f06 p3 danfoss christiansen

Upload: claudia-nobrega

Post on 01-Jun-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/9/2019 F06 P3 Danfoss Christiansen

    1/20

  • 8/9/2019 F06 P3 Danfoss Christiansen

    2/20

    Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 2

    Danfoss Electronic Expansion Valve Product Range

    ETS 6

    ETS 12.5, ETS 25

    ETS 50, ETS 100

    ETS 250, ETS 400

  • 8/9/2019 F06 P3 Danfoss Christiansen

    3/20

  • 8/9/2019 F06 P3 Danfoss Christiansen

    4/20

    Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 4

    Section of refrigeration circuit

    EKC 316A, 312EKD/EXD 316

  • 8/9/2019 F06 P3 Danfoss Christiansen

    5/20

    Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 5

    Refrigeration Circuit 

    System Components Overview

    Controller Actuator Sensors

    Examples

    Temp Sensor Pt 1000 Ω

    Type AKS11, AKS21, AKS21W, AKS10 etc

    pressure transmitterAKS 32R, MBS1900 etc

    AST

    EIM 336 MCX

    EKC 316A, 312, EKD 316

  • 8/9/2019 F06 P3 Danfoss Christiansen

    6/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 6

    Features Benefits Installers Wholesalers End users

    Precise control

     

    of liquid injection Energy saving Value selling Value selling Reduced running

    costs

    Optimized for part loads High flexibility Stockoptimization

    Precise regulation –reduced runningcosts

    Bi-flow operation and solenoid tightshut-off 

    Reversiblesystems

    Save time (lesscomponents)

    Stockoptimization

    Wide range for all commonRefrigerants, HFC/ HCFC

    Multi refrigerant Stockoptimization

    Integrated sight glass with moistureindicator

     

    (ETS 50/100/250/400)Refrigerantmonitoring

    System safety Stockoptimization

    Reduced componentcosts

    Bi-metal connections

     

    (ETS 50/100) Waterless

    brazing

    Save time Value selling Fast soldering

    Corrosion resistant design High quality Improved life time

    Low power consumption Improved energyefficiency

    Value selling Value selling Energy saving

    Features & BenefitsBack to General Content

  • 8/9/2019 F06 P3 Danfoss Christiansen

    7/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 7

    Operation – 

    ETS

    Electrical pulses controls the activationof the AST stepper motor.

    The direction of the rotation of thespindle depends on the phaserelationship of the power pulses.

    The rotation of the spindle istransformed into linear motion.

    Stepper motor 

    Sealing

    Spindle

    Ball bearing

    Gearing

    A B

    A

    B

    Flow A->B refers Normal Flow directionFlow B->A refers Reverse/Biflow Flow direction

  • 8/9/2019 F06 P3 Danfoss Christiansen

    8/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 8

    ETS 250 cut-away

    A B

  • 8/9/2019 F06 P3 Danfoss Christiansen

    9/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 9

    Operation - 

    ETS 6

    Electrical pulses change the polaritiesof the coil.

    The coil rotates the magnet rotor ofthe valve in a stepwise fashion.

    The valve has a screw structure andthe needle valve assembled with therotor moves linearly with the rotation.

    ETS 6

    A

    B

  • 8/9/2019 F06 P3 Danfoss Christiansen

    10/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 10

    Flow Characteristics

    •Capacity is based on: R407C, to = 5°C, tc = 32°C, tl = 28°C

    •Valve characteristics are optimized for part load conditions.

  • 8/9/2019 F06 P3 Danfoss Christiansen

    11/20

  • 8/9/2019 F06 P3 Danfoss Christiansen

    12/20

  • 8/9/2019 F06 P3 Danfoss Christiansen

    13/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 13

    13

    Office buildings, Hotels, Breweries, Supermarkets, Dairy Industries, Cold storage Etc.

    Chillers Systems

  • 8/9/2019 F06 P3 Danfoss Christiansen

    14/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 14

    Inverter Mini Split

    Modular Air-cooled Chillers

    VRF, Multi Split IT Cooling

    Bus/trailer Air Conditioning

    Heat Pump Water HeaterETS 6

  • 8/9/2019 F06 P3 Danfoss Christiansen

    15/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 15

    Application ETS 6: Residential A/C & Heat pumps

    US residential A/CDomestic Heat PumpAsia Stylemulti split A/C

    Heat pump unit

    1.

     

    Compressor.2.

     

    Controller.

    3.

     

    Four-way valve.4.

     

    Temperature sensor.5.

     

    Pressure sensor.6.

     

    Cartridge pressure control.7.

     

    Evaporator.8.

     

    Condenser.9.

     

    Temperature sensor.10

     

    .

     

    Expansion device.11

     

    .

     

    Sight glass.

    12

     

    .

     

    Liquid line filter drier.

  • 8/9/2019 F06 P3 Danfoss Christiansen

    16/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 16

    Valve Selection

    For easy andprecise selection ofvalves, use Danfoss’ 

     

    CoolSelectorsoftware

  • 8/9/2019 F06 P3 Danfoss Christiansen

    17/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 17

    Overview of Danfoss SH Controllers for Stepper Motor Valves

    EKD/EXD 316EKC 316A EIM 316/336EKC 312

    For chillers and general purpose Residential

     

    applica-

    tions, mini chillers

    Display Option. EKA 164A MMIMyK setup tool

    Adaptive superheat control (MSS)

    Load-defined

     

    SH control

    Thermostat ctrl

    Maximum Operateting Pressure (MOP)

    Solenoid relay

  • 8/9/2019 F06 P3 Danfoss Christiansen

    18/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 18

     Adaptive 

    Superheat Regulation

    Regulation is here based on the

    evaporator’s load by means of MSSsearch (MSS = lowest permissable

    superheat).

    With MSS search, the superheat

    reference is lowered to the exact point

    where instability sets in.

    The superheat is limited by the settings

    for min. and max. Superheat.

     Adaptive superheat

  • 8/9/2019 F06 P3 Danfoss Christiansen

    19/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 19

    Load-defined superheat regulation

    The reference follows a defined curve.

    This curve is defined by three values:the closing value,

    the min.value

    the max. value.

    These three values must be selected insuch a way that the curve is situated

    between the MSS curve and the curve

    for average temperature difference

     ΔTm (temperature difference between

    media temperature and evaporator

    temperature.

    Setting example = 4, 6 and 10K.

    Load-defined superheat

    In addition to adaptive superheat, EKC 316A features Load-defined superheatcontrol as well.

  • 8/9/2019 F06 P3 Danfoss Christiansen

    20/20

    El t i E i V l d C t llD f A t ti C t l 9 O t b 2012 | 20

    Danfoss can accept no responsibility for possible errors. Danfoss reserves the right to alter its products without notice. This applies to products already on order provided that suchalterations can be made without sub sequential changes being necessary in specifications already agreed. All trademarks in this material are the property of the respective companies.Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. ©Danfoss A/S, Refrigeration and Air Conditioning Division.