Page 1: Fault Indicator...earth fault indicator 02 07 05 08 FLS-ST/AU sub transmitter FLS-ST/C sub transmitter 10 12 When short circuit fault or earth fault occurs, fault indicators in front

Fault Indicator

Page 2: Fault Indicator...earth fault indicator 02 07 05 08 FLS-ST/AU sub transmitter FLS-ST/C sub transmitter 10 12 When short circuit fault or earth fault occurs, fault indicators in front

1

CONTENTS

FI-3A2F

short circuit fault indicator

FI-3P3O indicator

FI-3C1O

short circuit fault indicator

EFI-3E1O

earth fault indicator

02

07

05

08

FLS-ST/AU

sub transmitter

FLS-ST/C

sub transmitter

10

12

When short circuit fault or earth fault occurs, fault indicators in front of the fault point will flash or turn flag

to indicate the fault, the indicators behind the fault point will not indicate the fault. The operator can identify

the fault area (between the last flashed indicator and the first non-flashed indicator) by following the flashed

indicators. It can help operator to find out the fault point quickly.

The Di/Dt principle is used for fault determination and indication. When fault occurs, the current flow in the

line will increase suddenly, the internal magnetic field will change, and the fault indicator will determine the

fault based on surge value and duration of the short circuit current .

CREAT is the first company to detect the earth fault with signal injection method by assistance of a device

called signal source, and the earth fault accuracy is improved greatly after using the signal source.

The fault indicator is designed and tested as per IEEE 495-2007 international standard.

OVERVIEW

1 2Substation C.B.

S

3

S

Fault Indicating Normal Indicating Fault Point

1 2

4 5

3

6

Substation C.B.

1 2

S

3

S

Substation C.B.

Fault Indicating Normal Indicating Fault Point

Fault Indicating Normal Indicating Fault Point

Page 3: Fault Indicator...earth fault indicator 02 07 05 08 FLS-ST/AU sub transmitter FLS-ST/C sub transmitter 10 12 When short circuit fault or earth fault occurs, fault indicators in front

2 3

FI-3A2F is used in overhead line system.

I t i s c o m p o s e d o f c l a m p s t r u c t u r e , b o d y a n d

transparent cover. The clamp structure is made

of special stainless steel with low magnetic loss,

and its surface processed by Zn-Ni electroplating

technology improves its corrosion resistance

performance. All of printed circuit boards are sealed

in the upside of the fault indicator body by resin

epoxy, the environment withstanding level of fault

indicator will be thus improved. The fault indicator

can be remotely operated by connecting the APP

via communication adaptor. A 433MHz or 2.4GHz

radio model integrated in the fault indicator for

communication application.The high visible LED put

on the side surface of the battery container ensures

the long visible distance. The installation ring under

the transparent cover can be easily linked to the

hook of hot stick.

FI-3A2F SHORT CIRCUIT FAULT INDICATOR Description Data

Line Voltage Up to 46kV

Temperature Range -40℃ to 85℃

Accuracy ±10% at 20℃

Minimum Reset Current 3A

Minimum Load Current 3A

Tripping Factor More than 120A

Indication LED

Total Indicating Time ≥1000 hours

Flashing Frequency 22 per minute

Maximum Operation Voltage 46kV, 50/60 Hz

Withstand Current and Duration 25kA/10ms

Adjacent Cable Immunity 10cm ( 3inch ) @10kA

Cable Diameter Range 8mm—42mm

Radio Communication Frequency 433MHz/2.4GHz

Reset Manner Time/manual/current

Reset Time 4hrs/6hrs/8hrs/12hrs/24hrs

Casing Material UV stable polycarbonate

Clamp Material Stainless steel

Visibility150m in the day

300m at night

Weight 0.55kg

RATING

174

87

84

87

Page 4: Fault Indicator...earth fault indicator 02 07 05 08 FLS-ST/AU sub transmitter FLS-ST/C sub transmitter 10 12 When short circuit fault or earth fault occurs, fault indicators in front

4 5

MODEL DESCRIPTION

FI-3A2F-S00X

Indicate permanent and temporary fault, 6 LED indication, blue LED

indicate temporary fault and red LED indicate permanent fault, manual,

current and time reset. Communication is not available. 0X is reset time.

FI-3A2F/WEquip the 433MHz/2,4GHz radio model in fault indicator, parameters can

be set by APP.

FI-3C1O SHORT CIRCUIT FAULT INDICATORFI-3C1O fault indicator is used for short circuit

fault detection in the underground system which

installed in RMU or switchgear cabinet. The fault

can be remote indication via optical fiber.

FI-3C1O fault indicator consists of clamp structure

and body. The fault indicator adopts low power

consumption design with the power managed

by micro processor, so the battery can sustain

about 1000 hours flashing time. The environment

withstanding level can be greatly improved after

the battery and circuit board being sealed in the

enclosure by resin epoxy. The installation ring is

designed next to the body, making the structure

small and compact.

ORDER INFORMATION

103

83.7

145

125.5

Page 5: Fault Indicator...earth fault indicator 02 07 05 08 FLS-ST/AU sub transmitter FLS-ST/C sub transmitter 10 12 When short circuit fault or earth fault occurs, fault indicators in front

6 7

Description Data

Line Voltage Up to 46kV

Temperature range -40℃ to 85℃

Accuracy ±10% at 20℃

Minimum Reset Current 3A

Minimum Load Current 3A

Tripping Factor More than 120A

Indication Local and optical fiber remote indication

Total Indicating Time ≥1000 hours

Flashing Frequency 22 per minute

Maximum Operation Voltage 46kV

Withstand Current and Duration 25kA/200ms

Adjacent Cable Immunity 10cm (3inch) @10kA

Cable Diameter8mm—42mm

8mm—65mm

Reset Manner Time/manual/current

Reset Time 4hrs/6hrs/8hrs/12hrs/24hrs/48hrs

Casing Material UV stable polycarbonate

Clamp Material Stainless steel

Visibility Local

Weight 0.56kg

MODEL DESCRIPTION

FI-3C1O-S20XIndicate permanent fault, manual, time and current reset, application cable

outside diameter is 8—42mm, 0X is reset time.

FI-3C1O-B30XIndicate permanent fault, manual, time and current reset, application cable

outside diameter is 8—65mm, 0X is reset time.

RATING

ORDER INFORMATION

FI-3P3O INDICATORFI-3P3O indicator is installed in the RMU and

pad-mounted switchgear, it used for the remote

indication of underground fault. The FI-3P3O

fault indicator can remotely indicate the fault by

connecting the detectors with optical fiber as well

as transfering the data by electric signal via dry

contacts.

The potential-free connection between short

circuit detectors and earth detector to the FI-

3P3O indicator is done by optical fibers. A manual

reset button is set at the front of panel, by long

press, the battery status of indicator can be

checked. One 3.6V battery is assembled in the

fault indicator for power supply, ensuring that

the panel indicator can work 1000 hours without

maintenance.

92

44

55

Page 6: Fault Indicator...earth fault indicator 02 07 05 08 FLS-ST/AU sub transmitter FLS-ST/C sub transmitter 10 12 When short circuit fault or earth fault occurs, fault indicators in front

8 9

Description Data

Temperature Range -35℃ to 85℃

Electric Switch Rated Voltage DC/AC 12 to 250V

Electric Switch Rated Current 1A

Indication Local and remote via dry contacts

Battery Life ≥1000 hours

Withstand Voltage and Duration 2.5kV/60s

Fiber Distance 5m

Reset Manner Time/Manual

Casing Material UV stable polycarbonate

Weight 0.32 kg

MODEL DESCRIPTION

FI-3P3OLocal LED indication, battery can not be replaced, external source is not

available.

Description Data

Temperature Range -40℃ to 85℃

Accuracy ±3% at 20℃

Application Cable 50—89mm

Indication 1 red LED

Weight 0.25 kg

MODEL DESCRIPTION

FI-3E1O 15A /450ms, 60A/50ms over-current setting.

RATING

ORDER INFORMATION RATING

ORDER INFORMATION

EFI-3E1O EARTH FAULT INDICATOREFI-3E1O earth fault indicator is used for the

earth fault detection, which considers the

protection setting of distribution system, using

the zero-sequence current and duration time in

the tripping principle. When earth fault occurs,

the unbalance of three phases will cause the zero-

sequence current, and when the zero-sequence

current reach the setting value and duration, the

fault indicator will indicate the fault.

By using clip CT structure, the current detection

accuracy is improved. It is convenient to check the

fault feeder by local LED.

A B

FTU

Wires

Optical fi

ber

Detector

C D

3P3O Panel Fault Indicator

Reset/Safe-check

Detector Detector Detector

56

210

Ø150

Ø100

85

Page 7: Fault Indicator...earth fault indicator 02 07 05 08 FLS-ST/AU sub transmitter FLS-ST/C sub transmitter 10 12 When short circuit fault or earth fault occurs, fault indicators in front

10 11

Description Data

Temperature Range -40℃ to 85℃

Rated Voltage 6VDC ±20%

Power Consumption < 0.02W

Wireless Frequency 433MHz

Wireless Distance 3-20m

Battery Capacity 4.5Ah (replaced and charged )

GSM Model E-GSM/GPRS 900/1800

Cell Phone Card Power 3.5V

Detector Link Quantity 3 or 6

Battery Life 5-8 years

Size 125mm*220mm*220mm

Weight Less than 5 kg

MODEL DESCRIPTION

FLS-ST/AUMessage & GPRS communication, 433MHZ wireless communication solar

charging.

FLS-ST/AU SUB TRANSMITTERThe FLS-ST/AU sub transmitter is used to receive

and transfer signal in fault locating system. There

is a RF001 wireless communication model in the

sub transmitter, which is matched with the wireless

model in FI-3A6W/1 fault indicator. It can receive

the fault signal from fault indicator by 433MHz

wireless radio, after translating the signal as

per inner protocol, sub transmitter will send the

message to customer or center station by GPRS /

GSM net via inner model.

The FLS-ST/AU sub transmitter has a solar panel

to charge for inner capacitor bank. The main

supply of power is the capacitor bank, whose

inner alternated battery can keep 15 days power

supplying if the capacitor is power off and the

sunshine is not good. FLS-ST/AU can adopt wireless

setting, the special setting tool can be connected

with the sub transmitter by wireless model, which

has its parameters set by software installed in the

computer, no external wire, convenient and reliable.

RATING

ORDER INFORMATION

Page 8: Fault Indicator...earth fault indicator 02 07 05 08 FLS-ST/AU sub transmitter FLS-ST/C sub transmitter 10 12 When short circuit fault or earth fault occurs, fault indicators in front

12 13

Description Data

Temperature Range -40℃ to 70℃

Power Consumption < 0.04W

Maximum Consumption 8W

Wireless Frequency 433MHz

Power Supply 220VAC,PT/CT

GSM Model E-GSM/GPRS 900/1800

Cell Phone Card Power 3.5V

Detector Link Quantity 24

Size 430mm*265mm*135mm

Weight Less than 8 kg

MODEL DESCRIPTION

FLS-ST/C1D1 GSM message report, CT/PT power supply.

FLS-ST/C1G1 GPRS net signal transformation , CT/PT power supply.

FLS-ST/C SUB TRANSMITTERFLS-ST/C sub transmitter is a receiving and

transferring device in underground type fault

locating system, which can receive the signal from

panel indicator by dry contacts, and then send out

the information to upstream automation devices

by message or GPRS net after inner translation or

calculation, making the fault point be located in

short time.

The power supply of FLS-ST/C series sub transmitter

can be supplied by both CT and PT. Customers can

choose the power supply type as per their system

configuration in their orders. The sub transmitter

can be set via RS232 port, the setting process is

simple, and little maintenance work is needed.

RATING

ORDER INFORMATION