FCI ST50 Series Flow MetersLow Cost, Low Maintenance
Air, Compressed Air and Nitrogen Flow Measurementfor Process and Plant Applications
Wastewater Treatment Aeration ControlBlower and Dryer Air Flow ControlBurner and Furnace Air Flow ControlLake, Pond and Aquaculture AerationHVAC Duct/Damper ControlCompressed Air Distribution Measurements
FCI
ST50
FLO
WM
ETER
Easy to Install, Easy to UseThe ST50 Flow Meter is an accurate, easy to install, no
moving parts solution for measuring and controlling air, com-pressed air or nitrogen flow. ST50 utilizes FCI proven thermaldispersion technology to provide direct mass flow measurementresulting in higher performance at a lower cost than orificeplates, DP, Vortex shedding and other thermal devices. Themeter installs in line sizes ranging from 2 inches to 24 inches[51 mm to 610 mm] with 1/2″ or 3/4″ NPT.
ST50 uses precision, lithography structured platinum RTDsensors embedded in FCI’s equal mass small diameter, all metalthermowells. Combined with microprocessor electronics andprecision calibration, the ST50 achieves excellent accuracy, fastresponse and virtually maintenance free operation.
To serve a variety of application and installation requirementsthe ST50 is available in three standard configurations as shownbelow. (Other display options are described in Accessory RemoteDigital Display section.)
To provide convenient and easy access for wire-up and sig-nal isolation, the instrument’s enclosure features dual conduitports in either NPT or M20 threads, as well as removable frontand rear covers. ST50 can be ordered for DC (18V to 36V) orAC (85V to 265V) power.
The ST50 is available with four calibration and final set-upselections. Two are standard calibrations suitable for finalranging and set-up in the field and two are for factory customcalibration with factory performed final ranging and set-up.All final set-up and flow ranges are subject to 100:1 maximumand 3:1 minimum turndowns.
Two standard calibrations include one for air or nitrogenflow rates between 1.25 SFPS to 125 SFPS [0.4 NMPS to 38NMPS] in service pressures between 10 psia to 50 psia [0.7bar(a) to 3.5 bar(a)] and one for compressed air, air ornitrogen flows between 4 SFPS to 400 SFPS [1.2 NMPS to 122NMPS] in service pressures between 50 psia to 165 psia [3.5bar(a) to 11.4 bar(a)]. All final user configurations for flow
range, specific line size, standard volumetric or mass flowand engineering units are easily set-up in the field with a PC,PDA or FC88 programmer.
Alternatively, custom factory calibration and set-up is avail-able for air or nitrogen with flow between 0.8 SFPS to 150 SFPS[0.2 NMPS to 46 NMPS] at service pressure between 10 psia to50 psia [0.7 bar(a)to 3.5 bar(a)] or compressed air, air ornitrogen flow between 2.5 SFPS to 400 SFPS [0.8 NMPS to 122NMPS] with service pressure between 50 psia to 165 psia [3.5bar(a) to 11.4 bar(a)]. Custom calibration applications are sub-ject to validation by FCI’s AVAL flow meter optimizer programand a submittal of a completed FCI Application Data Sheet.
Extensive Outputs Ensure Application CompatibilityThe ST50 includes dual 4-20mA analog outputs which
are field assignable as flow rate or temperature. Flow rate isselectable for reading in standard volumetric or mass flowengineering units. Optionally available as a third output, is a0-1000Hz pulse output of total flow.
In all models a standard RS232C serial I/O link is providedfor instrument configuration, service/troubleshooting data, andmeasured readings. Also included in all models is a wireless IRsensor to enable wireless connectivity to PDA devices.
Features
� Direct mass, volumetric or velocity flow measurement� Dual 4-20mA analog outputs� Line/pipe sizes from 2 to 24 [51 mm to 610 mm]� Non-clogging, no moving parts sensor� RS232 and wireless IR communications� 4-digit digital display option� Small, compact design� Easy installation
FCI ST50 Series Flow Meters
Designed and Built to LastThe all stainless steel element with Hast-C tips, provides protection
from invasive conditions within the pipe and ensures long service life.The electronics are housed in an all metal NEMA 4X (IP67) ratedenclosure for ruggedness and dust/weather proof service in industrialplant installations.
Whether adding flow measurement to improve the process orreplacing high-maintenance flow meters, the ST50 provides an accu-rate, fast response and no-maintenance solution for air, compressedair and nitrogen flow measurement.
For remote mounted digital readouts of flow, temperature and /or total flow, three types of accessorydisplays are available.
Model DM10 is a LCD readout meter which can be inserted and located anywhere in the 4-20mA output loopfrom the ST50. It requires no separate power as it derives its power directly from the 4-20mA loop. The DM10 isuser scalable to ±1999 digits and features oversized, 1 inch H [25 mm] characters for an easy-to-read display.NEMA 4X rated. FM and CSA certified models optional
Size: 3.15″ H x 5.51″ W x 2.56″ D [80 mm H x 140 mm W x 65 mm D]Mounting: Wall. Panel mount or pipe mount kit optionalWire-Up: Screw terminals via 1/2″ conduit hole at bottom of case
Model DM15 is a high accuracy, 1/8 DIN panel mount, AC line powered meter with a bright red LED readout.It features a user scalable, ±9999 digit display and will accept both the 4-20 mA or 0-10 Vdc signals from the ST50.Optionally available with DM15 is a user programmable alarm setpoint with a Form C relay output.
Size: 1.89″ H x 3.78″ W x 5.35″ D [48 mm H x 96 mm W x 136 mm D]Mounting: Panel. Standard 1/8 DIN, 45 mm H x 92 mm W cutoutWire-Up: Screw terminals at rear of instrument
Model DM20 is a miniature sized, totalizer counter that accepts the pulse output from the ST50. It features an 8-digit(0 to 99999999 counts) LCD that can be reset via its front-panel push-button. It is a panel-mount style that can be locatedin the field, in a separate enclosure or in the control room. It is self-powered by a lithium battery (included, 10 year life).
Size: 0.944″ H x 1.89″ W x 1.20″ D [24 mm H x 48 mm W x 30.5 mm D]Mounting: Panel. 22.5 mm H x 45 mm W cutoutWire-Up: Screw-terminals at rear of instrument
Precision Calibration in FCI Flow LaboratoryTo ensure optimum accuracy, performance and quality, FCI
owns and operates a best-in-class test and NIST traceable calibra-tion laboratory. FCI product developments are subject to rigoroustesting and calibration integrity validation using high-speed dataacquisition systems and precision flow calibration equipment.Every FCI flow meter is also extensively tested and then calibratedusing actual gases under customer conditions to assure theirquality and performance.
� NIST traceability� Automated data acquisition� ISO 9001 certified� Flow, pressure and temperature calibrations
Accessory Remote Digital Displays
Exclusive “Wireless”Communications Option
With FCI’s unique new IR link option, anyPalm-OS based PDA can be used to communicatewith the ST50 without contact. This wireless IR linkfeatures a password protected, easy-to-follow menudriven program to access all its features. Parametersinclude measured readings and totalizer values, con-figuration settings, calibration downloads, diagnosticservice codes, and more. This wireless interface isideal to save cost and time when the ST50 will be
mounted in a hard to reach location. Requires FCI softwareaccessory kit P/N 019819-01 for the PDA.
ST50 Specifications
ST50 Dimension Drawing
InstrumentMedia Compatibility: Air, compressed air, and nitrogenPipe/Line Size Compatibility: 2″ to 24″ [51 mm to 610 mm]Range: Air, compressed air, or nitrogen: 0.75 SFPS to 400 SFPS[0.23 MPS to 122 MPS]Accuracy: Standard: ± 2% of reading, ± 0.5% of full scale
Optional: ± 1% of reading, ± 0.5% of full scaleRepeatability: ±0.5% of readingTemperature Compensation:
Standard: 40°F to 100°F [4°C to 38°C]Optional: 0°F to 250°F [-18°C to 121°C]
Turndown Ratio: 3:1 to 100:1Agency Approvals: 1
FM/CSA: Nonincendive for use in Class 1, Division 2,Groups A, B, C and D T4 Ta = 60°C IndoorHazardous (Classified) Locations.
ATEX/IECEx: II 3 G EEx nA II T6; II 3 D T65°C(DC input power only)
CPA, CE Mark, PED
Warranty: One year
Flow ElementInstallation: InsertionType: Thermal dispersionMaterial of Construction: 316 stainless steel body withHastelloy C thermowell sensors, 316 stainless steelcompression fitting with Teflon or stainless steel ferrulePressure (Maximum Operating without Damage):
Stainless steel ferrule: 500 psig [34 bar(g)]Teflon ferrule: 150 psig [10 bar(g)]
Temperature (Maximum Operation):Stainless steel ferrule: 0°F to 250°F [-18°C to 121°C]Teflon ferrule: 0°F to 200°F [-18°C to 93°C]
Process Connection: 1/2″ MNPT or 3/4″ MNPT withstainless steel or teflon ferruleInsertion Length: Field adjustable lengths: 1″ to 6″[25 mm to 152 mm]; 1″ to 12″[25 mm to 305 mm];or 1″ to 18″ [25 mm to 457 mm]
TransmitterEnclosure: NEMA 4X [IP67], aluminum, dual conduit portswith either 1/2″ NPT or M20x1.5 entries. Epoxy coated.Output Signal:
Standard: (2) 4-20mA, user assignable to flow rateand/or temperature
Optional: 0 -1000Hz pulse for total flowCommunication Port: RS232C. Wireless IR to PDA. 2
Input Power:DC: 18Vdc to 36Vdc (6 Watt maximum)AC: 85Vac to 265Vac (12 Watt maximum)
(CE Mark Approval from 100Vac to 240Vac)Operating Temperature: 0°F to 140°F [-18°C to 60 °C]Digital Display: ±9999 Counts LCD, 0.45″ H [11.4 mm]characters, user scalable to flow rate units or as 0-100%. 1
1 For applications in Div. 1 / Zone 1 environments and/or fordual-line digital display with built-in totalizer display, seeFCI Model ST51
2 Requires user supplied PDA and FCI software P/N 019819-01
Model * U LengthST50-xxx1 6.0 inches [152.4 mm]ST50-xxx2 12.0 inches [304.8 mm]ST50-xxx3 18.0 inches [457.2 mm]
*
Easy access to allwiring terminations
with removable frontand rear covers
DC or AC powered
Wireless IR link to PDA
Large, easy-to-read, userscalable LC display� ±9999 counts with programmabledecimal point
� scale to engineering units SCFM,SFPS, SCFH, NCMM, NCMH, NMPS,LB M/Hr, kg/Hr, or %
Choice of 1/2″ or 3/4″ NPTstainless steel or teflon ferrule
Adjustable compression fitting toset insertion depth
316 stainless steelprobe element
Premium Hastelloy C tips
Analog anddigital outputs
Dual conduit ports,NPT or M20, facilitate
power and signalwire run isolation
and access
Compact, rugged,NEMA 4X (IP67),
all metal enclosureand agency approvals
for hazardouslocation installations
Small mass sensor forfast response Temperature compensated,
precision calibration
Single Insertion Point, Mass Flow MeasurementWith premium components and attention to detail FCI’s ST50 series provides long-lasting flow meter quality and value.It’s features and functions ensure application compatibility, maximum installation convenience, superior industrialdurability and lowest maintenance.
ST50 Flow Meter
© Copyright 2009 by Fluid Components International LLC. All rights reserved. Manufactured in accordance with one or more of the following patents: US Patent Numbers: 4,929,088, 4,967,593, 4,981,368, 4,994,780, 5,111,692, 5,600,528, 5,780,737, 5,913,250, 6,208,254,6,340,243, 6,628,202, 6,843,110, China Patent Number: ZL00815586.0. FCI is a registered trademark of Fluid Components International LLC. Information subject to change without notice.
0409 2.5K Doc. No. 02MK011522G
Visit FCI on the Worldwide Web: www.fluidcomponents.comHeadquarters: 1755 La Costa Meadows DriveSan Marcos, California 92078 USAPhone: 760-744-6950 Toll Free: 800-854-1993 Fax: 760-736-6250
European Office: Persephonestraat 3-01 5047 TT Tilburg, The NetherlandsPhone: 31-13-5159989 Fax: 31-13-5799036
FCI is ISO 9001:2000 and AS9100 Certified
Locally represented by:
� ST51 Flow Meter
Insertion style flow meter similar to Model ST50 forbiogas, digester gas and other methane compositiongases, also with enhanced features for air applications.
– Two-line, Flow Rate + Totalizer Digital Display
– Agency Approvals for Div.1/Zone 1 Installations
– Pulse Output for External Totalizers is standard
– Special Low Flow Rate Calibration Option
� ST75 Flow Meter Series
In-line (spool-piece) version for applications withsmaller line sizes, 1/4″ to 2″ [6 to 51mm] and forall air and gases.
– For all air and gases including hydrocarbonsand hydrogen
– Two-line, Flow Rate + Totalizer Digital Display
– Agency Approvals for Div.1/Zone 1 Installations
Data sheets and full product details for Model ST51, ST75 Series and other FCI models are available at www.fluidcomponents.com
Companion FCI Flow Meters in the ST50/ST75 Series
ST51 Mass Flow Meter For Biogas, Digester Gas, Methane and Natural Gas
� Wastewater Treatment Plant Digester Systems
� Biogas Production and Recovery— Anaerobic Digester Processes— On-Farm Systems— Fermentation Systems
� Landfill Gas Recovery Systems
� Co-Gen Power Systems
� Coal Mine and Coal Bed Methane Recovery
The Model ST51 Flow Meter is an accurate, easy to install, no moving parts solution for measuring and controlling biogases, digester gases, methane and natural gas flow. Model ST51 utilizes FCI proven thermal dispersion technology to provide direct mass flow measurement resulting in higher performance at a lower cost than orifice plates, DP, Vortex shedding and other thermal devices.
Biogas and digester gas applications are challenged by wide flow variations and dirty, wet gas. Flow variation is experienced as these processes move from low production start-up phases to a consistent, sustainable process and by seasonal temperature change, where cold temperatures slow gas production and higher temperature accelerate gas production. While the primary composition of these gases is methane and CO2, residual H2S and wet vapor leave deposits and corrode surfaces. ST51 provides the solution to these challenges. It features a wide-turndown ratio, up to 100:1 and is highly sensitive to low flow measurement. To measure correctly in fluctuating temperatures, flow meters must include temperature compensation circuitry and it is standard in ST51. ST51 has no moving parts to foul or clog and is easily pulled from the pipe for occasional cleaning.
Model ST51 installs in line sizes ranging from 2" to 24" [51 mm to 610 mm] with 1/2" or 3/4" NPT.
The Model ST51 uses precision, lithography structured platinum RTD sensors embedded in FCI’s equal mass small diameter thermowells. Combined with microprocessor electronics and precision calibration, the Model ST51 achieves excellent accuracy, fast response and virtually maintenance free operation.
Biogas, digester gas and landfill gas compositions are dominated by methane (CH4) and present a potentially hazardous installation environment. Sound engineering practice and often regulations mandate that instrumentation
meet guidelines and have agency approvals for installation zone safety. Depending on actual installation location, at a minimum the environment will require Class I, Division II and often a more rigorous Class I, Division I [Zone 1 II2GD Ex d IIC] approvals. FCI Model ST51 meets all of these and has obtained the global agency approvals that ensure your installation is always safe and complies with regulations. And, unlike manufacturers who merely provide their transmitter electronics in an approved OEM enclosure, FCI submits its entire instrument to agency testing. FCI product approvals are different because they are comprehensive system approvals that also take into account the sensor and seal requirements as well the “T” (temperature) ratings. FCI agency approvals are on the total instrument. With ST51 you are assured of the integrity of total instrument approvals that meet or exceed safe engineering practice for your applications.
Features
� Triple Outputs – Dual 4-20 mA Analog – Pulse for Totalizer
� No Moving Parts, Non-Clogging
� Dual Line, Rate and Totalizer, Digital Display
� Small, Compact Design
� Easy to Install
� Hazardous Location Approved
� Integral and Remote Mount
Page 1 of 2
ST51 Specifications
InstrumentMedia Compatibility: Biogas, Digester Gas, Methane, Natural Gas, Air, Compressed Air, Nitrogen
Pipe/Line Size Compatibility: 2" to 24" [51 mm to 610 mm] 1
Flow Range: 0.3 sfps to 400 sfps [0,08 mps to 122 mps]
Accuracy: (at ≥ 0.75 sfps [≥ 0,21 nmps] 2)
Standard: ± 2% reading ± 0.5% full scale
Optional: ± 1% reading ± 0.5% full scale
Repeatability: ± 0.5% reading
Temperature Compensation:Standard: 40 °F to 100 °F [4 °C to 38 °C];
Optional: 0 °F to 250 °F [-18 °C to 121 °C]
Turndown Ratio: 3:1 to 100:1
Agency Approvals: FM, CSA/CRN: Class I, Div. 1, Groups B, C, D; Class I, Div. 2, Groups A-D
ATEX/IECEx: Zone 1, II 2 G Ex d IIC T6...T3, II 2 D Ex tD A21 IP67 T90°C...T300°C
Warranty: 1 year1 For line sizes 2" or smaller, see FCI ST75 Series2 Contact FCI for accuracy below 0.75 sfps [0,21 nmps]
Flow ElementInstallation: Insertion, variable length with 1/2" or 3/4" NPT(M) compression fitting.
Type: Thermal Dispersion
Material of Construction: 316L stainless steel body with Hastelloy-C22 thermowell sensors, 316 stainless steel compression fitting with Teflon or stainless steel ferrule.
Pressure (Maximum Operating without Damage): Stainless steel ferrule: 500 psig [34 bar(g)]
Teflon ferrule: 150 psig [10 bar(g)]
Operating Temperature: Stainless steel ferrule: 0 °F to 250 °F [-18 °C to 121 °C]
Teflon ferrule: 0 °F to 200 °F [-18 °C to 93 °C]
Process Connection: 1/2" MNPT or 3/4" MNPT with stainless steel or Teflon ferrule.
Insertion Length (Field Adjustable): 1" to 6" [25 mm to 152 mm] 1" to 12" [25 mm to 305 mm] 1" to 18" [25 mm to 457 mm]
Flow TransmitterEnclosure: NEMA 4X [IP67], aluminum, dual conduit ports with either 1/2" FNPT or M20x1.5 entries. Epoxy coated.
Operating Temperature: 0 °F to 140 °F [-18 °C to 60 °C]
Input Power: DC: 18 Vdc to 36 Vdc (6 watts max.)
AC: 85 Vac to 265 Vac (12 watts max.; CE Mark Approval from 100 Vac to 240 Vac)
Analog Output Signals: Dual 4-20 mA, user assignable to flow rate and/or temperature and a pulse output for total flow.
Communication Port: RS-232C. Wireless IR to PDA with optional digital display models.
Digital Display: Two-line x 16 character LCD; displays measured value and engineering units. Top line assigned to flow rate, second line user assignable to temperature reading, as flow totalizer or alternating. Display can be rotated in 90° increments for optimum viewing orientation.
Installation and Mounting: Integral with sensor element or remote mountable up to 50' [15 m].
© Copyright 2008 by Fluid Components International LLC. All rights reserved. Manufactured in accordance with one or more of the following patents: US Patent Numbers: 4,929,088, 4,967,593, 4,981,368, 4,994,780, 5,111,692, 5,600,528, 5,780,737, 5,913,250, 6,208,254, 6,340,243, 6,628,202, 6,843,110, China Patent Number: ZL00815586.0. FCI is a registered trademark of Fluid Components International LLC. Information subject to change without notice.
Doc. No. 02MK011532B1008 5K
Page 2 of 2
Visit FCI on the Worldwide Web: www.fluidcomponents.com
Headquarters: 1755 La Costa Meadows DriveSan Marcos, California 92078 USAPhone: 760-744-6950 Toll Free: 800-854-1993 Fax: 760-736-6250
European Office: Persephonestraat 3-01 5047 TT Tilburg, The NetherlandsPhone: 31-13-5159989 Fax: 31-13-5799036
FCI is ISO 9001:2000 and AS9100 Certified
Locally Represented By:
CONTENTS
Introduction....................................................... 3
Flow Meters ..................................................... 4
Thermal Dispersion.......................................... 4
Flow Switches .................................................. 4
Level Switches ................................................. 5
Vortab® Flow Conditioners .............................. 5
OEM and Custom Solutions ............................ 5
Flow Meter Selector ........................................ 6
Flow & Level Switches Selector ................... 8
Calibration Capabilities ................................. 10
Sales & Service Support .............................. 11
Fluid COmpONENTS iNTErNaTiONal solves flow and level measurement applications for industrial process and plant applications using patented thermal dispersion flow measure-ment technologies. With more than 40 years experience and the world’s largest installed base of thermal dispersion instruments, you can count on FCI to know your application and have proven solutions that will save you time and expense. From off-the-shelf products to custom engineered products and systems, FCI has the selection and an unequalled record of innova-tions to supply the optimal product for your application. From single-point to multi-point flow meters, from basic air flow to complex mixed, variable flare gas compositions, from water to the harshest of chemicals, FCI products will deliver superior accuracy, repeatability and long-term reliability at the lowest installed cost.
g air, Gas, liquid, Slurry applications
g mass Flow meters
g Solutions for line Sizes 1/4″ [6 mm] to 33′ [10 m] ducts
g Thermal dispersion mass Flow Technologies
g Global Sales and Service
g Extensive product Selection to Optimize application Solutions
g accuracy assurance with Calibration in Your actual Fluid and process Conditions
g lowest maintenance, No moving parts
g Fast, Easy installation
g Compliance and System approvals to Global Standards
g analog and digital Bus Communications
g Exclusive Flow Conditioners Solve installation Constraints
Chemical
Wastewater Treatment
Power & Energy
Oil & Gas
Petroleum
Pulp & Paper
Metals
Nuclear Power
Mining
Food & Beverage
Flow and Level Instrumentation Solutions for Industrial Processes
3
Heated Sensor
ΔT
Unheated Sensor
4
Mass Flow Meters– Thermal Dispersiong Air and Gas Applicationsg Direct Mass Flow Measuringg No Moving Partsg Low Cost Solution for Large Line Sizesg Wide Turn-Down Ratio, to 1000:1g Apply in Fluids to 850 °F [454 °C]
Thermal dispersion provides a gas flow measuring solution that is easy to install and virtually maintenance-free to save you time and costs. It has no moving parts and is inher-ently multivariable, measuring both flow and temperature. Insertion styles are particularly well suited for larger line size applications because probe length and the number of sensors are easily and economically added. Thermal dispersion technology places two thermowell protected platinum RTD tempera-ture sensors in the process stream. One RTD is heated while the other senses the actual process temperature. The temperature differ-ence between these sensors is measured and is directly proportional to the mass flow rate of the fluid.
FCI Air / Gas Mass Flow Meter SolutionFCI flow meters feature a patented no-moving parts flow element design that provides direct mass flow measurement with just a single process penetration. This saves space and eliminates unnecessary installa-tion, expense, and performance degradation associated with separate temperature and pressure sensors, and density calculation devices needed with inferred mass flow techniques. With no moving parts to plug or foul, FCI flow meters deliver extensive cost savings over alternative high maintenance technologies. The result is an accurate and highly repeatable mass flow measurement at the lowest total installed cost. In today’s complex process control schemes, FCI flow meters provide accurate gas flow measure-ments essential for process consistency, quality and safe plant operation.
Flow Switchesg Air, Gas, Liquid, Slurry Applicationsg Dual and Single Relay Output Modelsg No Mechanical Parts to Maintaing Apply in Fluids to 850 °F [454 °C]g Easy to Install and Set-up
FCI flow switches utilize thermal dispersion tech-nology to provide fast response, accurate fluid flow sensing. FCI’s FLT Series and Nutec Series flow switch products provide an extensive selection for perform- ance, features, functions and environmental packaging options to meet a wide range of flow applications and installation requirements.
5
OEM and Custom SolutionsFor unique applications or installation condi-tions, FCI has the technology, engineering capabilities and production capability to meet your needs. Whether you need a slight modi-fication to a standard FCI product or a totally unique product solution designed from the ground up, FCI will work closely with you on a solution. From special enclosures to exotic materials of construction, one-time specials to high-volume custom designs, FCI has pro-duced an extensive array of flow and level measuring solutions.
Got an application challenge?You will find FCI offers an extensive array of options and special solutions that ensure an optimal product for your installation or conditions. Examples include:
g Extended Temperature Serviceg Packing Glands and Ball Valves for Hot Tap Installationg Exotic Wetted Materials and Protective Coatingsg Alternative Packaging and Enclosures, like Sun Shieldsg VeriCal ™, Industry Exclusive In-situ Calibration Verification System Available for Models GF90 and GF03g Nuclear Qualified Products
Exclusive Flow Conditioners Solve Tough InstallationsFor plant conditions with limited piping straight-run or significant flow disturbances, FCI ensures accurate and repeatable flow measurements using Vortab flow conditioners. The patented, proven Vortab technology is widely recommended by industry experts, to be the single most effective solution for flow conditioning and flow straightening. FCI is the only thermal dispersion flow technology supplier authorized to provide Vortab flow conditioners with its products.
Level Switchesg High Reliability, No Moving Partsg Dual Function, Level and Temperatureg AC, DC and Loop Powering Optionsg 3-Phase Detectiong Interface Between Two Non-Miscible Fluids
FCI liquid level and interface switches pro-vide fast responding and accurate fluid level alarm or setpoint control. They sense the tem-perature difference between a heated sensor and an unheated reference sensor, where the difference is greatest in the absence of liquid and decreases proportionally as the elements are submerged in various fluids with varying thermal conductivities. When submerged the heated sensor cools as it dissipates heat and in turn, a change in magnitude of the tem-perature difference. Because all fluids exhibit different heat transfer characteristics FCI’s highly sensitive level switch technology can detect historically difficult interface applica-tions between fluids such as liquids, gases, emulsions, slurries and foam, regardless of their physical properties.
Flow Meters
ST50 ST51 ST98 GF90 GF03
Thermal Dispersion, Insertion
Thermal Dispersion Flow MetersFCI offers the widest selection of thermal disper-sion technology flow meters to provide solutions for industrial measurement of air and virtually any gas. They are direct mass flow measuring that will save you cost and installation time over other flow devices, that require installation of additional temperature and/or pressure sensors to merely “infer” mass flow. The meters are inherently dual-function, flow and tempera-ture, to provide the lowest cost, best value for applica-tions where fluid temperature is also required. With no moving parts or orifices to clog, these FCI flow meters provide long-life with minimal maintenance.
There are eight core models with features, functions and packaging designed to optimize measurements in an array of applications and conditions. For line sizes greater than 2 inches [50 mm], FCI’s “insertion” styles provide the eco-nomical, easy-to-install solution via a single tap point. For smaller lines, 2 inches [50 mm] or smaller, select the “in-line” styles.
The ST50 and ST51 are compact and economical, yet full-featured insertion meters that are easy to install and specify. Model ST50 is designed for air, compressed air and nitrogen applications requiring Division 2 [Zone 2] or lower ratings. Model ST51 is
designed for biogas, digester gas and other meth-ane composition gases, or air and compressed air applications in Division 1 [Zone 1].
ST75 is a compact, in-line meter with extensive standard features that is the economical, easy-to specify alternative to other maintenance-intensive flow technologies.
ST75V includes built-in Vortab flow conditioners and has an extensive selection of process connec-tions, including flanges.
ST98 and ST98l combine high-performance measurement with extensive selection of options,
6
air/Gases < < < < < < < < <
liquidsmodel/Series ST50 ST51 ST98 GF90 GF03 mT86 / mT91 ST75 / ST75V ST98l GF92line Size Compatibility 2″ to 24″
[51 mm to 610 mm]2″ to 24″
[51 mm to 610 mm]2″ to 42″
[51 mm to 1066 mm]2″ to 60″
[51 mm to 1524 mm]2″ to 99″
[51 mm to 2515 mm]20″ and Greater
[508 mm and Greater]1/4″ to 2″
[6 mm to 51 mm]1″ to 2″
[25 mm to 51 mm]1″ to 2″
[25 mm to 51 mm]Key Features and applications
• EasytoInstall• EasytoSpecify• Small,CompactPackage• AirandNitrogenApplications• DualAnalogOutputs• IdealforAerationandLarger Compressed Air Lines
• EasytoInstall• EasytoSpecify• Small,CompactPackage• Biogas,DigesterGas,Methane, Natural Gas Applications• DualAnalogOutputs• Division1[Zone1]Approved
• HighAccuracy• HighPerformance• ExtensiveOptions• ComprehensivePackaging and Installation Choices• IntegralHART,ProfibusI/O
• Upto3UniqueCalibrations• WidestFlowRange• 1000:1Turn-down• WidestTempRange• Built-inKeyboard• MostExtensiveDigitalDisplay
• FlareGasandVariable MixedGases• Built-in,MixedGas Compensator• LowestTotalCostSolution forMainFlares
• ForLargeStacksandDucts• MultipleSensors AutomaticallyAveraged• CEMS,LargeCombustion andPreheaterSystems• HighTemperatureVersions• Upto16FlowSensorsper System
• NPTorTubingConnections• EasytoSpecify• Small,CompactPackage• RateandTotalFlowOutputs• IdealforFuelGasandGas Injection Applications
• HighAccuracy• HighPerformance• ExtensiveOptions• ComprehensivePackaging and Installation Choices• IntegralHART,ProfibusI/O
• Upto3UniqueCalibrations• WidestFlowRange• WidestTurn-down• WidestTempRange• Built-inKeyboard• MostExtensiveDigitalDisplay
FlowRateTotal Flow Temperature Measurement
<
<(opt)<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
Flow range 1,2
TurndownRatioAccuracyRepeatabilityTemp(maxoperating)
Pressure(maxoperating)3
FlowElementWettedMaterials
Flow Element Construction
0.75SFPSto400SFPS[0,2NMPSto122NMPS]
100:1±1%rdg,0.5%FS
±0.5%rdg0 °F to 250 °F
[-18°Cto121°C]500psig
[34bar(g)]StainlessSteelwithHast-CTips
PressFit
0.3SFPSto400SFPS[0,08NMPSto122NMPS]
100:1±1%rdg,0.5%FS
±0.5%rdg0 °F to 250 °F
[-18°Cto121°C]500psig
[34bar(g)]StainlessSteelwithHast-CTips
PressFit
0.75SFPSto600SFPS[0,2NMPSto172NMPS]
100:1±1%rdg,0.5%FS
±0.5%rdg-40°Fto850°F
[-40°Cto454°C]0psigto250psig
[17bar(g)]StainlessSteel,Hastelloy
AllWelded
0.25SFPSto1,600SFPS [0,08NMPSto488NMPS]
1000:1±1%rdg,0.5%FS
±0.5%rdg-50°Fto500°F
[-45°Cto260°C]1,000psig [69bar(g)]
StainlessSteel,Hastelloy-C Monel,Tantalum
Brazed(std);AllWelded(opt)
0.5SFPSto275SFPS [0,15NMPSto84NMPS]
600:1±2%to5%rdg
±0.5%rdg-50°Fto350°F
[-45°Cto177°C]100psig
[6,9bar(g)]Stainless Steel
AllWelded
0.25SFPSto150SFPS [0,08NMPSto46NMPS]
100:1±3% FS±1%rdg
-50°Fto850°F [-45°Cto454°C]
50psig [3,4bar(g)]
StainlessSteel,Hastelloy-C, NickelorChromiumCarbide
Brazed
0.01 SCFM to 839 SCFM [0,01NCMHto1425NCMH]
100:1±1%rdg,0.5%FS
±0.5%rdg0 °F to 250 °F
[-18°Cto121°C]600psig
[41bar(g)]StainlessSteelwithHast-CTips
AllWelded
0.0062SCFMto1,850SCFM [0,01NCMHto3140NCMH]
100:1±1%rdg,0.5%FS
±0.5%rdg-50°Fto350°F
[-45°Cto177°C]250psig
[17bar(g)]StainlessSteel,Hastelloy-C
AllWelded
0.006SCFMto2,000SCFM [0,01NCMHto3398NCMH]
1000:1±1%rdg,0.5%FS
±0.5%rdg-50°Fto350°F
[-45°Cto177°C]1,000psig [69bar(g)]
StainlessSteel,Hastelloy-C, Monel
Brazed(std);AllWelded(opt)Transmitter
Outputs (standard)
Outputs (optional)
IntegralorRemoteMountingDigitalDisplayOptionPowerSupplyEnclosureAgencyApprovals
(Dual)4-20mA;RS232C
0-1kHzPulseofTotalFlow
<
<
AC,DCMetal,NEMA4X,IP67
FM,CSA,ATEX,CPA,CE,PEDNonincendiveforusein
ClassI,Div.2GrpA,B,C&D T4 Ta = 60°C Indoor Hazardous
(Classified)LocationsII3GEExnAIIT6;II3DT65°C
(Dual)4-20mA;0-1kHzPulseofTotalFlow;
RS232C
<
<
AC,DCMetal,NEMA4X,IP67
FM,CSA,ATEX,CE,PED
ClassI,Div.1,GrpB-D,Div.2,GrpA-D,Zone1,II2GExdIICT6…T3; II2DExtDA21IP67T90°C…T300°C
4-20mA,1-5Vdc,0-5Vdc or0-10Vdc;RS232C
HART;PROFIBUS-DP
<
<
AC,DCMetal,NEMA4X,IP66
FM,ATEX,CSA,CRN,GOST/RTN,IEC,CPA,NEPSI,CE,PED
ClassI/II,Div.1&2,GrpB-G,EExdIIC,II2G/D,T4
(Dual)4-20mA,1-5Vdc,0-5Vdcor0-10Vdc;(Dual)10ARelays;
RS232C
HART
Remote<(std)
AC,DCFiberglassorMetal,NEMA4X,IP66 FM,ATEX,CSA,CRN,GOST/RTN,
IEC,CPA,NEPSI,CE,PEDClassI/II,Div.1&2,GrpB-G,
EExdIIC,II2G/D,T4
(Dual)4-20mA,1-5Vdc,0-5Vdcor0-10Vdc;(Dual)10ARelays;
RS232C
HART
Remote<(std)
AC,DCMetal,NEMA4X,IP66
GOST,CE,PED
ClassI/II,Div.1&2,GrpB-G,EExdIIC,T4
(UptoFour)4-20mA,1-5Vdc, 0-5Vdcand/or0-10Vdc;(Dual)
2ADPDTRelays;RS232C
Remote*<(std)
AC,DCMetal,NEMA4X,IP66
GOST,CE,PED
ClassI/II,Div.1&2,GrpB-G,EExdIIC,T4
(Triple)4-20mA, 0-10Vdc&0-1kHzPulse;
RS232C
<
<
AC,DCMetal,NEMA4X,IP67
FM,CSA,ATEX,CE,PED
ClassI,Div.1,GrpB-D,Div.2,GrpA-D,Zone1,II2GExdIICT6…T3; II2DExtDA21IP67T90°C…T300°C
4-20mA,1-5Vdc,0-5Vdcor 0-10Vdc;RS232C
HART;PROFIBUS-DP
<
<
AC,DCMetal,NEMA4X,IP66
FM,ATEX,CSA,CRN,GOST/RTN,IEC,CPA,NEPSI,CE,PED
ClassI/II,Div.1&2,GrpB-G,EExdIIC,II2G/D,T4
(Dual)4-20mA,1-5Vdc,0-5Vdc or0-10Vdc;(Dual)10ARelays;
RS232C
HART
Remote<(std)
AC,DCMetal,NEMA4X,IP66FM,ATEX,CSA,CRN,
GOST/RTN,IEC,CPA,CE,PEDDiv.1&2,GrpB-G, IIG,EExdIICT4
Other Features, Options • WirelessIRLink • WirelessIRLink • Namur4-20mA Fault Output• HighPurity/Sanitary Versions
• VeriCal ™In-situCalibration Verification• Built-inKeypad
• VeriCalIn-situCalibration Verification• Built-inKeypad
• *FieldMount(MT86) or 19″RackMount(MT91)
• WirelessIRLink• Built-inVortab Flow Conditioner (ST75V)
• FlangedConnections• NamurNE434-20mA Fault Indication• Built-inVortab® Flow Conditioner• HighPurity/SanitaryVersions
• FlangedConnections• Built-inKeypad
mT86/91 ST75 ST98l GF92
Thermal Dispersion, In-Line
and the widest selection of gas calibrations that makes it industry’s most often specified.
GF90 and GF92 offer an extensive feature suite and unique 3-gas calibration option that solves the toughest industry application requirements.
GF03 is specifically designed for flare flow metering and to meet the stringent environmental regulations that apply to this application.
mT Series “multi-point” flow measuring systems can be configured with two (2) to sixteen (16) flow sensing elements to optimize measurements within the largest of pipe and duct sizes.
Notes:1 Actualmeasuringrangemayvarydependingonspecific
model code and fluid.2 SFPSis70°Fat14.7psia[NMPSis0°Cat1013,25mBara].3 Higherpressureratingsavailable,contactFCI.
7
FCIflowmetersprovidelong-lifewith
minimal maintenance.
air/Gases < < < < < < < < <
liquidsmodel/Series ST50 ST51 ST98 GF90 GF03 mT86 / mT91 ST75 / ST75V ST98l GF92line Size Compatibility 2″ to 24″
[51 mm to 610 mm]2″ to 24″
[51 mm to 610 mm]2″ to 42″
[51 mm to 1066 mm]2″ to 60″
[51 mm to 1524 mm]2″ to 99″
[51 mm to 2515 mm]20″ and Greater
[508 mm and Greater]1/4″ to 2″
[6 mm to 51 mm]1″ to 2″
[25 mm to 51 mm]1″ to 2″
[25 mm to 51 mm]Key Features and applications
• EasytoInstall• EasytoSpecify• Small,CompactPackage• AirandNitrogenApplications• DualAnalogOutputs• IdealforAerationandLarger Compressed Air Lines
• EasytoInstall• EasytoSpecify• Small,CompactPackage• Biogas,DigesterGas,Methane, Natural Gas Applications• DualAnalogOutputs• Division1[Zone1]Approved
• HighAccuracy• HighPerformance• ExtensiveOptions• ComprehensivePackaging and Installation Choices• IntegralHART,ProfibusI/O
• Upto3UniqueCalibrations• WidestFlowRange• 1000:1Turn-down• WidestTempRange• Built-inKeyboard• MostExtensiveDigitalDisplay
• FlareGasandVariable MixedGases• Built-in,MixedGas Compensator• LowestTotalCostSolution forMainFlares
• ForLargeStacksandDucts• MultipleSensors AutomaticallyAveraged• CEMS,LargeCombustion andPreheaterSystems• HighTemperatureVersions• Upto16FlowSensorsper System
• NPTorTubingConnections• EasytoSpecify• Small,CompactPackage• RateandTotalFlowOutputs• IdealforFuelGasandGas Injection Applications
• HighAccuracy• HighPerformance• ExtensiveOptions• ComprehensivePackaging and Installation Choices• IntegralHART,ProfibusI/O
• Upto3UniqueCalibrations• WidestFlowRange• WidestTurn-down• WidestTempRange• Built-inKeyboard• MostExtensiveDigitalDisplay
FlowRateTotal Flow Temperature Measurement
<
<(opt)<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
<
Flow range 1,2
TurndownRatioAccuracyRepeatabilityTemp(maxoperating)
Pressure(maxoperating)3
FlowElementWettedMaterials
Flow Element Construction
0.75SFPSto400SFPS[0,2NMPSto122NMPS]
100:1±1%rdg,0.5%FS
±0.5%rdg0 °F to 250 °F
[-18°Cto121°C]500psig
[34bar(g)]StainlessSteelwithHast-CTips
PressFit
0.3SFPSto400SFPS[0,08NMPSto122NMPS]
100:1±1%rdg,0.5%FS
±0.5%rdg0 °F to 250 °F
[-18°Cto121°C]500psig
[34bar(g)]StainlessSteelwithHast-CTips
PressFit
0.75SFPSto600SFPS[0,2NMPSto172NMPS]
100:1±1%rdg,0.5%FS
±0.5%rdg-40°Fto850°F
[-40°Cto454°C]0psigto250psig
[17bar(g)]StainlessSteel,Hastelloy
AllWelded
0.25SFPSto1,600SFPS [0,08NMPSto488NMPS]
1000:1±1%rdg,0.5%FS
±0.5%rdg-50°Fto500°F
[-45°Cto260°C]1,000psig [69bar(g)]
StainlessSteel,Hastelloy-C Monel,Tantalum
Brazed(std);AllWelded(opt)
0.5SFPSto275SFPS [0,15NMPSto84NMPS]
600:1±2%to5%rdg
±0.5%rdg-50°Fto350°F
[-45°Cto177°C]100psig
[6,9bar(g)]Stainless Steel
AllWelded
0.25SFPSto150SFPS [0,08NMPSto46NMPS]
100:1±3% FS±1%rdg
-50°Fto850°F [-45°Cto454°C]
50psig [3,4bar(g)]
StainlessSteel,Hastelloy-C, NickelorChromiumCarbide
Brazed
0.01 SCFM to 839 SCFM [0,01NCMHto1425NCMH]
100:1±1%rdg,0.5%FS
±0.5%rdg0 °F to 250 °F
[-18°Cto121°C]600psig
[41bar(g)]StainlessSteelwithHast-CTips
AllWelded
0.0062SCFMto1,850SCFM [0,01NCMHto3140NCMH]
100:1±1%rdg,0.5%FS
±0.5%rdg-50°Fto350°F
[-45°Cto177°C]250psig
[17bar(g)]StainlessSteel,Hastelloy-C
AllWelded
0.006SCFMto2,000SCFM [0,01NCMHto3398NCMH]
1000:1±1%rdg,0.5%FS
±0.5%rdg-50°Fto350°F
[-45°Cto177°C]1,000psig [69bar(g)]
StainlessSteel,Hastelloy-C, Monel
Brazed(std);AllWelded(opt)Transmitter
Outputs (standard)
Outputs (optional)
IntegralorRemoteMountingDigitalDisplayOptionPowerSupplyEnclosureAgencyApprovals
(Dual)4-20mA;RS232C
0-1kHzPulseofTotalFlow
<
<
AC,DCMetal,NEMA4X,IP67
FM,CSA,ATEX,CPA,CE,PEDNonincendiveforusein
ClassI,Div.2GrpA,B,C&D T4 Ta = 60°C Indoor Hazardous
(Classified)LocationsII3GEExnAIIT6;II3DT65°C
(Dual)4-20mA;0-1kHzPulseofTotalFlow;
RS232C
<
<
AC,DCMetal,NEMA4X,IP67
FM,CSA,ATEX,CE,PED
ClassI,Div.1,GrpB-D,Div.2,GrpA-D,Zone1,II2GExdIICT6…T3; II2DExtDA21IP67T90°C…T300°C
4-20mA,1-5Vdc,0-5Vdc or0-10Vdc;RS232C
HART;PROFIBUS-DP
<
<
AC,DCMetal,NEMA4X,IP66
FM,ATEX,CSA,CRN,GOST/RTN,IEC,CPA,NEPSI,CE,PED
ClassI/II,Div.1&2,GrpB-G,EExdIIC,II2G/D,T4
(Dual)4-20mA,1-5Vdc,0-5Vdcor0-10Vdc;(Dual)10ARelays;
RS232C
HART
Remote<(std)
AC,DCFiberglassorMetal,NEMA4X,IP66 FM,ATEX,CSA,CRN,GOST/RTN,
IEC,CPA,NEPSI,CE,PEDClassI/II,Div.1&2,GrpB-G,
EExdIIC,II2G/D,T4
(Dual)4-20mA,1-5Vdc,0-5Vdcor0-10Vdc;(Dual)10ARelays;
RS232C
HART
Remote<(std)
AC,DCMetal,NEMA4X,IP66
GOST,CE,PED
ClassI/II,Div.1&2,GrpB-G,EExdIIC,T4
(UptoFour)4-20mA,1-5Vdc, 0-5Vdcand/or0-10Vdc;(Dual)
2ADPDTRelays;RS232C
Remote*<(std)
AC,DCMetal,NEMA4X,IP66
GOST,CE,PED
ClassI/II,Div.1&2,GrpB-G,EExdIIC,T4
(Triple)4-20mA, 0-10Vdc&0-1kHzPulse;
RS232C
<
<
AC,DCMetal,NEMA4X,IP67
FM,CSA,ATEX,CE,PED
ClassI,Div.1,GrpB-D,Div.2,GrpA-D,Zone1,II2GExdIICT6…T3; II2DExtDA21IP67T90°C…T300°C
4-20mA,1-5Vdc,0-5Vdcor 0-10Vdc;RS232C
HART;PROFIBUS-DP
<
<
AC,DCMetal,NEMA4X,IP66
FM,ATEX,CSA,CRN,GOST/RTN,IEC,CPA,NEPSI,CE,PED
ClassI/II,Div.1&2,GrpB-G,EExdIIC,II2G/D,T4
(Dual)4-20mA,1-5Vdc,0-5Vdc or0-10Vdc;(Dual)10ARelays;
RS232C
HART
Remote<(std)
AC,DCMetal,NEMA4X,IP66FM,ATEX,CSA,CRN,
GOST/RTN,IEC,CPA,CE,PEDDiv.1&2,GrpB-G, IIG,EExdIICT4
Other Features, Options • WirelessIRLink • WirelessIRLink • Namur4-20mA Fault Output• HighPurity/Sanitary Versions
• VeriCal ™In-situCalibration Verification• Built-inKeypad
• VeriCalIn-situCalibration Verification• Built-inKeypad
• *FieldMount(MT86) or 19″RackMount(MT91)
• WirelessIRLink• Built-inVortab Flow Conditioner (ST75V)
• FlangedConnections• NamurNE434-20mA Fault Indication• Built-inVortab® Flow Conditioner• HighPurity/SanitaryVersions
• FlangedConnections• Built-inKeypad
Flow Switches & Level Sensors
FlT93B FlT93F FlT93S FlT93l FlT93C
FLT Series
FLT SeriesFCI’s FLT93 family sets the standard for industrial flow and level switch performance, reliability and value. FLT93 combines all-welded, thermal disper-sion sensors with precision electronics protected in a robust industrial enclosure to ensure superior flow or level sensing and long life in the rigors of industrial plant installations. All FLT93 Series switches feature field configurable, dual setpoints
for any combination of high and low trip points or as a dual function flow (or level) and temperature switch. All applications encounter temperature varia-tions and unlike other thermal dispersion switches, all FLT93’s include temperature compensation to ensure proper switch operation regardless of fluid or ambi-ent temperature changes. Further, all FLT93’s uniquely feature analog voltage outputs to set and validate trip points as well as FCI’s exclusive pre-check circuit
which allows the user to verify system setpoint/trip operation at anytime via a simple contact closure.
NuTec SeriesA remarkable family of switch products that com-bine innovations like non-intrusive designs and the economy of a single limit switch. You will find a NuTec switch for solving a diverse range of flow and level applications. FS2000 and LS2000, for
8
air/Gas Flow Switch < < < < < < < <
liquid Flow Switch < < < < < < <
level/interface Switch < < < < < <
model/Series FlT93B FlT93F FlT93S FlT93l FlT93C FS2000 FS2000H FS2000l lS2000line Size Compatibility (in flow applications)
1″ to 100″ [25 mm to 2500 mm]
1″ to 100″ [25 mm to 2500 mm]
1″ to 100″[25 mm to 2500 mm]
1/4″ to 1″[6 mm to 25 mm]
1″ to 100″[25 mm to 2500 mm]
1″ to 100″[25 mm to 2500 mm]
1 1/2″ to 60″[38 mm to 1525 mm]
1/2″ to 2″[12 mm to 51 mm]
n/a
Key Features and applications
• GeneralPurpose•Dual,Heavy-duty RelayOutputs
• FastResponse• SmallProcessConnection• Dual,Heavy-dutyRelay Outputs
• Heavy-duty• HighestTemperatureService• RetractablePackingGlands• Dual,Heavy-dutyRelay Outputs
•In-lineStyle•SmallLineSizes•SuperiorLowFlowDetection•Dual,Heavy-dutyRelay Outputs
•SanitaryApplications•Meets3ARequirements•Dual,Heavy-dutyRelay Outputs
•Economy,Industrial-grade Flow Switch •SingleAlarm/SwitchRelay•2-wireLoopPoweringOption•ReplacesMechanicalSwitches
•HighestFlowRanges•Non-intrusiveDesign•Unique,Flat-faceInstalls FlushwithPipeWall
•Non-intrusive,NoSensorPartsContactFluid•In-lineStyle•SmallLineSizes•HighPolishedFinishesfor SanitaryApplications
•Economy,Industrial-grade Level Switch•SingleAlarm/SwitchRelay•2-wireLoopPoweringOption•ReplacesMechanicalSwitches
Flow Capabilities1, 2
Range-Air/Gas
Range-Liquids:Water/WaterbasedRange-Liquids: Hydrocarbon-basedAccuracy Repeatability
0.25FPSto120FPS [0,08MPSto37MPS]
0.01FPSto3.0FPS [0,003MPSto0,9MPS]
0.01FPSto5.0FPS [0,003MPSto1,5MPS]
±5%rdg;±2%ofSetpoint
±0.5%rdg
0.25FPSto120FPS [0,08MPSto37MPS]
n/a
n/a
±5%rdg;±2%ofSetpoint
±0.5%rdg
0.25FPSto120FPS [0,08MPSto37MPS]
0.01 FPSto3.0FPS [0,003MPSto0,9MPS]
0.01 FPSto5.0FPS [0,003MPSto1,5MPS]
±5%rdg;±2%ofSetpoint
±0.5%rdg
0.25FPSto120FPS [0,08MPSto37MPS]
0.01 FPSto3.0FPS [0,003MPSto0,9MPS]
0.01 FPSto5.0FPS [0,003MPSto1,5MPS]
±5%rdg;±2%ofSetpoint
±0.5%rdg
0.6 cc/sec to20,000cc/sec
0.015 cc/sec to 50 cc/sec
0.33 cc/sec to 110 cc/sec
±5%rdg;±2%ofSetpoint
±0.5%rdg
0.5FPSto100FPS [0,15MPSto30MPS]
0.15FPSto1.5FPS [0,045MPSto0,45MPS]
0.15FPSto2.0FPS [0,045MPSto0,6MPS]
+2%ofSetpoint
±1.0%range
0.25FPSto750FPS [0,08MPSto230MPS]
0.1FPSto10.0FPS [0,03MPSto3MPS]0.2FPSto20.0FPS
[0,06MPSto6MPS]+2%ofSetpoint
±1.0%range
0.02 SCFM to 342 SCFM (line size dep.) [0,0006NCMHto9,7NCMH]
0.03GPMto85GPM(line size dep.) [0,11LPMto324LPM]
0.03GPMto85GPM(line size dep.) [0,11LPMto324LPM]
±3%ofSetpoint,±0.25%of Setpoint over 100 °F [38 °C]
±1.0%range
n/a
n/a
n/a
n/a
n/alevel Capabilities
Accuracy Repeatability
±0.25 inch ±[6,4mm]
±0.125 inch ±[3,2mm]
±0.1 inch ±[2,5mm]±0.05 inch ±[1,3mm]
±0.25 inch ±[6,4mm]
±0.125 inch ±[3,2mm]
±0.25 inch ±[6,4mm]
±0.125 inch ±[3,2mm]
±0.25 inch ±[6,4mm]
±0.125 inch ±[3,2mm]
n/a
n/a
n/a
n/a
n/a
n/a
±0.125 inch ±[3,2mm]±0.06 inch ±[1,5mm]
Temperature Compensation < < < < < <(opt) <(opt) <(opt) <(opt)Sensor Operating Temp range -40°Fto350°F
[-40°Cto177°C]
-40°Fto350°F [-40°Cto177°C]
opt:100°Fto500°F [-73°Cto260°C]
-40°Fto350°F [-40°Cto177°C]
opt:100°Fto500°F [-73°Cto260°C]
opt:-100°Fto850°F [-73°Cto454°C]
-40°Fto350°F [-40°Cto177°C]
opt:100°Fto500°F [-73°Cto260°C]
-40°Fto350°F [-40°Cto177°C]
opt:100°Fto500°F [-73°Cto260°C]
-40°Fto250°F[-40°Cto121°C]
-40°Fto250°F[-40°Cto121°C]
-40°Fto250°F[-40°Cto121°C]
-40°Fto250°F[-40°Cto121°C]
Sensor Operating pressure3 2,350psig[162bar(g)]
2,350psig[162bar(g)]
2,350psig[162bar(g)]
2,000psig[138bar(g)]
2,350psig[162bar(g)]
500psig[35bar(g)]
500psig[35bar(g)]
500psig[35bar(g)] 100psig[7bar(g)]w/sanitaryflange
500psig[35bar(g)]
Flow Element Wetted materials Stainless Steel StainlessSteel,SSI-Electro-polish,Hastelloy,Monel
StainlessSteel,Hastelloy,Monel,Titanium
StainlessSteel,Hastelloy,Monel,Titanium
Stainless Steel (20RaPolished)
Stainless Steel Stainless Steel Stainless Steel (opt.10Raor20RaPolished)
Stainless Steel
Flow Element Construction AllWelded AllWelded AllWelded AllWelded AllWelded AllWeldedorPressFit AllWelded AllWelded AllWeldedorPressFitTransmitters
Outputs/Control Circuit
RemoteMountableElectronicsPowerSupplyEnclosure AgencyApprovals(system)
DualSPDTor
SingleDPDTRelays,6ADCVoltageOutputforCalibration,
DC VoltageofTemperature
AC,DCMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,IEC,CE,PEDCLIDiv1&2,GrpB-G;
EExdIICT4;SIL-2
DualSPDTor
SingleDPDTRelays,6ADCVoltageOutputforCalibration,
DC VoltageofTemperature<
AC,DCMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,IEC,CE,PEDCLIDiv1&2,GrpB-G;
EExdIICT4;SIL-2
DualSPDTor
SingleDPDTRelays,6ADCVoltageOutputforCalibration,
DC VoltageofTemperature<
AC,DCMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,IEC,CE,PEDCLIDiv1&2,GrpB-G;
EExdIICT4;SIL-2
DualSPDTor
SingleDPDTRelays,6ADCVoltageOutputforCalibration,
DC VoltageofTemperature<
AC,DCMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,IEC,CE,PEDCLIDiv1&2,GrpB-G;
EExdIICT4;SIL-2
DualSPDTor
SingleDPDTRelays,6ADCVoltageOutputforCalibration,DC VoltageofTemperature
<
AC,DCMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,IEC,CE,PEDCLIDiv1&2,GrpB-G;
EExdIICT4;SIL-2
SPDTRelay,6AandOpen Collector or
mASignalandOpenCollector
AC,DC,4-20mALoopMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,CE,PEDATEXforDCpoweredonly
CLIDiv1&2,GrpB-G;II3GEExnAIIT6,II3DT62C;
II3GEExnCIICT6,II3DT62C
SPDTRelay,6AandOpen Collector or
mASignalandOpenCollector
AC,DCMetal,NEMA4X,IP66
FM
CLIDiv1&2,GrpB-G
SPDTRelay,6AandOpen Collector or
mASignalandOpenCollector
AC,DCMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,CE,PEDATEXforDCpoweredonly
CLIDiv1&2,GrpB-G;II3GEExnAIIT6,II3DT62C;II3GEExnCIICT6,II3DT62C
SPDTRelay,6AandOpen Collector or
mASignalandOpenCollector
AC,DC,4-20mALoopMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,CE,PEDATEXforDCpoweredonly
CLIDiv1&2,GrpB-G;II3GEExnAIIT6,II3DT62C;II3GEExnCIICT6,II3DT62C
Other Features, Options •PrecheckFailGuard •PrecheckFailGuard•RackMountOption•NuclearQualifiedVersions•3-yearWarranty
•PrecheckFailGuard•RackMountOption•NuclearQualifiedVersions•3-yearWarranty
•PrecheckFailGuard•RackMountOption•NuclearQualifiedVersions•3-yearWarranty
•PrecheckFailGuard•RackMountOption•NuclearQualifiedVersions•3-yearWarranty
FS2000 FS2000H FS2000l lS2000
NuTec Series
flow and level respectively, provide a low cost so-lution to replace high maintenance mechanical switches. For high flow applications or when the application will benefit from a non-invasive design, the FS2000H is the product of choice. FS2000H is an easy-to-install insertion type design yet, with its unique flush-with-pipe-wall mounting it is totally non-invasive into the fluid. For smaller line sizes and/or sanitary applications, the model
FS2000L is an in-line style switch with sensors imbedded into the pipe wall for totally non-intrusive and unobstructed flow.
Notes:
1 Actualmeasuringrangemayvarydependingonspecificmodel code and fluid.
2 SFPSis70°Fat14.7psia[NMPSis0°Cat1013,25mBara.]
3 Higherpressureratingsavailable,contactFCI.
9
IndustryreliesonruggedFLTSeries
forcriticalflowapplications.
air/Gas Flow Switch < < < < < < < <
liquid Flow Switch < < < < < < <
level/interface Switch < < < < < <
model/Series FlT93B FlT93F FlT93S FlT93l FlT93C FS2000 FS2000H FS2000l lS2000line Size Compatibility (in flow applications)
1″ to 100″ [25 mm to 2500 mm]
1″ to 100″ [25 mm to 2500 mm]
1″ to 100″[25 mm to 2500 mm]
1/4″ to 1″[6 mm to 25 mm]
1″ to 100″[25 mm to 2500 mm]
1″ to 100″[25 mm to 2500 mm]
1 1/2″ to 60″[38 mm to 1525 mm]
1/2″ to 2″[12 mm to 51 mm]
n/a
Key Features and applications
• GeneralPurpose•Dual,Heavy-duty RelayOutputs
• FastResponse• SmallProcessConnection• Dual,Heavy-dutyRelay Outputs
• Heavy-duty• HighestTemperatureService• RetractablePackingGlands• Dual,Heavy-dutyRelay Outputs
•In-lineStyle•SmallLineSizes•SuperiorLowFlowDetection•Dual,Heavy-dutyRelay Outputs
•SanitaryApplications•Meets3ARequirements•Dual,Heavy-dutyRelay Outputs
•Economy,Industrial-grade Flow Switch •SingleAlarm/SwitchRelay•2-wireLoopPoweringOption•ReplacesMechanicalSwitches
•HighestFlowRanges•Non-intrusiveDesign•Unique,Flat-faceInstalls FlushwithPipeWall
•Non-intrusive,NoSensorPartsContactFluid•In-lineStyle•SmallLineSizes•HighPolishedFinishesfor SanitaryApplications
•Economy,Industrial-grade Level Switch•SingleAlarm/SwitchRelay•2-wireLoopPoweringOption•ReplacesMechanicalSwitches
Flow Capabilities1, 2
Range-Air/Gas
Range-Liquids:Water/WaterbasedRange-Liquids: Hydrocarbon-basedAccuracy Repeatability
0.25FPSto120FPS [0,08MPSto37MPS]
0.01FPSto3.0FPS [0,003MPSto0,9MPS]
0.01FPSto5.0FPS [0,003MPSto1,5MPS]
±5%rdg;±2%ofSetpoint
±0.5%rdg
0.25FPSto120FPS [0,08MPSto37MPS]
n/a
n/a
±5%rdg;±2%ofSetpoint
±0.5%rdg
0.25FPSto120FPS [0,08MPSto37MPS]
0.01 FPSto3.0FPS [0,003MPSto0,9MPS]
0.01 FPSto5.0FPS [0,003MPSto1,5MPS]
±5%rdg;±2%ofSetpoint
±0.5%rdg
0.25FPSto120FPS [0,08MPSto37MPS]
0.01 FPSto3.0FPS [0,003MPSto0,9MPS]
0.01 FPSto5.0FPS [0,003MPSto1,5MPS]
±5%rdg;±2%ofSetpoint
±0.5%rdg
0.6 cc/sec to20,000cc/sec
0.015 cc/sec to 50 cc/sec
0.33 cc/sec to 110 cc/sec
±5%rdg;±2%ofSetpoint
±0.5%rdg
0.5FPSto100FPS [0,15MPSto30MPS]
0.15FPSto1.5FPS [0,045MPSto0,45MPS]
0.15FPSto2.0FPS [0,045MPSto0,6MPS]
+2%ofSetpoint
±1.0%range
0.25FPSto750FPS [0,08MPSto230MPS]
0.1FPSto10.0FPS [0,03MPSto3MPS]0.2FPSto20.0FPS
[0,06MPSto6MPS]+2%ofSetpoint
±1.0%range
0.02 SCFM to 342 SCFM (line size dep.) [0,0006NCMHto9,7NCMH]
0.03GPMto85GPM(line size dep.) [0,11LPMto324LPM]
0.03GPMto85GPM(line size dep.) [0,11LPMto324LPM]
±3%ofSetpoint,±0.25%of Setpoint over 100 °F [38 °C]
±1.0%range
n/a
n/a
n/a
n/a
n/alevel Capabilities
Accuracy Repeatability
±0.25 inch ±[6,4mm]
±0.125 inch ±[3,2mm]
±0.1 inch ±[2,5mm]±0.05 inch ±[1,3mm]
±0.25 inch ±[6,4mm]
±0.125 inch ±[3,2mm]
±0.25 inch ±[6,4mm]
±0.125 inch ±[3,2mm]
±0.25 inch ±[6,4mm]
±0.125 inch ±[3,2mm]
n/a
n/a
n/a
n/a
n/a
n/a
±0.125 inch ±[3,2mm]±0.06 inch ±[1,5mm]
Temperature Compensation < < < < < <(opt) <(opt) <(opt) <(opt)Sensor Operating Temp range -40°Fto350°F
[-40°Cto177°C]
-40°Fto350°F [-40°Cto177°C]
opt:100°Fto500°F [-73°Cto260°C]
-40°Fto350°F [-40°Cto177°C]
opt:100°Fto500°F [-73°Cto260°C]
opt:-100°Fto850°F [-73°Cto454°C]
-40°Fto350°F [-40°Cto177°C]
opt:100°Fto500°F [-73°Cto260°C]
-40°Fto350°F [-40°Cto177°C]
opt:100°Fto500°F [-73°Cto260°C]
-40°Fto250°F[-40°Cto121°C]
-40°Fto250°F[-40°Cto121°C]
-40°Fto250°F[-40°Cto121°C]
-40°Fto250°F[-40°Cto121°C]
Sensor Operating pressure3 2,350psig[162bar(g)]
2,350psig[162bar(g)]
2,350psig[162bar(g)]
2,000psig[138bar(g)]
2,350psig[162bar(g)]
500psig[35bar(g)]
500psig[35bar(g)]
500psig[35bar(g)] 100psig[7bar(g)]w/sanitaryflange
500psig[35bar(g)]
Flow Element Wetted materials Stainless Steel StainlessSteel,SSI-Electro-polish,Hastelloy,Monel
StainlessSteel,Hastelloy,Monel,Titanium
StainlessSteel,Hastelloy,Monel,Titanium
Stainless Steel (20RaPolished)
Stainless Steel Stainless Steel Stainless Steel (opt.10Raor20RaPolished)
Stainless Steel
Flow Element Construction AllWelded AllWelded AllWelded AllWelded AllWelded AllWeldedorPressFit AllWelded AllWelded AllWeldedorPressFitTransmitters
Outputs/Control Circuit
RemoteMountableElectronicsPowerSupplyEnclosure AgencyApprovals(system)
DualSPDTor
SingleDPDTRelays,6ADCVoltageOutputforCalibration,
DC VoltageofTemperature
AC,DCMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,IEC,CE,PEDCLIDiv1&2,GrpB-G;
EExdIICT4;SIL-2
DualSPDTor
SingleDPDTRelays,6ADCVoltageOutputforCalibration,
DC VoltageofTemperature<
AC,DCMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,IEC,CE,PEDCLIDiv1&2,GrpB-G;
EExdIICT4;SIL-2
DualSPDTor
SingleDPDTRelays,6ADCVoltageOutputforCalibration,
DC VoltageofTemperature<
AC,DCMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,IEC,CE,PEDCLIDiv1&2,GrpB-G;
EExdIICT4;SIL-2
DualSPDTor
SingleDPDTRelays,6ADCVoltageOutputforCalibration,
DC VoltageofTemperature<
AC,DCMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,IEC,CE,PEDCLIDiv1&2,GrpB-G;
EExdIICT4;SIL-2
DualSPDTor
SingleDPDTRelays,6ADCVoltageOutputforCalibration,DC VoltageofTemperature
<
AC,DCMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,IEC,CE,PEDCLIDiv1&2,GrpB-G;
EExdIICT4;SIL-2
SPDTRelay,6AandOpen Collector or
mASignalandOpenCollector
AC,DC,4-20mALoopMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,CE,PEDATEXforDCpoweredonly
CLIDiv1&2,GrpB-G;II3GEExnAIIT6,II3DT62C;
II3GEExnCIICT6,II3DT62C
SPDTRelay,6AandOpen Collector or
mASignalandOpenCollector
AC,DCMetal,NEMA4X,IP66
FM
CLIDiv1&2,GrpB-G
SPDTRelay,6AandOpen Collector or
mASignalandOpenCollector
AC,DCMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,CE,PEDATEXforDCpoweredonly
CLIDiv1&2,GrpB-G;II3GEExnAIIT6,II3DT62C;II3GEExnCIICT6,II3DT62C
SPDTRelay,6AandOpen Collector or
mASignalandOpenCollector
AC,DC,4-20mALoopMetal,NEMA4X,IP66
FM,CSA,ATEX,CRN,CE,PEDATEXforDCpoweredonly
CLIDiv1&2,GrpB-G;II3GEExnAIIT6,II3DT62C;II3GEExnCIICT6,II3DT62C
Other Features, Options •PrecheckFailGuard •PrecheckFailGuard•RackMountOption•NuclearQualifiedVersions•3-yearWarranty
•PrecheckFailGuard•RackMountOption•NuclearQualifiedVersions•3-yearWarranty
•PrecheckFailGuard•RackMountOption•NuclearQualifiedVersions•3-yearWarranty
•PrecheckFailGuard•RackMountOption•NuclearQualifiedVersions•3-yearWarranty
FCI Calibration EnsuresInstalled AccuracyAll FCI products are tested and calibrated to rigorous standards to ensure you get the instrument that does the job you specified. To design and produce the highest quality flow instrumentation, FCI operates a world-class, fully NIST traceable flow calibration labora-tory that is certified to meet such stringent standards as MIL-STD 45662A and ANSI/NCSL Z-540. Other suppliers are often limited to air and water calibrations then rely on un-validated theoretical equivalencies for other fluids. FCI has proven this procedure to
be inadequate and may result in installed errors well outside published specifications. For most fluids, FCI thermal dispersion flow meters are calibrated using the actual fluid, as well as the actual temperature and process conditions of your application. The result is a flow meter you can install with total confidence and assurance that it meets your application. For other suppliers to per-form an actual gas calibration equal to FCI’s, they typically must send their final product to an outside laboratory that will result in extra charges and shipment delays to you.
More than 16 precision flow standstomatchfluids,fluidconditions,flowratesandlinesizeswithyourapplication.
Calibrated To Your Application
10
Choosing FCI is Easyg Pre-SaleSupportGetsYoutheRightProductg Post-SaleServiceToEnsureContinuousOperationg Free,On-lineFlowSizingToolg ProductTrainingWorkshops
InadditiontothebroadrangeofproductsandsuperiorcalibrationyoucancountonFCItoprovidesuperiorpre-saleandpost-saleserviceandsupporttoensuretherightproductandlong-termoperation.WithFCIyougetpre-salesupportandapplica-tionsassistancebyqualified,trainedandprocessexperiencedengineers.And,FCItakestheguessworkoutofspecifyingtherightflowmeterforyourapplications.AVALisFCI’sexclusiveprogramthatwillselectandrecommendoptimumsolutionsaswellasadviseofengineeringandinstallationconsiderationsforyourflowmeterapplication.UsingAVALiseasyandsimplyasksyoutoputtheparametersofyourapplicationintoadrop-downmenu.AVALisalwaysavailabletoassistyoubyvisitingFCIwebsiteat:www.fluidcomponents.com.
FCI’spost-salesupport isunmatched.Onsitefieldservice,fieldstart-upassistance,recalibration,24-hour service and technical support hot line, instrument maintenance plans and FCI sponsoredproductknowledgeworkshopsareallavailabletoyouasanFCIcustomer.
©Copyright2009byFluidComponentsInternationalLLC.Allrightsreserved.Manufacturedinaccordancewithoneormoreofthefollowingpatents:USPatentNumbers:4,929,088,4,967,593,4,981,368,4,994,780,5,111,692,5,600,528,5,780,737,5,913,250,6,208,254,6,340,243,6,628,202,6,843,110,ChinaPatentNumber:ZL00815586.0.FCIisaregisteredtrademarkofFluidComponentsInternationalLLC.Informationsubjecttochangewithoutnotice.VortabisaregisteredtrademarkoftheVortabCompany.
Visit FCi on the Worldwide Web: www.fluidcomponents.comHeadquarters: 1755 La Costa Meadows DriveSan Marcos, California 92078 USAphone: 760-744-6950 Toll Free: 800-854-1993 Fax: 760-736-6250
European Office: Persephonestraat 3-01 5047 TT Tilburg, The Netherlandsphone: 31-13-5159989 Fax: 31-13-5799036
FCi is iSO 9001:2000 and aS9100 Certified