FaultVoltageOperatedEarthLeakageCircuitBreakers(ELCB)
PostedbymusabahnasyMay1
Avoltageoperatedearthleakagecircuitbreakercomprisesacontactswitchingsystemtogetherwithavoltagesensitivetripcoil.Oninstallations,thiscoilisconnectedbetweenthemetalworktobeprotectedandasgoodaconnectionwithearthascanbeobtained.Anyvoltageriseaboveearthonthatmetalworkexceedingthesettingofthecoilwillcausethebreakertotripsogivingindirectshockriskprotection.
Trippingcoilsaredesignedsothatafaultvoltageoperateddevicewilloperateona40Vrisewhentheearthelectroderesistanceis500or24Vona200electrode.Singleandmultiphaseunits,withorwithoutovercurrentfacilities,areavailableforloadcurrentsupto100A
Atestdeviceisprovidedonavoltageoperatedunittoenabletheoperationofthecircuitbreakertobechecked,operationofthedeviceappliesavoltagetothetripcoilsosimulatingafault.
-
5/10/2015 Zone4info.comFaultVoltageOperatedEarthLeakageCircuitBreakers(ELCB)
http://zone4info.com/articles/print/1136/format/smoothbox 2/2
Trippingofthecircuitbreakerbymeansofthetestdeviceshowstheintegrityoftheelectricalmechanicalelementsthattheunitisoperatingwiththecorrectorderofoperatingvoltageand,inaddition,provestheconductorfromthecircuitbreakertotheearthelectrode.Itcannotproveotherfeaturesoftheinstallation.
Whilstthevoltageoperated()willoperatewhensubjectedtoafaultvoltageof20Vormore,itshouldbenotedthatitcannotrestrictthevoltageinmagnitudeonlyinduration.
CurrentOperatedEarthLeakageCircuitBreakers
Forindustrialapplications,earthleakagecircuitbreakersoperatingonmilliampereresidualcurrentsorworkingonfaultvoltageprincipleareoflittleuse,sincemilliamperesofearthleakagecurrentforanextensiveindustrialsystemisanormaloperatingsituation.Trippingbasedonthesecurrentswillresultinnuisanceforthenormaloperation.Milliamperesofcurrentinasystem,whereexposedconductivepartsofequipmentsareeffectivelyearthedandfaultloopimpedanceiswithinreasonablevalues,willgiveriseonlytoagroundpotential/contactpotentialriseofafewmillivolts.Thiswillinnowaycontributetoshockorfirehazard.Hereobjectionablefaultcurrentswillbeafeworafewtenthsofamperes.Insuchcases,residualcurrentoperateddevicessensitivetothesecurrentsmustbemadeuseofforearthfaultcurrentandstableoperationoftheplantwithoutnuisancetripping.Thisisachievedeitherbyseparaterelaysorinbuiltreleasesinitiatingtripsignalstothecircuitbreakers