Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

Upload: jennifer-wiley

Post on 26-Mar-2015

215 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

Field Proven Performance – Industrial Grade Support

Training:DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

Page 2: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

2

PLR5000 radio based products PLR580D – discrete only PLR580DA – discrete & analog

SRM radio based products DD1000/SRM – discrete only DDAA1000/SRM – discrete & analog

Products

NOTE: Master and Remote are different products

Page 3: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

3

Block Diagram

Wireless I/O Extender Block Diagram

Discrete I/O (STD)ToCoax/Antenna

DataPowerControl

Power (12VDC)

Modem Internals

InterfaceModule

Standard: DiscreteOptional: 4 – 20ma

RFModule

(900MHz or 2.4GHz)

Indicators

JumpersConfig Port

4 – 20ma I/O (OPT)

Page 4: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

4

Inputs Self-sensing, no external power required G – shared common

Outputs Open collector transistor, requires 12 or

24VDC power G – shared common (emitters) On RF signal loss

Master outputs hold last value Remote outputs return to OFF state

Discrete I/O

Page 5: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

5

Discretes – Master to Remotes

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

REMOTEPWR

DC POWER -

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

MASTERPWR

DC POWER -

STATUS

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

REMOTEPWR

DC POWER -

DC DC

Remote 0 Remote 1Master

Page 6: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

6

Discretes – Remotes to Master

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

MASTERPWR

DC POWER -

STATUS

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

REMOTEPWR

DC POWER -

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

REMOTEPWR

DC POWER -

DC

Remote 0 Remote 1Master

Page 7: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

7

Inputs Do not provide loop power Single ended, G terminal shared by all inputs

Outputs Provide power Single ended, G terminal shared by all

outputs On RF signal loss

Master outputs return to 4ma Remote outputs hold last value

Analog I/O

Page 8: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

8

Analog – Master to Remotes

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

REMOTEPWR

DC POWER -

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

MASTERPWR

DC POWER -

STATUS

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

REMOTEPWR

DC POWER -

DC

A-txAMa

4-20

A-txBMa

4-20

A-txCMa

4-20

A-txDMa

4-20

A-txEMa

4-20

A-txFMa

4-20

A-txGMa

4-20

A-txHMa

4-20

A-rxAMa

4-20

A-rxBMa

4-20

A-rxCMa

4-20

A-rxDMa

4-20

A-rxEMa

4-20

A-rxFMa

4-20

A-rxGMa

4-20

A-rxHMa

4-20

Remote 0 Remote 1Master

Power only if transmitters don’t provide power

PLR580DA / DDAA1000/SRM configuration software was used to map four analog channels to each remote.

4-20

ma

Tra

nsm

itte

rs

4-20ma Receivers

Page 9: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

9

Analog – Remotes to Master

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

REMOTEPWR

DC POWER -

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

MASTERPWR

DC POWER -

STATUS

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

REMOTEPWR

DC POWER -

A-rxAMa

4-20A-rxBMa

4-20 A-rxCMa

4-20A-rxDMa

4-20 A-rxEMa

4-20A-rxFMa

4-20 A-rxGMa

4-20A-rxHMa

4-20

Remote 0 Remote 1Master

Power only if senors don’t provide it

PLR580DA / DDAA1000/SRM configuration software was used to map four analog channels to each remote.

DC

A-txAMa

4-20

A-txBMa

4-20

A-txCMa

4-20

A-txDMa

4-20

DC

A-txEMa

4-20

A-txFMa

4-20

A-txGMa

4-20

A-txHMa

4-20

4-2

0ma

Tra

ns

mit

ters

4-2

0ma

Rec

eiv

ers

4-2

0ma

Tra

ns

mit

ters

Page 10: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

10

PLC Interface

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

REMOTEPWR

DC POWER -

8CONTACT CLOSURE INPUT

G1234567 8CONTACT CLOSURE OUTPUT

G1234567

84 – 20 mA OUTPUT

G 1 2 3 4 5 6 784 – 20 mA INPUT

G 1 2 3 4 5 6 7

DATA-LINC GROUP

TxCD

Rx

(425)882-2206

PLR580Wireless I/O Extender

MASTERPWR

DC POWER -

STATUS

DL-M

DK-M

DJ-M

DI-M

GND

DD-M

DC-M

DB-M

DA-M

GND

GND

AI-M

AJ-M

AK-M

AL-M

AB-M

AC-M

AA-M

GND

AD-M

DL-R

DK-R

DJ-R

DI-R

GND

SW-4

SW-3

SW-2

SW-1

R1

R2

R3

R4

DA-R

DC-R

DD-R

DB-R

AI-R

AJ-R

AK-R

AL-R

GND

TX-4

TX-3

TX-2

TX-1

RX-4

RX-3

RX-2

RX-1

AD-R

AC-R

AB-R

AA-R

GND

Master

Remote

Process Discrete InputsProcess Discrete Outputs

Process 4-20 ma Outputs

Process 4-20 ma Inputs

Power Supply

LED PS1

LED PS2

MY PLC

CPU 7E

LED 4

LED 5LED 1

LED 2

LED 3

RUN TEST STOP

LED 6

LED 7

LED 8

10/100

SP 1

SP 2

Ethernet

AI-6SE

4-20 maInput

Module

DI-16CO

DiscreteInput

DO-16CO

DiscreteOutput

AO-6SE

4-20 maOutputModule

note 2

note 2

note 1

note 1

NOTES1. Analog inputs require power either from the tranducer or an external source.

2. Digital outputs require external power.

GND

Page 11: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

11

Both RF and I/O modules must be configured RF Module

Can use all radio features (P2P, P2MP, repeaters...) Configured using HyperTerminal

I/O module configured using EEPROM software Defines number of remotes in master Assigns the remote number (address) Sets I/O module baud rate (must match to radio

baud rate) Maps (assigns) analog points for each remote

NOTE: REMOVE I/O TERMINAL STRIPS OR I/O POWER BEFORE CONFIGURING

I/O Extender Configuration

Page 12: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

12

Configuration Port & Jumpers

Configuration Port

* Strap P1/P2 to RUN RF for normal operation.* Strap P1/P2 to CONFIG RF to configure RF module with Hyperterminal.* Strap P1/P2 to CONFIG PIC to configure I/O module using EEPROM software.

Radio Menu Button

Page 13: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

13

Module Configuration

I/O Extender Configuration

DataPowerControl

Modem Internals

InterfaceModule

Standard: DiscreteOptional: 4 – 20ma

RFModule

(900MHz or 2.4GHz)

Indicators

JumpersConfig Port

To configure:- Jumpers set to “Config RF”- Use Hyperterminal

To configure:- Jumpers set to “Config PIC”- Use EEPROM software

Page 14: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

14

Configuration Utility Program

Page 15: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

15

INDICATOR

DESCRIPTION

CD Carrier DetectP2P Networks – Solid ONP2MP Networks

Remotes – Solid ONMaster – Flashing when receiving data from

remote(s)

TX Flashing as RF data is being received

RX Flashing as RF data is being sent

STATUS (indicator on master unit only)OFF – Normal operationFLASHING or ON – Failed communications

POWER ON – Unit power applied (does not indicate I/O power)

Indicator Lights

Page 16: Field Proven Performance – Industrial Grade Support Training: DD(AA)1000 & PLR580D(A) Wireless I/O Extenders

16

Always remove I/O power when configuring or reseting the units. This is not required for new version products with configuration switches.

It is possible during power brownout conditions that the I/O module gets “lost” and must be reset by cycling the power (remove I/O power too). New version products with configuration switches correct this.

Early model I/O extenders cannot be field configured.

ERRATA