Software rel. 2.3.x
FILLING CHECK VERSION WITH LEVEL SENSOR + RPM DISPLAY
2
CONTENTS
● Legendofsymbols.....................................................................................................3INTRODUCTION ............................................................................................................4 Productdescription....................................................................................................4INTENDED USE .............................................................................................................4CONTENT OF THE PACKAGE .....................................................................................4PRECAUTIONS .............................................................................................................4RISKS AND PROTECTIONS BEFORE ASSEMBLY ....................................................5 Positioning..................................................................................................................5 Powersupplyandsensorconnection........................................................................5ASSEMBLY DIAGRAMS ...............................................................................................6CONTROLS IN THE MENU ...........................................................................................7 Firstswitchingon.......................................................................................................7 Controlsinthemenu..................................................................................................8 Workparameters........................................................................................................9MENU STRUCTURE ....................................................................................................10PRELIMINARY SETUP FOR USE ............................................................................... 11 Alarms...................................................................................................................... 11 RPMAlarms.............................................................................................................13 Sensors....................................................................................................................14 Flowmetercalibration (TOBEUSEDFORAUTOMATICTANKCALIBRATIONONLY).............................15 Sensors>Manualcalibration...................................................................................16 Tank..........................................................................................................................17 Tankcalibration........................................................................................................18 Language.................................................................................................................22 Unitsofmeasurement..............................................................................................23 Displaycontrast........................................................................................................24 Alarmtones..............................................................................................................25 Keytones..................................................................................................................25 Operatingmode.......................................................................................................26 Setupmanagement..................................................................................................27 Testmenu.................................................................................................................29USE ..............................................................................................................................31MAINTENANCE / DIAGNOSTICS / REPAIRS ............................................................32 Troubleshooting........................................................................................................32END OF LIFE DISPOSAL ............................................................................................32TECHNICAL DATA ......................................................................................................33 Devicetechnicaldata...............................................................................................33 Setupmenu..............................................................................................................34GUARANTEE TERMS .................................................................................................35
3
● Legendofsymbols
= Genericdanger
= Warning
This manual is an integral part of the equipment to which it refers and must accompany the equipment in case of sale or change of ownership. Keep it for any future reference; ARAG reserves the right to modify product specifications and instructions at any moment and without notice.
4
INTRODUCTION
Productdescription
VISIOisaverycompactandaccuratetop-notchmultifunctiondisplay,abletodisplayanykindofinformationconcerningagriculturaltreatments.Operatorcanselecttherequiredfunctionviasoftware.Itcandisplayseveraltypesofvalues,whichchangeaccordingtosetoperatingmodeandtypeofconnectedsensors.
INTENDED USE
This device is designed towork onagriculturalmachinery for spraying and cropsprayingapplications.ThemachineisdesignedandbuiltincompliancewithENISO14982standard(Electromagneticcompatibility-Forestryandfarmingmachines),harmonizedwith2004/108/ECDirective.
CONTENT OF THE PACKAGE
ThetablebelowindicatesthecomponentsthatyouwillfindintheVISIOpackage:
Legend:
1 VISIO2 Fixingkit3 Instructionmanual (onCD-ROM)4 Installationsheet
PRECAUTIONS
•Donotaimwaterjetsattheequipment.•Donotusesolventsorfueltocleanthecaseoutersurface.•Donotcleanequipmentwithdirectwaterjets.•Complywiththespecifiedpowervoltage(12VDC).•Incaseofvoltaicarcwelding,removeconnectorsfromVISIOanddisconnectthepowercables.•OnlyuseARAGgenuinesparepartsandaccessories.
P o w e r c a b l e ,s e n s o r s a n dconnection cablesto be connectedto VISIO must beorderedseparately.
5
RISKS AND PROTECTIONS BEFORE ASSEMBLY
Allinstallationworksmustbedonewithbatterydisconnected,usingsuitabletoolsandanyindividualprotectionequipmentdeemednecessary.
Positioning
1) Set mounting rail in cabin and fasten it with the relevant screws (1), in a position where VISIO can be easily seen and at hands' reach, but away from any moving organs.2) Secure VISIO to rail and push down until locked in place.3) Fasten wiring so that it does not interfere with any moving parts.
Powersupplyandsensorconnection
Sensorsandpowersupplymustbeinstalledandconnectedbyqualifiedpersonnel.VISIOmustbeexclusivelyconnectedtoARAGequipment.WHENARCWELDINGISREQUIRED,MAKESURETHATEQUIPMENTPOWER IS SWITCHED OFF; DISCONNECT POWER CABLES IF NEEDED.ARAGisnotliablefordamagetothesystem,persons,animalsorpropertycausedbyVISIOwrongorunsuitableassembly.Failuretoobservetheaboveinstructionsautomaticallyvoidsthewarranty.
Wirecolor (powercable) Connectionof
red positive
black negative
green countingabort-groundconnection
yellow countingabort-connection+12VDC
power supplysensors
6
ASSEMBLY DIAGRAMS
3
4
+12Vdc
GND
Counting abortGround connection
(green wire)
Counting abortConnection
+12VDC
(yellow wire)
Legend:
1)Powercable2)Connectioncablefordoublesensors3)Levelsensor4)Rpmsensor
7
CONTROLS IN THE MENU
Firstswitchingon
Atfirstswitchingon,VISIOwillrunaguidedprocedureallowingusertosetthedevice'sbasicsettings.
Press toscrollthroughitems,OKtosaveandmoveontonextsetting,orESCtogobacktoprevioussetting.
WARNING:Beforechangingoperatingmode,makesurethatallsensors/flowmetersareDISCONNECTEDfromthedevice.
8
Controlsinthemenu
Inthefollowingpages,accordingtothesetoperatingmode,somemenuitemscouldslightlydifferfromtheshownones.
SWITCHING ONAPressfor1secondBPressthekeyafewtimestoviewthevariousvaluesinextendedmode(ondisplaycentralpart)Everytimethedeviceisswitchedon,itwillshortlyshowapagewiththenameofdeviceandsoftwareversion
SWITCHING OFFAPressfor2seconds
ACCESS TO SETUP MENUFromthemainpage,presskeysatthesametimefor2secondstoopentheSetupMenu
SELECTION AND ACCESS TO MENU ITEMS
APressafewtimestoscrollthroughitems(selecteditemisindicatedbyablackline)BPresstoopentheselectedmenuitem
Thethreedotsunderanitemindicatepresenceofanothersetupmenu
9
EDITING A VALUEAPresstomovethroughdigitsBPressafewtimestoeditthehighlighteddigitCPresstoconfirm.ThedisplaygoesbacktopreviouspageDPresstoexitpagewithoutconfirmingmodification
Editedvaluemustfallwithintherangeshown
Workparameters
0
0% 50%25% 100%75%
0.00.00.00.0 rpm
Fromthemainpage,presskeyfortwosecondstoopenWorkParametersmenu,andsetvaluesforLevelcorrection.
10
MENU STRUCTURE
Alarms
Tank reserveMax levelSens. 1 min rpmSens. 1 max rpm
Sensors
Calib. flowmeterMan. calibration
Options
Language
Units of measurem.
Flowrate
VolumelGalm
3
Display contrast
Alarm tones
Keytones
l/minGPMm
3/h
Operating mode
0 rpm
0
0% 50%25% 100%75%
Tank
Capacity
Tank zero value
CalibrationMan. calibrationAuto calibration
Load/Save TankSave tank profileLoad tank profile
Rpm 1Man. calibration
Setup management
Save setupLoad setup
Test
Firmware versionBattery voltageDisplayKeysSensors
Level/RPM
11
PRELIMINARY SETUP FOR USE
Alarms
Setthedesiredalarmdisplaythresholds.
Tank reserve alarm
Setthevalueoftheminimumfluidquantityleftinthetank.
1)Opentankreservealarmmenu(Setupmenu>Alarms>Tankreserve).ThedisplaywillshowthecurrentsettingbelowtheselecteditemPress OK toedittheselectedmenuitem
2)Todeactivatethealarm,press and
atthesametimeuntilthesetvalue
disappearsandthemessageOFF isdisplayedinstead.Carryoutthesameproceduretoenablealarmagain.3)Setalarmvalue:A)PresstomovethroughdigitsB)PressafewtimestoeditthehighlighteddigitC)Presstosavechanges,orD)Presstoquitthepagewithoutconfirmingchanges
12
Maxtanklevel
Set themaximumtankcapacitypercentagevaluefor thedesiredalarmactivationthreshold.
1)Opentankmaxlevelmenu(Setupmenu>Alarms>Maxlevel).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.PressOKtoedittheselectedmenuitem.
2)Toactivatethealarm,press and
atthesametimeuntilthemessageOFFgoesoffandthealarmvalueisdisplayedinstead.Carryoutthesameproceduretodisablealarmagain.3)Setalarmvalue:A)PresstomovethroughdigitsB)PressafewtimestoeditthehighlighteddigitC)Presstosavechanges,orD)Presstoquitthepagewithoutconfirmingchanges
13
RPMAlarms
SetthedesiredalarmdisplaythresholdsforminimumandmaximumRpmvalues.
1)OpenAlarmmenu(Setupmenu>Alarms).
MinimumandmaximumRpmalarmsaresetinthesameway.
Thedisplaywillshowthecurrentsettingbelowtheselecteditem.PressOKtoedittheselectedmenuitem.
Thismenuallowssettingtwodifferentsensors(ifavailable).
Incaseonlyonesensorisused,useitemsrelatedtosensor1toperformthecorrectsettings.
Sens. 1 min rpm
Min ValueMax Value
19999
OFF o
2)Toactivatethealarm,press and
atthesametimeuntilmessageOFFgoesoffandtheRpmalarmvalueisdisplayedinstead.Carryoutthesameproceduretodisablealarmagain.
Sens. 1 min rpm
Min ValueMax Value
19999
o0010 rpmC B
D A
3)Setalarmvalue:A)PresstomovethroughdigitsB)PressafewtimestoeditthehighlighteddigitC)Presstosavechanges,orD)Presstoquitthepagewithoutconfirmingchanges
14
Sensors
1)OpenSensorsmenu(Setupmenu>Sensors)
Themenuitemsdisplayedbelowchangeaccordingtothesetoperationmode:whenmoreitemsareavailable,selectthedesiredoneandpressOKtoeditit.
15
Flowmetercalibration (TOBEUSEDFORAUTOMATICTANKCALIBRATIONONLY)
Duetothedifferentsystemconfigurations(tubes,valves,etc.)ratereadingcouldnotbecorrect.Itisthereforerecommendedtoperformasprayingtest.Ifmeasuredvalueisdifferentfromactualvalue,changetherateconstantthroughanautomaticcalibrationprocedureormanuallycalculatetheconstant.
Manual calibration
Inordertomanuallysetrateconstant,calculateandsetsuitableconstantusingthefollowingformula:
1)Openmanualcalibrationmenu(Setupmenu(Setupmenu>Sensors>Calib.flowmeter>Man.calibration).UnderCalibration,menu,selectMan.Calibration,toviewcurrentlysetconstantvaluebelowtheitem.PressOKtoeditthevalue.
Forflowmeterconstantvalue,refertothecorrespondingmanual.
2)Setflowmeterconstantvalue:A)PresstomovethroughdigitsB)PressafewtimestoeditthehighlighteddigitC)Presstosavechanges,orD)Presstoquitthepagewithoutconfirmingchanges
[quantity measured by equipment]
[actually sprayed quantity]x [constant indicated on flowmeter body]
16
Sensors>Manualcalibration
VISIOprocesses the rotationspeed information related toaspecificpart throughthepulsesfromtheRpmsensor.ThemanualcalibrationallowsenteringtheRpmconstantvalue.
1)OpenSensorsmenu(Setupmenu>Sensors).
2)Presstoopenmanualcalibrationmode.
Thismenuallowssettingtwodifferentsensors(ifavailable).
Incaseonlyonesensorisused,useitemsrelatedtoRpm1toperformthesettings.
3)SettheRpmconstantvalue,i.e.thenumberofdetectionpoints,suchasmagnetsorboltsfittedontherotatingshaftwhoserotationspeedshallbedetected:A)PresstomovethroughdigitsB)PressafewtimestoeditthehighlighteddigitC)Presstosavechanges,orD)Presstoquitthepagewithoutconfirmingchanges
17
Tank
Fromthismenuitispossibletoviewandsetanumberoftankvalues.-Capacity:thedisplayshowsthemaximumtankcapacityvalue,aspreviouslycalculatedthroughcalibration. Thisvalueisread-only.
Tank zero value
Setlevelsensorzerovalue.Thelevelsensormustberesetinthefollowingcases:1)Iftherearediscrepanciesbetweenthequantityoffluidinthetankandthevaluemeasuredbythelevelsensor(e.g.,fluidpresencedetectedbutemptytank).2)EVERYTIMEacalibrationcurveisuploadedviaUSB.ThetankzerovaluemustALWAYSbesavedWITHANEMPTYTANK.
1)Opentankzerovaluemenu(Setupmenu>Tank>Tankzerovalue).ThedisplaywillshowthecurrentsettingbelowtheselecteditemPressOKtoedittheselectedmenuitem
2)PressOK:VISIOwillsavethelevelsensorzerovalue,whichwillbeshowninthebottompartofthedisplay(e.g.,3.964mAintheimageontheside).
Ifasensormalfunctionoccurs,themessageCheck sensor! willbeshowninthetoppartofthedisplay.
18
Tankcalibration
Thetankprofilecalibrationcanbecarriedoutinmanualorautomaticmode.Duringcalibration,VISIOwillsaveupto200calibrationpointstocreatethetankprofilecurve.If necessary, the tank profile can be saved and reimported intoVISIO orcompatibleARAGComputers(Bravo180S/300S/400S/Delta80/Ninja)atalatertime(e.g.,whenreusingthesametank).Beforestartingtheprocedurecarryoutthefollowingoperations:1)Fill the tankwith cleanwaterWITHOUTADDINGCHEMICALSUBSTANCES.Thetankmustbefull.2)Visuallycheckthereachedlevel.
Automatic tank calibration
1)Openautomaticcalibrationmenu(Setupmenu>Tank>Autocalibration).PressOKtoedittheselectedmenuitem.
2)Setthetankmaximumcapacityvalue,i.e.,thetheoreticalquantityoffluidthatwaspreviouslyintroduced:A)PresstomovethroughdigitsB)PressafewtimestoeditthehighlighteddigitC)Presstosavechanges,orD)Presstoquitthepagewithoutconfirmingchanges.Assoonasmenuisopen,theequipmentisreadytostartmeasuringwithnofurthercontrolsbeingrequired.
19
3)Starttankdraining.Thedisplaywillstartshowingtheincreasingmeasuredfluidquantityvalue(centralareaofthedisplay),theinstantflowratevalue(bottomright),andtheprogressivenumberofmeasuredcalibrationpoints(bottomleft).
Ifasensormalfunctionoccurs,themessageCheck sensor! willbeshowninthetoppartofthedisplay.
4)Oncethetankhasbeencompletelydrained,thevalueinthecentralareaofthedisplaywillstopchanging,andthemessageCompl. calibr.? will appearinthedisplaytoppart
PressOKfor1secondtocompletecalibration.5)Thedisplaywillgobacktothepreviousmenuandwillshowtheacquiredvalue.Incaseofmeasurementerrors,orifitisnecessarytostopthecalibration,pressESCfor2secondstoquitthecalibrationprocedurewithoutsaving.Inthiscase,thecurvewillbetheonepreviouslymeasured,orthedefaultcurve.
20
Manual tank calibration
Toperformmanualcalibration,proceedasfollows:1)Calculate thesuitable calibration intervalwith respect to tankmaximumcapacity,bearinginmindthat:-itispossibletosaveupto200calibrationpoints;-ahighnumberofcalibrationpointsmakesformoreaccuratemeasurements.2)Adoptareliablemethodformeasuringthefluidquantitythatwaspreviouslycalculated.Example:
[2000 liters] = maximum tank capacity;[200 points] = set calibration points;[10 liters] * = measurement value in liters.*IMPORTANT:Setameasurementvaluethatisslightlyhigher(e.g.,11liters)thantheformula,inordertomakeupforanyerrorsintheevaluationoftankmaximumcapacity.
1)Openmanualcalibrationmenu(Setupmenu>Tank>Man.Calibration).
PressOKtoedittheselectedmenuitem.Assoonasmenuisopen,theequipmentisreadytostartmeasuringwithnofurthercontrolsbeingrequired.
2)Starttankdraining.Oncethemeasurementcontainerisfull,stopdrainingand,inthedisplaycentralpart,enterthevolumeofthedrainedfluidwithrespecttothepreviouscalibrationpoint:A)PresstomovethroughdigitsB)PressafewtimestoeditthehighlighteddigitC)Presstoconfirm.
[2000 liters]
[200 points]= [10 liters]
21
Themessage Stabilization willappearinthedisplaytoppartforafewseconds,thenitwillswitchbackto Rec. cal. point.
Thevalueofcalibrationpointswillincreasebyoneunit,andthevalueoftheprogressivelydrainedpartialvolumewillshowthequantityoffluidmeasureduptothatmoment.VISIOisreadyforanewmeasurement.
Itispossibletosavecalibrationpointsobtainedwithdifferentquantitiesofdrainedfluid.
4)Oncethetankhasbeenemptiedcompletely,pressOKkeyfor1secondtocompletethecalibrationprocessandsavetherelevantcurve.
5)Thedisplaywillgobacktothepreviousmenuandwillshowtheacquiredvalue.Incaseofmeasurementerrors,orifitisnecessarytostopthecalibration,pressESCkeyfor1secondtoquitthecalibrationprocedurewithoutsaving.Inthiscase,thecurvewillbetheonepreviouslymeasured,orthedefaultcurve.
22
Language
Setthedesiredlanguage.
Options
Language
English
Units of measurem.Display contrast
Openlanguagesettingmenu(Setupmenu>Options>Language).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.
PressOK toeditlanguage.
2 1
2
Language
English
ČeskDeutsch
Español
1)Selectalanguagethrough .
2)PressOK tosave,orESC toquitwithoutsaving.
23
Unitsofmeasurement
Setunitofmeasurementforthevaluesdetectedbythedevice.
Rate units of measurement
Openinstantrateunitofmeasurementsettingmenu(Setupmenu>Options>Unitsofmeasurem.>Flowrate).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.PressOKtoselectflowrateunitofmeasurement.
1)Selectaunitthrough .
2)PressOKtosave,orESCtoquitwithoutsaving.
Volume units of measurement
Openvolumeunitofmeasurementsettingmenu(Setupmenu>Options>Unitsofmeasurem.>Volume).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.PressOKtoselectvolumeunitofmeasurement.
1)Selectaunitthrough .
2)PressOKtosave,orESCtoquitwithoutsaving.
24
Displaycontrast
Setdisplaycontrast.
Opendisplaycontrastmenu(Setupmenu>Options>Displaycontrast).
Thedisplaywillshowthecurrentsettingbelowtheselecteditem.PressOK toedittheselectedmenuitem.
1)Setavaluethrough .Everytimeyoupressit,valuewillincreaseby5%up
to100%.Usekey todecreasevalue
by5%.2)PressOK tosave,orESC toquitwithoutsaving.
25
Alarmtones
Enable/disablethealarmtones.
Openalarmtonesmenu(Setupmenu>Options>Alarmtones).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.PressOK toedittheselectedmenuitem.
1)Setstatusthrough .
2)PressOK tosave,orESC toquitwithoutsaving.
Keytones
Enable/disablekeytones.
1)Openkeytonesmenu(Setupmenu>Options>Keytones).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.PressOK toedittheselectedmenuitem.
1)Setstatusthrough .
2)PressOK tosave,orESC toquitwithoutsaving.
26
Operatingmode
Setrequiredoperatingmode.
Openoperatingmodemenu(Setupmenu>Options>Operatingmode).Thedisplaywillshowthecurrentsettingbelowtheselecteditem.PressOK tochangetheoperatingmode.
1)Selecttherequiredoperatingmode
through .
2)PressOK tosave,orESC toquitwithoutsaving.
WARNING:OnceOKispressed,thepageontwhesidewillbedisplayed.Beforechangingoperatingmode,makesurethatallsensorsareDISCONNECTEDfromthedevice.PressOKtoconfirmchanges.ConnectthesensorsREQUIREDFORTHE SET OPERATING MODE.
27
Setupmanagement
VISIOsettingscanbeloadedfromorsavedonaUSBpendriveinordertoreconfigureit ifrequired,fixproblemsorsetanotherVISIOwithnoneedtorepeatallmanualoperations.Onceinstallationiscompleted,andVISIOoperationhasbeenchecked,werecommendtosaveallsettingsontoaUSBpendrive.TobeabletousethefollowingfunctionsitisnecessarytoinsertaUSBpendriveintherelevantportatthebottomofVISIO.
1)OpenSetupmanagementmenu(Setupmenu>Setupmanagement).
PressOK toedittheselectedmenuitem.
Load setupAllowstoselectaconfigurationfilesavedintheUSBpendriveandtosetVISIOagain.WARNING:ByloadingtheSETUP.BIN filecontainedintheUSBpendriveontotheVISIO,allcurrentsettingswillbelost.
1)Selectthedesiredcontrolthrough key.2)PressOK toconfirmloading,orESC toquitwithoutsaving.
TheSETUP.BINfilecanbeloadedonlyifitissavedintheUSBpendriverootdirectory.Ifsetupdownloadinvolveschangingoperatingmodeandusingdifferentsensorsthantheonesinuse,makesurethatallsensorsareDISCONNECTEDfromthedevice.PressOKtoconfirmloading.Reconnectsensors.
28
Save setupAllowssavingVISIOconfigurationfileontheUSBpendrive:itwillbepossibletoloaditagainanytimethesamesettingsneedtoberetrieved.
1)Selectthedesiredcontrolthrough
key.2)PressOK toconfirmsaving,orESC toquitwithoutsaving.
IfaSETUP.BINfileisalreadypresentintheUSBpendriverootdirectory,thefilewillbeoverwritten.
29
Testmenu
ThismenuallowsusertoviewsomedataandcarryoutanoperationtestofVISIO:-Firmwareversion:thedisplayshowsthefirmwareversioninstalled.-Batteryvoltage:thedisplayshowsthepowervoltageofthedevice.
Display test
Displaytestchecksthedevicedisplaycorrectoperation.
1)Opendisplaytestmenu(Setupmenu>Test>Display).Press OK toperformthetest.
Allpixelsondisplayareturnedon.PressESCtogobacktopreviouspage.
Keys test
Keystestchecksthedevicekeyscorrectoperation.
Openkeystestmenu(Setupmenu>Test>Keys).
Press OK toperformthetest.
1)Pressanykeyandthecorrespondingdisplayareawillturnon.PressESC toquit:assoonasyouacknowledgetheswitch-ononofthecorrespondingareaonthedisplay,devicewillgobacktopreviouspage.
30
Sensors test
Sensorstestcheckscorrectoperationofthesensorsconnectedtothedevice.
Opensensorstestmenu(Setupmenu>Test>Sensors).
Press OK toperformthetest.
Thedisplaywillshowthecurrentsensorreadingbelowtheselecteditem.1)Severalsensorscouldbedisplayed,dependingonthesetoperatingmode.Inthiscase,selectrequiredsensor
through .
2)PressESCtoquit.
31
USE
Themainpageshowsthedisplaydividedintothreehorizontalparts:-toppart:theprogressbarshowsthetanklevelinpercentage;-centralpart:thevaluerepresentsthevolumeoffluidinsidethetank;-bottompart:Thevaluerepresentsthenumberofrevolutionsperminuteoftherotatingpart.
Pressthe keyseveraltimestoview
avalueinextendedmodeuntilvalueisondisplaycentralpart.
32
MAINTENANCE / DIAGNOSTICS / REPAIRS
•Cleanonlywithasoftwetcloth.•Donotuseaggressivedetergentsorproducts.•Donotcleanequipmentwithdirectwaterjets.
Troubleshooting
FAULT CAUSE REMEDY
VISIOisoffordoesnotswitchon
Nopowersupply Checkpowercableconnections
DeviceisOFF PresstheONkey
VISIOshowswrongdata
Wrongsetup Checkdisplayeddatasetup
Sensorfault ContactthenearestAssistanceCenterVISIOfault
Fillingpump(ifany)doesnotstart
PumpStopModulenotpowered
Checkpowersupplyconnection
END OF LIFE DISPOSAL
Disposeofthesystemincompliancewiththeestablishedlegislationinthecountryofuse.
33
TECHNICAL DATA
Devicetechnicaldata
Description VISIO
Display GraphicLCD,128x64pixels,back-lighting
Powersupplyvoltage 9÷16Vdc
Protectionagainstshort-circuit •
Protectionagainstpolarityinversion •
Max.frequency 1.2KHz
Analoginputs 4÷20mA
Digitaloutput-Maxcurrent 100mA
Maximumpowerinput(withnosensorsconnected) 160mA
Operatingtemperature -20°C÷70°C-4°F÷+158°F
Storagetemperature -30°C÷80°C-22°F÷+176°F
Size 126x79x66mm
Weight 245g
34
Setupmenu
Data Min. Max. Default UoM Notes
Calib.flowmeter Calibration 1 10000 OFF pls/l --
Rpm Calibration 1 9999 100 pls/rv
Alarms
Min.RPM 1 9999 OFF rpm Alarmcanbedisabledbysettingvalueto"OFF"
Max.RPM 1 9999 OFF rpm Alarmcanbedisabledbysettingvalueto"OFF"
Reservetank 1 1000 50 l Alarmcanbedisabledbysettingvalueto"OFF"
Max.level 0.1 100 OFF % Alarmcanbedisabledbysettingvalueto"OFF"
Display Contrast 0 100 50 % --
Options
Language - - English -
Availablelanguages:Italiano,English,Español,Português,Français,Deutsch,Cesky,Polski,Русский,Magyar,ニホン .
Flowrateunitsofmeasurement - - l/min. l/min. Availableunitsofmeasurement:
l/min,GPM,m3/h
Volumeunitsofmeasurement - - l liters Availableunitsofmeasurement:
l,gal,m3
35
GUARANTEE TERMS
1. ARAGs.r.l.guaranteesthisapparatusforaperiodof360days(1year)fromthedateofsaletotheclientuser(dateofthegoodsdeliverynote).
Thecomponentsoftheapparatus,thatintheunappealableopinionofARAGarefaultyduetoanoriginaldefectinthematerialorproductionprocess,willberepairedorreplacedfreeofchargeatthenearestAssistanceCenteroperatingatthemomenttherequestforinterventionismade.Thefollowingcostsareexcluded:
- disassemblyandreassemblyoftheapparatusfromtheoriginalsystem;- transportoftheapparatustotheAssistanceCenter.2. Thefollowingarenotcoveredbytheguarantee:- damagecausedbytransport(scratches,dentsandsimilar);- damageduetoincorrectinstallationortofaultsoriginatingfrominsufficientor
inadequatecharacteristicsoftheelectricalsystem,ortoalterationsresultingfromenvironmental,climaticorotherconditions;
- damageduetotheuseofunsuitablechemicalproducts,forspraying,watering,weedkillingoranyothercroptreatment,thatmaydamagetheapparatus;
- malfunctioningcausedbynegligence,mishandling,lackofknowhow,repairsormodificationscarriedoutbyunauthorizedpersonnel;
- incorrectinstallationandregulation;- damageormalfunctioncausedbythelackofordinarymaintenance,suchascleaning
offilters,nozzles,etc.;- anythingthatcanbeconsideredtobenormalwearandtear.3. Repairingtheapparatuswillbecarriedoutwithintimelimitscompatiblewiththe
organizationalneedsoftheAssistanceCenter. Noguaranteeconditionswillberecognizedforthoseunitsorcomponentsthathavenot
beenpreviouslywashedandcleanedtoremoveresidueoftheproductsused;4. Repairscarriedoutunderguaranteeareguaranteedforoneyear(360days)fromthe
replacementorrepairdate.5. ARAGwillnotrecognizeanyfurtherexpressedorintendedguarantees,apartfrom
thoselistedhere. Norepresentativeorretailerisauthorizedtotakeonanyotherresponsibilityrelativeto
ARAGproducts. Theperiodoftheguaranteesrecognizedbylaw,includingthecommercialguarantees
andallowancesforspecialpurposesarelimited,inlengthoftime,tothevaliditiesgivenhere.
InnocasewillARAGrecognizelossofprofits,eitherdirect,indirect,specialorsubsequenttoanydamage.
6. ThepartsreplacedunderguaranteeremainthepropertyofARAG.7. Allsafetyinformationpresentinthesalesdocumentsregardinglimitsinuse,
performanceandproductcharacteristicsmustbetransferredtotheenduserasaresponsibilityofthepurchaser.
8. AnycontroversymustbepresentedtotheReggioEmiliaLawCourt.
C o n f o r m i t y D e c l a r a t i o n
ARAG s.r.l.Via Palladio, 5/A42048 Rubiera (RE) - ItalyP.IVA 01801480359
Dichiara
che il prodottodescrizione: Visualizzatore multifunzionemodello: Visioserie: 4670610
risponde ai requisiti di conformità contemplati nella seguente Direttiva Europea:2004/108/CE e successive modificazioni(Compatibilità elettromagnetica)
Riferimenti alle Norme Applicate:UNI EN ISO 14982(Macchine agricole e forestali - Compatibilità elettromagneticaMetodi di prova e criteri di accettazione)
Rubiera, 6 Marzo 2013
Giovanni Montorsi
(Presidente)
42048 RUBIERA (Reggio Emilia) - ITALYVia Palladio, 5/ATel. +39 0522 622011Fax +39 0522 [email protected]
Only use genuine ARAG accessories or spare parts to make sure manufacturer guaranteed safety conditions are maintained in time. Always refer to ARAG spare parts catalog.
D20
287_
GB
-m04
03/2
017