f871112369241051

Upload: madhu-tallapanenimadhu

Post on 07-Apr-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/3/2019 f871112369241051

    1/23

    256 Int. J. Renewable Energy Technology, Vol. 1, No. 3, 2010

    Copyright 2010 Inderscience Enterprises Ltd.

    Long-term stabilisation of grid connected wind farms

    with FACTS controllers

    N. Senthil Kumar* and M. Abdullah Khan

    Department of Electrical Engineering,

    B.S.A. Crescent Engineering College,

    Vandalur, Chennai-48, India

    E-mail: [email protected]

    *Corresponding author

    Abstract: The increasing power demand has led to the growth of newtechnologies that play an integral role in shaping the future energy market.Keeping in view of the environmental constraints, grid connected wind turbinesare promising in increasing system reliability. This paper presents the impactof FACTS controllers on the long-term dynamic stability of power systemsconnected with wind farms based on doubly fed induction generator systems.The stability assessment is made first for a three-phase short circuit without theFACTS controllers in the power network and then with the FACTS controllers.The long-term dynamic simulation results yield information on:

    1 the impact of faults and slow wind speed changes on the performance ofwind driven induction generators

    2 the change in controllable parameters of the FACTS controllers followingthe faults and wind speed changes

    3 transient reactive power ratings of FACTS controllers for enhancementof rotor speed stability of induction generators and angle stability ofsynchronous generators.

    Keywords: wind energy conversion systems; flexible AC transmissionsystems; rotor angle stability; rotor speed stability; long-term dynamic

    simulation.

    Reference to this paper should be made as follows: Kumar, N.S. andKhan, M.A. (2010) Long-term stabilisation of grid connected wind farms withFACTS controllers, Int. J. Renewable Energy Technology, Vol. 1, No. 3,

    pp.256278.

    Biographical notes: N. Senthil Kumar is presently working as an AssistantProfessor (Senior Grade) in the Department of Electrical and ElectronicsEngineering at BSA Crescent Engineering College. He has 12 years of teachingand six years of research experience. He has undergone the EUROSTAGsoftware training programme at Tractable Engineering, Brussels, Belgium. Hisarea of research includes modelling of FACTS devices for power systemstudies and modelling of wind energy conversion systems for power systemstability analysis. He has three international journals to his credit.

    M. Abdullah Khan has 40 years of teaching and research experience. His areaof research includes power system analysis and optimisation and power systemdynamics. He has published several papers in reputed international journals.

  • 8/3/2019 f871112369241051

    2/23

    Long-term stabilisation of grid connected wind farms with FACTS controllers 257

    1 Introduction

    As power systems became interconnected, areas of generation were found to be prone

    to electromechanical oscillations. These oscillations have been observed in many

    power systems worldwide. As the level of power transmission rose, largely through

    existing interconnections, which were becoming relatively weak and inadequate, load

    characteristics added to the problem causing spontaneous oscillations. The oscillations

    may be local to a single generator or generator plant (local oscillations, 1.02 Hz) or

    they may involve a number of generators widely separated geographically (interarea

    oscillations, 0.20.8 Hz). If not controlled, these oscillations may lead to total or partial

    power interruption (Kundur, 1994).

    Wind energy development is consumer and environment friendly, it requires shorter

    construction time and is cost competitive. It becomes one of the most competitive sources

    of renewable energy. However, wind power has some disadvantages. For example, wind

    power is considered as an intermittent power supply because wind does not blow 100%

    of the time. Besides, the superior wind sites are usually located in remote areas; therefore,it may require substantial infrastructure improvement to deliver the wind-generated

    power to the load centre. There are four major types of wind generators, which are used

    very widely:

    1 squirrel cage induction generators

    2 doubly fed induction generators

    3 direct driven synchronous generator

    4 permanent magnet synchronous generator.

    For the present work, we have used doubly fed induction generator model for executing

    dynamic simulations. The dynamic stability of a single wind turbine generator supplying

    an infinite bus through a transmission line was studied by developing the linearised

    model of the power system under different loading conditions (Abdel-Magid andEl-Amin, 1987).

    The effect of wind turbines on the transient fault behaviour of the Nordic power

    system was investigated for different faults in Jauch et al. (2007). A novel error driven

    dynamic controller for the static synchronous compensator (STATCOM) FACTS device

    was designed to stabilise both wind energy conversion stand-alone system as well

    as hybrid scheme of wind turbine with hydro generators (Elmoursi and Sharaf, 2006). A

    new definition on rotor speed stability of asynchronous generators is proposed in

    Samuelsson and Lindahl (2005). A control structure for DFIG-based turbines under

    unbalanced conditions is proposed in Xiu and Wang (2007). The application of voltage

    source converter (VSC) based transmission controllers for wind energy conversion

    systems is discussed in Varma and Sidhu (2006). Wind turbine model for power system

    stability analysis was derived and discussed in Coughlan et al. (2007). The dynamic

    behaviour of the power system is analysed with high wind power penetration in

    Akhmatov (2003). The impact of FACTS controllers on the rotor speed/rotor anglestability of power systems connected with wind farms is discussed in Kumar and Khan

    (2008).

    The objective of the present work is to study the impact of FACTS controllers on

    the long-term dynamic stability of power systems with wind farms based on doubly

  • 8/3/2019 f871112369241051

    3/23

    258 N.S. Kumar and M.A. Khan

    fed induction generators. The dynamic stability of the system is studied by running time

    domain simulations without and with FACTS controllers. The following FACTS

    controllers are taken up for the analysis:

    1 static var compensator (SVC)

    2 static synchronous compensator (STATCOM)

    3 thyristor controlled series capacitor (TCSC)

    4 unified power flow controller (UPFC).

    The induction generator absorbs reactive power during its normal operating condition.

    This may create low voltage and dynamic instability in the system (Chompoo-Inwai

    et al., 2005).

    This paper is organised as follows. Section 2 presents the modelling of power system

    and wind turbine along with FACTS controllers. Section 3 presents the dynamic

    simulation results obtained for a three-phase transient fault on the system with andwithout FACTS controllers. Section 4 presents the results and discussion on the

    simulation results obtained. Section 5 presents the conclusions.

    2 Modelling of the power system and induction generator

    In general, for the purpose of dynamic analysis, power systems are modelled by a set of

    differential and algebraic equations (DAE), that is:

    x f (x, y, , p)

    0 g(x, y, , p)

    =

    =

    (1)

    where

    n

    x R is a vector of state variables associated with the dynamic states ofgenerators, loads and other system controllers; my R is a vector of algebraic variables

    associated with steady state variables resulting from neglecting fast dynamics (e.g., most

    load voltage phasor magnitudes and angles);l

    R is a set of uncontrollable parameters,

    such as variations in active and reactive power of loads; andk

    p R is a set of

    controllable parameters such as transformer tap, AVR settings and FACTS controller

    reference voltages (Mithulananthan et al., 2003).

    2.1 Modelling of wind energy conversion system

    Normally, a wind turbine creates mechanical torque on a rotating shaft, while an

    electrical generator on the same rotating shaft is controlled to produce an opposing

    electromagnetic torque. The power and torque equations for the wind turbine are as

    follows. The doubly fed induction generator is the most commonly used machine for

    wind power generation. The rotor terminals are fed with a symmetrical three-phase

    voltage of variable frequency and amplitude. This voltage is supplied by a VSC usually

    equipped with IGBT-based power electronics circuitry. The basic structure of the DFIG-

    based wind energy conversion scheme is shown in Figure 1.

  • 8/3/2019 f871112369241051

    4/23

    Long-term stabilisation of grid connected wind farms with FACTS controllers 259

    3p

    1P C AV

    2

    = (2)

    PT =

    (3)

    where

    P output power of the turbine (W)

    T mechanical torque (Nm)

    rotor speed of wind turbine (rad/s)

    density of air (= 1.22 kg/m3)

    A swept area of the blade (m2)

    Cp performance coefficient

    V wind speed (m/s).

    Figure 1 Wind energy conversion scheme and its associated controls

    The wind farm is represented as an aggregated model of ten wind turbines of each 2 MW

    (EUROSTAG Release 4.3 Package Documentation Parts 1, 2 and 3, 2004).

    The main controller manages the overall control functions, whereas pitch and

    power controller are subordinate units. The wind energy conversion scheme used for

  • 8/3/2019 f871112369241051

    5/23

    260 N.S. Kumar and M.A. Khan

    simulation consists of a doubly fed induction generator (rotor circuit connected to the

    grid through power electronic converter). The converter adjusts the frequency of the

    rotor feeding current to enable variable speed operation. The power electronic converterconsists of two-VSCs connected through capacitor.

    If shaft, turbine and generator damping are neglected, the two-mass model is

    described by the following equations:

    tt t s s

    dT J K

    dt

    = + (4)

    re g s s

    dT J K

    dt

    = (5)

    t r

    d

    dt

    = (6)

    where Tt is the mechanical torque referred to the generator side (Nm), Te is the

    electromagnetic torque (Nm), Jt is the equivalent turbine-blade inertia referred to the

    generator side (kg m2), t is the turbines rotational speed (rad/s), r is the generators

    rotational speed (rad/s), Ks is the shaft stiffness (N.m/rad) and s is the angular

    displacement between the ends of the shaft (rad). Figure 2 gives the two mass

    representation of the wind turbine (Gaztanaga et al., 2007).

    Figure 2 Two-mass representation of the wind turbine

    2.2 Doubly fed induction generator model

    Equations (7) to (11) represent the complete set of mathematical relationships that

    describe the dynamic behaviour of the machine. The per unit system is adopted as a unit

    of measurement for all quantities and the sign convention is chosen in such a way that

    consumed inductive reactive powers are positive (note also that o is equal to 1.0 p.u.).

    Voltage equations:

    ss s s s

    dr I j V

    dt

    = + (7)

    r

    r r r r r

    d

    r I j( ) Vdt

    = + (8)

    Flux linkages:

    s s s m r l I l I = + (9)

  • 8/3/2019 f871112369241051

    6/23

    Long-term stabilisation of grid connected wind farms with FACTS controllers 261

    r m s r r l I l I = + (10)

    Equations of motion:

    ( )r sd sq sq sd ms

    d 1i i t

    dt

    = +

    (11)

    where

    Is, Ir stator and rotor currents

    Vs, Vr stator and rotor terminal voltages

    s, r stator and rotor flux linkages

    lm mutual inductance (in per unit it is equal to Xm)

    rs, rr stator and rotor resistances

    r, rotor angular speed, synchronous speed

    d, q-direct quadrature axis component

    tm mechanical torque.

    The DFIG model used is a third order model [equations (7), (8) and (11)], the state

    variables being stator, rotor flux components and rotor speed. The variable frequency

    rotor voltage permits the adjustment of rotor speed to match the optimum operating point

    at any practical wind speed. In normal mode, the rotor side converter is used to control

    the real and reactive power outputs of the machine. Independent control of real and

    reactive power can be achieved through rotor current control. The rotor current controller

    is modelled using the model editor menu of EUROSTAG.

    From the basic equations of DFIG (seven to ten) setting all derivatives to zero (steady

    state) and with stator resistance rs = 0, we get:

    s m rr r r m r r

    s

    (v jx i )V r i js x x i

    jx

    = + +

    (12)

    Considering a coordinate system where the d-axis is located along Vs, it follows that:

    ( )mrd r rd s rq r s

    xV r i s V i x

    x

    = +

    (13)

    rq r rq rd r V r i s i x= + (14)

    where leakage coefficient2m

    r s

    x1

    x x

    =

    is introduced.

    s is the operating slip of the generator. The voltage drops over the rotor resistance in

    (13) and (14) can be interpreted as auxiliary signals, which are outputs of the intended

    rotor current controller. PI controllers are introduced to control the rotor voltages and

    hence rotor currents.

  • 8/3/2019 f871112369241051

    7/23

    262 N.S. Kumar and M.A. Khan

    ( )rd I rd ref rd1

    1V K 1 i i

    pT

    = +

    (15)

    and

    ( )rq I rq ref rq1

    1V K 1 i i

    pT

    = +

    (16)

    The corresponding block diagram of the rotor current controller is shown in Figure 3. The

    wind turbines use a simplified control scheme and are not LVRT equipped.

    Figure 3 Rotor current controller (see online version for colours)

    The line or grid side converter has to transmit the active power from the dc link to the

    grid so that the dc link voltage is kept within limits. The corresponding controller and

    converter model is shown in Figure 4. The output is the active current that is injected into

    the grid node.

    Figure 4 Block diagram of line side converter control

  • 8/3/2019 f871112369241051

    8/23

    Long-term stabilisation of grid connected wind farms with FACTS controllers 263

    2.3 Synchronous generators

    In power system dynamic studies, the synchronous generator is commonly represented by using models of varying degrees of complexity the simplest being the classical

    (second order) model that assumes a constant voltage behind transient reactance. The

    synchronous machine model used for this dynamic analysis is the two-axis model with

    four state variables (Ed, Eq, , ).

    2.4 Static var compensators

    SVC is basically a shunt connected static var generator/absorber whose output is adjusted

    to exchange capacitive or inductive current so as to maintain or control specific power

    system variables; (Figure 5) typically, the controlled variable is the SVC bus voltage.

    One of the major reasons for installing an SVC is to improve dynamic voltage control,

    and thus, increase system loadability. The SVC bus is modelled as a PV bus in the load

    flow programme. It is modelled as a variable susceptance controller as shown in Figure 6for the execution of the dynamic simulation programme.

    Figure 5 Ideal SVC

    Figure 6 Dynamic model of SVC

  • 8/3/2019 f871112369241051

    9/23

    264 N.S. Kumar and M.A. Khan

    An additional stabilising signal and supplementary control superimposed on the voltage

    control loop of an SVC can provide damping of system oscillations during transient faults

    and disturbances.

    2.5 Static synchronous compensator

    Figure 7 Block diagram of STATCOM

    Figure 8 Dynamic model of STATCOM

  • 8/3/2019 f871112369241051

    10/23

    Long-term stabilisation of grid connected wind farms with FACTS controllers 265

    The STATCOM resembles in many respects a synchronous compensator, but without

    inertia. The basic electronic block of a STATCOM is the VSC, (Figure 7) which in

    general converts an input dc voltage into a three-phase output voltage at fundamentalfrequency, with rapidly controllable amplitude and phase. is the phase shift between the

    controller VSC AC voltage and its bus voltage V. Vref is the reference voltage setting.

    A phase control strategy is assumed for control of the STATCOM bus voltage and

    additional control block and signals added for oscillation damping as shown in Figure 8.

    2.6 Thyristor controlled series capacitors

    TCSC schemes typically use a thyristor-controlled reactor in parallel with a capacitor

    to vary the effective compensating reactance. In practice, several capacitor banks, each

    with its own thyristor-controlled reactor, may be used to meet the specific application

    requirements. For the purpose of analysis, the TCSC, regardless of its practical

    implementation, can be considered simply as a continually variable capacitor whose

    reactance is controllable in the range of 0 Xc Xcmax. The controllable series capacitivereactance cancels part of the reactive line reactance resulting in a reduced overalltransmission impedance and correspondingly increased transmittable power. The single

    line diagram of the TCSC is shown in Figure 9.

    Figure 9 Thyristor controlled series capacitor

    Figure 10 Dynamic model of TCSC

  • 8/3/2019 f871112369241051

    11/23

    266 N.S. Kumar and M.A. Khan

    The variable reactance model of TCSC is as shown in Figure 10. Vcap is the voltage

    across the capacitor and Xc is the variable reactance inserted by the TCSC module into

    the line. Xref is the steady state reactance of the fixed capacitor under normal conditionsto maintain the steady state power flow (Mathur and Varma, 2002).

    2.7 Unified power flow controllers

    The UPFC is the most versatile FACTS controller developed so far, with all

    encompassing capabilities of voltage regulation, series compensation and phase shifting.

    It comprises two VSCs coupled through a common dc link. The series converter (VSC2)

    is controlled to inject a voltage phasor Vse, in series with the line, which can be varied

    from zero to Vsemax and the phase angle of Vse can be independently varied from zero

    to 360. The single line diagram is shown in Figure 11.

    The UPFC is modelled in the power flow programme using the power injection

    model with two real and reactive power injections at two nodes of the system. The power

    injections at both the nodes are selected such that the base case power flow with

    induction generator is maintained. The active and reactive power flow control loops of

    the UPFC are shown in Figures 12 and 13.

    Figure 11 Single line diagram of UPFC

    Figure 12 Active power control loop

  • 8/3/2019 f871112369241051

    12/23

    Long-term stabilisation of grid connected wind farms with FACTS controllers 267

    Figure 13 Reactive power control loop

    The stabilising signal for the UPFC is derived from a power oscillation-damping block,

    which uses active power flow as the input signal. Pflow ref is the reference value of active

    power flow in the line on which UPFC is connected. The reference value of the active

    power flow can be set depending on the operating condition of the power system. Pflow is

    the actual active power flow in the line. Vseq is the component of series injected voltage in

    quadrature with the line current.

    Qref from the above figure is the reference value of reactive power flow in the UPFC

    controller. Qflow is the actual reactive power flow in the line and Vsep is the component of

    AC voltage injected in phase with the line current.

    2.7.1 Parameter tuning

    The gains of the FACTS controllers in the forward path of the transfer function are

    tuned by using an optimisation algorithm which minimises the voltage oscillations of

    the induction generator bus. The tuning is posed as an optimisation problem with the

    objective as minimising the oscillations of point of common coupling (PCC) voltage from

    the desired value and is given by:

    2ref k

    k

    min max

    Minimise: SSDI (V V )

    K K K

    =

    (17)

    where Vref = 1.0 per unit and SSDI is the sum squared deviation index of the PCC

    voltage.

    3 Long-term dynamic simulation results and stability investigation

    The single line diagram of the test system with the wind turbine connected is shown

    in Figure 14. The test system consists of a seven bus system with two synchronous

    generators G1 and G2. The doubly fed induction generator (IG) is connected to the grid

    through a three winding transformer. IG denotes the stator of the doubly fed induction

    generator. At node ST, the stator of induction generator is connected, and at node RT, the

    rotor of the doubly fed induction generator is connected denotes the rotor of the inductiongenerator.The dynamic performance of the FACTS controllers with wind turbines is

    investigated following the disturbance sequence mentioned below.

    1 at t = 2 seconds, a three-phase fault on line 23 in the second line near bus 3

  • 8/3/2019 f871112369241051

    13/23

    268 N.S. Kumar and M.A. Khan

    2 at t = 2.125 seconds, the three-phase fault is cleared

    3 at t = 20 seconds, the wind speed increases from 2 m/s to 7 m/s (a ramp increase)

    4 at t = 50 seconds, the load at bus 5 is increased by 15 MW (load increase).

    At bus 5, the load is represented as a combination of impedance and voltage frequency

    dependant load in the dynamic simulation. The shunt connected FACTS controllers

    (SVC and STATCOM) are located at bus 3 and the series connected FACTS controllers

    are located in one of the lines in grid wind farm line (23). The total MW load on the two

    load buses 5 and 4 of the test system is 500 MW and 5,000 MW respectively. The steady

    state active power generated by generator G1 800 MW and that of G2 is 5,000 MW. The

    wind genertor (IG) supplies 5.5 MW in the steady state.

    This specific test system is chosen for the dynamic simulation study as this system

    has only two synchronous machines which is good enough for conducting stability

    investigation on a wind farm. The doubly fed induction generator is modelled as two

    active power injections in the load flow programme of EUROSTAG at nodes ST and RT.

    The FACTS controllers are modelled as power injections or current injections in theload flow programme. The SVC is modelled as a shunt reactive current in the load

    flow programme. The TCSC and UPFC is modelled with two power injections between

    buses 23.

    Figure 14 Single line diagram of the power system with wind turbine stator connected to node STand rotor connected to node RT

    BUS 3

    IG

    BUS 1 BUS 2

    G1

    ST

    ROTOR

    BUS 5

    RT

    G2

    BUS 4

    The dynamic simulation results will be presented in the following sequence:

    1 rotor angle deviations of synchronous generators with wind farm without and with

    FACTS controllers

    2 rotor speed deviation of induction generator without FACTS controllers and with

    FACTS controllers

  • 8/3/2019 f871112369241051

    14/23

    Long-term stabilisation of grid connected wind farms with FACTS controllers 269

    3 active power injected by the wind turbine stator and rotor without and with FACTS

    controllers

    4 induction generator termianl (stator and rotor) voltages without and with FACTS

    controllers

    5 controllable outputs of the FACTS controllers following the disturbance and wind

    speed changes.

    3.1 Rotor angle deviations of synchronous generators with wind farm and withFACTS controllers

    Figure 15 shows the rotor angle deviation of the synchronous generator G1 without

    FACTS controllers in the network.

    From Figure 15, it can be observed that after the fault the generator rotor angle of G1

    oscillates around the steady state rotor angle value of 65.8. It can be observed that after

    the load increase at time t = 50 seconds, the rotor angle of synchronous generatoraccelerates to a new equilibrium value. The rotor angle response of the generators

    with SVC is stable with a settling time of ten seconds after the transient fault. The

    controller parameters of the SVC/STATCOM are tuned to stabilise the oscillations. The

    dynamic performance of STATCOM and TCSC are almost comparable and give a stable

    response after the load increase at time t = 50 seconds. The peak overshoot following the

    load shedding is more with STATCOM than SVC.

    Figure 15 Rotor angle deviation of synchronous generator G1 without and with FACTScontrollers

  • 8/3/2019 f871112369241051

    15/23

    270 N.S. Kumar and M.A. Khan

    From Figure 15, it can be observed that there are no sustained oscillations with UPFC in

    the network even after the load increase at bus 5. Also, there are no oscillations following

    load increase at bus 5 in 50 seconds. This is due the fact that the shunt branch UPFCcontributes reactive power to the network after the transient fault and subsequent changes

    in the network conditions. Table 1 shows the comparative analysis of different FACTS

    controllers in the network. The comparison is made on the basis of the settling time

    obtained after the three-phase fault is cleared with FACTS controllers in the network.

    Table 1 Comparison of SVC, STATCOM, TCSC and UPFC for enhancement of dynamicstability in a multimachine power system with DFIG after the transient fault

    S. no.WithoutFACTS

    SVC STATCOM TCSC UPFC

    Settling time 20 sec 10 sec 1 sec 2 sec 1 sec

    All the FACTS controllers are located in the electical midpoint of the transmission

    line, so that intergenerator oscillations occuring between the two areas are damped out

    effectively.

    3.2 Rotor speed deviation of induction generator without FACTS controllersand with FACTS controllers

    Figure 16 Rotor speed deviation of induction generator FACTS

  • 8/3/2019 f871112369241051

    16/23

    Long-term stabilisation of grid connected wind farms with FACTS controllers 271

    Figure 16 demonstrates the rotor speed deviation of the induction generators without

    FACTS controllers in the network. From Figure 16, it can be observed that the rotor

    speed deviation without FACTS controllers in the network following wind speed increaseat time t = 20 seconds is more than 1.12 p.u. It can be observed that the DFIG speed

    remains closer to the steady state operating speed (0.9 p.u.) with UPFC in the network.

    This is due to the reactive power contribution from both the series and shunt branches of

    UPFC. The DFIG speed with SVC is around 1.12 p.u. and with STATCOM it is near

    1.06 p.u. This can be attributed due to the faster trasient response of the STATCOM than

    the SVC.

    3.3 Active power injected by the wind turbine stator and rotor without and withFACTS controllers

    Figure 17 shows the active power injected by the wind farm into the grid following the

    grid disturbance and wind speed increase. The stator protection system associated with

    the induction generator disconnects the stator from the grid if the terminal voltage of theinduction generator is less than 0.75 p.u. for a period of 0.1 seconds, hence, the stator

    active power delivered comes down to zero after the fault. The stator of the induction

    generator is connected back to the grid after a period of 60 seconds by a reconnection

    mechanism. Observe the solid line in Figure 17 which shows the active power injected

    into the grid by DFIG without FACTS.

    Figure 17 Active power injected by stator and rotor of induction generator without FACTS

  • 8/3/2019 f871112369241051

    17/23

    272 N.S. Kumar and M.A. Khan

    The active power injected comes down to zero from its initial value of 5.5 MW specified

    in the load flow, as the DFIG protection system disconnects the stator from the grid at

    two seconds because of the transient fault. The fault is cleared at time t = 2.125 seconds.The induction generator terminal voltage increases and the machine is connected back to

    the grid after a specified time delay at time t = 65 seconds without FACTS controllers in

    the network.

    With the FACTS controllers in the network, the voltage does not reduce below

    0.75 p.u. Hence, the induction generator is not disconnected from the grid. At time

    t = 20 seconds, the wind speed increases to 7 m/s. Hence, the real power injected by the

    induction generator increases from its initial value of 5.5 MW to 18 MW.

    The power calculation according to (2) is based on a single wind speed. However,

    in reality, the wind speed may differ slightly in direction and intensity across the area

    traversed by the blades. To consider this effect, the wind speed is supplied through a lag

    block to the power conversion equation. This creates a slight change in the active power

    delivered to the grid before the disturbance at one second (Figure 17).

    It can be observed that the STATCOM has an improved transient response compared

    to SVC. There are no sustained oscillations in active power delivered to the grid with

    STATCOM (Figure 17). It can also be observed that the wind farm is not disconnected

    from the power grid with shunt connected FACTS controllers in the network.

    After the load increase at time t = 50 seconds, the stabilising loops of all the FACTS

    controllers (Figures 6, 8, 10 and 12) are activated which modulates the line active power

    flow and regulates the bus voltage. The active power injected reduces only by a fraction

    of an MW with UPFC and STATCOM in the network.

    3.4 Induction generator termianl voltages without and with FACTS controllers

    The response of PCC terminal voltage following the transient fault and wind speed

    increase without and with FACTS is shown in Figure 18.

    Figure 18 Voltage at bus 5 (PCC voltage) without and with FACTS (see online versionfor colours)

  • 8/3/2019 f871112369241051

    18/23

    Long-term stabilisation of grid connected wind farms with FACTS controllers 273

    From Figure 18, it is clear that after subsequent fault clearing the voltage at the stator

    terminals of the induction generator lies at around 0.7 p.u. after the fault clearance. This

    leads to disconnection of DFIG stator terminals from the network as the under voltagerelay is set with a voltage threshold of 0.75 p.u. for 0.1 seconds. However, with UPFC

    and STATCOM in the network, the dip in the PCC terminal voltage is only 0.8 p.u. after

    the transient fault. Hence, the induction generators are not disconnected from the grid.

    3.5 Controllable outputs of the FACTS controllers following the disturbanceand wind speed changes

    Figures 19 and 20 show the change in transient ratings of FACTS controllers following

    the disturbance and wind speed changes with SVC and STATCOM controllers.

    It can be observed from Figure 19 that there are transients in the reactive power

    injected after the load shedding at time t = 50 seconds.

    From Figures 19 and 20, it can be observed that the dynamic MVAr rating of

    STATCOM is lesser than SVC for the transient fault and wind speed changes. Thereactive power exchanged with the system swings from (10 MVAr to 50 MVAr) with

    SVC, whereas the swing in reactive power is only (0.08 MVAr to 0.06 MVAr)

    following the disturbance and wind speed changes.

    The corresponding change in reactive power at the TCSC and UPFC terminals is

    shown in Figures 2122.

    Figure 19 Dynamic reactive power support provided by SVC

  • 8/3/2019 f871112369241051

    19/23

    274 N.S. Kumar and M.A. Khan

    Figure 20 Dynamic reactive power support provided by STATCOM

    Figure 21 Change in reactive power at TCSC terminals

  • 8/3/2019 f871112369241051

    20/23

    Long-term stabilisation of grid connected wind farms with FACTS controllers 275

    Figure 22 Change in reactive power at UPFC terminals

    Figure 21 shows the change in TCSC reactive power at its terminals. The dynamic

    reactive power support provided by the TCSC terminals swings from 350 MVAr to

    +350 MVAr after the transient fault and wind speed changes. The corresponding change

    in reactive power rating of UPFC is between (400 MVAr to +500 MVAr) after thedisturbance (Figure 22). There is no appreciable change in reactive power delivered to the

    network following wind speed changes for both TCSC and UPFC (observe the graph

    between 1050 seconds).

    4 Results and discussion

    From the results, we conclude that among shunt connected FACTS controllers, the

    STATCOM provides better damping the oscillations compared to that of the SVC.

    Also, the dynamic reactive compensation (transient rating) required by the STATCOM is

    lesser than SVC. This is due to the fact that a STATCOM is basically voltage sourced

    converter-based shunt controller and SVC is a shunt connected passive thyristor switched

    capacitor/reactor. Among the series connected FACTS controllers, the UPFC damps

    both rotor angle oscillations of synchronous generators and rotor speed oscillations

    of induction generator very effectively when compared with TCSC. This is due to the

    reactive support provided by the shunt branch of the UPFC following the disturbance.

    However, the reactive power rating of UPFC is very high compared to that of the TCSC.

    It is suggested that a STATCOM of suitable rating may be installed at the PCC with or

  • 8/3/2019 f871112369241051

    21/23

    276 N.S. Kumar and M.A. Khan

    without a capacitor may be used for stabilising rotor speed oscillations associated with

    doubly fed variable speed induction generators following transient faults and wind speed

    increase.

    5 Conclusions

    The development of wind turbine and wind farm models is vital because as the level of

    wind penetration increases, it poses dynamic in stability problems in the power system.

    For the present work, we have taken a taken a doubly fed induction generator model and

    illustrated the presence of sustained oscillations with wind farms. This paper has

    described a comprehensive study of the application of both shunt and series connected

    FACTS controllers to a wind farm for enhancement of power system damping. The

    dynamic simulation study is carried out to take care of wind speed changes. All the

    FACTS controllers modelled make use of a steady state loop (primary objective of

    regulating bus voltage or maintaining power flow) and a stabilising loop. The transient

    reactive power ratings of FACTS controllers are arrived after carrying out long-term

    dynamic simulation study.

    Acknowledgements

    I sincerely thank my father Mr. S.K. Natarajan and wife Bhuvana for encouraging me at

    times of pressure during the research work.

    References

    Abdel-Magid, Y.L. and El-Amin, I.M. (1987) Dynamic stability of wind-turbine generators underwidely varying load conditions, Electrical Power and Energy Systems, July, Vol. 9, No. 3,

    pp.180188.Akhmatov, V. (2003) Analysis of dynamic behavior of electric power systems with large amount

    of wind power, PhD thesis, Technical University of Denmark, April.

    Chompoo-Inwai, C., Lee, W-J., Fuangfoo, P., Williams, M. and Liao, J.R. (2005) System impactstudy for the interconnection of wind generation and utility system, IEEE Transactions on

    Industry Applications, Vol. 41, No. 1, pp.163168.

    Coughlan, Y., Smith, P., Mullane, A. and Malley, M.O. (2007) Wind turbine modeling for powersystem stability analysis a system operator perspective, IEEE Transactions on PowerSystems, Vol. 22, No. 3, pp.929936.

    Elmoursi, M.S. and Sharaf, A.M. (2006) Novel STATCOM controllers for voltage stabilization ofstand alone hybrid (wind/small hydro) schemes, International Journal of Emerging Electric

    Power Systems , Vol. 7, No. 3, Art. 5, pp.127.

    EUROSTAG Release 4.3 Package Documentation Parts 1, 2 and 3 (2004).

    Gaztanaga, H., Etxeberria-Ottadui, I. and Ocnasu, D. (2007) Real time analysis of the transient

    response improvement of wind farms by using a reduced scale STATCOM prototype, IEEETransactions on Power Systems, May, Vol. 22, No. 2, pp.658666.

    Jauch, C., Sorensen, P., Norheim, I. and Rasmussen, C. (2007) Simulation of the impact of wind power on the transient fault behavior of the Nordic power system, Electric Power SystemResearch, Vol. 77, pp.135144.

  • 8/3/2019 f871112369241051

    22/23

    Long-term stabilisation of grid connected wind farms with FACTS controllers 277

    Kumar, N.S. and Khan, M.A. (2008) Impact of FACTS controllers on the dynamic stability of power systems connected with wind farms, International Journal of Wind Engineering,

    March, Vol. 32, No. 2, pp.115132.Kundur, P. (1994)Power System Stability and Control, McGraw Hill, New York.

    Mathur, R.M. and Varma, R.K. (2002) Thyristor-based FACTS Controllers for ElectricalTransmission Systems, IEEE Press, Wiley and Sons Publications.

    Mithulananthan, N., Canizares, C.A. and Rogers, G.J. (2003) Comparison of PSS, SVC andSTATCOM controllers for damping power system oscillations,IEEE Transactions on PowerSystems, Vol. 8, No. 2, pp.786792.

    Samuelsson, O. and Lindahl, S. (2005) On speed stability,IEEE Transactions on Power Systems,Vol. 20, No. 2, pp.11791180.

    Varma, R.K. and Sidhu, T.S. (2006) Bibliographic review of FACTS and HVDC applications inwind power systems, International Journal of Emerging Electric Power Systems, Vol. 7,

    No. 3, Art. 7, pp.116.

    Xiu, L. and Wang, Y. (2007) Dynamic modeling and control of DFIG based wind turbines underunbalanced network conditions, IEEE Transactions on Power Systems, February, Vol. 22,

    No. 1, pp.314323.

    Appendix

    A Parameters

    Base values for the per unit system conversion:

    base power: 100 MVA

    base voltage: 0.69 KV for low voltage bus bar, 150 KV for high voltage bus bar.

    B Doubly fed induction generator

    Rated apparent power MVA: 2 MVA

    Rotor inertia: 3.527 MW s/MVA

    Rs (p.u.) = 0.0693

    Xs (p.u.) = 0.080823

    Rr(p.u.) = 0.00906

    Xr(p.u) = 0.09935

    Xm (p.u) = 3.29

    Rotor speed for synchronisation: 0.9 p.u.

    Minimum rotor speed: 0.56 p.u.

    Maximum rotor speed: 1.122 p.u.

  • 8/3/2019 f871112369241051

    23/23

    278 N.S. Kumar and M.A. Khan

    C Transformers

    Three winding transformer (150 KV: 0. 69 KV)

    Primary rated apparent power = 25 MVA

    Secondary rated apparent power = 25 MVA

    Tertiary rated apparent power = 6 MVA.