Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 2
Danfoss Electronic Expansion Valve Product Range
ETS 6
ETS 12.5, ETS 25
ETS 50, ETS 100
ETS 250, ETS 400
-
8/9/2019 F06 P3 Danfoss Christiansen
3/20
-
8/9/2019 F06 P3 Danfoss Christiansen
4/20
Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 4
Section of refrigeration circuit
EKC 316A, 312EKD/EXD 316
-
8/9/2019 F06 P3 Danfoss Christiansen
5/20
Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 5
Refrigeration Circuit
-
System Components Overview
Controller Actuator Sensors
Examples
Temp Sensor Pt 1000 Ω
Type AKS11, AKS21, AKS21W, AKS10 etc
pressure transmitterAKS 32R, MBS1900 etc
AST
EIM 336 MCX
EKC 316A, 312, EKD 316
-
8/9/2019 F06 P3 Danfoss Christiansen
6/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 6
Features Benefits Installers Wholesalers End users
Precise control
of liquid injection Energy saving Value selling Value selling Reduced running
costs
Optimized for part loads High flexibility Stockoptimization
Precise regulation –reduced runningcosts
Bi-flow operation and solenoid tightshut-off
Reversiblesystems
Save time (lesscomponents)
Stockoptimization
Wide range for all commonRefrigerants, HFC/ HCFC
Multi refrigerant Stockoptimization
Integrated sight glass with moistureindicator
(ETS 50/100/250/400)Refrigerantmonitoring
System safety Stockoptimization
Reduced componentcosts
Bi-metal connections
(ETS 50/100) Waterless
brazing
Save time Value selling Fast soldering
Corrosion resistant design High quality Improved life time
Low power consumption Improved energyefficiency
Value selling Value selling Energy saving
Features & BenefitsBack to General Content
-
8/9/2019 F06 P3 Danfoss Christiansen
7/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 7
Operation –
ETS
Electrical pulses controls the activationof the AST stepper motor.
The direction of the rotation of thespindle depends on the phaserelationship of the power pulses.
The rotation of the spindle istransformed into linear motion.
Stepper motor
Sealing
Spindle
Ball bearing
Gearing
A B
A
B
Flow A->B refers Normal Flow directionFlow B->A refers Reverse/Biflow Flow direction
-
8/9/2019 F06 P3 Danfoss Christiansen
8/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 8
ETS 250 cut-away
A B
-
8/9/2019 F06 P3 Danfoss Christiansen
9/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 9
Operation -
ETS 6
Electrical pulses change the polaritiesof the coil.
The coil rotates the magnet rotor ofthe valve in a stepwise fashion.
The valve has a screw structure andthe needle valve assembled with therotor moves linearly with the rotation.
ETS 6
A
B
-
8/9/2019 F06 P3 Danfoss Christiansen
10/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 10
Flow Characteristics
•Capacity is based on: R407C, to = 5°C, tc = 32°C, tl = 28°C
•Valve characteristics are optimized for part load conditions.
-
8/9/2019 F06 P3 Danfoss Christiansen
11/20
-
8/9/2019 F06 P3 Danfoss Christiansen
12/20
-
8/9/2019 F06 P3 Danfoss Christiansen
13/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 13
13
Office buildings, Hotels, Breweries, Supermarkets, Dairy Industries, Cold storage Etc.
Chillers Systems
-
8/9/2019 F06 P3 Danfoss Christiansen
14/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 14
Inverter Mini Split
Modular Air-cooled Chillers
VRF, Multi Split IT Cooling
Bus/trailer Air Conditioning
Heat Pump Water HeaterETS 6
-
8/9/2019 F06 P3 Danfoss Christiansen
15/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 15
Application ETS 6: Residential A/C & Heat pumps
US residential A/CDomestic Heat PumpAsia Stylemulti split A/C
Heat pump unit
1.
Compressor.2.
Controller.
3.
Four-way valve.4.
Temperature sensor.5.
Pressure sensor.6.
Cartridge pressure control.7.
Evaporator.8.
Condenser.9.
Temperature sensor.10
.
Expansion device.11
.
Sight glass.
12
.
Liquid line filter drier.
-
8/9/2019 F06 P3 Danfoss Christiansen
16/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 16
Valve Selection
For easy andprecise selection ofvalves, use Danfoss’
CoolSelectorsoftware
-
8/9/2019 F06 P3 Danfoss Christiansen
17/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 17
Overview of Danfoss SH Controllers for Stepper Motor Valves
EKD/EXD 316EKC 316A EIM 316/336EKC 312
For chillers and general purpose Residential
applica-
tions, mini chillers
Display Option. EKA 164A MMIMyK setup tool
Adaptive superheat control (MSS)
Load-defined
SH control
Thermostat ctrl
Maximum Operateting Pressure (MOP)
Solenoid relay
-
8/9/2019 F06 P3 Danfoss Christiansen
18/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 18
Adaptive
Superheat Regulation
Regulation is here based on the
evaporator’s load by means of MSSsearch (MSS = lowest permissable
superheat).
With MSS search, the superheat
reference is lowered to the exact point
where instability sets in.
The superheat is limited by the settings
for min. and max. Superheat.
Adaptive superheat
-
8/9/2019 F06 P3 Danfoss Christiansen
19/20Electronic Expansion Valves and ControllersDanfoss Automatic Controls 9 October 2012 | 19
Load-defined superheat regulation
The reference follows a defined curve.
This curve is defined by three values:the closing value,
the min.value
the max. value.
These three values must be selected insuch a way that the curve is situated
between the MSS curve and the curve
for average temperature difference
ΔTm (temperature difference between
media temperature and evaporator
temperature.
Setting example = 4, 6 and 10K.
Load-defined superheat
In addition to adaptive superheat, EKC 316A features Load-defined superheatcontrol as well.
-
8/9/2019 F06 P3 Danfoss Christiansen
20/20
El t i E i V l d C t llD f A t ti C t l 9 O t b 2012 | 20
Danfoss can accept no responsibility for possible errors. Danfoss reserves the right to alter its products without notice. This applies to products already on order provided that suchalterations can be made without sub sequential changes being necessary in specifications already agreed. All trademarks in this material are the property of the respective companies.Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. ©Danfoss A/S, Refrigeration and Air Conditioning Division.