final article chai and kunnath

Upload: david-flores

Post on 02-Jun-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 Final Article Chai and Kunnath

    1/12

  • 8/11/2019 Final Article Chai and Kunnath

    2/12

    Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063 1053

    minimum wall thickness requirement is reproduced here; for

    walls with two layers of vertical reinforcement, it needs to

    satisfy the following inequality:

    twkm ( +2)(Ar+2)lw

    1700

    (1)

    wherekm= 1.0, unless it can be shown thatkm=

    ln

    (0.25+0.055Ar)lw0.1 (3)

    where is the displacement ductility factor, Ar is the

    aspect ratio of the wall, i.e. total wall height divided by wall

    length,ln is the clear vertical distance between floors, lw is

    the length of the wall, l is the vertical reinforcement ratio,

    fy is the yield strength of the reinforcement, and fc is the

    concrete compressive strength. Although not immediatelyapparent, the minimum wall thickness required by [4] is

    quite different from that required by [10]. For example,

    for a 10-story wall with a displacement ductility factor of = 4, aspect ratio of Ar = 6, vertical reinforcementratio ofl = 0.02, concrete compressive strength of fc=34.5 MPa, and steel yield strength of fy = 414 MPa,the [4] minimum wall thickness is 9.7% of the floor-

    to-floor (story) height, where the unsupported height has

    been assumed to be 90% of the story height, i.e. ln =0.9hs . This minimum wall thickness is significantly larger

    than that required by [10], which is 5.6% of the story

    height. In view of the significant difference between the

    two codes, an assessment of the minimum wall thicknesses

    and their comparison under different design parameters is

    warranted.

    2. Stability of structural walls

    The phenomenon of inelastic buckling of structural

    walls under reversed cyclic loading is admittedly complex;

    for tractable solutions, appropriate simplifications must be

    made. A basic understanding of the inelastic buckling of

    walls may be provided by a cyclic axially loaded reinforced

    concrete column, the response of which is assumed to berepresentative of the high tension/compression region of

    the wall. Although the effect of strain gradient across the

    wall is not included, the idealization is nonetheless useful

    in identifying critical parameters governing the buckling

    mechanism.

    The reversed cyclic response of an axially loaded

    reinforced concrete column is demonstrated using the

    following test data from [2]. The photographs in Fig. 1(a)

    and (b) show the condition of the test column after

    being loaded to different tensile strain amplitudes. The test

    column, which had a rectangular cross-section of 100 mm 200 mm, was reinforced with six No. 3 bars (db

    =9.5 mm)

    providing a longitudinal reinforcement ratio of 2.1%. The

    length of the test column wasL o=1500 mm, correspondingto a length-to-width ratio of 14.75. Transverse ties were

    provided at close spacing of six times the longitudinal bar

    diameter simulating a well-confined condition in the end

    region of a ductile wall. The close spacing of the transverse

    reinforcement was also intended to prevent local buckling ofthe longitudinal reinforcement.

    Fig. 1(c) shows the hysteretic response of the test column

    under axial tension/compression cycles. The nominal axial

    strain a , plotted on the y-axis of both plots, corresponds

    to the average strain measured over several cracks in the

    middle portion of the column, while the normalized out-of-

    plane displacement, plotted on thex -axis of the left hand plot

    ofFig. 1(c), corresponds to the out-of-plane displacement

    measured at mid-height of the column divided by the

    width of the column tw. The x -axis on the right hand

    plot ofFig. 1(c) corresponds to the applied axial force

    on the column. The loading history consisted of a tensile

    strain cycle followed by a compression cycle with a targetcompressive strain amplitude that was about 1/7 of the

    tensile strain amplitude. The axial tensile strains imposed on

    the test column, namelya= 0.0078, 0.0108, 0.0133and0.0161, are shown in both plots ofFig. 1(c). It canbe seen that, for axial tensile strain less than or equal to

    0.0133, the test column remained stable with relativelysmall out-of-plane displacement of /tw 0.05. For anaxial tensile strain to0.0161, however, the out-of-planedisplacement of the column upon subsequent compression

    increased significantly, causing the column to buckle. The

    stable condition following a tensile strain ofa= 0.0133is shown inFig. 1(a), in contrast to the buckled column aftera tensile strain of a = 0.0161 in Fig. 1(b). Althoughonly one test specimen is provided, Fig. 1 nonetheless

    demonstrates the importance of the tensile strain cycle for

    the cyclic stability of structural walls. Further test results are

    given in [2].

    3. Methodology and basic equations

    Since the current use of structural walls in buildings

    often involves different height and length, amount of

    reinforcement, wall-to-floor area ratio etc., an assessment

    of the minimum wall thickness with these parameters isinstructive. The methodology and basic equations governing

    the minimum wall thickness are first discussed, and this is

    followed by a presentation of results for various parameters

    including ground motions that are representative of current

    design earthquakes.

    3.1. Elastic response acceleration spectrum

    The required thickness of structural walls depends on

    the ductility demand, which is a function of the ratio of

    wall lateral strength to elastic force demand. In this study,

    the elastic force demand uses a NewmarkHall type elastic

  • 8/11/2019 Final Article Chai and Kunnath

    3/12

    1054 Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063

    (a) Stable column up to tensile strain of 1.33%. (b) Buckled column after tensile strain

    of 1.61%.

    (c) Hysteretic response of test column.

    Fig. 1. Stability of a reinforced concrete column when subjected to large amplitude reversed cyclic tensile/compression loading.

    response acceleration spectrum, which was used earlier byChai et al. [3], and is shown inFig. 2. The elastic response

    acceleration, as characterized in terms of an amplification

    factor a , is specified in three period regions:

    a=

    1.0+2.5(ca1)T/ Tcca2cv ( xg)max/[( xg)maxT]

    for

    0< T 0.4Tc0.4Tc < T TcTc < T

    (4)

    where the coefficient ca is the ratio of spectral elastic

    response acceleration to peak ground acceleration in the

    acceleration-controlled region, and the coefficient cv is the

    ratio of spectral elastic response velocity to peak groundvelocity in the velocity-controlledregion. On the basis of the

    average values obtained by Vidic et al. [11], coefficients caandcv are taken as 2.5 and 2.0 respectively. The term Tc in

    Eq.(4) corresponds to the characteristic period of the ground

    motion, which is given by Vidic et al. [11]:

    Tc=2cv

    ca

    ( xg)max( xg)max

    (5)

    where the ratio( xg)max/( xg)max corresponds to the inverseof the peak ground acceleration to peak ground velocity

    (referred to asa/vratio herein), which has been shown to be

  • 8/11/2019 Final Article Chai and Kunnath

    4/12

    Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063 1055

    Fig. 2. Amplification factor for elastic response acceleration.

    a useful parameter for characterizing the frequency contentas well as the duration of the earthquake ground motion [9].

    For rock or firm soil sites located near the source of the

    earthquake, the ground motion tends to be characterized by

    a high a/v ratio with a relatively short duration, whereas

    for soft sites at moderate distance from the source, the

    ground motion tends to be characterized by a low a /v ratio

    with an increased duration. The elastic response acceleration

    amplification factor inFig. 2corresponds to foura/vratios,

    i.e. ultrahigh, high, normal and low a/v ratios. Note that

    the shape of the elastic response acceleration spectrum

    changes with thea/vratio as the period range for maximum

    response shifts to the longer period region for decreasinga/vratio.

    3.2. Fundamental period

    The use of elastic response acceleration spectrum for

    elastic force demand requires an estimate of the period of the

    wall. To this end, the expression proposed by Wallace [13]

    for prismatic reinforced concrete cantilever walls is used:

    T= 8.8 hwlw

    n

    whs

    Ec gp(6)

    where hw = total height of wall, lw = length of wall,n= number of stories, w= tributary floor weight per unitarea, hs = floor-to-floor height (assumed uniform), g=acceleration due to gravity (= 9.81 m/s2), Ec= elasticmodulus of concrete, which is taken as 4730

    fc where f

    c

    is the concrete cylinder strength in MPa, and p= wall-to-floor area ratio in the direction of lateral loading. It

    should be noted that a cracked-section stiffness with Icr=0.5Ig has been used in Eq. (6). A study by Wallace and

    Moehle [12] has shown that Eq. (6) correlates well with

    the measured small amplitude vibration periods of mid-rise

    US and Chilean structural wall buildings with a wall-to-floor

    area ratio in the range of 1% to 4.7%.

    Fig. 3. Kinematic and equilibrium conditions for the ultimate limit state of

    rectangular wall sections.

    3.3. Lateral strength

    The level of ductility demand, and hence the magnitude

    of tensile strain in the end region of the wall, depends on

    the lateral strength of the wall. The flexural strength of a

    concrete section can be estimated using the traditional [1]

    equivalent stress block approach in conjunction with a linear

    strain profile for the ultimate condition. For a rectangular

    section with distributed longitudinal reinforcement plus

    end reinforcement, such as that shown in Fig. 3, the

    normalized neutral axis depth cu may be determined usingthe equilibrium equation for vertical forces:

    cucu

    lw

    = 10{2k1+k2[2w+( )(t+w(21))]}171+40k2w

    (7)

    where cu= neutral axis depth measured from the extremecompression fiber, w = vertical reinforcement ratio inthe middle portion of the wall, t= overall (or average)reinforcement ratio, i.e. total longitudinal steel area divided

    by gross wall area, k1 = axial force ratio Pu/fclwtwwhere Pu is the axial force acting on the wall, k2= ratioof the steel yield strength to concrete compressive strength

    fy /fc , and1 is the equivalent stress block parameter asdefined in [1]. The axial force Pu may be estimated from

  • 8/11/2019 Final Article Chai and Kunnath

    5/12

    1056 Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063

    the tributary floor weight w and the number of stories n,

    in which case the result is Pu = nwlwtw/p, where p isthe wall-to-floor area ratio defined before. The parameter

    in Eq.(7) is defined as the end length divided by the wall

    length (see Fig. 3). It should be noted that in estimating

    the vertical forces, the end reinforcement is assumed to

    be stressed to fy and fy for tension and compressionreinforcement, respectively, where and >1. The higher

    stress level in the end reinforcement is intended to reflect

    the increased likelihood of the actual yield strength being

    higher than the nominal value as well as the possible strain

    hardening of reinforcement at the ultimate limit state. A

    value of = = 1.25 is used in this paper. For thelongitudinal reinforcement in the middle region, however,

    the reinforcement is assumed to be stressed to fy instead

    of 1.25fy for both tension and compression since the strain

    in that region is smaller. Note that the flexural strength of

    the wall is not expected to be significantly affected by the

    assumed stress level in the middle portion of the wall since

    the reinforcement ratio in the middle region tends to besmaller and their corresponding forces operate at a smaller

    lever arm with respect to the centerline of the wall.

    Upon the determination of the neutral axis depth, the

    flexural strength of a rectangular section may be determined

    by taking moments about the centerline of the wall, which in

    normalized form is given by

    MuMu

    fc twl2w

    = 140

    {cu(171+40k2w)(cu)2(1721+40k2w)

    10k2(1)[(+ )(tw)+ 2(+2)w ]}. (8)Since current seismic design is to ensure a ductile response,

    the lateral strength of structural walls may be established on

    the basis of the flexural strength at the critical section. By

    adopting the commonly assumed linearly distributed lateral

    force on the wall, the lateral strength of the wall may be

    estimated as

    Vu=3Mu

    2hw(9)

    where an effective height of two-thirds of the overall height

    has been assumed for the wall.

    3.4. Ductility-based force reduction factor

    The amount of yielding and hence ductility demand on

    a structural wall may be determined in a manner similar to

    the construction of inelastic response spectra using a force

    reduction factor R, which is defined as the ratio of minimum

    elastic force to actual lateral strength. Extensive numerical

    studies have been conducted to determine the appropriate

    level of force reduction for a given ductility capacity, and

    various expressions have been proposed in the literature

    (e.g. [6,11]). In this study, the RT relation proposed

    by Vidic et al. [11] for a stiffness-degrading hysteretic model

    is used:

    R=

    ( 1)T/ To+1

    for T ToT > To

    (10)

    where

    To=0.65Tc0.3 (11)where To is the period of transition between the ascending

    region and the constant region of R, and Tc is the charac-

    teristic period as defined previously in Eq. (5). The force

    reduction factor R increases linearly with period T in the

    short period range (T To) and remains constant andequal to the displacement ductility factor in the long period

    range(T > To). Note that the transition period To increases

    slightly with increased displacement ductility factor.

    3.5. Maximum tensile strain

    The maximum tensile strain imposed in the end regionof the wall is related to the curvature demand on the wall.

    By assuming that the inelastic deformation is facilitated by

    a plastic hinge rotation at the base of the wall, the curvature

    ductility factor may be written as [7]

    =( 1)

    3

    Lphe

    1 Lp

    2he

    +1 (12)where lp is the equivalent plastic hinge length, he is an

    effective height, taken as 2/3 of the height of the wall. The

    equivalent plastic hinge length depends on the geometry

    of the wall, with generally longer plastic hinge length for

    slender walls. In this paper, the equivalent plastic hinge

    length proposed by Paulay and Priestley [7] is used:

    0.3lwlp= (0.20+0.044Ar)lw0.8lw. (13)For walls with aspect ratios in the range of 2 Ar 10, theequivalent plastic hinge length lp varies between 0.29lwand

    0.64lw.

    Since non-zero strain gradient exists across the section,

    the location for calculating the critical tensile strain must be

    properly identified. To this end, the critical tensile strain is

    calculated at the center of the end region, i.e. at a distance(1

    0.5)lw from the extreme compression fiber. The

    critical tensile strain, denoted as sm in Fig. 3, may bewritten in terms of the curvature ductility factor as

    sm= 2y (10.5cu ) (14)where y is the yield strain of the wall reinforcement, and

    other parameters have been previously defined. In deriving

    Eq.(14), the equivalent elasto-plastic yield curvature y of

    the wall has been taken as [8]

    y=2y

    lw. (15)

    It should be noted that, even though Eq.(15) was originally

    proposed for rectangular sections with w =

    0.5%

  • 8/11/2019 Final Article Chai and Kunnath

    6/12

    Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063 1057

    Fig. 4. Maximum tensile strain in end regions of cantilever structural walls.

    distributed reinforcement [8], it is also used for walls with

    w=0.25% distributed reinforcement in this paper.To illustrate the potentially large tensile strain in the

    end region of the structural wall, Fig. 4 shows a plot of

    the critical tensile strain for a 10-story wall subjected to a

    peak ground acceleration of 0.4gand a peak ground velocity

    of 66.7 cm/s. The floor-to-floor height is taken as 3.05 m

    and the tributary floor weight is taken as 8.38 kN/m2. The

    wall-to-floor area ratio is 1% and the end length is taken

    as 5% of the wall length, i.e. = 0.05. It can be seenfrom Fig. 4 that the critical tensile strain increases with

    increased aspect ratio, but decreases with increased overallwall reinforcement. For an aspect ratio of Ar = 10, themaximum tensile strain may reach as high as sm = 3.5%for the case of a low reinforcement ratio of t = 0.5%.Although Fig. 5 corresponds to only one particular set of

    ground motion parameters, the magnitude of the critical

    tensile strain is expected to increase with increased intensity

    of the ground motion.

    3.6. Stability criterion

    Recognizing that the tensile strain in the end region of the

    wall is a critical parameter, the stability of structural wallsmay be ensured by limiting the magnitude of the tensile

    strain in that region. The following inequality was proposed

    by Chai and Elayer [2] for the critical tensile strain:

    sm 2

    2

    tw

    lo

    2c+3y (16)

    where lo is the buckled length of the wall. Although

    the buckled length is generally difficult to assess,

    recommendations nonetheless exist in the literature. For

    example, [7] recommends that the buckled length lo be

    equal to the equivalent plastic hinge length lp . Such a

    recommendation may result in an excessively long buckled

    length for tall slender walls. In this paper, the buckled length

    is taken to be equal to the equivalent plastic length, as

    recommended by Paulay and Priestley [7] in Eq. (16), but

    is limited to one-half of the story height in order to reflect

    the restraint against buckling by the top and bottom floor

    slabs. The parameter c in Eq.(16) was originally derived

    by Paulay and Priestley [7], and is given by

    c=0.5

    1+2.35m

    5.53m2 +4.70m

    (17)

    where m is the mechanical reinforcement ratio in the end

    region of the wall, and is defined as

    m= endfy

    fc(18)

    and end is the end region reinforcement ratio, which may

    be written in terms of the overall reinforcement ratio t and

    reinforcement ratio in the middle portion of the wall w:

    end=

    tw(12 )2

    . (19)

    The tensile strain limit of Eq.(16) and the stability criterion

    of Eq. (17) may be used in conjunction with the seismic

    demand and force reduction to calculate the minimum wall

    thickness of structural walls.

    4. Results

    Minimum wall thickness is assessed for a range of

    ground motion a /v ratios, wall reinforcement ratios, wall-

    to-floor area ratios, floor tributary weights and numbers of

    stories. Results are presented in terms of story-height-to-

    wall-thickness ratio hs /tw . In this paper, a uniform storyheight ofhs= 3.05 m is assumed and the length over whichthe end reinforcement is concentrated is taken as 5% of the

    wall length, i.e. = 0.05. A concrete compressive strengthof fc= 34.5 MPa and steel yield strength of fy=414 MPaare also assumed.

    4.1. Ground motion parameters

    Since the stability of structural walls is influenced by

    the magnitude of the tensile strain, the minimum wall

    thickness is expected to vary with the intensity of the ground

    motion. A peak ground acceleration of 0.4g, assumed to berepresentative of the seismic intensity in zone IV of [10], is

    used in this paper. The effect of site conditions on minimum

    wall thickness is studied by varying the a/v ratio. In this

    case, four a/v ratios, namely, 2.0g/m s1, 1.4g/m s1,1.0g/m s1 and 0.6g/m s1, are used, and these ratios arereferred to as ultrahigh, high, normal and low a/v ratios,

    respectively. For a peak ground acceleration of 0.4gand for

    these a/v ratios, the peak ground velocities are 20 cm/s,

    28.6 cm/s, 40 cm/s and 66.7 cm/s, respectively.

    Fig. 5(a)(d) show plots of the story-height-to-wall-

    thickness ratio hs /tw versus wall aspect ratio Ar for a

    range of reinforcement ratios from t =

    0.5% to 2%.

  • 8/11/2019 Final Article Chai and Kunnath

    7/12

    1058 Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063

    (a) Lowa/vratio=0.6g/m s1. (b) Normala/vratio=1.0g/m s1.

    (c) Higha/vratio=1.4g/m s1. (d) Ultrahigha /vratio=2.0g/m s1.

    Fig. 5. Story-height-to-wall-thickness ratio for varyinga /vratios. Assumed parameters are n=10,h s= 3.05 m,= 0.05, p=1% andw=8.38 kN/m2.

    The solid line corresponds to results obtained in this

    study, while the short dashed line corresponds to the

    minimum wall thickness required by [4] and the long dashed

    line corresponds to the minimum wall thickness required

    by [10]. It should be noted that, for plotting the [10]

    story-height-to-wall-thickness ratio, the unsupported heightis taken as 90% of the floor-to-floor height, i.e. ln =0.9hs . For the[4] minimum wall thickness in Eq. (1), the

    displacement ductility factor is calculated using the

    force-reduction factor of Eq. (10) instead of a constant

    displacement ductility factor. For the plots inFig. 5(a)(d),

    the number of stories is n= 10, the tributary floor weightis w = 8.38 kN/m2, and the wall-to-floor area ratio isp=1%.

    It can be seen from Figs. 5(a)(d) that the hs /tw ratio

    generally decreases with increasing aspect ratio of the wall,

    i.e. thicker wall is required for slender walls. For the low

    a/v ratio of 0.6g/m s1 in Fig. 5(a), which represents a

    soft soil condition, the h s /tw ratio varies from about 14 at

    an aspect ratio of Ar = 3 to about 10 at Ar = 10. Forthis a/v ratio, the hs /tw ratio is not sensitive to the wall

    reinforcement ratio from Ar= 3 to 10. For normal and higha/v ratios in Figs. 5(b) and (c), however, the hs /tw ratio

    becomes increasingly sensitive to wall reinforcement ratio,where a rapid increase in hs /tw ratio is noted for increasing

    wall reinforcement. The increase in hs /tw ratio is due to

    limited yielding of the wall, which occurs as a result of

    increasing lateral strength with increased wall reinforcement

    ratio. For the ultrahigh a/v ratio in Fig. 5(d), yielding is

    reduced significantly, resulting in a very large h s /tw ratio.

    The actual hs /tw ratio is out of range of the y-axis and

    hence not plotted inFig. 5(d). Note that, although results for

    the h s /tw ratio are sensitive to the wall reinforcement ratio

    for the case of normal and high a/v ratios, the minimum

    wall thickness required by [4] is not sensitive to the wall

    reinforcement ratio.

  • 8/11/2019 Final Article Chai and Kunnath

    8/12

    Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063 1059

    It can also be seen from Figs. 5(a)(d) that the hs /twratio increases with increasing a /v ratio, with the smallest

    hs /tw ratio being calculated for the low a/v ratio of

    0.6g/m s1. The small hs /tw ratio for low a/v ratiois due to the changing shape of the elastic response

    acceleration spectrum. Since the fundamental period of 10-

    story walls generally lies in the velocity-controlled regionof the response spectrum, and since the predominant period

    of the ground motion tends to shift towards a longer period

    for low a/v ratio, a decreasing a/v ratio tends to result

    in an increased spectral response, thereby increasing the

    ductility demand, and hence a larger tensile strain and wall

    thickness.

    Results in Figs. 5(a)(d) also show that the hs /tw ratio

    may be smaller than that required by [10] and[4], depending

    on the ground motion parameters, wall reinforcement ratios

    and wall aspect ratios. For the case of low a/v ratio, the

    hs /tw ratio is smaller than that of [10] for an aspect ratio

    of Ar

    3, which means that the required wall thickness

    is larger than that of [10]. On the other hand, the hs /twratio compares fairly well with that of [4], even though the

    ratio tends to be slightly smaller than that of [4] in the large

    aspect ratio range, e.g. Ar 8. In the case of the normala/v ratio, the hs /tw ratio compares fairly well with that

    required by both [10] and [4] for t = 0.5% and 1% inthe large aspect ratio range. For higher reinforcement ratios

    oft= 1.5% and 2%, however, the hs /tw ratio is largerthan that required by [10] and [4]. In the case of high or

    ultrahigh a/v ratios, the h s /tw ratio obtained in this study

    is significantly larger than that required by [10] and [4],

    indicating that the current code provision is conservative

    with respect to these ground motion parameters. It is alsoof interest to note that, while results from this study indicate

    a monotonically decreasinghs /tw ratio, the trend forh s /twratio required by [4] indicates a slight increase in hs /twratio

    for aspect ratio Ar 7 for alla/vratios.

    4.2. Wall-to-floor area ratio

    The fundamental period of structural walls depends on

    the percentage of wall area, as evident in Eq. (6), and

    consequently, the hs /tw ratio is expected to be influenced

    by the wall-to-floor area ratio.Fig. 6(a)(d) show the hs /tw

    ratio for wall-to-floor area ratios of p = 1%, 2%, 3%and 4%. In this case, the hs /tw ratio is assessed for a low

    a/v ratio of 0.6g/m s1 since a low a/v ratio generallyresults in greater spectral response. The same peak ground

    acceleration of 0.4g is used and the tributary floor weight

    is taken as w= 8.38 kN/m2, and the number of stories istaken asn=10.

    Trends observed for differenta/vratios inFigs. 5(a)(d)

    are also observed inFigs. 6(a)(d) for different wall-to-floor

    area ratios. For the wall-to-floor area ratio of p = 1%in Fig. 6(a), the hs /tw ratio is not sensitive to the wall

    reinforcement ratio. For increased wall-to-floor area ratios,

    however, the h s /tw ratio becomes increasingly sensitive to

    the wall reinforcement ratio. For example, for the wall-to-

    floor area ratio of p= 4% inFig. 6(d) and for an aspectratio of Ar = 10, the hs /tw ratio increases from 9 fort= 0.5% to h s /tw= 14 for t= 2%. Also for the caseof a low reinforcement ratio oft= 0.5%, the h s /tw ratioremains relatively constant with respect to the wall-to-floor

    area ratio, as can be seen by comparing the solid lines fort= 0.5% for all wall-to-floor area ratios in Fig. 6(a)(d).As an example, for a reinforcement ratio of t = 0.5%and for an aspect ratio of Ar = 10, the hs /tw ratio is10.4 for p= 1%, compared to the hs /tw ratio of 8.7 forp=4%.

    Results inFig. 6(a)(d) also indicate that theh s /tw ratio

    for low a/v ratio is generally smaller than that required

    by [10] or [4]. The hs /tw ratio required by [4] is also

    smaller than that required by the [10] for large aspect ratios.

    However, comparison between the two codes depends on the

    value of the a/v ratio since the [4] requirement is taken

    to be dependent on the displacement ductility factor. As

    such, the [4] hs /tw , which is expected to increase withincreasing a/v ratio, may increase above that of [10] in

    some cases.

    4.3. Tributary floor weight

    Tributary floor weight, which affects the period of the

    wall, is expected to influence the hs /tw ratio of the wall.

    Figs. 7(a)(d) show the story-height-to-wall-thickness ratio

    for tributary floor weight from w = 6.49 kN/m2 to10.39 kN/m2. The range of floor weight is considered to

    represent reasonable limits in current building design. The

    same lowa/vratio of 0.6g/m s1 and the same peak groundacceleration of 0.4g are used. The number of stories is

    kept at n= 10 and the wall-to-floor area ratio is taken asp=1%.

    It can be seen from Figs. 7(a)(d) that the hs /tw ratio

    is relatively insensitive to the tributary floor weight, even

    though an increased tributary floor weight results in a

    slightly larger hs /tw ratio. For example, for the tributary

    floor weight of w = 6.49 kN/m2 in Fig. 7(a) and for anaspect ratio of Ar = 8, the hs /tw ratio is 9.9 for thelow reinforcement ratio oft= 0.5%. With an increasedtributary floor weight of w = 10.39 kN/m2 in Fig. 7(d)but for the same low reinforcement ratio oft= 0.5% andwall aspect ratio of Ar= 8, the hs /tw ratio is 11.2. Theincrease inhs /twratio is about 11% and is mainly due to the

    longer period of the wall as a result of increased tributary

    floor weight, which tends to reduce the spectral response,

    and hence reduced ductility demand in the wall. The relative

    insensitivity of the h s /tw ratio to the tributary floor weight

    is also observed for higher longitudinal reinforcement ratio.

    For the same aspect ratio of Ar = 8 but for a higherlongitudinal reinforcement ratio oft= 2%, thehs /twratiois 10.4 for w = 6.49 kN/m2 inFig. 7(a). In comparison,the hs /tw ratio increases only slightly to 10.6 for w =10.39 kN/m2 inFig. 7(d). Comparison of results with code

  • 8/11/2019 Final Article Chai and Kunnath

    9/12

  • 8/11/2019 Final Article Chai and Kunnath

    10/12

    Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063 1061

    (a) Floor weightw=6.49 kN/m2. (b) Floor weightw=7.79 kN/m2.

    (c) Floor weightw=9.09 kN/m2. (d) Floor weightw=10.39 kN/m2.

    Fig. 7. Story-height-to-wall-thickness ratio for varying tributary floor weight. Assumed parameters are ( xg )max = 0.4g, ( xg )max= 66.7 cm/s, n = 10,hs= 3.05 m,= 0.05 and p=1%.

    contrast to the monotonically increasing trend of 10-, 15-

    and 20-story walls.

    5. Summary and conclusions

    This paper examines the out-of-plane stability of planar

    structural walls under seismic loading and its implications

    in design. Factors governing out-of-plane buckling as well

    as the methodology for determining the required thickness

    of planar walls are discussed; this is followed by an

    assessment of the minimum wall thickness for a peak ground

    acceleration of 0.4g, assumed to be representative of the

    ground motion for Zone IV of 1997 Uniform Building Code.

    The effect of site conditions is studied by varying the ratio

    of the peak ground acceleration to the peak ground velocity

    (a/v) ratio. Although results are presented primarily in

    terms of story-height-to-wall-thickness ratio, concluding

    remarks will be made with reference to the minimum wall

    thickness. Also because of the large number of parameters

    involved and only results from a limited set of parameters

    being presented, concluding remarks are only intended for

    those parameters.

    Results for 10-story walls with a wall-to-floor area ratio

    of 1% and tributary floor weight of 8.38 kN/m2 indicated

    that the minimum wall thickness increases with decreasing

    a/v ratio, i.e. thicker walls are required for the lower a/v

    ratios. The increase in wall thickness is due to the changing

    shape of the elastic response acceleration spectrum, which

    generally indicates a softening of the site for decreasing

    a/v ratio. Since the period of mid-height walls generally

    falls in the velocity-controlled region of the spectrum and

    since a decreasing a/v ratio tends to result in a longer

    predominant period, an increase in spectral response and

    hence larger thickness is expected for the low a/v ratio.

  • 8/11/2019 Final Article Chai and Kunnath

    11/12

    1062 Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063

    (a) Number of stories=5. (b) Number of stories=10.

    (c) Number of stories=15. (d) Number of stories=20.

    Fig. 8. Story-height-to-wall-thickness ratio for different number of stories. Assumed parameters are( xg )max=0.4g,( xg )max=66.7 cm/s,w=8.38 kN/m2,hs= 3.05 m,= 0.05 and p=1%.

    Results for the same set of 10-story walls also indicated

    that the minimum wall thickness is not conservative with

    respect to the 1997 Uniform Building Code and 1995 New

    Zealand Concrete Code (NZS 3101) for the low a/v ratio

    of 0.6g/m s

    1. For the normal a/v ratio of 1.0g/m s

    1,

    however, results for minimum wall thickness generally agree

    well with those for the codes, whereas for high and ultrahigh

    a/v ratios of 1.4g/m s1 and 2.0g/m s1, both codesare conservative. Assessment based on the low a/v ratio

    of 0.6g/m s1 indicated that the minimum wall thicknessgenerally decreases with increase in the wall-to-floor area

    ratio, even though the amount of decrease depends on the

    wall reinforcement ratio. For the low a/v ratio and wall-

    to-floor area ratios between 1% and 4%, the minimum

    wall thickness is larger than that required by both building

    codes, even though results agree better with [4]. Study in

    this paper also indicated that the minimum wall thickness

    is not sensitive to the tributary floor weight. In contrast,

    however, the minimum wall thickness is rather sensitive to

    the wall height, or equivalently, the number of stories. For

    the low a/v ratio of 0.6g/m s1, wall-to-floor area ratioof 1%, and tributary weight of 8.38 kN/m2, large wall

    thickness is predicted for short walls. The large thickness

    is primarily due to shortening of the structural period,

    which tends to increase the spectral response of the wall

    and hence increased ductility demand. For the case of the

    lowa /v ratio, the minimum wall thickness required by [4]

    also shows reasonable agreement with results for 10- and

    15-story walls. Although results presented in this paper

    are instructive for prescribing the minimum thickness of

    ductile planar structural walls, future code development

    or revision should nonetheless be verified by experimental

    testing of actual structural walls. Analyses in this paper

    were also carried out on the assumption of isolated planar

  • 8/11/2019 Final Article Chai and Kunnath

    12/12

    Y.H. Chai, S.K. Kunnath / Engineering Structures 27 (2005) 10521063 1063

    walls whereas many real buildings may exhibit significant

    torsional response when subjected to seismic load. Further

    investigation of structural wall stability under the influence

    of torsional response of buildings is warranted.

    References

    [1] ACI 318. Building code requirements for structural concrete and

    commentary. Detroit: American Concrete Institute; 1999.

    [2] Chai YH, Elayer TD. Lateral stability of reinforced concrete columns

    under axial reversed cyclic tension and compression. ACI Structural

    Journal 1999;96(5):7809.

    [3] Chai YH, Fajfar P, Romstad KM. Formulation of duration-dependent

    inelastic seismic design spectrum. Journal of Structural Engineering,

    ASCE 1998;124(8):91321.

    [4] NZS 3101. Concrete structures standard part 1 and 2. Private bag

    2439. Wellington 6020, New Zealand, 1995.

    [5] Paulay T. The design of ductile reinforced concrete structural walls

    for earthquake resistance. Earthquake Spectra 1986;2(4):783824.

    [6] Paulay T, Priestley MJN. Seismic design of reinforced concrete and

    masonry buildings. Wiley Interscience Publication; 1992.

    [7] Paulay T, Priestley MJN. Stability of ductile structural walls. ACI

    Structural Journal 1993;90(4):38592.

    [8] Priestley MJN, Kowalsky MJ.Aspects of drift and ductility capacity of

    rectangular cantilever structural walls. Bulletin New Zealand National

    Society for Earthquake Engineering 1998;31(6):7385.

    [9] Tso WK, Zhu TJ, Heidebrecht AC. Seismic energy demands on re-

    inforced concrete moment-resisting frames. Earthquake Engineering

    and Structural Dynamics 1993;22:53345.

    [10] UBC. Uniform building code, vol. 2. In: International conference of

    building officials. 1997.

    [11] Vidic T, Fajfar P, Fischinger M. Consistent inelastic design spectra:

    strength and displacement. Earthquake Engineering and Structural

    Dynamics 1994;23:50721.

    [12] Wallace JW, Moehle JP. Ductility and detailing requirements of

    bearing wall buildings. Journal of Structural Engineering, ASCE

    1992;116(6):162544.

    [13] Wallace JW. New methodology for seismic design of RC shear walls.

    Journal of Structural Engineering, ASCE 1994;120(3):86384.