fiat_binder
DESCRIPTION
Architectural Structural Electrical Civil Cover Project Data/Schedules General Notes Accessibility Standards Accessibility Standards Accessibility Standards Accesibility Standards Site Plan First Floor Plan Finish Plan Furniture Plan Reflected Ceiling Plan Roof Plan Exterior Elevations Building Sections Enlarged Plans Wall Sections Wall Sections S T A T E OF T E X A S 4710 Bellaire Blvd. Suite 105 - Bellaire, TX 77401 - Tel: (713) 660-6102 - Fax: (713) 660-8550 REG P1 Plumbing Plan 2 72 4TRANSCRIPT
REG ISTERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
ArchitecturalG-001G.01G.02A0.1A0.2A0.3A0.4A1.0A1.1A1.2A1.3A1.4A1.5A2.1A3.1A4.1A5.1A5.2
CoverProject Data/SchedulesGeneral NotesAccessibility StandardsAccessibility StandardsAccessibility StandardsAccesibility StandardsSite PlanFirst Floor PlanFinish PlanFurniture PlanReflected Ceiling PlanRoof PlanExterior ElevationsBuilding SectionsEnlarged PlansWall SectionsWall Sections
4710 Bellaire Blvd. Suite 105 - Bellaire, TX 77401 - Tel: (713) 660-6102 - Fax: (713) 660-8550
GOREE
Clear Lake Fiat15711 Gulf Freeway, Tx 77598
Job Number: 1034Client: Garff Auto Group
S1 Foundation PlanS2. Structural DetailsS.3 General Notes
Structural
M1.1 Mechanical PlanMechanical
E1.1 Electrical PlanE2.1 Power PlanE3 Electrical Site Plan
Electrical
P1 Plumbing PlanPlumbing
A NEW FACILITY DESIGN ISSUED FOR PERMIT 1ST OF APRIL TWENTY ELEVEN
C1 Grading and drainage planC2 Site Utility planC3 Storm Water Pollution Prevention planC4 Sanitary Sewer and Storm Sewer DetailsC5 Storm Water Polluition Prevention Plan
Civil
G.01
REG I
STERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\1034_prj06.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 GULF FREWAY,Tx 77598Job Number: 1034Client: Garff AutoGroup
192
Index
Friday, March 11, 20115:55 PM
Revision History:
ID 01 02 02 03 03 04 05 06 07 08 09 11 12 29 29 29 30Quantity 1 1 1 1 2 1 1 1 1 1 1 1 1 1 2 2 1
W x H Size 50'-0"x12'-0" 17'-5"x10'-0" 17'-5 3/8"x10'-0" 21'-6"x10'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 5'-10 7/8"x8'-0" 3'-0"x8'-0" 8'-0"x8'-0" 3'-0"x6'-0"
2D Symbol
3D Front View
Door Legend
2006 INTERNATIONAL FIRE CODE
2008 NATIONAL ELECTRIC CODE
NEW FIAT DEALERSHIP, HOUSTON, TX
2006 INTERNATIONAL BUILDING CODE
2006 UNIFORM MECHANICAL CODE
GENERAL
APPLICABLE CODES:
PROJECT:
2008 INTERNATIONAL ENERGY CONSERVATION CODE
TYPE OF PROJECT: AUTOMOTIVE SHOWROOM / SALES BUILDING
TEXAS ACCESSIBILITY STANDARDS
BUILDING CODE ANALYSIS:
STRUCTURAL FRAME, INCL. COLUMNS, GIRDERS, TRUSSES:
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS. (HOURS)
BEARING WALLS:
ROOF CONSTRUCTION, INCLUDING SUPPORTING BEAMS AND JOISTS:
EXTERIOR WALLS:INTERIOR WALLS:
PER TABLE 601 (FOR TYPE II B CONSTRUCTION)
NONBEARING WALLS AND PARTITIONS:EXTERIOR WALLS:INTERIOR WALLS:FLOOR CONSTRUCTION, INCLUDING SUPPORTING BEAMS AND JOISTS:
a.b.
c.
d.e.
00
O
0
0
0
0
6. 1 PERSON / 100 S.F. (GROSS AREA)4,707 S.F./100 S.F. = 48 OCCUPANTS
BUSINESS AREAS:ACTUAL OCCUPANT LOADS:
NUMBER OF EXITS: TABLE 1018.1
a. OCCUPANCY B: 4 STORIES; 23,000 SF PER FLOOR
4.
OCCUPANCY TYPE: (BUSINESS GROUP B)
PER TABLE 503
PER SECTION 304
3.
2.
CONSTRUCTION TYPE: II B ( UNSPRINKLERED )PER SECTION 602 AND TABLE 601.
1.
ALLOWABLE HEIGHT AND BUILDING AREAS
NUMBER OF REQUIRED EXISTS 48 OCCUPANT X 0.2" = 9.6" (MIN. 2 EXISTS)
1.
PLUMBING CODE ANALYSIS:
FIRE EXTINGUISHERS:TABLE 906.3(1), 906.3(2), AND NFPA 10
75 FEETB. MAXIMUM TRAVEL DISTANCE IS
RATING IS 2A.A. BASIC MINIMUM EXTINGUISHER
REQUIRED: 1 / PROVIDED: 11. IN BUSINESS OCCUPANCY (SHOWROOM)
REQUIRED PLUMBING FIXTURES PER INTERNATIONAL BUILDING CODE, 2003 EDITION - TABLE 2902.1
LAV. PROVIDED
MALE FEMALE
1 121
W.C. PROVIDED
MALE FEMALE FOUNTAIN
1 HI-LO
ELECTRIC DRINKING
11GROUP B
OCCUPANCY URINALS **
FEC FIRE EXTINGUISHER
4,707 S.F. / 100 (B OCCUPANCY) = 48 OCCUPANTS = 48/2 = 24 OF EACH SEX
W.C. REQUIRED
MALE FEMALE
1
LAV. REQUIRED
MALE FEMALE
** SUBSTITUTE @ 2/3 PER (1) W.C. REQUIRED
1 1
NUMBER OF PROVIDED EXISTS 4 EXISTSUNIT #
01
02
02
03
03
03
04
05
06
07
08
09
11
12
29
29
29
30
TYPE LOCATION
SHOWROOM
F&I
F&I
SERVICE WRITERS
TELE
JAN.
BREAK RM.
MENS
WOMENS
SERVICE MGR.
GSM
BDC
ROOM #
100
107
108
116
109
110
111
112
113
106
104
105
CONSTRUCTION FRAME
---
LEAF SIZE
W.
50'-0"
17'-5 3/8"
17'-5"
3'-0"
3'-0"
21'-6"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
5'-10 7/8"
3'-0"
8'-0"
3'-0"
HT.
12'-0"
10'-0"
10'-0"
8'-0"
8'-0"
10'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
6'-0"
THK.
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 5/8"
0'-1 3/8"
0'-1 3/8"
0'-2"
FINISH GLASS RATED REMARKS
SHOWROOM100
SALES MGR.101SALES
102SALES
103
GSM104
BDC105 SERVICE MGR.
106
F&I107
F&I108
TELE109
JAN.110 BREAK RM.
111MENS
112
WOMENS113
CASHIER114
CAFE115
SERVICE WRITERS116
WAITING117
SERVICE DRIVE118
STYLE CENTERSTYLE CENTER
FIAT ACCESSORIESFIAT SPEED SHOP
COMPRESSOR YARD
109A
107A
111A
112A
113A
104A
106A
105A
108A
110A
100C
116B
116A
100A
100B
1
1
2
2
3
3
D D
A A
C C
B B
#DrgID#LayID
#DrgID#LayID
#DrgID#LayID
FEC
EXIT
EXIT
EXIT
#DrgID#LayID
#DrgID#LayID
SHOWROOM DISPLAY2,590 SF
SALES DEPT1,468 SF
CUSTOMER CORE1,158 SF
SERVICE DRIVE1,155 SF
EMPLOYEE334 SF
Provided Capacity
Showroom / Sales / Customer Core: (8 showroom vehicle display)
Employee Facilities (477sf/2):
Building Circulation (15% of 4,795 SF):GRAND TOTAL:
Project Square FootagesRequired Capacity
5,216 SF
334 SF
Included Above5,550 SF
4,555 SF
240 SF
720 SF5,515 SF
Total Parking, Support, & Circulation: 53,102 SF 65,790 SF
Planning Volume Used = 1000
Service Shop - Future: (11 stalls) 6,310 SF (12 stalls) 7,895 SFParts - Future: 4,503 SF 5,125 SF
Service Write-up canopy:-
(4 Cars) 1,158 SF
3 Door Elevations
SCALE: 3/32" = 1'-0"6 Code Sheet Floor Plan
0 8' 16' 24'
G.02
REG I
STERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\1034_prj06.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 GULF FREWAY,Tx 77598Job Number: 1034Client: Garff AutoGroup
183
General Notes
Monday, March 14, 201110:58 AM
Revision History:
G.01
REG I
STERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\1034_prj06.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 GULF FREWAY,Tx 77598Job Number: 1034Client: Garff AutoGroup
182
Index
Monday, March 21, 20119:35 AM
Revision History:
ID 01 02 02 03 03 04 05 06 07 08 09 11 12 29 29 29 30Quantity 1 1 1 1 2 1 1 1 1 1 1 1 1 1 2 2 1
W x H Size 50'-0"x12'-0" 17'-5"x10'-0" 17'-5 3/8"x10'-0" 21'-6"x10'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 5'-10 7/8"x8'-0" 3'-0"x8'-0" 8'-0"x8'-0" 3'-0"x6'-0"
2D Symbol
3D Front View
Door Legend
2006 INTERNATIONAL FIRE CODE
2008 NATIONAL ELECTRIC CODE
NEW FIAT DEALERSHIP, HOUSTON, TX
2006 INTERNATIONAL BUILDING CODE
2006 UNIFORM MECHANICAL CODE
GENERAL
APPLICABLE CODES:
PROJECT:
2008 INTERNATIONAL ENERGY CONSERVATION CODE
TYPE OF PROJECT: AUTOMOTIVE SHOWROOM / SALES BUILDING
TEXAS ACCESSIBILITY STANDARDS
BUILDING CODE ANALYSIS:
STRUCTURAL FRAME, INCL. COLUMNS, GIRDERS, TRUSSES:
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS. (HOURS)
BEARING WALLS:
ROOF CONSTRUCTION, INCLUDING SUPPORTING BEAMS AND JOISTS:
EXTERIOR WALLS:INTERIOR WALLS:
PER TABLE 601 (FOR TYPE II B CONSTRUCTION)
NONBEARING WALLS AND PARTITIONS:EXTERIOR WALLS:INTERIOR WALLS:FLOOR CONSTRUCTION, INCLUDING SUPPORTING BEAMS AND JOISTS:
a.b.
c.
d.e.
00
O
0
0
0
0
6. 1 PERSON / 100 S.F. (GROSS AREA)4,707 S.F./100 S.F. = 48 OCCUPANTS
BUSINESS AREAS:ACTUAL OCCUPANT LOADS:
NUMBER OF EXITS: TABLE 1018.1
a. OCCUPANCY B: 4 STORIES; 23,000 SF PER FLOOR
4.
OCCUPANCY TYPE: (BUSINESS GROUP B)
PER TABLE 503
PER SECTION 304
3.
2.
CONSTRUCTION TYPE: II B ( UNSPRINKLERED )PER SECTION 602 AND TABLE 601.
1.
ALLOWABLE HEIGHT AND BUILDING AREAS
NUMBER OF REQUIRED EXISTS 48 OCCUPANT X 0.2" = 9.6" (MIN. 2 EXISTS)
1.
PLUMBING CODE ANALYSIS:
FIRE EXTINGUISHERS:TABLE 906.3(1), 906.3(2), AND NFPA 10
75 FEETB. MAXIMUM TRAVEL DISTANCE IS
RATING IS 2A.A. BASIC MINIMUM EXTINGUISHER
REQUIRED: 1 / PROVIDED: 11. IN BUSINESS OCCUPANCY (SHOWROOM)
REQUIRED PLUMBING FIXTURES PER INTERNATIONAL BUILDING CODE, 2003 EDITION - TABLE 2902.1
LAV. PROVIDED
MALE FEMALE
1 121
W.C. PROVIDED
MALE FEMALE FOUNTAIN
1 HI-LO
ELECTRIC DRINKING
11GROUP B
OCCUPANCY URINALS **
FEC FIRE EXTINGUISHER
4,707 S.F. / 100 (B OCCUPANCY) = 48 OCCUPANTS = 48/2 = 24 OF EACH SEX
W.C. REQUIRED
MALE FEMALE
1
LAV. REQUIRED
MALE FEMALE
** SUBSTITUTE @ 2/3 PER (1) W.C. REQUIRED
1 1
NUMBER OF PROVIDED EXISTS 4 EXISTSUNIT #
01
02
02
03
03
03
04
05
06
07
08
09
11
12
29
29
29
30
TYPE LOCATION
SHOWROOM
F&I
F&I
SERVICE WRITERS
TELE
JAN.
BREAK RM.
MENS
WOMENS
SERVICE MGR.
GSM
BDC
ROOM #
100
107
108
116
109
110
111
112
113
106
104
105
CONSTRUCTION FRAME
---
LEAF SIZE
W.
50'-0"
17'-5 3/8"
17'-5"
3'-0"
3'-0"
21'-6"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
5'-10 7/8"
3'-0"
8'-0"
3'-0"
HT.
12'-0"
10'-0"
10'-0"
8'-0"
8'-0"
10'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
6'-0"
THK.
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 5/8"
0'-1 3/8"
0'-1 3/8"
0'-2"
FINISH GLASS RATED REMARKS
SHOWROOM100
SALES MGR.101SALES
102SALES
103
GSM104
BDC105 SERVICE MGR.
106
F&I107
F&I108
TELE109
JAN.110 BREAK RM.
111MENS
112
WOMENS113
CASHIER114
CAFE115
SERVICE WRITERS116
WAITING117
SERVICE DRIVE118
STYLE CENTERSTYLE CENTER
FIAT ACCESSORIESFIAT SPEED SHOP
COMPRESSOR YARD
109A
107A
111A
112A
113A
104A
106A
105A
108A
110A
100C
116B
116A
100A
100B
1
1
2
2
3
3
D D
A A
C C
B B
#DrgID#LayID
#DrgID#LayID
#DrgID#LayID
FEC
EXIT
EXIT
EXIT
#DrgID#LayID
#DrgID#LayID
SHOWROOM DISPLAY2,590 SF
SALES DEPT1,468 SF
CUSTOMER CORE1,158 SF
SERVICE DRIVE1,155 SF
EMPLOYEE334 SF
Provided Capacity
Showroom / Sales / Customer Core: (8 showroom vehicle display)
Employee Facilities (477sf/2):
Building Circulation (15% of 4,795 SF):GRAND TOTAL:
Project Square FootagesRequired Capacity
5,216 SF
334 SF
Included Above5,550 SF
4,555 SF
240 SF
720 SF5,515 SF
Total Parking, Support, & Circulation: 53,102 SF 65,790 SF
Planning Volume Used = 1000
Service Shop - Future: (11 stalls) 6,310 SF (12 stalls) 7,895 SFParts - Future: 4,503 SF 5,125 SF
Service Write-up canopy:-
(4 Cars) 1,158 SF
3 Door Elevations
SCALE: 3/32" = 1'-0"6 Code Sheet Floor Plan
0 8' 16' 24'
G.01
REG I
STERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\BIM\1034_prj07.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 Gulf Freeway, Tx77598Job Number: 1034Client: Garff AutoGroup
182
ProjectData/Schedules
Friday, April 01, 20111:52 PM
Revision History:Revised per COH 4.1.11
1
1
ID 01-CASED OPENIN 02-CASED OPENIN 02-CASED OPENIN 03-CASED OPENIN 30 100A 100B 100C 104A 105A 106A 107A 108A 109A 110A 111A 112A 113A 116A 116BQuantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
W x H Size 50'-0"x12'-0" 17'-5"x10'-0" 17'-5 3/8"x10'-0" 21'-6"x10'-0" 3'-0"x6'-0" 8'-0"x8'-0" 5'-10 7/8"x8'-0" 8'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0" 3'-0"x8'-0"
2D Symbol
3D Front View
Door Legend
2006 INTERNATIONAL FIRE CODE
2008 NATIONAL ELECTRIC CODE
NEW FIAT DEALERSHIP, HOUSTON, TX
2006 INTERNATIONAL BUILDING CODE
2006 UNIFORM MECHANICAL CODE
GENERAL
APPLICABLE CODES:
PROJECT:
2008 INTERNATIONAL ENERGY CONSERVATION CODE
TYPE OF PROJECT: AUTOMOTIVE SHOWROOM / SALES BUILDING
TEXAS ACCESSIBILITY STANDARDS
BUILDING CODE ANALYSIS:
STRUCTURAL FRAME, INCL. COLUMNS, GIRDERS, TRUSSES:
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS. (HOURS)
BEARING WALLS:
ROOF CONSTRUCTION, INCLUDING SUPPORTING BEAMS AND JOISTS:
EXTERIOR WALLS:INTERIOR WALLS:
PER TABLE 601 (FOR TYPE II B CONSTRUCTION)
NONBEARING WALLS AND PARTITIONS:EXTERIOR WALLS:INTERIOR WALLS:FLOOR CONSTRUCTION, INCLUDING SUPPORTING BEAMS AND JOISTS:
a.b.
c.
d.e.
00
O
0
0
0
0
6. 1 PERSON / 100 S.F. (GROSS AREA)4,707 S.F./100 S.F. = 48 OCCUPANTS
BUSINESS AREAS:ACTUAL OCCUPANT LOADS:
NUMBER OF EXITS: TABLE 1018.1
a. OCCUPANCY B: 4 STORIES; 23,000 SF PER FLOOR
4.
OCCUPANCY TYPE: (BUSINESS GROUP B)
PER TABLE 503
PER SECTION 304
3.
2.
CONSTRUCTION TYPE: II B ( UNSPRINKLERED )PER SECTION 602 AND TABLE 601.
1.
ALLOWABLE HEIGHT AND BUILDING AREAS
NUMBER OF REQUIRED EXISTS 48 OCCUPANT X 0.2" = 9.6" (MIN. 2 EXISTS)
1.
PLUMBING CODE ANALYSIS:
FIRE EXTINGUISHERS:TABLE 906.3(1), 906.3(2), AND NFPA 10
75 FEETB. MAXIMUM TRAVEL DISTANCE IS
RATING IS 2A.A. BASIC MINIMUM EXTINGUISHER
REQUIRED: 1 / PROVIDED: 11. IN BUSINESS OCCUPANCY (SHOWROOM)
REQUIRED PLUMBING FIXTURES PER INTERNATIONAL BUILDING CODE, 2003 EDITION - TABLE 2902.1
LAV. PROV.
MALE FEMALE
1 121
W.C. PRO.
MALE FEMALE FOUNTAIN
1 HI-LO
ELECTRIC DRINKING
11GROUP B
OCCUPANCY URINALS **
FEC FIRE EXTINGUISHER
4,707 S.F. / 100 (B OCCUPANCY) = 48 OCCUPANTS = 48/2 = 24 OF EACH SEX
W.C. REQ.
MALE FEMALE
1
LAV. REQ.
MALE FEMALE
** SUBSTITUTE @ 2/3 PER (1) W.C. REQUIRED
1 1
NUMBER OF PROVIDED EXISTS 4 EXISTS
UNIT #
01-CASED OPENIN
02-CASED OPENIN
02-CASED OPENIN
03-CASED OPENIN
30
100A
100B
100C
104A
105A
106A
107A
108A
109A
110A
111A
112A
113A
116A
116B
TYPE LOCATION
SHOWROOM
SHOWROOM
SHOWROOM
SERVICE WRITERS
SHOWROOM
SHOWROOM
SHOWROOM
GSM
BDC
SERVICE MGR.
F&I
F&I
TELE
JAN.
BREAK RM.
MENS
WOMENS
SERVICE WRITERS
SERVICE WRITERS
ROOM #
100
100
100
116
100
100
100
104
105
106
107
108
109
110
111
112
113
116
116
CONSTRUCTION
C.A. ALUMINUM
C.A. ALUMINUM
C.A. ALUMINUM
C.A. ALUMINUM
C.A. ALUMINUM
C.A. ALUMINUM
C.A. ALUMINUM
METAL
PLAM
PLAM
PLAM
PLAM
C.A. ALUMINUM
C.A. ALUMINUM
FRAME
---
LEAF SIZE
W.
50'-0"
17'-5"
17'-5 3/8"
21'-6"
3'-0"
8'-0"
5'-10 7/8"
8'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
3'-0"
HT.
12'-0"
10'-0"
10'-0"
10'-0"
6'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
THK.
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-2"
0'-1 3/8"
0'-1 5/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
0'-1 3/8"
FINISH GLASS
EXT. GLAZING
EXT. GLAZING
EXT. GLAZING
INT. GLASS
INT. GLASS
INT. GLASS
INT. GLASS
INT. GLASS
EXT. GLAZING
EXT. GLAZING
RATED REMARKS
SHOWROOM100
SALES MGR.101SALES
102SALES
103
GSM104
BDC105 SERVICE MGR.
106
F&I107
F&I108
TELE109
JAN.110 BREAK RM.
111MENS
112
WOMENS113
CASHIER114
CAFE115
SERVICE WRITERS116
WAITING117
SERVICE DRIVE118
STYLE CENTERSTYLE CENTER
FIAT ACCESSORIESFIAT SPEED SHOP
COMPRESSOR YARD
109A
107A
111A
112A
113A
104A
106A
105A
108A
110A
100C
116B
116A
100A
100B
1
1
2
2
3
3
D D
A A
C C
B B
#DrgID#LayID
#DrgID#LayID
#DrgID#LayID
FEC
EXIT
EXIT
EXIT
#DrgID#LayID
#DrgID#LayID
SHOWROOM DISPLAY2,590 SF
SALES DEPT1,468 SF
CUSTOMER CORE1,158 SF
SERVICE DRIVE1,155 SF
EMPLOYEE334 SF
SCALE:
AREA CALCSNO SCALE
Provided Capacity
Showroom / Sales / Customer Core: (8 showroom vehicle display)
Employee Facilities (477sf/2):
Building Circulation (15% of 4,795 SF):GRAND TOTAL:
Project Square FootagesRequired Capacity
5,216 SF
334 SF
Included Above5,550 SF
4,555 SF
240 SF
720 SF5,515 SF
Total Parking, Support, & Circulation: 53,102 SF 65,790 SF
Planning Volume Used = 1000
Service Shop - Future: (11 stalls) 6,310 SF (12 stalls) 7,895 SFParts - Future: 4,503 SF 5,125 SF
Service Write-up canopy:-
(4 Cars) 1,158 SF
Door Schedule
Vicinity Map
2 Door Elevations
SCALE: 3/32" = 1'-0"5 Code Sheet Floor Plan
0 8' 16' 24'
A0.3
REG I
STERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\1034_prj06.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 Gulf Freeway, Tx77598Job Number: 1034Client: Garff AutoGroup
186
AccessibilityStandards
Monday, April 04, 201110:04 AM
Revision History:
48 m
in
24 min
Latch Side ApproachSwinging Door
pull side
NOTE: Y = 54" min. if door has closer
X
Y
Van Accessible Space at End Row
36 min
60 min
12 min 12 min
180 Degree Turns
36 min
23'-0"" Min
8'-0"" Min9'-0"" Min5'-0"" Min9'-0"" Min
Curb Ramp
Handicap Sign
border (typ)5" wide blue paint
18'-0
"
Y
X
Hinge Side Approach -Swinging Door
pull side
NOTE: X = 36" min. if Y = 60" X = 42" min. if Y = 54"
Slop
e
Slope
X
IF X IS LESS THAN 48", THENTHE SLOPE OF FLARED SIDESHALL NOT EXCEED 1:12
T-Shaped Space for
48 m
in
X
Front Approach -Swinging Door
push side
NOTE: X = 12" min.if door has both acloser and latch
60 m
in
18 min, 24 preferred
Front Approach -Swinging Door
pull side
32 min
36 min
Minimum Clear Widthfor Single Wheelchair
60 min
Minimum Clear Widthfor Two Wheelchairs
60 min60
min
Wheelchair Turning Space
48
30
Clear Floor Space
48
30
Forward Approach
48
30
Parallel Approach
48
30
Clear Floor SpaceX
in Alcove
48"
30"
Clear Floor Space
X
in Alcove
X
30"
Additional ManeuveringClearance for Alcove
648
X
Clearance for Alcove
12
Additional Maneuvering
C
AB
D
E
FIGURE 1
#4 REINF. @ 24" O.C.18" LONG #4 DOWELSAT 24" O.C.
FIGURE 2
FIGURE 3
(A) (B)
FIGURE 4
6'-0
"
Slope
5'-0" 5'-0"4'-0" MIN.
Slo
pe
SlopeSlope
FIGURE 9
2'-0
"
4" wide painted bluestripping at 24" OC
ACCESSIBLE PARKINGSPACES AND ACCESSAISLES SHALL HAVESURFACE SLOPE NOT TOEXCEED 1:50 IN ALLDIRECTIONS.
Standard accessible parkingspace
Van accessible parkingspace
pre-cast wheel stop -typical
FIGURE 11
The entire ramp, includingflared sides shall have alight reflective value thatsignificantly contrasts withadjoining pedestrian routes
flared side beyond
(A)
FIGURE 25
(B)
(C)
1/8" DEEP X 1/4" WIDE GROOVESAT 2" O.C. WHERE WATER DOES NOT ACCUMULATE
42" M
AX
FOR
CH
ILD
ROOM
**
*
*
*1'-6"
HOLD
44" M
AX.
FO
R A
DU
LT
1'-5
"M
AX.
TOP
OF
RIM
1'-2" MAX. HT.FOR CHILDREN
1'-3"MIN.
2'-5
"
2'-1
0"
MIN
. CLE
AR
MAX
.
2'-2" MIN. FOR CHILDREN
NOTE: 30" MAX. HT. OFSINK RIM OR COUNTERSURFACE FOR CHILDREN
3'-0
" MA
X.
REMOVE SHARPPROJECTIONS &INSULATE EXPOSEDTRAPS & SUPPLIES
URINAL WALL HUNGLAVATORY
SHELF
1'-0" 3'-6"
11/2"
3'-0" MAX.
1'-5
" MIN
.
TOP OFSEAT
FOR
CH
ILD
1'-2
" HIG
H
1'-5
"M
IN.
3'-0
"2'
-6" M
AX.
HT.
OF
GR
AB
BAR
FO
R C
HIL
D
TOILET TISSUEDISPENSER
TOILET
4"3'-0"
1'-6"HOLD
42" M
AX.
FOR
CH
ILD
RE
N
44" M
AX. F
OR
AD
ULT
S
TOILET
PROVIDE WALL FRAMING AND FASTENERS TO ENSURE THATTHE GRAB BAR ASSEMBLY CAN RESIST 250 POUND-FT OF FORCEFROM ANY DIRECTION
LOCATE LEVERON WIDE SIDEOF TOILET
1 1/2" O.D.
2'-9
"
2'-2
"±
NAPKIN DISPOSALSIGNAGEAND FINISH HARDWARE
4'-0
"
3'-0
"
TO H
AR
DW
ARE
OR
"U" P
ULL
TO L
EVER
KN
OB
5'-0
"
8"MAX.
4'-0
"
1'-3
"
ACCESSIBLE ROOMIDENTIFICATION SIGNW/GRADE 2 BRAILLESEE SIGNAGE NOTESABOVE FOR ADD. REQ.
SWITCHES,THERMOSTATS,& OTHERCONTROLS
ELECT. OUTLETS,PHONE OUTLETS,COMMUNICATIONLINKS, ETC. -
CONTROLS/OUTLETS
42" MAXIMUM FOR CHILDREN
48" M
AX.
5'-0
"
48" M
AX.
VENDING
&/OR WASTE
TOWELDISPENSER
MIRROR
6'-2
" MIN
.
40" M
AX.
TO B
OTT
OM
OF
REF
LEC
TIN
G S
UR
FAC
E REF
LEC
TIN
G S
UR
FAC
ETO
TO
P O
F
RECEPTACLE
2'-10" MAX. HT.FOR CHILDREN
TELEPHONE
4'-6
" MA
X.
2'-3
"O
R B
ELO
W
TO O
PER
ABL
E C
ON
TRO
LS
42" MAX. HT.FOR HIGHESTOPERABLE PARTOF TELEPHONESFOR CHILDREN- IF REQUIRED
3'-7
" MAX
.
BENDING DIFFICULTIES)
DRINKING FOUNTAIN(FOR THOSE W/
STANDARD HT.
9"
6" MAX.
MAX
.
2'-3
"C
LEAR
3'-0
" MA
X.
4'-0
" MA
X.
ACCESSILBEDRINKING
FOR CHILDREN2'-8" MAX. HT.FOUNTAIN
HI/LO DRINKING
3'-7
" MA
X.
3'-0
" MAX
.TO
SPO
UT
FOUNTAIN
SHADED AREA DENOTESMAX. PROJECTION OFALL PROTRUSIONS BELOWDRINKING FOUNTAIN - TYP. LAVATORY COUNTER - TYP.
ALL PROTRUSIONS BELOWMAX. PROJECTION OFSHADED AREA DENOTES
LAVATORY OR SINKCOUNTER MOUNTED
9"
2'-3
" MIN
.
6 1/
2" M
AX.
AT S
INKS
2'-5
" MIN
.
2'-1
0" M
AX.
MAX
.
6" MAX.
8"8"MIN. MIN.
19" MIN. AT SINKS17" MIN.
2'-0" MAX.1'-6" MAX.
FOR CHILDREN
26" M
IN.
FOR
CH
ILD
RE
N
30" M
AX.
FOR
CH
ILD
RE
N
TYPICAL
CLE
AR
FIGURE 25
FIGURE 25
SCALE: 1/4" = 1'-0"1 Tas 03
A1.0
REG I
STERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\BIM\1034_prj07.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 Gulf Freeway, Tx77598Job Number: 1034Client: Garff AutoGroup
188
Site Plan
Friday, April 01, 20112:30 PM
Revision History:Revised per COH 4.1.11
SCALE: 1' = 1'-0"2 1034ASP1.dwg
0 1/2'' 1'' 2''
SCALE: 1"=30'
1
A1.1
REG ISTERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\1034_prj06.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 Gulf Freeway, Tx77598Job Number: 1034Client: Garff AutoGroup
189
First Floor Plan
Monday, April 04, 201110:06 AM
Revision History:
109A
107A
111A
112A
113A
104A
106A
105A
108A
110A
100C
116B
116A
100A
100B
1
1
2
2
3
3
D D
A A
C C
B B
1'-4 1/4" 72'-3 3/8" 1'-4 1/4" 31'-7 5/8" 1'-3 1/2"
77'-0" 6'-11 3/4"
36'-9
5/8"
3'-4"
9'-5"
3'-2 5
/8"28
'-0"
30'-0
"13
'-0"
1'-3 3
/8"
12'-6" 62'-6" 1'-6" 28'-10" 2'-7"
8'-6"
17'-5
3/8"
30'-0
"5'-
0"25
'-0"
5'-0"
10'-6
"
11'-3
5/8"
11'-1
1 1/8"
6'-10
3/4"
6'-9 1
/2"
5'-0" 9'-1 1/2" 9'-1 1/2" 7'-4" 10'-5"
10'-0" 15'-7" 10'-4 3/4"
8'-6"
17'-5
"12
'-0 1/
2"3'-
2"10
'-0"
3'-4"
5'-0"
16'-0
1/2"
75'-6
"
9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 5'-0" 9'-0"
16'-0 1/2" 5'-10 7/8" 7'-1 1/8" 6'-6 1/8" 5'-10 3/8"
8'-5"
12'-0
"5'-
0"2'-
7"8'-
4 5/8"
11 3/
8"
20'-6
1/8"
39'-5
"3'-
0"
62'-1
1 1/8"
21'-8 5/8" 8'-3 7/8" 7'-3"
21'-0 1/4"
4'-6 3
/4"3'-
11 1/
4"
1'-6"
75'-0"
107'-11"
R 16'-10 5/16"
R 3'
R 3'
R 3'-5 7/8"
R 3'-5 7/8"
R 2'-9"
R 3'
R 3'
#DrgID#LayID
1A2.1
2A2.1
4A2.1
3A2.1
SHOWROOM100
SALES MGR.101SALES
102SALES
103
GSM104
BDC105 SERVICE MGR.
106
F&I107
F&I108
TELE109
JAN.110 BREAK RM.
111MENS
112
WOMENS113
CASHIER114
CAFE115
SERVICE WRITERS116
WAITING117
SERVICE DRIVE118
STYLE CENTERSTYLE CENTER
FIAT ACCESSORIESFIAT SPEED SHOP
COMPRESSOR YARD
6A3.1
6A3.1
STYLE CENTERSTYLE CENTER
SCALE: 1/8" = 1'-0"1 1st Floor Dimensional Plan
0 4' 8' 16'
SCALE: 3/8" = 1'-0"2 Enlarged Plan @ Style Center
0 2' 4' 6'
SCALE: 3/16" = 1'-0"3 Merchandising Elevations
0 4' 8' 12'
A1.2
REG ISTERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\1034_prj06.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 GULF FREWAY,Tx 77598Job Number: 1034Client: Garff AutoGroup
1910
Finish Plan
Friday, March 11, 20112:32 PM
Revision History:
109A
107A
111A
112A
113A
104A
106A
105A
108A
110A
100C
116B
116A
100A
100B
1
1
2
2
3
3
D D
A A
C C
B B
#DrgID#LayID
4A4.1
1A4.1
4A2.1
3A2.1
A
A
A
A
B
A A
A
A
AA
BB
B
B
B
C
C1P2B2
C1P2B2
C1P1B2
C1P1B2
C1P1B2
C1P1B2
C1P1B2
C1P1B2
C1P1B2
C1P1B2
C1P1B2
C1P1B2
PT-2P1B2
PT-2CT-1B1 PT-2
CT-1B1
P1
SC-1P1
SC-1
PT-2P1B2
PT-2P1B2
PT-2P1B2
PT-2P1B2
PT-2P1B2
PT-1PT-1
SHOWROOM100
SALES MGR.101SALES
102SALES
103
GSM104
BDC105 SERVICE MGR.
106
F&I107
F&I108
TELE109
JAN.110 BREAK RM.
111MENS
112
WOMENS113
CASHIER114
CAFE115
SERVICE WRITERS116
WAITING117
SERVICE DRIVE118
STYLE CENTERSTYLE CENTER
FIAT ACCESSORIESFIAT SPEED SHOP
COMPRESSOR YARD
6A3.1F3
F4
F1
F2
F6
FLOOR
GYPSUM BOARD CASING BEAD TRIM BOTHSIDES
ATTACH TOP RUNNER TRACK TO CEILINGGRID MAIN TIES AT 4'-0" THROUGH CONT.NEOPRENE TAPE
CONT. 2" SOUND ATTEN. INSUL.EXTEND 48" BOTH SIDES OF WALL
SECTION
4" METAL STUDS - 4" ACOUST. INSUL
6" METAL STUDS - 6" ACOUST. INSUL
3-5/8" METAL STUDS - 3" ACOUST. INSUL
PLAN VIEW
STC -SOUND TRANSMISSION CLASSL/240 LIMITING HEIGHT FIRE RATINGPARTITION TYPE
---------------
F1F2F3F4F6
---40404040
2 7/8"
3 3/4"
4 7/8"
5 1/4"
7 1/4"
1-5/8" METAL STUDS
2-1/2" METAL STUDS - 2" ACOUST. INSUL
SECTION
9'-6"12'-6"16-0"17'-3"20'-0"
25 GAUGE METAL STUDS WITH ONE LAYER OF 5/8" GYPSUM BOARD EACH SIDEAND FULL DEPTH ACOUSTICAL INSULATION FULL HEIGHT
SCHE
DULE
D CE
ILING
HEI
GHT
SCALE: 3" = 1'-0"B PARTITION TYPE B
H2
H3
H1
CONT. ACOUSTICAL SEALANTTYPICAL BOTH SIDES
FLOOR
SCHEDULED CEILING -REFER TOREFLECTED CEILING PLAN
CONT. ACOUSTICAL SEALANTTYPICAL BOTH SIDES
CONT. METAL STUD RUNNERS
12" LONG 5/8" GYP. BD. GUSSETEACH STUD AT 48" O.C. VERTICALLY
UNDERSIDE OF STRUCTURE
CONT. METAL STUD RUNNERS
FIRE SAFING AT STRUCTURE IFREQUIRED TO BE FIRE RATED
STC -SOUND TRANSMISSION CLASSL/240 LIMITING HEIGHT FIRE RATINGPARTITION TYPE
1 HOUR - UL U4201 HOUR - UL U4201 HOUR - UL U420
525252
H1H2H3
PLAN VIEW
SECTION
SECTION
VARIES: RE PLANS(MAX. 24")
2-1/2" METAL STUDS2" ACOUST. INSUL.3-5/8" METAL STUDS3" ACOUST. INSUL.
1-5/8" METAL STUDS2" ACOUST. INSUL.
13'-3"17'-6"22'-9"
TWO 25 GAUGE METAL STUD WALLS WITH ONE LAYER OF 5/8" GYPSUM BOARD EACH SIDEAND FULL DEPTH ACOUSTICAL INSULATION
SCHE
DULE
D CE
ILING
HEI
GHT
SCALE: 3" = 1'-0"C PARTITION TYPE H
FLOOR
ATTACH TOP RUNNER TRACK TO CEILINGGRID MAIN TIES AT 4'-0" THROUGH CONT.NEOPRENE TAPE
CONT. 2" SOUND ATTEN. INSUL.EXTEND 48" BOTH SIDES OF WALL
SECTION
PLAN VIEW
SECTION
SCHE
DULE
D CE
ILING
HEI
GHT
SCALE: 3" = 1'-0"A PARTITION TYPE A
NO.COLOR AND MATERIALSPECIFICATIONS LOCATION MANUFACTURER/SUPPLIER*
FINISH SCHEDULE
PL-1
P-1 LOCAL SHERWIN WILLIAMSSUPPLIER
PT-1FIANDREFIAT BLANCO EXPO24"x24"
PT-2
C-1
CT-1 THROUGHOUT U.N.O. ARMSTRONG CEILING SYSTEMS
WB-1 PORCELAIN OR CERAMIC WALL BASETO MATCH TILE IN GIVEN ROOMOR AREA
FIAT RUNWAYMANUF:STYLE:SIZE:
FIANDREFIAT MULTIBRAND12"x24"
FIELD PORCELAN TILEMANUF:STYLE:SIZE:
INTERFACEACCENT FLANNEL, #6599CARPET TILE, 50cmX50cm
CARPET TILEMANUF:STYLE:SIZE:
LOCAL SUPPLIER
LOCAL SUPPLIER
LOCAL SUPPLIER
SHOWROOM
MATTE AT RESTROOM FLOORS
AS NOTED ON PLAN
ARMSTRONG
DUNE #1775, WHITE
24"x24", 9/16 GRID
CEILING TILEMANUF:STYLE:SIZE:
VB-1 VINYL WALL BASE CAPRICORK FLOORING800.492.2613
SS-1 SOLID SURFACE T.B.D. LOCAL SUPPLIER
WILSONART
PLASTIC LAMINATEMANUF:STYLE:SIZE:
SHERWIN WILLIAMSESSENTIAL GRAY, SW6002
PAINTMANUF:STYLE:
GENERAL PAINT COLOR THROUGHOUT
P-2 LOCAL SHERWIN WILLIAMSSUPPLIER
SHERWIN WILLIAMSMINK, SW6004
PAINTMANUF:STYLE:
ACCENT PAINT COLOR
P-3 LOCAL SHERWIN WILLIAMSSUPPLIER
SHERWIN WILLIAMSHEARTTHROB, SW6866
PAINTMANUF:STYLE:
ACCENT PAINT COLOR
CT-1AMERICAN OLEANURBAN CANVASDESIGNER WHITE 00614.25"x12.75"
CERAMIC TILEMANUF:STYLE:COLOR:SIZE:
RESTROOM WALLS, GLOSS
SC-1 SEALED CONCRETE
T.B.D.
LOCAL SUPPLIER
SCALE: 1/8" = 1'-0"1 1st Floor Finish Plan
0 4' 8' 16'
A1.3
REG I
STERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\1034_prj06.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 GULF FREWAY,Tx 77598Job Number: 1034Client: Garff AutoGroup
1911
Furniture Plan
Friday, March 11, 20112:45 PM
Revision History:
109A
107A
111A
112A
113A
104A
106A
105A
108A
110A
100C
116B
116A
100A
100B
1
1
2
2
3
3
D D
A A
C C
B B
2A2.1
4A2.1
3A2.1
SHOWROOM100
SALES MGR.101SALES
102SALES
103
GSM104
BDC105 SERVICE MGR.
106
F&I107
F&I108
TELE109
JAN.110 BREAK RM.
111MENS
112
WOMENS113
CASHIER114
CAFE115
SERVICE WRITERS116
WAITING117
SERVICE DRIVE118
STYLE CENTERSTYLE CENTER
FIAT ACCESSORIESFIAT SPEED SHOP
COMPRESSOR YARD
6A3.1
6A3.1
SCALE: 1/8" = 1'-0"1 1st Floor Furniture Plan
0 4' 8' 16'
A1.4
REG ISTERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\BIM\1034_prj07.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 Gulf Freeway, Tx77598Job Number: 1034Client: Garff AutoGroup
1812
Reflected CeilingPlan
Friday, April 01, 20112:25 PM
Revision History:Revised per COH 4.1.11
1
1
FIXTURE LEGEND
1x4 PARABOLIC
NEW 250W 2x2 MTL. HAILDE FIXTURESW/ DROP LENS
A
L11(-8)
FLUORESCENT STRIP WITH DIFFUSER.NIS-K2001-263 32W T8 3500K LAMP WHITEFINISH.L11-8 = 8' STRIPLSI LIGHITNG, INC.
RECESSED 6"Ø 32W CFL DOWNLIGHT.B
C
NOTES:
1. CEILING TO BE TYPE 'A' UNLESS NOTED OTHERWISE.
2. CEILINGS SHALL BE AT 9'-0" A.F.F UNLESS NOTED OTHERW
3. ACOUSTICAL GRID FOR LAY-IN CEILINGS SHALL BE ARRANSO AS TO ALLOW FOR A MINIMUM 6" LAY-IN BORDER PANEWALLS.
4. COORDINATE CEILING HEIGHTS w/ STRUCTURAL MEMBERS, DUCTS, AND MECHANICAL EQUIPMENT.
5. REFER TO ELECTRICAL AND MECHANICAL PLANS FOR LIGHTIFIXTURES, MECHANICAL GRILL TYPES AND FIXTURES NOTOTHERWISE SHOWN ON REFLECTED CEILING PLANS.
6. EMERGENCY AND EXIT LIGHTING SHALL BE PROVIDED ASREQUIRED BY CODE.
7. AT AREAS NOTED TO PAINTED EXPOSED STRUCTURE CONTRASHALL PAINT ALL EXPOSED STRUCTURAL STEEL, METAL BUILCOMPONENTS, EXPOSED PIPING, CONDUIT, ELECTRICAL JUNCBOXES AND METAL BUILDING ROOF CURBS.
8. CONTRACTOR SHALL INSTALL & PROVIDE LOCK AND KEY ATACCESS PANELS.
1
1
2
2
3
3
D
A
C
B
LL
LL
LL
DownlightDownlight
9'-8 1/2" 12'-11 3/4" 10'-2 3/4"
4'-0" x 6'-0" GATE
7'-0" CHAIN LINK FENCING WITHVISIBILITY SLATS
LINE OF WALLABOVE
AFC CLADDING1'-0" RETURNAT SOFFIT
AFC CLADDING1'-0" RETURNAT SOFFIT
SCALE: 1/8" = 1'-0"5 1ST Floor
0 4' 8' 16'
A1.5
REG ISTERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\1034_prj06.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 GULF FREWAY,Tx 77598Job Number: 1034Client: Garff AutoGroup
1913
Roof Plan
Friday, March 11, 20112:14 PM
Revision History:
1
1
2
2
3
3
D D
A A
C C
B B
ROOF SLOPE1/2" : 12
ROOF SLOPE1/2" : 12
ROOF SLOPE1/2" : 12
EAVE GUTTERWITH D.S.
EAVE GUTTERWITH D.S.
EAVE GUTTERWITH D.S.
EAVE GUTTERWITH D.S.
ROOF AND OVERFLOWDRAINS
ROOF AND OVERFLOWDRAINS
ROOF AND OVERFLOWDRAINS
ROOF AND OVERFLOWDRAINS
ROOF AND OVERFLOWDRAINS
POLAR WHITE STANDING SEAM PER COHNOTE:
SCALE: 1/8" = 1'-0"1 Roof Plan
0 4' 8' 16'
A2.1
REG ISTERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\1034_prj06.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Clear Lake Fiat15711 GULF FREWAY,Tx 77598Job Number: 1034Client: Garff AutoGroup
1914
ExteriorElevations
Friday, March 11, 20111:29 PM
Revision History:
1 2 3
+17'-0"+18'-0"
+12'-0"
72'-3 3/8" 32'-11 7/8"
1 1
25 5 2
66
A B C D
+17'-0"+18'-0"
13'-0" 30'-0" 28'-0"
6
1 2
5
2
3 2 1
+18'-0"+17'-0"
32'-11 7/8" 72'-3 3/8"
10
52
D C B A
+17'-0"+18'-0"
28'-0" 30'-0" 13'-0"
1 1
5 2 2 2
1
2
3
4
1" INSULATED CLEAR GLASS GLAZING SYSTEM
DARK GREY FIBER CEMENT FASCIA PANEL
5
ILLUMINATED DEALER LETTERS SIGNAGECENTERD ON FASCIA
6
7
8
9
RED ACM PROTOTYPE CORNER ELEMENT
PROTOTYPE ILLUMINATED FIAT LOGO SIGNAGE
ILLUMINATED SERVICE LETTERS SIGNAGECENTERED ABOVE THE SERVICE ENTRY
10
SHOWROOM VEHICLE ACCESS DOORS
Elevation Key Notes
MANUF: KAWNEERPRODUCT: 1600 WALL SYSTEM 1/2VERT: STRUCTURAL SILICONE GLAZEDHORIZ: CAPTURED CURTAIN WALL WITH MULLION CAPSIZE: AS REQUIRED FOR STRUCTURAL INTEGRITYFINISH: CLEAR ANODIZED ALUMINUMGLAZING: 1" INSULATED GLAZING UNITS(MIN), LOW-E CLEAR GLASSDOORS: KAWNEER HEAVYWALL 350
CURTAINWALL / STOREFRONTMANUF:
ALUMINUM COMPOSITE METAL PANELMANUF: ALPOLICREP: 1.800.422.7270SIZE: AS SHOWNCOLOR: BBR REDTHICK: 4MM
BUILDING SIGNAGE - DEALER LETTERS AND SERVICE LETTERSMANUF: PRINCIPLE GROUPTYPE: INDIVIDUAL LETTERSLIGHTING: BACKLIT, OPTIONALMATERIAL: PAINTED ALUMINUM
EXTERIOR PAINTMANUF: SHERWIN WILLIAMSCOLOR: MINK - SW6004PRODUCT TYPE: SUPER PAINT EXTERIOR LATEX
COLOR MATCHED RIVETS
ACM DRY SYSTEM REVEAL
EXTERIOR FIBER CEMENT PANELSMANUF: AMERICAN FIBER CEMENT CORPORATIONNAME: ETER-COLOR
COLOR: E-20-DARK GREY INSTALLED WITH VISIBLE FIXING WITH COLOR MATCHED RIVETS
Exterior Finish Schedule
PRE-FINISHED DARK GREY METAL PANELSTO MATCH SHERWIN WILLIAMS SW-6004
SIZE: 2'x8' OR 2'x10' x 5/ 16"
SCALE: 1/8" = 1'-0"1 South Elevation
0 4' 8' 16'
SCALE: 1/8" = 1'-0"2 West Elevation
0 4' 8' 16'
SCALE: 1/8" = 1'-0"3 North Elevation
0 4' 8' 16'
SCALE: 1/8" = 1'-0"4 East Elevation
0 4' 8' 16'
A3.1
REG ISTERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\1034_prj06.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 GULF FREWAY,Tx 77598Job Number: 1034Client: Garff AutoGroup
1815
Building Sections
Monday, March 14, 201111:00 AM
Revision History:
+17'-0"
+18'-0"
+12'-0"
+11'-0"
0"
+9'-0"
GYP.BD WALL HUNGFROM CEILING
CURVED STYLECENTER WALL
R13 INSULATION
SCALE: 1/8" = 1'-0"6 BUILDING SECTION F
0 4' 8' 16'
SCALE: 1' = 1'-0"7 ACM/AFC Header Detail
0 1/2'' 1'' 2'' SCALE: 1' = 1'-0"8 Curtain Wall Detail
0 1/2'' 1'' 2''SCALE: 1' = 1'-0"
9 Curtain Wall Detail0 1/2'' 1'' 2''
A5.1
REG I
STERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\1034_prj06.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 GULF FREWAY,Tx 77598Job Number: 1034Client: Garff AutoGroup
1918
Wall Sections
Friday, March 11, 20115:34 PM
Revision History:
SCALE: 1" = 1'-0"2 Wall Section at Service Canopy
0 6'' 1' 2' SCALE: 1" = 1'-0"3 Wall Section at Showroom
0 6'' 1' 2'
A5.2
REG I
STERED ARCHITECT
STATE O F TEXAS
Fred H. Goree
2724
COPYRIGHTED DOCUMENT THIS DRAWING AND THE BIM/CAD FILE FROM WHICH IT HAS BEEN GENERATED ARE PROVIDED AS AN INSTRUMENT OF SERVICE FOR THIS PROJECT. THESE DOCUMENTS ARE THE SOLE PROPERTY FRED GOREE ARCHITECTS. ANY USE OF THESE DOCUMENTS, DATA AND DESIGNS FOR PURPOSES OTHER THAN THOSE ASSOCIATED WITH THIS PROJECT WITHOUT THE EXPRESSED, WRITTEN PERMISSION OF FRED GOREE ARCHITECTS IS PROHIBITED.
Clea
r Lak
e Fi
at
P:\Clear_Lake_Fiat-GA1034\1034_prj06.pln
A N
EW F
ACIL
ITY
DES
GIN
FO
R
SHEET ___ OF ___
Drawn by: michael keller
Clear Lake Fiat15711 GULF FREWAY,Tx 77598Job Number: 1034Client: Garff AutoGroup
1919
Wall Sections
Friday, March 11, 20115:44 PM
Revision History:
SCALE: 1' = 1'-0"1 Wall Section at Notch
0 1/2'' 1'' 2''