fan blade pitch - cooling tower depotcoolingtowerdepot.com/docs/fin-fan-check.pdf · fan blade...

1
Fin Fan check if there is a system vibration issue Mark fan blade numbers with mark on each fan blade FAN BLADE PITCH FAN BLADE TRACKING FAN BLADE SWEEP MAX RUNNING AMP READING Fan Pitch Design 1 2 3 4 5 6 7 8 Blade # As Found After Adjustment Pitch must be within +/-0.2 Mount Protractor on flat bar as base and place it approximatley 1” from tip of blade. Trace each blade with marker on pleum Mark lines with blade number The difference between levels of highest and lowest outlests should not be more than 1/2” Measure from trailing edge to trailing edge of the next blade. All sweep measurements must be within 1” of each other. As Found After Adjustment Tracking must be within 1/2’ Amp Reading Before: Amp Reading After: As Found After Adjustment Between Blade # 1-2 2-3 3-4 4-5 5-6 6-7 7-8 8-9 Sweep must be close

Upload: others

Post on 05-Jun-2020

20 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FAN BLADE PITCH - Cooling Tower Depotcoolingtowerdepot.com/docs/Fin-Fan-Check.pdf · Fan Blade Pitch Fan Pitch Design. Blade # As Found After Adjustment Pitch must be within +1-0.20

Fin Fan check if there is a system vibration issue

Mark fan blade numbers with mark on each fan blade

FAN BLADE PITCH

FAN BLADE TRACKING

FAN BLADE SWEEP

MAX RUNNING AMP READING

Fan Pitch Design

12345678

Blade # As Found After Adjustment

Pitch must be within +/-0.2Mount Protractor on flat bar as base and place it approximatley 1” from tip of blade.

Trace each blade with marker on pleumMark lines with blade number

The difference between levels of highest and lowest outlests should not be more than 1/2”

Measure from trailing edge to trailing edge of the next blade. All sweep measurements must be

within 1” of each other.

As Found After Adjustment

Tracking must be within 1/2’

Amp Reading Before: Amp Reading After:

As Found After AdjustmentBetweenBlade #

1-22-33-44-55-66-77-88-9

Sweep must be close