Page 1: Fan P-NO 2 (SF-R-12)

Kruger Ventilation Industries(Thailand).Ltd.30/105 Moo1 Sinsakorn Industrial EstateChetsadawithi Rd, Khok Kham, Mueng,Samutsakorn 74000Tel: +662-105-0399 Fax: +662-105-0370-2Email: [email protected]

DateCompanyAttentionProjectReferenceNotes

METROPOLITAN WATERWORKNO.2 (SF-R-12)

Date 11.2a.355 Date 30/10/2013 Date 15:44:47 Date

Fan Type

Unit

Operating Conditions

Air Volume

Static Pressure

Velocity Pressure

Total Pressure

Outlet Velocity

Fan Total Efficiency

Fan Static Efficiency

Fan Speed

Air Temperature

Altitude

Fan Absorbed Power

Recommended Motor

Motor Speed

Service Factor

Plenum Size

Outlet Size

Rec. Airflow Variation

Fan Pulley / Bush / Shaft

Motor Pulley / Bush / Shaft

Belt Length

Number of Belts / f

Static Belt Tension/Belt

Belt Deflection

Belt Speed (<40m/s)

Bearing Life ( L10 / L50 )

Starting Torque

Operating Limits

Max. Absorbed Power

Max. Fan Speed

Temperature (Min-Max)

DIDW Backward Curved

BDB560/CM (CLI)

Ducted

18000 m3/h

75.0 mmwg

5.7 mmwg

80.7 mmwg

9.80 m/s

78.6 %

73.1 %

1337 rpm

20.0 C

0 m

5.13 kW

D132M ( 7.50 kW )

-

20 %

-

-

-

-

-

-

-

-

-

-

-

-

12.00 kW

1700 rpm

-20° to +85°C

Hz 63 125 250 500 1k 2k 4k 8k Overall

Lwi(Lin)84 84 89 83 82 77 71 64 92 dB

Lwi(A) 59 69 80 80 82 78 72 63 86 dB(A)

Lpi(A) 48 58 69 69 70 67 61 52 75 dB(A)

* Sound data is for the inlet side

* Sound Pressure Level 1m, Free Field

Absorbed Power in kW

10

8

6

4

2

0

Static Pressure in mmwg 100

80

60

40

20

0

Total Efficiency % 100

80

60

40

20

0

30k20k10k0

Air Volume in m3/h

A A

1030

B

892

C

603

D

714

E

714

F

280

F1

125

G

390

H

844

J

764

K

814

L

1000

M

93

P

48

R

7

t

12

t1

8

w

70

z

43

Od

40

UxS

13x18