final article chai and kunnath
TRANSCRIPT
-
8/11/2019 Final Article Chai and Kunnath
1/12
-
8/11/2019 Final Article Chai and Kunnath
2/12
Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063 1053
minimum wall thickness requirement is reproduced here; for
walls with two layers of vertical reinforcement, it needs to
satisfy the following inequality:
twkm ( +2)(Ar+2)lw
1700
(1)
wherekm= 1.0, unless it can be shown thatkm=
ln
(0.25+0.055Ar)lw0.1 (3)
where is the displacement ductility factor, Ar is the
aspect ratio of the wall, i.e. total wall height divided by wall
length,ln is the clear vertical distance between floors, lw is
the length of the wall, l is the vertical reinforcement ratio,
fy is the yield strength of the reinforcement, and fc is the
concrete compressive strength. Although not immediatelyapparent, the minimum wall thickness required by [4] is
quite different from that required by [10]. For example,
for a 10-story wall with a displacement ductility factor of = 4, aspect ratio of Ar = 6, vertical reinforcementratio ofl = 0.02, concrete compressive strength of fc=34.5 MPa, and steel yield strength of fy = 414 MPa,the [4] minimum wall thickness is 9.7% of the floor-
to-floor (story) height, where the unsupported height has
been assumed to be 90% of the story height, i.e. ln =0.9hs . This minimum wall thickness is significantly larger
than that required by [10], which is 5.6% of the story
height. In view of the significant difference between the
two codes, an assessment of the minimum wall thicknesses
and their comparison under different design parameters is
warranted.
2. Stability of structural walls
The phenomenon of inelastic buckling of structural
walls under reversed cyclic loading is admittedly complex;
for tractable solutions, appropriate simplifications must be
made. A basic understanding of the inelastic buckling of
walls may be provided by a cyclic axially loaded reinforced
concrete column, the response of which is assumed to berepresentative of the high tension/compression region of
the wall. Although the effect of strain gradient across the
wall is not included, the idealization is nonetheless useful
in identifying critical parameters governing the buckling
mechanism.
The reversed cyclic response of an axially loaded
reinforced concrete column is demonstrated using the
following test data from [2]. The photographs in Fig. 1(a)
and (b) show the condition of the test column after
being loaded to different tensile strain amplitudes. The test
column, which had a rectangular cross-section of 100 mm 200 mm, was reinforced with six No. 3 bars (db
=9.5 mm)
providing a longitudinal reinforcement ratio of 2.1%. The
length of the test column wasL o=1500 mm, correspondingto a length-to-width ratio of 14.75. Transverse ties were
provided at close spacing of six times the longitudinal bar
diameter simulating a well-confined condition in the end
region of a ductile wall. The close spacing of the transverse
reinforcement was also intended to prevent local buckling ofthe longitudinal reinforcement.
Fig. 1(c) shows the hysteretic response of the test column
under axial tension/compression cycles. The nominal axial
strain a , plotted on the y-axis of both plots, corresponds
to the average strain measured over several cracks in the
middle portion of the column, while the normalized out-of-
plane displacement, plotted on thex -axis of the left hand plot
ofFig. 1(c), corresponds to the out-of-plane displacement
measured at mid-height of the column divided by the
width of the column tw. The x -axis on the right hand
plot ofFig. 1(c) corresponds to the applied axial force
on the column. The loading history consisted of a tensile
strain cycle followed by a compression cycle with a targetcompressive strain amplitude that was about 1/7 of the
tensile strain amplitude. The axial tensile strains imposed on
the test column, namelya= 0.0078, 0.0108, 0.0133and0.0161, are shown in both plots ofFig. 1(c). It canbe seen that, for axial tensile strain less than or equal to
0.0133, the test column remained stable with relativelysmall out-of-plane displacement of /tw 0.05. For anaxial tensile strain to0.0161, however, the out-of-planedisplacement of the column upon subsequent compression
increased significantly, causing the column to buckle. The
stable condition following a tensile strain ofa= 0.0133is shown inFig. 1(a), in contrast to the buckled column aftera tensile strain of a = 0.0161 in Fig. 1(b). Althoughonly one test specimen is provided, Fig. 1 nonetheless
demonstrates the importance of the tensile strain cycle for
the cyclic stability of structural walls. Further test results are
given in [2].
3. Methodology and basic equations
Since the current use of structural walls in buildings
often involves different height and length, amount of
reinforcement, wall-to-floor area ratio etc., an assessment
of the minimum wall thickness with these parameters isinstructive. The methodology and basic equations governing
the minimum wall thickness are first discussed, and this is
followed by a presentation of results for various parameters
including ground motions that are representative of current
design earthquakes.
3.1. Elastic response acceleration spectrum
The required thickness of structural walls depends on
the ductility demand, which is a function of the ratio of
wall lateral strength to elastic force demand. In this study,
the elastic force demand uses a NewmarkHall type elastic
-
8/11/2019 Final Article Chai and Kunnath
3/12
1054 Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063
(a) Stable column up to tensile strain of 1.33%. (b) Buckled column after tensile strain
of 1.61%.
(c) Hysteretic response of test column.
Fig. 1. Stability of a reinforced concrete column when subjected to large amplitude reversed cyclic tensile/compression loading.
response acceleration spectrum, which was used earlier byChai et al. [3], and is shown inFig. 2. The elastic response
acceleration, as characterized in terms of an amplification
factor a , is specified in three period regions:
a=
1.0+2.5(ca1)T/ Tcca2cv ( xg)max/[( xg)maxT]
for
0< T 0.4Tc0.4Tc < T TcTc < T
(4)
where the coefficient ca is the ratio of spectral elastic
response acceleration to peak ground acceleration in the
acceleration-controlled region, and the coefficient cv is the
ratio of spectral elastic response velocity to peak groundvelocity in the velocity-controlledregion. On the basis of the
average values obtained by Vidic et al. [11], coefficients caandcv are taken as 2.5 and 2.0 respectively. The term Tc in
Eq.(4) corresponds to the characteristic period of the ground
motion, which is given by Vidic et al. [11]:
Tc=2cv
ca
( xg)max( xg)max
(5)
where the ratio( xg)max/( xg)max corresponds to the inverseof the peak ground acceleration to peak ground velocity
(referred to asa/vratio herein), which has been shown to be
-
8/11/2019 Final Article Chai and Kunnath
4/12
Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063 1055
Fig. 2. Amplification factor for elastic response acceleration.
a useful parameter for characterizing the frequency contentas well as the duration of the earthquake ground motion [9].
For rock or firm soil sites located near the source of the
earthquake, the ground motion tends to be characterized by
a high a/v ratio with a relatively short duration, whereas
for soft sites at moderate distance from the source, the
ground motion tends to be characterized by a low a /v ratio
with an increased duration. The elastic response acceleration
amplification factor inFig. 2corresponds to foura/vratios,
i.e. ultrahigh, high, normal and low a/v ratios. Note that
the shape of the elastic response acceleration spectrum
changes with thea/vratio as the period range for maximum
response shifts to the longer period region for decreasinga/vratio.
3.2. Fundamental period
The use of elastic response acceleration spectrum for
elastic force demand requires an estimate of the period of the
wall. To this end, the expression proposed by Wallace [13]
for prismatic reinforced concrete cantilever walls is used:
T= 8.8 hwlw
n
whs
Ec gp(6)
where hw = total height of wall, lw = length of wall,n= number of stories, w= tributary floor weight per unitarea, hs = floor-to-floor height (assumed uniform), g=acceleration due to gravity (= 9.81 m/s2), Ec= elasticmodulus of concrete, which is taken as 4730
fc where f
c
is the concrete cylinder strength in MPa, and p= wall-to-floor area ratio in the direction of lateral loading. It
should be noted that a cracked-section stiffness with Icr=0.5Ig has been used in Eq. (6). A study by Wallace and
Moehle [12] has shown that Eq. (6) correlates well with
the measured small amplitude vibration periods of mid-rise
US and Chilean structural wall buildings with a wall-to-floor
area ratio in the range of 1% to 4.7%.
Fig. 3. Kinematic and equilibrium conditions for the ultimate limit state of
rectangular wall sections.
3.3. Lateral strength
The level of ductility demand, and hence the magnitude
of tensile strain in the end region of the wall, depends on
the lateral strength of the wall. The flexural strength of a
concrete section can be estimated using the traditional [1]
equivalent stress block approach in conjunction with a linear
strain profile for the ultimate condition. For a rectangular
section with distributed longitudinal reinforcement plus
end reinforcement, such as that shown in Fig. 3, the
normalized neutral axis depth cu may be determined usingthe equilibrium equation for vertical forces:
cucu
lw
= 10{2k1+k2[2w+( )(t+w(21))]}171+40k2w
(7)
where cu= neutral axis depth measured from the extremecompression fiber, w = vertical reinforcement ratio inthe middle portion of the wall, t= overall (or average)reinforcement ratio, i.e. total longitudinal steel area divided
by gross wall area, k1 = axial force ratio Pu/fclwtwwhere Pu is the axial force acting on the wall, k2= ratioof the steel yield strength to concrete compressive strength
fy /fc , and1 is the equivalent stress block parameter asdefined in [1]. The axial force Pu may be estimated from
-
8/11/2019 Final Article Chai and Kunnath
5/12
1056 Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063
the tributary floor weight w and the number of stories n,
in which case the result is Pu = nwlwtw/p, where p isthe wall-to-floor area ratio defined before. The parameter
in Eq.(7) is defined as the end length divided by the wall
length (see Fig. 3). It should be noted that in estimating
the vertical forces, the end reinforcement is assumed to
be stressed to fy and fy for tension and compressionreinforcement, respectively, where and >1. The higher
stress level in the end reinforcement is intended to reflect
the increased likelihood of the actual yield strength being
higher than the nominal value as well as the possible strain
hardening of reinforcement at the ultimate limit state. A
value of = = 1.25 is used in this paper. For thelongitudinal reinforcement in the middle region, however,
the reinforcement is assumed to be stressed to fy instead
of 1.25fy for both tension and compression since the strain
in that region is smaller. Note that the flexural strength of
the wall is not expected to be significantly affected by the
assumed stress level in the middle portion of the wall since
the reinforcement ratio in the middle region tends to besmaller and their corresponding forces operate at a smaller
lever arm with respect to the centerline of the wall.
Upon the determination of the neutral axis depth, the
flexural strength of a rectangular section may be determined
by taking moments about the centerline of the wall, which in
normalized form is given by
MuMu
fc twl2w
= 140
{cu(171+40k2w)(cu)2(1721+40k2w)
10k2(1)[(+ )(tw)+ 2(+2)w ]}. (8)Since current seismic design is to ensure a ductile response,
the lateral strength of structural walls may be established on
the basis of the flexural strength at the critical section. By
adopting the commonly assumed linearly distributed lateral
force on the wall, the lateral strength of the wall may be
estimated as
Vu=3Mu
2hw(9)
where an effective height of two-thirds of the overall height
has been assumed for the wall.
3.4. Ductility-based force reduction factor
The amount of yielding and hence ductility demand on
a structural wall may be determined in a manner similar to
the construction of inelastic response spectra using a force
reduction factor R, which is defined as the ratio of minimum
elastic force to actual lateral strength. Extensive numerical
studies have been conducted to determine the appropriate
level of force reduction for a given ductility capacity, and
various expressions have been proposed in the literature
(e.g. [6,11]). In this study, the RT relation proposed
by Vidic et al. [11] for a stiffness-degrading hysteretic model
is used:
R=
( 1)T/ To+1
for T ToT > To
(10)
where
To=0.65Tc0.3 (11)where To is the period of transition between the ascending
region and the constant region of R, and Tc is the charac-
teristic period as defined previously in Eq. (5). The force
reduction factor R increases linearly with period T in the
short period range (T To) and remains constant andequal to the displacement ductility factor in the long period
range(T > To). Note that the transition period To increases
slightly with increased displacement ductility factor.
3.5. Maximum tensile strain
The maximum tensile strain imposed in the end regionof the wall is related to the curvature demand on the wall.
By assuming that the inelastic deformation is facilitated by
a plastic hinge rotation at the base of the wall, the curvature
ductility factor may be written as [7]
=( 1)
3
Lphe
1 Lp
2he
+1 (12)where lp is the equivalent plastic hinge length, he is an
effective height, taken as 2/3 of the height of the wall. The
equivalent plastic hinge length depends on the geometry
of the wall, with generally longer plastic hinge length for
slender walls. In this paper, the equivalent plastic hinge
length proposed by Paulay and Priestley [7] is used:
0.3lwlp= (0.20+0.044Ar)lw0.8lw. (13)For walls with aspect ratios in the range of 2 Ar 10, theequivalent plastic hinge length lp varies between 0.29lwand
0.64lw.
Since non-zero strain gradient exists across the section,
the location for calculating the critical tensile strain must be
properly identified. To this end, the critical tensile strain is
calculated at the center of the end region, i.e. at a distance(1
0.5)lw from the extreme compression fiber. The
critical tensile strain, denoted as sm in Fig. 3, may bewritten in terms of the curvature ductility factor as
sm= 2y (10.5cu ) (14)where y is the yield strain of the wall reinforcement, and
other parameters have been previously defined. In deriving
Eq.(14), the equivalent elasto-plastic yield curvature y of
the wall has been taken as [8]
y=2y
lw. (15)
It should be noted that, even though Eq.(15) was originally
proposed for rectangular sections with w =
0.5%
-
8/11/2019 Final Article Chai and Kunnath
6/12
Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063 1057
Fig. 4. Maximum tensile strain in end regions of cantilever structural walls.
distributed reinforcement [8], it is also used for walls with
w=0.25% distributed reinforcement in this paper.To illustrate the potentially large tensile strain in the
end region of the structural wall, Fig. 4 shows a plot of
the critical tensile strain for a 10-story wall subjected to a
peak ground acceleration of 0.4gand a peak ground velocity
of 66.7 cm/s. The floor-to-floor height is taken as 3.05 m
and the tributary floor weight is taken as 8.38 kN/m2. The
wall-to-floor area ratio is 1% and the end length is taken
as 5% of the wall length, i.e. = 0.05. It can be seenfrom Fig. 4 that the critical tensile strain increases with
increased aspect ratio, but decreases with increased overallwall reinforcement. For an aspect ratio of Ar = 10, themaximum tensile strain may reach as high as sm = 3.5%for the case of a low reinforcement ratio of t = 0.5%.Although Fig. 5 corresponds to only one particular set of
ground motion parameters, the magnitude of the critical
tensile strain is expected to increase with increased intensity
of the ground motion.
3.6. Stability criterion
Recognizing that the tensile strain in the end region of the
wall is a critical parameter, the stability of structural wallsmay be ensured by limiting the magnitude of the tensile
strain in that region. The following inequality was proposed
by Chai and Elayer [2] for the critical tensile strain:
sm 2
2
tw
lo
2c+3y (16)
where lo is the buckled length of the wall. Although
the buckled length is generally difficult to assess,
recommendations nonetheless exist in the literature. For
example, [7] recommends that the buckled length lo be
equal to the equivalent plastic hinge length lp . Such a
recommendation may result in an excessively long buckled
length for tall slender walls. In this paper, the buckled length
is taken to be equal to the equivalent plastic length, as
recommended by Paulay and Priestley [7] in Eq. (16), but
is limited to one-half of the story height in order to reflect
the restraint against buckling by the top and bottom floor
slabs. The parameter c in Eq.(16) was originally derived
by Paulay and Priestley [7], and is given by
c=0.5
1+2.35m
5.53m2 +4.70m
(17)
where m is the mechanical reinforcement ratio in the end
region of the wall, and is defined as
m= endfy
fc(18)
and end is the end region reinforcement ratio, which may
be written in terms of the overall reinforcement ratio t and
reinforcement ratio in the middle portion of the wall w:
end=
tw(12 )2
. (19)
The tensile strain limit of Eq.(16) and the stability criterion
of Eq. (17) may be used in conjunction with the seismic
demand and force reduction to calculate the minimum wall
thickness of structural walls.
4. Results
Minimum wall thickness is assessed for a range of
ground motion a /v ratios, wall reinforcement ratios, wall-
to-floor area ratios, floor tributary weights and numbers of
stories. Results are presented in terms of story-height-to-
wall-thickness ratio hs /tw . In this paper, a uniform storyheight ofhs= 3.05 m is assumed and the length over whichthe end reinforcement is concentrated is taken as 5% of the
wall length, i.e. = 0.05. A concrete compressive strengthof fc= 34.5 MPa and steel yield strength of fy=414 MPaare also assumed.
4.1. Ground motion parameters
Since the stability of structural walls is influenced by
the magnitude of the tensile strain, the minimum wall
thickness is expected to vary with the intensity of the ground
motion. A peak ground acceleration of 0.4g, assumed to berepresentative of the seismic intensity in zone IV of [10], is
used in this paper. The effect of site conditions on minimum
wall thickness is studied by varying the a/v ratio. In this
case, four a/v ratios, namely, 2.0g/m s1, 1.4g/m s1,1.0g/m s1 and 0.6g/m s1, are used, and these ratios arereferred to as ultrahigh, high, normal and low a/v ratios,
respectively. For a peak ground acceleration of 0.4gand for
these a/v ratios, the peak ground velocities are 20 cm/s,
28.6 cm/s, 40 cm/s and 66.7 cm/s, respectively.
Fig. 5(a)(d) show plots of the story-height-to-wall-
thickness ratio hs /tw versus wall aspect ratio Ar for a
range of reinforcement ratios from t =
0.5% to 2%.
-
8/11/2019 Final Article Chai and Kunnath
7/12
1058 Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063
(a) Lowa/vratio=0.6g/m s1. (b) Normala/vratio=1.0g/m s1.
(c) Higha/vratio=1.4g/m s1. (d) Ultrahigha /vratio=2.0g/m s1.
Fig. 5. Story-height-to-wall-thickness ratio for varyinga /vratios. Assumed parameters are n=10,h s= 3.05 m,= 0.05, p=1% andw=8.38 kN/m2.
The solid line corresponds to results obtained in this
study, while the short dashed line corresponds to the
minimum wall thickness required by [4] and the long dashed
line corresponds to the minimum wall thickness required
by [10]. It should be noted that, for plotting the [10]
story-height-to-wall-thickness ratio, the unsupported heightis taken as 90% of the floor-to-floor height, i.e. ln =0.9hs . For the[4] minimum wall thickness in Eq. (1), the
displacement ductility factor is calculated using the
force-reduction factor of Eq. (10) instead of a constant
displacement ductility factor. For the plots inFig. 5(a)(d),
the number of stories is n= 10, the tributary floor weightis w = 8.38 kN/m2, and the wall-to-floor area ratio isp=1%.
It can be seen from Figs. 5(a)(d) that the hs /tw ratio
generally decreases with increasing aspect ratio of the wall,
i.e. thicker wall is required for slender walls. For the low
a/v ratio of 0.6g/m s1 in Fig. 5(a), which represents a
soft soil condition, the h s /tw ratio varies from about 14 at
an aspect ratio of Ar = 3 to about 10 at Ar = 10. Forthis a/v ratio, the hs /tw ratio is not sensitive to the wall
reinforcement ratio from Ar= 3 to 10. For normal and higha/v ratios in Figs. 5(b) and (c), however, the hs /tw ratio
becomes increasingly sensitive to wall reinforcement ratio,where a rapid increase in hs /tw ratio is noted for increasing
wall reinforcement. The increase in hs /tw ratio is due to
limited yielding of the wall, which occurs as a result of
increasing lateral strength with increased wall reinforcement
ratio. For the ultrahigh a/v ratio in Fig. 5(d), yielding is
reduced significantly, resulting in a very large h s /tw ratio.
The actual hs /tw ratio is out of range of the y-axis and
hence not plotted inFig. 5(d). Note that, although results for
the h s /tw ratio are sensitive to the wall reinforcement ratio
for the case of normal and high a/v ratios, the minimum
wall thickness required by [4] is not sensitive to the wall
reinforcement ratio.
-
8/11/2019 Final Article Chai and Kunnath
8/12
Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063 1059
It can also be seen from Figs. 5(a)(d) that the hs /twratio increases with increasing a /v ratio, with the smallest
hs /tw ratio being calculated for the low a/v ratio of
0.6g/m s1. The small hs /tw ratio for low a/v ratiois due to the changing shape of the elastic response
acceleration spectrum. Since the fundamental period of 10-
story walls generally lies in the velocity-controlled regionof the response spectrum, and since the predominant period
of the ground motion tends to shift towards a longer period
for low a/v ratio, a decreasing a/v ratio tends to result
in an increased spectral response, thereby increasing the
ductility demand, and hence a larger tensile strain and wall
thickness.
Results in Figs. 5(a)(d) also show that the hs /tw ratio
may be smaller than that required by [10] and[4], depending
on the ground motion parameters, wall reinforcement ratios
and wall aspect ratios. For the case of low a/v ratio, the
hs /tw ratio is smaller than that of [10] for an aspect ratio
of Ar
3, which means that the required wall thickness
is larger than that of [10]. On the other hand, the hs /twratio compares fairly well with that of [4], even though the
ratio tends to be slightly smaller than that of [4] in the large
aspect ratio range, e.g. Ar 8. In the case of the normala/v ratio, the hs /tw ratio compares fairly well with that
required by both [10] and [4] for t = 0.5% and 1% inthe large aspect ratio range. For higher reinforcement ratios
oft= 1.5% and 2%, however, the hs /tw ratio is largerthan that required by [10] and [4]. In the case of high or
ultrahigh a/v ratios, the h s /tw ratio obtained in this study
is significantly larger than that required by [10] and [4],
indicating that the current code provision is conservative
with respect to these ground motion parameters. It is alsoof interest to note that, while results from this study indicate
a monotonically decreasinghs /tw ratio, the trend forh s /twratio required by [4] indicates a slight increase in hs /twratio
for aspect ratio Ar 7 for alla/vratios.
4.2. Wall-to-floor area ratio
The fundamental period of structural walls depends on
the percentage of wall area, as evident in Eq. (6), and
consequently, the hs /tw ratio is expected to be influenced
by the wall-to-floor area ratio.Fig. 6(a)(d) show the hs /tw
ratio for wall-to-floor area ratios of p = 1%, 2%, 3%and 4%. In this case, the hs /tw ratio is assessed for a low
a/v ratio of 0.6g/m s1 since a low a/v ratio generallyresults in greater spectral response. The same peak ground
acceleration of 0.4g is used and the tributary floor weight
is taken as w= 8.38 kN/m2, and the number of stories istaken asn=10.
Trends observed for differenta/vratios inFigs. 5(a)(d)
are also observed inFigs. 6(a)(d) for different wall-to-floor
area ratios. For the wall-to-floor area ratio of p = 1%in Fig. 6(a), the hs /tw ratio is not sensitive to the wall
reinforcement ratio. For increased wall-to-floor area ratios,
however, the h s /tw ratio becomes increasingly sensitive to
the wall reinforcement ratio. For example, for the wall-to-
floor area ratio of p= 4% inFig. 6(d) and for an aspectratio of Ar = 10, the hs /tw ratio increases from 9 fort= 0.5% to h s /tw= 14 for t= 2%. Also for the caseof a low reinforcement ratio oft= 0.5%, the h s /tw ratioremains relatively constant with respect to the wall-to-floor
area ratio, as can be seen by comparing the solid lines fort= 0.5% for all wall-to-floor area ratios in Fig. 6(a)(d).As an example, for a reinforcement ratio of t = 0.5%and for an aspect ratio of Ar = 10, the hs /tw ratio is10.4 for p= 1%, compared to the hs /tw ratio of 8.7 forp=4%.
Results inFig. 6(a)(d) also indicate that theh s /tw ratio
for low a/v ratio is generally smaller than that required
by [10] or [4]. The hs /tw ratio required by [4] is also
smaller than that required by the [10] for large aspect ratios.
However, comparison between the two codes depends on the
value of the a/v ratio since the [4] requirement is taken
to be dependent on the displacement ductility factor. As
such, the [4] hs /tw , which is expected to increase withincreasing a/v ratio, may increase above that of [10] in
some cases.
4.3. Tributary floor weight
Tributary floor weight, which affects the period of the
wall, is expected to influence the hs /tw ratio of the wall.
Figs. 7(a)(d) show the story-height-to-wall-thickness ratio
for tributary floor weight from w = 6.49 kN/m2 to10.39 kN/m2. The range of floor weight is considered to
represent reasonable limits in current building design. The
same lowa/vratio of 0.6g/m s1 and the same peak groundacceleration of 0.4g are used. The number of stories is
kept at n= 10 and the wall-to-floor area ratio is taken asp=1%.
It can be seen from Figs. 7(a)(d) that the hs /tw ratio
is relatively insensitive to the tributary floor weight, even
though an increased tributary floor weight results in a
slightly larger hs /tw ratio. For example, for the tributary
floor weight of w = 6.49 kN/m2 in Fig. 7(a) and for anaspect ratio of Ar = 8, the hs /tw ratio is 9.9 for thelow reinforcement ratio oft= 0.5%. With an increasedtributary floor weight of w = 10.39 kN/m2 in Fig. 7(d)but for the same low reinforcement ratio oft= 0.5% andwall aspect ratio of Ar= 8, the hs /tw ratio is 11.2. Theincrease inhs /twratio is about 11% and is mainly due to the
longer period of the wall as a result of increased tributary
floor weight, which tends to reduce the spectral response,
and hence reduced ductility demand in the wall. The relative
insensitivity of the h s /tw ratio to the tributary floor weight
is also observed for higher longitudinal reinforcement ratio.
For the same aspect ratio of Ar = 8 but for a higherlongitudinal reinforcement ratio oft= 2%, thehs /twratiois 10.4 for w = 6.49 kN/m2 inFig. 7(a). In comparison,the hs /tw ratio increases only slightly to 10.6 for w =10.39 kN/m2 inFig. 7(d). Comparison of results with code
-
8/11/2019 Final Article Chai and Kunnath
9/12
-
8/11/2019 Final Article Chai and Kunnath
10/12
Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063 1061
(a) Floor weightw=6.49 kN/m2. (b) Floor weightw=7.79 kN/m2.
(c) Floor weightw=9.09 kN/m2. (d) Floor weightw=10.39 kN/m2.
Fig. 7. Story-height-to-wall-thickness ratio for varying tributary floor weight. Assumed parameters are ( xg )max = 0.4g, ( xg )max= 66.7 cm/s, n = 10,hs= 3.05 m,= 0.05 and p=1%.
contrast to the monotonically increasing trend of 10-, 15-
and 20-story walls.
5. Summary and conclusions
This paper examines the out-of-plane stability of planar
structural walls under seismic loading and its implications
in design. Factors governing out-of-plane buckling as well
as the methodology for determining the required thickness
of planar walls are discussed; this is followed by an
assessment of the minimum wall thickness for a peak ground
acceleration of 0.4g, assumed to be representative of the
ground motion for Zone IV of 1997 Uniform Building Code.
The effect of site conditions is studied by varying the ratio
of the peak ground acceleration to the peak ground velocity
(a/v) ratio. Although results are presented primarily in
terms of story-height-to-wall-thickness ratio, concluding
remarks will be made with reference to the minimum wall
thickness. Also because of the large number of parameters
involved and only results from a limited set of parameters
being presented, concluding remarks are only intended for
those parameters.
Results for 10-story walls with a wall-to-floor area ratio
of 1% and tributary floor weight of 8.38 kN/m2 indicated
that the minimum wall thickness increases with decreasing
a/v ratio, i.e. thicker walls are required for the lower a/v
ratios. The increase in wall thickness is due to the changing
shape of the elastic response acceleration spectrum, which
generally indicates a softening of the site for decreasing
a/v ratio. Since the period of mid-height walls generally
falls in the velocity-controlled region of the spectrum and
since a decreasing a/v ratio tends to result in a longer
predominant period, an increase in spectral response and
hence larger thickness is expected for the low a/v ratio.
-
8/11/2019 Final Article Chai and Kunnath
11/12
1062 Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063
(a) Number of stories=5. (b) Number of stories=10.
(c) Number of stories=15. (d) Number of stories=20.
Fig. 8. Story-height-to-wall-thickness ratio for different number of stories. Assumed parameters are( xg )max=0.4g,( xg )max=66.7 cm/s,w=8.38 kN/m2,hs= 3.05 m,= 0.05 and p=1%.
Results for the same set of 10-story walls also indicated
that the minimum wall thickness is not conservative with
respect to the 1997 Uniform Building Code and 1995 New
Zealand Concrete Code (NZS 3101) for the low a/v ratio
of 0.6g/m s
1. For the normal a/v ratio of 1.0g/m s
1,
however, results for minimum wall thickness generally agree
well with those for the codes, whereas for high and ultrahigh
a/v ratios of 1.4g/m s1 and 2.0g/m s1, both codesare conservative. Assessment based on the low a/v ratio
of 0.6g/m s1 indicated that the minimum wall thicknessgenerally decreases with increase in the wall-to-floor area
ratio, even though the amount of decrease depends on the
wall reinforcement ratio. For the low a/v ratio and wall-
to-floor area ratios between 1% and 4%, the minimum
wall thickness is larger than that required by both building
codes, even though results agree better with [4]. Study in
this paper also indicated that the minimum wall thickness
is not sensitive to the tributary floor weight. In contrast,
however, the minimum wall thickness is rather sensitive to
the wall height, or equivalently, the number of stories. For
the low a/v ratio of 0.6g/m s1, wall-to-floor area ratioof 1%, and tributary weight of 8.38 kN/m2, large wall
thickness is predicted for short walls. The large thickness
is primarily due to shortening of the structural period,
which tends to increase the spectral response of the wall
and hence increased ductility demand. For the case of the
lowa /v ratio, the minimum wall thickness required by [4]
also shows reasonable agreement with results for 10- and
15-story walls. Although results presented in this paper
are instructive for prescribing the minimum thickness of
ductile planar structural walls, future code development
or revision should nonetheless be verified by experimental
testing of actual structural walls. Analyses in this paper
were also carried out on the assumption of isolated planar
-
8/11/2019 Final Article Chai and Kunnath
12/12
Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063 1063
walls whereas many real buildings may exhibit significant
torsional response when subjected to seismic load. Further
investigation of structural wall stability under the influence
of torsional response of buildings is warranted.
References
[1] ACI 318. Building code requirements for structural concrete and
commentary. Detroit: American Concrete Institute; 1999.
[2] Chai YH, Elayer TD. Lateral stability of reinforced concrete columns
under axial reversed cyclic tension and compression. ACI Structural
Journal 1999;96(5):7809.
[3] Chai YH, Fajfar P, Romstad KM. Formulation of duration-dependent
inelastic seismic design spectrum. Journal of Structural Engineering,
ASCE 1998;124(8):91321.
[4] NZS 3101. Concrete structures standard part 1 and 2. Private bag
2439. Wellington 6020, New Zealand, 1995.
[5] Paulay T. The design of ductile reinforced concrete structural walls
for earthquake resistance. Earthquake Spectra 1986;2(4):783824.
[6] Paulay T, Priestley MJN. Seismic design of reinforced concrete and
masonry buildings. Wiley Interscience Publication; 1992.
[7] Paulay T, Priestley MJN. Stability of ductile structural walls. ACI
Structural Journal 1993;90(4):38592.
[8] Priestley MJN, Kowalsky MJ.Aspects of drift and ductility capacity of
rectangular cantilever structural walls. Bulletin New Zealand National
Society for Earthquake Engineering 1998;31(6):7385.
[9] Tso WK, Zhu TJ, Heidebrecht AC. Seismic energy demands on re-
inforced concrete moment-resisting frames. Earthquake Engineering
and Structural Dynamics 1993;22:53345.
[10] UBC. Uniform building code, vol. 2. In: International conference of
building officials. 1997.
[11] Vidic T, Fajfar P, Fischinger M. Consistent inelastic design spectra:
strength and displacement. Earthquake Engineering and Structural
Dynamics 1994;23:50721.
[12] Wallace JW, Moehle JP. Ductility and detailing requirements of
bearing wall buildings. Journal of Structural Engineering, ASCE
1992;116(6):162544.
[13] Wallace JW. New methodology for seismic design of RC shear walls.
Journal of Structural Engineering, ASCE 1994;120(3):86384.