fedral rowco brochure 090104 - pdl : electronic and ... · switch and socket. this prevents the...
TRANSCRIPT
Page 2
Heavy Duty
FEDERAL & ROWCO products have been in thefield for decades, with a reputation forperformance excellence in harsh environments.Use FEDERAL & ROWCO where you need aproduct that can take a beating or withstand hightemperatures without compromising performanceor safety.
Both FEDERAL and ROWCO products are madefrom high quality aluminium, providing you alightweight, corrosion resistant product suitablefor demanding industrial applications, wheresafety and durability is a priority.
FEDERAL and ROWCO are true heavy dutyindustrial solutions.
Rigorous Testing
FEDERAL switches are the most versatile available.Besides testing to AS3133, FEDERAL switcheshave been tested to EN60947-3, providing severalspecialist ratings specific to certain applications.This means that a FEDERAL switch can bematched directly and accurately to an application,providing confidence to specifiers and end-users.All FEDERAL one-way switches are SwitchDisconnectors, meaning they are suitable for useas isolating switches.
Besides ensuring versatility, the vigorous testingregime undertaken by FEDERAL switches istestament to the superior quality of the productoffer. This superiority translates to less equipmentdowntime and improved safety in the workplace,both issues of great importance to businessmanagers and their technical experts.
The same high-performance switches used inFEDERAL are also used in all ROWCO switchedsocket outlets.
Built to Last
The FEDERAL & ROWCO range uses diecastaluminium exteriors that offer excellent impactresistance, ensuring long product life, indoors oroutdoors. The materials used are proven tooperate in extreme temperatures from –20oC to+60oC ambient.
Switch status information is cast onto product toensure it is visible even in the harshest ofconditions.
IP Rating
FEDERAL & ROWCO products are rated to IP66.FEDERAL & ROWCO synthetic gaskets providehigh performance protection in all situations forpeace of mind.
Modular Design
Based upon 3 frame sizes, the FEDERAL &ROWCO range has been designed as a family ofproducts, allowing interchangeability. This meansthat junction / utility boxes can be mounted andwith only a cover change, can be turned into aswitch or switched socket outlet.
Federal/Rowco . . . Heavy Duty Industrial Switchgear Solutions
Page 3
Safety in action
ROWCO switched socket outlets have beendesigned for safety. All single phase productsfeature double pole switching and all three phaseproducts feature an interlock mechanism betweenswitch and socket. This prevents the insertion orwithdrawal of plugtops when the switch is in theON position.
All switches can be padlocked off in two locations.Each of these two padlock positions can accept an8mm hasp padlock or a scissor lockout tag. Thisfeature supports important occupational healthand safety procedures employed throughoutindustry.
Easy installation
FEDERAL and ROWCO products were designedwith installers in mind. All products can bemounted using internal or external options,depending on what the application requires. Thisflexibility extends to the earthing point - these canbe relocated within the enclosure to suit on-siterequirements.
All larger switches in the FEDERAL range are basemounted, in recognition of the large cable sizesused in these applications. Through this wesupport simpler and faster installation.
All products are supplied with stainless steel coverscrews. These screws offer excellent non-corrosive properties and are treated to preventchemical reaction with the aluminium castings.These cover screws are standard metric thread, soalternatives can be easily arranged should the needarise.
All conduit entry points and rear cut-out guides aremetric for familiarity and ease of use.
FEDERAL Metal Isolator Switches
Size 1 Size 2 Size 3
1 Pole 20A 32A
3 Pole 16A 20A 32A 40A 50A 63A 80A 100A 125A
4 Pole 20A 32A 40A 50A 63A 80A
6 Pole 20A 32A 63A
7 Pole 32A
FEDERAL Metal Changeover Switches
FEDERAL Metal Forward / Reverse Switches
Page 4
FEDERAL Metal Isolator Switches 6• Frame Size 1• 1 Pole – 4 Pole• 16A – 32A
FEDERAL Metal Isolator Switches 8• Frame Size 2• 3 Pole – 7 Pole• 20A – 63A
FEDERAL Metal Isolator Switches 12• Frame Size 3• 3 Pole – 6 Pole• 63A – 125A
FEDERAL Metal Changeover and 14Forward / Reverse Switches• Frame Size 1• 1 Pole – 4 Pole• 20A – 32A
FEDERAL Metal Changeover and 16Forward / Reverse Switches• Frame Size 2 & Frame Size 3• 3 Pole - 4 Pole• 32A - 63A
Page 5
Contents
VARIO Add-on Auxiliary Contacts 28
MATRIX Straight and Angled Plugs 26• 3 Pin – 7 Pin• 10A – 50A
ROWCO Junction Boxes 24
• Frame Size 1 & 2
ROWCO Metal Switched Socket Outlets 20• Frame Size 2• 3 Pin – 7 Pin• 10A – 50A
FEDERAL Metal Retrofit Isolator Switches 18• Frame Size A & B• 3 Pole – 4 Pole• 20A – 32A
Page 6
FEDERAL Metal Isolator Switches - IP66
Frame Size 1
A range of top-performing switches built tohandle heavy duty environments. FEDERALisolator switches are industry leaders, interms of versatility, range and ease ofinstallation.
All switches meet the requirements ofisolation required by AS3000:2000 and areclassified as Switch Disconnectors underAS3947-3.
All versions feature ease of installationbenefits, multiple ratings for versatility andhave been designed to ensure user safety.
Feature:
• 1 - 4 pole switches up to 32A• Cover mounted switch mechanisms• Comprehensive switching ratings• IP66 weather protection rating• Dual padlocking points• Multiple earthing points• Multiple mounting options• Long-life synthetic gasket• Earth bonding wire from cover to base
supplied with each product as standard
DimensionalDrawings
WR320M
WiringDiagrams
ASingle Pole,
Single Throw
BTriple Pole,
Single Throw
CFour Pole,
Single Throw
Page 7
Cat No WR120M WR132M WR316M WR320M WR332M WR420M WR432M
Rated Operational Voltage
Ue (~50Hz) Volts 240 240 415 415 415 415 415
Rated Insulation Voltage
Ui (~50Hz) Volts 660 660 660 660 660 690 690
Rated Impulse Withstand Voltage
Uimp (~50Hz) kV 2.5 2.5 2.5 2.5 2.5 6 6
Rated Thermal Current Enclosed
Amps 20 32 16 20 32 20 32
Rated Duty Uninterrupted Uninterrupted Uninterrupted Uninterrupted Uninterrupted Uninterrupted Uninterrupted
Description Single Single 3 Pole 3 Pole 3 Pole 4 Pole 4 Pole
Pole Pole
Wiring Diagram A A B B B C C
Frame Size Size 1 Size 1 Size 1 Size 1 Size 1 Size 1 Size 1
Switch Mounting Type Cover Cover Cover Cover Cover Cover Cover
Mount Mount Mount Mount Mount Mount Mount
Cable Cross Sections
Solid or Standard Min (mm2) 1 1 1 1 1 1 1
Max (mm2) 16 16 16 16 16 10 10
Switch Rating @ AS3133
0.4pf Inductive 20AX 32AX - - - - -
415V M Rating M150 M180 M120 M150 M180 - -
Switch Rating @ EN60947-3
AC21A 415V Amps 20 32 16 20 32 20 32
AC23A 240/415V kW 3 4 7.5 11 15 7.5 11
Amps 21 28 15 21 28 14 21
AC3 240/415V kW 2.2 3 5.5 7.5 11 5.5 7.5
Amps 15 21 11 15 21 11 14
DC21A 32V Amps - - 16 20 32 - -
Rated Short Time
Withstand CurrentAmps/1 second 1500 1500 1500 1500 1500 300 384
Rated Short Circuit
Making Capacity kAp 1 1 1 1 1 1 1
FEDERAL Metal Isolator Switches - IP66
NOTES:
AC21A Switch of AC Resistive loads,
including moderate overloads.
AC23A Switch of motor loads or other
highly inductive loads.
AC3 Squirrel-cage motors: starting,
switching motors off during
running.
DC21ASwitch of DC Resistive loads,
including moderate overloads.
Page 8
FEDERAL Metal Isolator Switches - IP66
Frame Size 2
A range of top-performing switches built tohandle heavy duty environments. FEDERALisolator switches are industry leaders, interms of versatility, range and ease ofinstallation.
All switches meet the requirements ofisolation required by AS3000:2000 and areclassified as Switch Disconnectors underAS3947-3.
All versions feature ease of installationbenefits, multiple ratings for versatility andhave been designed to ensure user safety.
All switches are base mounted, with safetyinterlock to ensure cover cannot be removedwith switch in the on position.
Feature:
• Up to 7 pole 32A switches• Up to 4 pole 63A switches• Base mounted switch mechanisms
- with safety interlock• Comprehensive switching ratings• IP66 weather protection rating• Dual padlocking points• Multiple earthing points• Multiple mounting options• Long-life synthetic gasket• Earth bonding wire from cover to base
supplied with each product as standard• Circuit or product ID recess
DimensionalDrawings
WR632M
Page 9
WiringDiagrams
C
BTriple Pole,
Single Throw
Four Pole,Single Throw
Cat No WR340M WR350M WR363M WR440M
Rated Operational Voltage
Ue (~50Hz) Volts 415 415 415 415
Rated Insulation Voltage
Ui (~50Hz) Volts 660 690 690 690
Rated Impulse Withstand Voltage
Uimp (~50Hz) kV 2.5 2.5 6 6
Rated Thermal Current Enclosed
Amps 40 50 63 40
Rated Duty Uninterrupted Uninterrupted Uninterrupted Uninterrupted
Description 3 Pole 3 Pole 3 Pole 4 Pole
Wiring Diagram B B B C
Frame Size Size 2 Size 2 Size 2 Size 2
Switch Mounting Type Cover Mount Base Mount Base Mount Base Mount
Cable Cross Sections
Solid or Standard Min (mm2) 6 6 2.5 1
Max (mm2) 35 35 25 10
Switch Rating @ AS3133
0.4pf Inductive - - - -
415V M Rating M200 M250 - -
Switch Rating @ EN60947-3
AC21A 415V Amps 40 50 63 40
AC23A 240/415V kW 18.5 18.5 22 15
Amps 35 35 40 28
AC3 240/415V kW 15 15 18.5 11
Amps 28 28 35 21
DC21A 32V Amps 40 50 - -
Rated Short Time
Withstand Current Amps/1 second 2500 1500 756 480
Rated Short Circuit
Making Capacity kAp 2.5 2.1 2.1 1
Maximum number of
Add-on Auxiliary Contact Module - 1 1 -
FEDERAL Metal Isolator Switches - IP66
See VARIO Add-on Auxiliary Contact on page 28 for further information.
Page 10
FEDERAL Metal Isolator Switches - IP66
Cat No WR450M WR463M WR620M WR632M WR732M
Rated Operational Voltage
Ue (~50Hz) Volts 415 415 415 415 415
Rated Insulation Voltage
Ui (~50Hz) Volts 690 690 690 690 690
Rated Impulse Withstand Voltage
Uimp (~50Hz) kV 6 6 6 6 6
Rated Thermal Current Enclosed
Amps 50 63 20 32 32
Rated Duty Uninterrupted Uninterrupted Uninterrupted Uninterrupted Uninterrupted
Description 4 Pole 4 Pole 6 Pole 6 Pole 7 Pole
Wiring Diagram C C D D E
Frame Size Size 2 Size 2 Size 2 Size 2 Size 2
Switch Mounting Type Base Mount Base Mount Base Mount Base Mount Base Mount
Cable Cross Sections
Solid or Standard Min (mm2) 2.5 2.5 1 1 1
Max (mm2) 25 25 10 10 10
Switch Rating @ AS3133
0.4pf Inductive - - - - -
415V M Rating - - - - -
Switch Rating @ EN60947-3
AC21A 415V Amps 50 63 20 32 32
AC23A 240/415V kW 22 22 7.5 11 11
Amps 40 40 14 21 21
AC3 240/415V kW 18.5 18.5 5.5 7.5 7.5
Amps 35 35 11 14 14
DC21A 32V Amps - - - - -
Rated Short Time
Withstand Current Amps/1 second 756 756 300 384 384
Rated Short Circuit
Making Capacity kAp 2.1 2.1 1 1 1
WiringDiagrams
D
CFour Pole,
Single Throw
Six Pole,Single Throw
ESeven Pole,
Single Throw
Page 11
Page 12
FEDERAL Metal Isolator Switches - IP66
Frame Size 3
A range of top-performing switches built tohandle heavy duty environments. FEDERALisolator switches are industry leaders, interms of versatility, range and ease ofinstallation.
All switches meet the requirements ofisolation required by AS3000:2000 and areclassified as Switch Disconnectors underAS3947-3.
All versions feature ease of installationbenefits, multiple ratings for versatility andhave been designed to ensure user safety.
All switches are base mounted, with safetyinterlock to ensure cover cannot be removedwith switch in the on position.
Feature:
• Up to 3 pole 125A switches• Up to 4 pole 80A switches• Up to 6 pole 63A switches• Base mounted switch mechanisms• Comprehensive switching ratings• IP66 weather protection rating• Dual padlocking points• Multiple earthing points• Multiple mounting options• Long-life synthetic gasket• Earth bonding wire from cover to base
supplied with each product as standard• Circuit or product ID recess
DimensionalDrawings
WR3125M
Page 13
FEDERAL Metal Isolator Switches - IP66
WiringDiagrams
Cat No WR380M WR3100M WR3125M WR480M WR663M
Rated Operational Voltage
Ue (~50Hz) Volts 415 415 415 415 415
Rated Insulation Voltage
Ui (~50Hz) Volts 690 690 690 690 690
Rated Impulse Withstand Voltage
Uimp (~50Hz) kV 6 6 6 6 6
Rated Thermal Current Enclosed
Amps 80 100 125 80 63
Rated Duty Uninterrupted Uninterrupted Uninterrupted Uninterrupted Uninterrupted
Description 3 Pole 3 Pole 3 Pole 4 Pole 6 Pole
Wiring Diagram B B B C D
Frame Size Size 3 Size 3 Size 3 Size 3 Size 3
Switch Mounting Type Base Mount Base Mount Base Mount Base Mount Base Mount
Cable Cross Sections
Solid or Standard Min (mm2) 2.5 10 10 2.5 2.5
Max (mm2) 25 95 95 25 25
Switch Rating @ AS3133
0.4pf Inductive - - - - -
415V M Rating - - - - -
Switch Rating @ EN60947-3
AC21A 415V Amps 80 100 125 80 63
AC23A 240/415V kW 30 37 37 30 22
Amps 55 66 66 55 40
AC3 240/415V kW 22 30 30 22 18.5
Amps 40 55 55 40 35
DC21A 32V Amps - - - - -
Rated Short Time
Withstand Current Amps/1 second 960 1500 1500 960 756
Rated Short Circuit
Making Capacity kAp 2.1 2.8 2.8 2.1 2.1
Maximum Number of
Add-on Auxiliary Contact Module 1 2 2 2 1
C
BTriple Pole,
Single Throw
Four Pole,Single Throw
D
Six Pole,Single Throw
See VARIO Add-on Auxiliary Contact on page 28 for further information.
NOTES:
AC21A Switch of AC Resistive loads,
including moderate overloads.
AC23A Switch of motor loads or other
highly inductive loads.
AC3 Squirrel-cage motors: starting,
switching motors off during
running.
DC21ASwitch of DC Resistive loads,
including moderate overloads.
Page 14
FEDERAL Metal Changeover and Forward/Reverse Switches – IP66
DimensionalDrawings
Frame Size 1
A range of changeover and forward / reverseswitches suited for harsh industrialenvironments.
With comprehensive motor ratings, theseswitches are ready for heavy dutyapplications.
All versions feature ease of installationbenefits, multiple ratings for versatility andhave been designed to ensure user safety.
Feature:• Comprehensive motor ratings for each
model• Heavy duty performance• IP66 weather protection rating• Dual padlocking points• Multiple earthing points• Multiple mounting options• Long-life synthetic gasket• Earth bonding wire from cover to base
supplied with each product as standard• Circuit or product ID recess
Changeover Switches• 1 & 3 pole, 20A & 32A ratings• Cover mounted switch mechanisms
Reversing Switches• 3 pole at 20A & 32A rating• Cover mounted mechanism
WRC320M
Frame Size 1
Page 15
Cat No WRC120M WRC132M WRC320M WRC332M WRC420M
Rated Operational
Voltage Ue (~50Hz) Volts 240 240 415 415 415
Rated Thermal
Current Enclosed Amps 20 32 20 32 20
Wiring Diagram A A B B C
Description 1 Pole 1 Pole 3 Pole 3 Pole 4 Pole
Changeover Changeover Changeover Changeover Changeover
Frame Size Size 1 Size 1 Size 1 Size 1 Size 1
Cable Cross Sections
Solid or Standard mm2 2 x 2.5 2 x 6 2 x 2.5 2 x 6 2 x 2.5
Switch Rating @ EN60947-3
AC21A 415V, 1 Phase Amps 20A 32A - - -
3 Phase Amps - - 20 32 20
AC23A 415V, 3 Phase kW - - 7.5 15 7.5
Amps - - 15 28 15
AC23A 240V, 1 Phase kW 2.5 7.5 - - -
Amps 15 26 - - -
AC3 415V, 3 Phase kW - - 5.5 11 5.5
Amps - - 11 21 11
AC3 240V, 1 Phase kW 2.2 - - - -
Amps - - - - -
Rated Short Circuit Time
Withstand Current Amps/1 second 140 480 140 480 140
WiringDiagrams
FEDERAL Metal Changeover and Forward/Reverse Switches – IP66
A
B
Single Pole ChangeoverSwitch, Double
Throw with Centre off
Triple Pole ChangeoverSwitch, Double Throw
with Centre Off
C
Four Pole ChangeoverSwitch, Double Throw
with Centre Off
D
NOTES:
AC21A Switch of AC Resistive loads,
including moderate overloads.
AC23A Switch of motor loads or other
highly inductive loads.
AC3 Squirrel-cage motors: starting,
switching motors off during
running.
Cat No WRR320M WRR332M
Rated Operational
Voltage Ue (~50Hz) Volts 415 415
Rated Thermal
Current Enclosed Amps 20 32
Wiring Diagram D D
Description 3 Pole 3 Pole
Reversing Reversing
Frame Size Size 1 Size 1
Cable Cross Sections
Solid or Standard mm2 2 x 2.5 2 x 6
Switch Rating @ EN60947-3
AC21A 415V, 1 Phase Amps - -
3 Phase Amps 20 32
AC23A 415V, 3 Phase kW 7.5 15
Amps 15 28
AC3 415V, 3 Phase kW 5.5 11
Amps 11 21
Rated Short Circuit Time
Withstand Current Amps/1 second 140 480
Page 16
FEDERAL Metal Changeover and Forward/Reverse Switches – IP66
WRC432M
DimensionalDrawings
Frame Size 2 & Frame Size 3
A range of changeover and forward / reverse switchessuited for harsh industrial environments.
With comprehensive motor ratings, these switches areready for heavy duty applications.
All versions feature ease of installation benefits, multipleratings for versatility and have been designed to ensureuser safety.
Feature:
• Comprehensive motor ratings for each model• Heavy duty performance• IP66 weather protection rating• Dual padlocking points• Multiple earthing points• Multiple mounting options• Long-life synthetic gasket• Earth bonding wire from cover to base supplied with
each product as standard• Circuit or product ID recess
Changeover switches
• 4 pole at 32A and 3 pole at 63A ratings• Cover mounted (32A) and Base mounted (63A) switch
mechanisms
Reversing switches
• 3 pole at 63A ratings• Base mounted (63A) switch mechanisms
Frame Size 2
Frame Size 3
Page 17
WiringDiagrams
FEDERAL Metal Changeover and Forward/Reverse Switches – IP66
Cat No WRC432M
Rated Operational
Voltage Ue (~50Hz) Volts 415
Rated Thermal
Current Enclosed Amps 32
Wiring Diagram C
Description 4 Pole
Changeover
Frame Size Size 2
Cable Cross Sections
Solid or Standard mm2 2 x 6
Switch Rating @ EN60947-3
AC21A 415V, 1 Phase Amps -
3 Phase Amps 32
AC23A 415V, 3 Phase kW 15
Amps 28
AC3 415V, 3 Phase kW 11
Amps 21
Rated Short Circuit Time
Withstand Current Amps/1 second 480 480
B
Triple Pole ChangeoverSwitch, Double Throw
with Centre Off
C
Four Pole ChangeoverSwitch, Double Throw
with Centre Off
Cat No WRC363M WRR363M
Rated Operational
Voltage Ue (~50Hz) Volts 415 415
Rated Thermal
Current Enclosed Amps 63 63
Wiring Diagram B E
Description 3 Pole 3 Pole
Changeover Reversing
Frame Size Size 3 Size 3
Cable Cross Sections
Solid or Standard mm2 2 x 16 2 x 16
Switch Rating @ EN60947-3
AC21A 415V, 1 Phase Amps - -
3 Phase Amps 63 63
AC23A 415V, 3 Phase kW 30 30
Amps 55 55
AC3 415V, 3 Phase kW 18.5 18.5
Amps 35 35
Rated Short Circuit Time
Withstand Current Amps/1 second 1000 1000
NOTES:
AC21A Switch of AC Resistive loads,
including moderate overloads.
AC23A Switch of motor loads or other
highly inductive loads.
AC3 Squirrel-cage motors: starting,
switching motors off during
running.
E
Page 18
FEDERAL Metal Retrofit Isolator Switches - IP56
Frame size A & B
A range of isolators designed to install ontoexisting enclosures for simplifiedmaintenance.
To support existing installations into thefuture, these switches offer the variety ofratings available on standard FEDERALisolators.
Feature:
• Comprehensive motor ratings for eachmodel
• Heavy duty performance• IP56 weather protection rating• Dual padlocking points• Supplied without base• Long-life synthetic gasket• Earth bonding wire from cover to base
supplied with each product as standard• Circuit or product ID recess
DimensionalDrawings
WR432RFM
Frame Size A
Frame Size B
Page 19
FEDERAL Metal Retrofit Isolator Switches - IP56
WiringDiagrams
Cat No WR320RFM WR332RFM WR432RFM*
Rated Operational Voltage
Ue (~50Hz) Volts 415 415 415
Rated Insulation Voltage
Ui (~50Hz) Volts 690 690 690
Rated Impulse Withstand Voltage
Uimp (~50Hz) kV 6 6 6
Rated Thermal Current Enclosed
Amps 20 32 32
Rated Duty Uninterrupted Uninterrupted Uninterrupted
Description 3 Pole 3 Pole 4 Pole
Wiring Diagram B B C
Frame Size Size A Size B Size B
Switch Mounting Type Base Mount Base Mount Base Mount
Cable Cross Sections
Solid or Standard Min (mm2) 1 1 1
Max (mm2) 10 10 10
Switch Rating @ EN60947-3
AC21A 415V Amps 25 32 32
AC23A 240V kW 5.5 5.5 -
Amps 20 20 -
AC23A 415V kW 7.5 11 11
Amps 14 21 21
AC3 240V kW 4 4 -
Amps 14 14 -
AC3 415V kW 5.5 7.5 7.5
Amps 11 14 14
Rated Short Time
Withstand Current Amps/1 second 300 384 384
Rated Short Circuit Making Capacity
kAp 1 1 1
IP Rating IP 56 IP 56 IP 56
Correspond to the old version of the Federal Switch.
* Can be used to replace old WR420M and WR435M covers or switch mechanisms
C
BTriple Pole,
Single Throw
Four Pole,Single Throw
NOTES:
AC21A Switch of AC Resistive loads,
including moderate overloads.
AC23A Switch of motor loads or other
highly inductive loads.
AC3 Squirrel-cage motors: starting,
switching motors off during
running.
DC21ASwitch of DC Resistive loads,
including moderate overloads.
Page 20
DimensionalDrawings
RC550M
Frame Size 2A range of heavy duty switched socketoutlets designed for top performance inharsh industrial environments.
Comprehensive switch ratings, includingmotor ratings, are standard across allproducts.
Safety is a key feature across the range, withdouble pole switching on single phaseproduct and an interlocking mechanismbetween switch and socket on three phaseproducts, as standard.
Feature:
• One piece combinations• Comprehensive switch ratings, including
motor ratings• Single phase combinations feature
double pole switching as standard• Three phase combinations feature
internal switch / socket interlocking asstandard
• 19 different pin configurations availableas standard, up to 50A three phase
• IP66 weather protection rating• Dual padlocking points• Long-life synthetic gasket• Earth bonding wire from cover to base
supplied with each product as standard
ROWCO Metal Switched Socket Outlets - IP66
Page 21
ROWCO Metal Switched Socket Outlets - IP66
SocketConfigurations
Cat No RC310DPM RC310LSDPM RC310XDPM RC315DPM RC320DPM RC332DPM
Rated Operational
Voltage Ue (~50Hz) Volts 240 240 110 240 240 240
Rated Thermal
Current Enclosed Amps 10 10 10 15 20 32
Interlock Feature Yes Yes
IP Rating IP IP66 IP66 IP66 IP66 IP66 IP66
SWITCH
Description 1 Way 1 Way 1 Way 1 Way 1 Way 1 Way
Double Pole Double Pole Double Pole Double Pole Double Pole Double Pole
Cable Cross Sections
Solid or Standard Min (mm2) 1 1 1 1 1 1
Max (mm2) 16 16 16 16 16 16
Switch Rating @ AS3133
0.4pf Inductive 10AX 10AX 10AX 16AX 20AX 32AX
250V M Rating M100 M100 M100 M120 M150 M180
Switch Rating @ EN60947-3
AC23A 240V kW 2.2 2.2 2.2 2.2 3 4
Amps 15 15 15 15 21 28
AC23A 415V kW - - - - - -
Amp - - - - - -
SOCKET
Number of Pins Including (Earth Pin) 3 3 3 (2 Round 3 3 3
(Flat) (Round Live & Flat (Flat) (Round) (Round)
Earth) Earth)
Configuration c d f g h j
Cable Cross Sections
Solid or Standard Min (mm2) 0.75 0.75 0.75 0.75 1 1
Max (mm2) 10 10 10 10 10 16
Matching Plug
(MATRIX Series PLug) Straight MP310 MP310L MP310X MP315 MP320 MP332
Angled - - - - MPA320 MPA332
NOTES:
AC23A Switch of motor loads or other
highly inductive loads.
AC3 Squirrel-cage motors: starting,
switching motors off during running.
See MATRIX Plug on Pages 26 and 27... For further information.
c d
f g
h j
WiringDiagrams
3 PIN COMBINATIONS WITHDOUBLE POLE SWITCH
ALL SOCKETS VIEWEDFROM FRONT
EXTERNALCONNECTIONS BYCUSTOMER
INTERNALCONNECTIONS
Page 22
ROWCO Metal Switched Socket Outlets - IP66
SocketConfigurations
Cat No RC410M RC420M RC432M RC440M RC450M
Rated Operational
Voltage Ue (~50Hz) Volts 415 415 415 415 415
Rated Thermal
Current Enclosed Amps 10 20 32 40 50
Interlock Feature Yes Yes Yes Yes Yes
IP Rating IP IP66 IP66 IP66 IP66 IP66
SWITCH
Description 1 Way 1 Way 1 Way 1 Way 1 Way
3 Pole 3 Pole 3 Pole 3 Pole 3 Pole
Cable Cross Sections
Solid or Standard Min (mm2) 1 1 1 6 6
Max (mm2) 16 16 16 35 35
Switch Rating @ AS3133
0.4pf Inductive 10AX 20AX 32AX 50AX 50AX
250V M Rating M100 M150 M180 M250 M250
Switch Rating @ EN60947-3
AC3 415V kW 5.5 7.5 11 15 18
Amps 11 15 21 28 35
AC23A 415V kW 5.5 11 15 18 15
Amp 11 21 28 35 28
SOCKET
Number of Pins Including (Earth Pin) 4 (Round) 4 (Round) 4 (Round) 4 (Round) 4 (Round)
Configuration A C D E F
Cable Cross Sections
Solid or Standard Min (mm2) 1 1 1 1 4
Max (mm2) 10 10 16 16 25
Matching Plug
(MATRIX Series PLug) Straight MP410 MP420 MP432 MP440 MP450
Angled MPA410 MPA420 MPA432 MPA440 MPA450
See MATRIX Plug on Pages 26 and 27... For further information.
Cat No RC510M RC520M RC532M RC540M RC550M
Rated Operational
Voltage Ue (~50Hz) Volts 415 415 415 415 415
Rated Thermal
Current Enclosed Amps 10 20 32 40 50
Interlock Feature Yes Yes Yes Yes Yes
IP Rating IP IP66 IP66 IP66 IP66 IP66
SWITCH
Description 1 Way 1 Way 1 Way 1 Way 1 Way
3 Pole 3 Pole 3 Pole 3 Pole 3 Pole
Cable Cross Sections
Solid or Standard Min (mm2) 1.0 1.0 1.0 6.0 6.0
Max (mm2) 16 16 16 35 35
Switch Rating @ AS3133
0.4pf Inductive 10AX 20AX 32AX 50AX 50AX
250V M Rating M100 M150 M180 M250 M250
Switch Rating @ EN60947-3
5AC3 415V kW 5.5 7.5 11 15 18.5
Amps 11 15 21 28 35
AC23A 415V kW 5.5 11.0 15.0 18.5 15
Amp 11 21 28 35 28
SOCKET
Number of Pins Including (Earth Pin) 5 (Round) 5 (Round) 5 (Round) 5 (Round) 5 (Round)
Configuration G H I J K
Cable Cross Sections
Solid or Standard Min (mm2) 1 1 1 1 4
Max (mm2) 10 10 16 16 25
Matching Plug
(MATRIX Series PLug) Straight MP510 MP520 MP532 MP540 MP550
Angled MPA510 MPA520 MPA532 MPA540 MPA550
A C
D E
F G
H I
J K
L M
N
Page 23
ROWCO Metal Switched Socket Outlets - IP66
WiringDiagrams
See MATRIX Plug on Pages 26 and 27... For further information.
Cat No RC610M RC710M RC720M
Rated Operational
Voltage Ue (~50Hz) Volts 415 415 415
Rated Thermal
Current Enclosed Amps 10 10 20
Interlock Feature Yes Yes Yes
IP Rating IP IP66 IP66 IP66
SWITCH
Description 1 Way 1 Way 1 Way
3 Pole 3 Pole 3 Pole
Cable Cross Sections
Solid or Standard Min (mm2) 1 1 1
Max (mm2) 16 16 16
Switch Rating @ AS3133
0.4pf Inductive 10AX 10AX 20AX
250V M Rating M100 M100 M150
Switch Rating @ EN60947-3
AC23A 240V kW 5.5 5.5 11
Amps 11 11 21
AC23A 415V kW 5.5 5.5 7.5
Amp 11 11 15
SOCKET
Number of Pins Including (Earth Pin) 6 (Round) 7 (Round) 7 (Round)
Configuration L M N
Cable Cross Sections
Solid or Standard Min (mm2) 1 1 1
Max (mm2) 10 10 10
Matching Plug
(MATRIX Series PLug) Straight MP610 MP710 MP720
Angled MPA610 MPA710 MPA720
4 PIN COMBINATIONS WITHTRIPLE POLE SWITCH
5 PIN COMBINATIONS WITHTRIPLE POLE SWITCH
ALL SOCKETS VIEWEDFROM FRONT
EXTERNALCONNECTIONS BYCUSTOMER
INTERNALCONNECTIONS
6 PIN COMBINATIONS WITHTRIPLE POLE SWITCH
7 PIN COMBINATIONS WITHTRIPLE POLE SWITCH
NOTES:
AC23A Switch of motor loads or other
highly inductive loads.
AC3 Squirrel-cage motors: starting,
switching motors off during running.
Page 24
RJ1
DimensionalDrawings
A range of versatile junction / utility boxes foruse in harsh industrial environments.
Both sizes allow the mounting of equipmenton din rail or gear tray internally as standard.
Feature:
• Lid can be drilled out to take 22mm or30mm Telemecanique control equipment
• Bases can accept a section of din rail or agear tray for the secure, protectedmounting of field equipment
• Multiple earthing points as standard• Multiple mounting options• IP66 weather protection rating• Long-life synthetic gasket• Earth bonding wire from cover to base
supplied with each product as standard
ROWCO Junction Boxes – IP66
RJ1
Page 25
Cat No RJ1 RJ2
Frame Size Size 1 Size 2
Number of Mounting
Conduit Entries
25 mm2 2 -
32 mm2 1 2
40 mm2 - 1
Back Entry Cut-outs
25/32 mm2 1 2
32 mm2 - -
40 mm2 - -
Dimensions
Length mm 137 238
Width mm 99 120
Depth mm 96.2 96.2
ROWCO Junction Boxes – IP66
DimensionalDrawingsRJ2
Page 26
MATRIX Straight and Angled Plugs - IP66
MP410MP210
A comprehensive range of plugtops and cordextension sockets for single phaseapplications. All plugtops are rated to IP66when matched to an IP66 socket,combination or cord extension socket.
Designed for the food industry, MATRIXplugtops allow superior hygiene standards tobe maintained where they are mostimportant. Clean product lines minimiseareas where food or waste can build up.
The new small frame size MATRIX plugtopsboast an M20 rear thread and standardexternal components, allowing cableconnection flexibility and simplifiedmaintenance.
MATRIX plugtops feature clear bodies,allowing for quick and easy inspection of theterminals, cord clamping and cable entryareas.
Special chemical resistant versions ofplugtops are available for use in harshchemical environments. These plugtops arefully orange, without clear bodies.
DimensionalDrawings
Feature:• IP66 rated• Transparent body• Designed for the food industry• M20 rear thread on small frame size
plugtops, allowing flexibility in cableconnection
• Small frame size plugtops all share thesame external components, allowing forsimplified maintenance stockholdings andminimised machine downtime whenreplacement products are needed
• All plugs feature the certainty of a cordclamp and the convenience of rear cableentry for terminals
• Fully special chemical resistant option (V)
Page 27
MATRIX Straight and Angled Plugs - IP66
PlugConfigurations
Cat No. (Straight) MP310 MP310L MP310X MP315 MP320
Cat No. (Angled) MPA320
Rated Operational
Voltage Ue (~50Hz) Volts 250 250 110 250 250
Rated Thermal
Current Enclosed Amps 10 10 10 15 20
Number of Pins 3 3 (2 Flat and 3 (2 Round 3 3
(Include Earth Pin) (Flat) Round Earth) and Flat Earth) (Flat) (Round)
Plug Configuration c d f g h
Cable Entry Diameter Min (mm) 6 6 6 6 7
Max (mm) 9 12.5 12.5 12.5 16
Terminal Capacity Min (mm2) 0.75 0.75 0.75 1 1
Max (mm2) 1.5 1.5 1.5 2.5 6
IP Rating IP IP66 IP66 IP66 IP66 IP66
Cat No. (Straight) MP332 MP410 MP420 MP432 MP440
Cat No. (Angled) MPA332 MPA410 MPA420 MPA432 MPA440
Rated Operational
Voltage Ue (~50Hz) Volts 250 500 500 500 500
Rated Thermal
Current Enclosed Amps 32 10 20 32 40
Number of Pins 3 4 4 4 4
(Include Earth Pin) (Round) (Round) (Round) (Round) (Round)
Plug Configuration j A C D E
Cable Entry Diameter Min (mm) 10 7 7 10 10
Max (mm) 27 16 16 27 27
Terminal Capacity Min (mm2) 2.5 1 1 2.5 2.5
Max (mm2) 16 6 6 16 16
IP Rating IP IP66 IP66 IP66 IP66 IP66
Cat No. (Straight) MP450 MP510 MP520 MP532 MP540
Cat No. (Angled) MPA450 MPA510 MPA520 MPA532 MPA540
Rated Operational
Voltage Ue (~50Hz) Volts 500 500 500 500 500
Rated Thermal
Current Enclosed Amps 50 20 32 40 50
Number of Pins 4 5 5 5 5
(Include Earth Pin) (Round) (Round) (Round) (Round) (Round)
Plug Configuration F G H I J
Cable Entry Diameter Min (mm) 10 7 7 10 10
Max (mm) 27 16 16 27 27
Terminal Capacity Min (mm2) 4 1 1 2.5 2.5
Max (mm2) 16 6 6 16 16
IP Rating IP IP66 IP66 IP66 IP66 IP66
Cat No. (Straight) MP550 MP610 MP710 MP720
Cat No. (Angled) MPA550 MPA610 MPA710 MPA720
Rated Operational
Voltage Ue (~50Hz) Volts 500 500 500 500
Rated Thermal
Current Enclosed Amps 10 10 20
Number of Pins 5 6 7 7
(Include Earth Pin) (Round) (Round) (Round) (Round)
Plug Configuration K L M N
Cable Entry Diameter Min (mm) 10 7 7 7
Max (mm) 27 16 16 16
Terminal Capacity Min (mm2) 4 1 1 1
Max (mm2) 16 6 6 6
IP Rating IP IP66 IP66 IP66 IP66
c d
h
g
j
f
D E
G
CA
I
J
H
F
K
M
N
L
Page 28
VARIO Add-on Auxiliary Contacts
FEDERAL Series offer 2 VARIO Clip-onauxiliaries contacts for control circuitapplications.
Both auxiliaires are easily clippied tothe switch.
Some switches can accept 2 Auxiliaries.
Feature:
• Clip on auxiliaries cover both LV and ELV applications.• The VZ7 offer 1x late N/O, 1x early break N/C contacts.
DimensionalDrawings
VZ20
Page 29
VARIO Add-on Auxiliary Contacts
WiringDiagrams
Cat No VZ7 VZ20
Rated Operational Voltage
Ue (~50Hz) Volts 415 415
Rated Insulation Voltage
Ui (~50Hz) Volts 690 690
Rated Impulse Withstand Voltage
Uimp (~50Hz) kV 6 6
Rated Thermal
Current Enclosed Amps 10 10
Auxiliary Contact Discriptions N / O + N / C * N / O + N / O
Cable Cross Sections
Solid or Standard
Flexible cable + cable end mm2 2 x 0.75 ... 1.5 2 x 0.75 ... 1.5
Solid cable mm2 2 x 1 ... 2.5 2 x 1 ... 2.5
AC Switch Rating @ EN60947-5
AC15 230V Amps 6 6
240V Amps 6 6
400V Amps 4 4
415V Amps 4 4
DC Switch Rating @ EN60947-5
DC11 24V Amps 8 8
48V Amps 8 8
60V Amps 4 4
110V Amps 2 2
220V Amps 1 1
250V Amps 0.8 0.8
14 13
22 21
14 13
24 23
VZ7
VZ20
*Late make N / O, early break N / C contacts
Page 30
Socket Configurations
320
h
4 pin
432
D440
E
510
G
420
C410
A
5 pin
6 pin
7 pin
532
I540
J520
H
610
L
720
N710
M
310LS
d315
g310
c332
j
450
F
550
K
10A 40A 50A20A 32A
10A 10A 15A 20A
240 Volt - To AS3112 and AS3123
500 Volt - To AS3124
3 pin
10A
310X
f
32A
Page 31
Plug Configurations
10A 40A 50A20A 32A
310
c
4 pin
432
D440
E450
F
510
G
420
C410
A
5 pin
6 pin
7 pin
532
I540
J550
K520
H
610
L
720
N710
M
3 pin
315
g320
h332
j310LS
d
10A 10A 15A 20A
240 Volt - To AS3112 and AS3123
500 Volt - To AS3124
10A
310X
f
32A
Page 32
Rating Conversion
0.37 0.5 3.60.55 0.75 4.80.75 1 6.11.1 1.5 8.81.5 2 11.7
1.8 2.5 14.42.2 3 17.13 4 22.24 5 27.14.4 6 31.8
kW hp 240V A
1 Phase
0.37 0.5 - 10.55 0.75 - 1.210.75 1 2 1.51.1 1.5 2.5 21.5 2 3.5 2.6
2.2 3 5 3.83 4 6.5 53.7 5 7.5 5.94 5.5 8.4 6.55.5 7.5 11 9
7.5 10 14 129 12 17 13.910 13.5 - 1511 15 21 18.415 20 28 23
18.5 25 35 28.522 30 40 3325 35 47 39.430 40 55 4533 45 60 50
37 50 66 5540 54 71 6045 60 80 6551 70 90 7555 75 100 80
59 80 105 8563 85 115 8975 100 135 125
kW hp 415V A
3 Phase
500V A
These values are given as a guide only.They may vary depending on the type of motor and the manufacturer.
Page 33
Switch Rating Information
Page 33
AS3947-3 AC3 - Switching of squirrel cage motors.
AC3 has no A or B classification for frequency of operation and all ratings are for frequent operation, as described above. AC3provides ratings directly applicable to the direct starting and switching off of motors during operation and as such is one of theharshest switch ratings available for motors.
The AC3 rating of an WR350M switch is 28 Amps (15kW). This switch can be used to start or stop a motor that has a full loadcurrent of up to 28 Amps.
AC3 is the rating best suited for control equipment being turned on or off directly under load. Examples include conveyors, lathesand process equipment. With a frequent operation classification, these switches may be operated many times per hour.
AS3947-3 AC23A - Switching of motor or other highly inductive loads.
As above, this rating covers AC supply and frequent operation. AC23A is the best utilisation category for switching of mostcommon types of motors. Most other highly inductive loads typically involve motors of some type. Examples are heat pumps,compressors and air conditioners.
The AC23A rating of an MSW350WH switch is 35 Amps (18.5kW). This switch can be matched to a motor that has a full loadcurrent of up to 35 Amps.
Generally these switches are used in conjunction with other motor control equipment such as motorstarters or soft starters and onlyhave to operate during a fault or period of isolation.
AS3947-3 AC23A - Switching of motor or other highly inductive loads.
As above, this rating covers AC supply and frequent operation. AC23A is the best utilisation category for switching of mostcommon types of motors. Most other highly inductive loads typically involve motors of some type. Examples are heat pumps,compressors and air conditioners.
The AC23A rating of an WR350M switch is 35 Amps (18.5kW). This switch can be matched to a motor that has a full load currentof up to 35 Amps.
Generally these switches are used in conjunction with other motor control equipment such as motorstarters or soft starters and onlyhave to operate during a fault or period of isolation.
AS3947-5 AC15 - Control of electromagnetic loads.
This rating covers the switch control of electromagnetic loads, including control devices such as relays, contactors and valves.
AS3947-3 DC21A - Switching of DC Resistive loads.
As for AC21A except covers DC applications.
AS3947-3 Rated short time withstand current (Icw / kA).
This is the recommended maximum current the switch can withstand under fault conditions without failing or showing signs ofdamage and is the switch equivalent of a 4.5kA or 6kA rating assigned to an MCB. Values are expressed as kA.
An WR350M switch has a 1.5kA rating so it can carry a 1500 Amp load for 1 second without damage.
AS3947-3 requires performance of at least 12x rated current for 1 second. Federal switches offer performance levels muchhigher than this.
IMPORTANTThe above information is an opinion only. All installers and equipment users should satisfy themselves as to the suitability of equipment foreach particular application. No liability will be accepted for reliance on this information.
Page 34
Switch Rating Information
IMPORTANTThe above information is an opinion only. All installers and equipment users should satisfy themselves as to the suitability of equipment foreach particular application. No liability will be accepted for reliance on this information.
AS3947-3 Rated short circuit making capacity (Icm / kAp).
This rating provides performance information relating to the presence of a short circuit condition when the switch is switched ON.Values are given as kAp and indicate what current load can be carried until circuit protection devices activate.
An WR350M switch has a 2.1kAp rating so it can switch ON a 2100 Amp prospective short circuit and carry it for as long as theprinciple protection devices (MCB or Fuses) take to operate.
A "Rated short circuit breaking capacity" relates to the opposite - switching OFF in the presence of a short circuit condition.This rating is not typically published as circuit protection devices are designed to act before a manual switch operation can beundertaken.
Uninterrupted Duty
A duty without any off-load period in which the main contacts of an equipment remain closed, whilst carrying a steady current without interruption for periods of more than eight hours (weeks, months, or even years).
AS3133 M Motor Rating
M rating indicates the Switch is suitable for control of motors with a nominated locked rotor current of XX amps - MXX.
An WR350M switch has an M200 rating so it can switch ON or OFF under locked rotor conditions a Motor with a 200 Amp lockedrotor current. The locked rotor current is generally 8 to 10 times the full load current and simulates current draw when a motor isstalled.
AS3133 Resistive rating
This rating is typically the one quoted most widely for a particular switch. The rating relates to resistive loads with a moderateinductive element.
An WR350M switch has a 50 Amp resistive rating so it can switch ON and OFF a resistive load of 50 Amps.
Page 35
2
3
4
5
6
Protected against solid bodies largerthan 12mm. (e.g. finger of the hand)
Protected against solid bodies largerthan 2.5mm. (e.g. tools, wire)
Protected against solid bodies larger than1mm. (fine tools and small wires)
Protected against dust (no harmfuldeposits)
Completely protected against dust
1
2
3
4
5
6
1st FigureProtection against solid objects.
2nd FigureProtection against harmful lngress of water.
Protected against vertically fallingdrops of water.
Protected against drops of water fallingat up to 15° from the vertical.
Protected against spraying water atup to 60° from the vertical.
Protected against splashing waterfrom all directions.
Protected against jets of water fromall directions.
Protected against jets of water ofsimilar force to heavy seas.
IP Ratings
AUS0
3110
2
As standards, specifications change from time to time.Please ask for confirmation of the information given in this publication.