accordance with Sections 16, 17, 18, 19, 22 and 25,

    respectively.

    WORKABILITY

    AND SLUMP

    5 of 12

  • 8/3/2019 Final Tech. Specification

    6/12

    2.10

    2.11

    2.12

    2.13

    a. The maximum water-cement ratio shall be as specified in Table 5.3. For

    cements other than those indicated in Table 5.3, the maximum water-

    cement ratio shall be as specified in the Special Provisions.

    Table 5.3 Maximum water-cement Ratios

    Type of cement Max. Water-cement ratio (%)Portland cement (1)

    Type A Portland blast-furnace slag cement

    Type A Portland fly-ash cement

    Type A Portland pozzolan cement

    65

    Type B Portland blast-furnace slag cement

    Type B Portland fly-ash cement

    Type B Portland pozzolan cement

    60

    b. The water-cement ratio shall be a value necessary for attaining the

    proportioning strength but not more than the maximum value specified

    in a above.

    a. The cement content shall be not less than the values calculated fromthe water-cement ratio in 5.4 and unit water content in 5.5.

    b. The cement content shall be at least 270 kg/m3.

    The air content of concrete containing an air-entraining admixture, air-

    entraining and water-reducing admixture or air-entraining and high-rangewater-reducing admixture shall be as specified in the Special Provisions.

    Unless specified in the Special Provisions, it shall be 4.5%.

    a. In placing, concrete shall be deposited as near as practicable to its

    final position. Care shall be exercised to prevent concrete from stainingsurfaces of reinforcement, formwork and preset tile that are out of the

    concreting section being placed.

    b. At construction joints, concrete shall be placed and compacted withcare to leave no unsound portion near the joints due to inadequate

    compaction or concentration of bleeding water.

    c. Concrete shall be placed continuously to achieve monolithic concrete

    in a section for which one sequence of concrete placing is planned.

    d. The rate of placing shall be in the range of allowing efficient

    compaction depending on the workability of concrete and construction

    conditions of the relevant portions.

    e. The free-fall height in placing concrete shall be limited to a range in

    WATER-CEMENT

    RATIO

    CEMENTCONTENT

    AIR CONTENT

    PLACING

    6 of 12

  • 8/3/2019 Final Tech. Specification

    7/12

    2.14

    2.15

    2.16

    which no segregation of concrete occurs.

    f. The time limit for intervals between placing operations shall bedetermined in the range of causing no cold joints, subject to approval by

    the Architect/Engineer.

    g. Displacement of steel bars, forms. Spacers or steel bar supports shallbe corrected before placing concrete to ensure proper cover depth.

    a. Concrete shall be compacted around reinforcement and embedded metals

    and into corners of the forms so that dense concrete can be obtained.

    b. Internal vibrators, form vibrators or tamping rods shall be used for

    compaction. Other tools shall be used as auxiliary equipment where

    necessary.

    c. Internal vibrators shall be used on each fresh layer of concrete and

    inserted vertically to a depth so that the tips of vibrators penetrate the top

    level of the previously placed layer of concrete. The distance betweeninsertions of vibrators shall be not more than 60 cm, and vibrating shall be

    continued until cement paste rises to the concrete surface.

    d. Form vibrators shall be vibrated systematically according to the depth and

    rate of concrete placing so that dense concrete can be achieved.

    Beginning immediately after placement, concrete shall be protected from

    rapid drying excessively hot or cold temperatures, rapid temperature changes,

    vibration and external forces for the period necessary for sufficient hydration

    of the cement and hardening of he concrete.

    Concrete after placement shall be moist-cured by being covered withsheathing with low water permeability, curing mats or watertight sheeting, or

    by water spraying, fogging, or application of a curing compound. The curing

    period shall be in accordance with Table 8.1 according to planned service lifeclasses.

    Table 8.1 Moist Curing Period

    Planned service life classCement type

    General/Standard Long-term

    High-early-strength Portland cement 3 days 5 days

    Normal Portland cement 5 days 7 days

    Other cements 7 days 10 days

    For concrete members 18 cm or more in thickness made using high-early

    strength Portland cement or normal Portland cement, moist curing may beterminated even before the completion of the moist curing period specified in

    a above, if it is confirmed that the compressive strength of the concrete*

    meets the requirements of Table 8.2.

    COMPACTION

    CURING

    MOIST CURING

    7 of 12

  • 8/3/2019 Final Tech. Specification

    8/12

    2.17

    [Note] * This should be carried out in accordance with JASS 5 T-603(Method of Test for Compressive Strength for Estimating Strength of

    Concrete in Structure). The curing method should be the same as that for

    control specimens for concrete in structure.

    Table 8.2 Compressive Strength of Concrete Required for Terminating Moist Curing(N/mm

    2)

    Planned service life classCement type

    General/Standard Long-term

    High-early-strength Portland cement

    Normal Portland cement 10 15

    a. When sheathing is to be removed after the period of retaining

    sheathing specified in 12.9 but before the period specified in a above or

    before the concrete attains the compressive strength specified in babove, the exposed surfaces of concrete shall be kept moist by spraying

    water, fogging or other appropriate methods until the end of the specified

    period or until the specified compressive strength is attained.

    b. Under high air temperature, strong wind or direct sunlight, curing

    shall be controlled to avoid rapid drying of the concrete surfaces.

    a. The design cover depth shall not be less than the values given in

    Table 10.1 and shall be specified in the Design Documents or Special

    Provisions. Unless specified in the Special Provisions or DesignDocuments, the minimum cover depth shall be the values given in Table

    10.1.

    Table 10.1 Standard Values of Design Cover Depth

    PortionDesign Cover Depth

    With finishing(1) Without finishing

    Portions not

    in contact

    with theground

    Floor slabs, roof

    slabs, nonbearing

    walls

    Indoor 30 30

    Outdoor 30 40

    Columns, beam,

    bearing walls

    Indoor 40 40

    Outdoor 40 50

    Retaining walls 50 50

    Portion incontact with

    the ground

    Columns, beams, floor slabs,walls, risers of continuous

    footing

    50(2)

    Foundations, retaining walls 70(2)

    Note: (1) This refers to finishing effective in increasing durability.(2) For lightweight concrete, these values shall be increased by 10 mm.

    b. Where effective measures against reinforcement corrosion are taken, thecover depth and corrosion-inhibiting treatment for diagonal bars placed at

    corners and openings of buildings to control cracking shall be as specified

    in the Special Provisions or Design documents. Unless specified in theSpecial Provisions or Design Documents, the design cover depth shall be

    as specified in Table 10.1.

    DESIGN COVERDEPTH

    8 of 12

  • 8/3/2019 Final Tech. Specification

    9/12

    9 of 12

  • 8/3/2019 Final Tech. Specification

    10/12

    3. STRUCTURAL STEEL (JASS 6 1993)

    3.1 This Section covers general requirements for structural steel

    work, fabrication, methods and precautions for erection ofsteel structures and other miscellaneous general requirements

    to construction work in which structural steel is used for main

    structural members of buildings or structure. This Section alsocovers furnishing, fabricating and installing and painting

    metal not otherwise specified under other Sections of the

    Specifications.

    SCOPE

    3.2. The applicable requirements of this Section shall apply to all

    Structural Steel Work under this specification.

    GENERAL

    3.3. Structural steel shall conform to the requirement of

    JAPANESE ARCHITECTURAL STANDARDS

    SPECIFICATION (JASS 6 1993), Structural steelspecification for building constructions. The different shapes

    of angles and their dimensions are provided in JASS 6 1993

    Code, but for reference a typical detail provide in AnnexureA.

    STRUCTURAL

    STEEL

    3.4 Except as otherwise shown on the Drawings, welding material

    shall conform the standard specification for class of basemetal sizes and building conditions for standard shown in

    table.

    Standard No. Title

    JIS Z 3211

    JIS Z 3212JIS Z 3214JIS Z 3351

    JIS Z 3352

    JIS Z 3312

    JIS Z 3315

    JIS Z 3313

    Covered electrodes for mild steel

    Covered electrodes for high strength steelCovered electrodes for atmospheric corrosion resisting steelSubmerged are welding fluxes for carbon steel and low alloy

    steelSubmerged are welding fluxes for carbon steel and high

    strength steelMAG welding solid wires for mild steel and high strengthsteelSolid wire for CO2 gas shielded are welding of atmospheric

    corrosion resisting steelAre welding flux cored wires for mild steel and high strengthsteel

    WELDING

    MATERIAL

    3.4.1 Welding rod for manual welding of structural carbon steels,E-60 or E-70 series electrodes shall be used. For High-

    strength low alloy steels E-70 series Low Hydrogen

    Electrodes shall be used.

    STRUCTURALWELDING ROD

    3.5. Except as otherwise indicated on the Drawings or specified

    herein, bolts and nuts shall conform the requirements of AIJStructure Steel Standard Specifications for Carbon Steel

    Externally and Internally Threaded Standard Fasteners. Bolts

    BOLTS, NUTS AND

    WASHERS

    10 of 12

  • 8/3/2019 Final Tech. Specification

    11/12

    shall be Grade A for general application, with square orhexagon heads. Nuts shall be 4T of JIS B 1180 and 4T of JIS

    B 1181 of similar material, finish class of fit and thread series

    as their companion bolts and shall be washer-faced except asotherwise indicated or specified. Anchor bolts shall be of

    diameter as shown hooked or eyed as required and provided

    with sleeve nuts and double nuts as shown. Screw anchordevices for setting in concrete to permit withdrawal of anchor

    bolts after concrete have set.

    3.5.1 The Building Standards Law prescribes that hexagon boltfastening cannot be generally applied except for structures

    with maximum eaves height of not more than 9m, span of not

    more than 13m and total floor area of not more than 3,000m2.Therefore, hexagon bolt fastening is limited to relatively

    insignificant structures.

    HEXAGON BOLT

    3.6 The angles, channels or girders being used shall conform to

    the above mentioned specifications. All sections to beused in fabrication shall be of correct cut-lengths, not to produce any extra tension in the members due to

    shortening or increase in cut-lengths, more than exactly

    required.

    FABRICATING

    3.7 i) This part concerns anticorrosive paint on steel frames to

    give them long-term rust resistance. The classification and

    scope of paint shall comply with the special notes.

    ii) Temporary anticorrosive paint to prevent stains due to rust

    general during the construction period shall comply with thespecial notes.

    ANTICORROSIVE

    PAINT

    3.8 The work covered by this Clause includes furnishing and

    installing miscellaneous structural steel work includingthe following:

    1. Steel stairs

    2. Steel ladders

    3. Fixed or removable railing

    4. Embedded steel anchors/fasteners.

    5. Miscellaneous work required in

    structural steel.

    MISCELLANEOUS

    METAL

    3.9 Structural steel trusses, stairs, door frames and windows etc

    complete with stringers, grating treads and landings,structural steel supports, handrail supports and other

    fastenings shall be furnished and installed in accordance

    STEEL TRUSSES,

    STAIRS, DOORFRAMES AND

    WINDOWS ETC

    11 of 12

  • 8/3/2019 Final Tech. Specification

    12/12

    with the details, sizes and dimensions, and at the locationsshown on the Drawings.

    3.9.1 All material for steel trusses, stairs, door frames and windowsetc, except as otherwise shown, shall be steel conforming

    to JASS 6 (1993) Specifications for Structural Steel work

    for building constructions.

    MATERIAL

    3.9.2 All Steel fabrications shall be in a first class workmanlike

    manner. The units shall be shop assembled and fabricated

    in sub-assemblies for convenient installation. Fieldconnections shall be made as indicated on the Drawings.

    INSTALLATION

    3.10 The embedded metalwork to be furnished and installed underthis Clause shall include anchor bolts, anchor bars, and

    other metal work required for installation. The embedded

    metal work shall be of materials and standards specifiedon the Drawings. Before placing concrete care shall be

    taken to determine that all embedded items are firmly andsecurely fastened.

    EMBEDDEDMETALWORK

    12 of 12