DESCRIPTION

ezPAC SA320/330. April 2011. SATEC 25 years of Innovation in measurement & management of Energy and Power Quality. The Full Range of Electricity Management Solutions for Every Application. PAS. eXpertpower™ Server ( SaaS ). eXpertpower™ Server (Pro Edition). Internet. eXpertpower™. LAN. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: ezPAC SA320/330

April 2011

ezPAC SA320/330

Page 2: ezPAC SA320/330

SATEC25 years of Innovation in measurement & management of Energy and Power Quality

Page 3: ezPAC SA320/330

RS232/422/485, Profibus, TCP/IP, Dialup modem, GPRS, RF

Modbus RTU, ASCII, DNP3.0, Modbus/TCP, DNP3/TCP, IEC 61850

ETC2002

LAN

eXpertpower™ Server (Pro Edition)

COMMERCIAL & INDUSTRIAL

Multi-Tenant Submetering

Power Measurement

Energy Efficiency & Cost Allocation

Energy Management & Billing

Asset ManagementSubstation

Automation

UTILITIES & RENEWABLEALL

Power Quality Analysis

Fault Recording

Revenue Metering

Smart Grid & Demand Response

C192PFBFM136 PM172 PM174/5 EM720 EM920 ezPAC

PAS

PM130 PLUS PM296

eXpertpower™

Internet

eXpertpower™ Server (SaaS)

The Full Range of Electricity Management Solutions for Every Application

Page 4: ezPAC SA320/330

COMMERCIAL INDUSTRIAL UTILITIES

Generation

OEM

Semiconductors

Automotive

Mining

Process Industry

Pharmaceutical

Gas

Transmission

DistributionSports

Residential

Hi-TechTelecom

BanksSupermarkets /Wholesale

Universities

Transportation

Data Centers

Page 5: ezPAC SA320/330

ezPAC SA320/330

6-in-1 solution: Revenue Metering Power Quality Distributed Fault Recorder Sequence of Events (SoE) Backup Protection Equipment Devices Control

Page 6: ezPAC SA320/330

ezPAC Movie

Page 7: ezPAC SA320/330

Substation Automation Relay Target Information

– Get all of the information available from a digital relay without replacing the electromechanical one

Add-On Protective Relaying Backup– Under / over frequency relay– Automatic load shed & restore (0.01 Hz with adjustable time delay)– Reclosing relay– Multi-shot automatic reclosing– Synchro-check and LLDB/LBDL supervision– Permit / block reclose– Phase angle, slip frequency, LLDB/LBDL control– Time over-current relay backup– Back up prime TOC relay curve with up to 32 current magnitude and

duration set-points Various Communication protocols

– Modbus– DNP3.0– IEC 61850

Page 8: ezPAC SA320/330

Sequence of Events (SoE)

Four types of events:– digital input– relay output– Fault– Set-point

Each input point is programmableto be NO or NC

Programmable status words Programmable De-bounce times 1-256 msec Up to 160 discrete inputs – wet or dry contacts

Page 9: ezPAC SA320/330

Fault Recorder 4 measured currents IRIG-B time synchronization Up to 20 minutes of continuous recording

with 256 MB memory Programmable fault thresholds and hysteresis Up to 150 amps fault currents (30 x In) Zero-sequence currents and voltages Current and voltage unbalance Under-voltage, neutral current Ready-to-use fault reports—fault currents magnitude and

duration, coincident volts magnitude, fault waveforms and RMS Distance to fault calculation Multi-feeder (up to 3) fault recorder Waveforms from 2 separate locations (via PAS)

Page 10: ezPAC SA320/330

Power Quality Recorder Class A IEC 61000-4-30 Power Quality analysis:

– Sags/swells (dips/over-voltages), interruptions, frequency variations, Flicker, voltage unbalance, harmonic and inter-harmonic voltages

Programmable thresholds and hysteresis Built-in EN50160 statistics & reports Redundant auxiliary power supply for recording major dips & interruptions Harmonics & inter-harmonics according to IEC 61000-4-7 Directional power harmonics and power factor phasors THD, TDD and K-Factors Symmetrical components Flicker measurement according to IEC 61000-4-15 Selectable sampling rate up to 256 samples/cycle Event recorder for logging internal diagnostic events, control events and

I/O operations Waveform & data recorder

Page 11: ezPAC SA320/330

Transient Recorder Transient pulses as short as 20μs at 50 Hz (17μs at 60 Hz) Up to 1024 samples per cycle Amplitude relative to ground as per EN 50160 (4 channels) Up to 2kV measurement, 6kV withstand

Page 12: ezPAC SA320/330

Display Options

Page 13: ezPAC SA320/330

Case StudySubstation Automation System (SAS) SATEC products (ezPAC, PM175 and PM130) are

the heart of the substation automation system (SAS) solution provided by NPT throughout the entire Russian Federation

Two configurations:– Comprehensive for

220 and 750kV– Standard for 6, 10,

35 and 110 kV

Page 14: ezPAC SA320/330

Key Design Concepts

SATEC IEDs provide protection, automation, measurement and control functions

SCADA-system for operational control Open system concept reduces dependency on

vendors Standard protocols for IED and HMI

communication Wide use of Factory Acceptance Testing (FAT) Integration of substation protection and

automatics into control software

Page 15: ezPAC SA320/330
Page 16: ezPAC SA320/330

SATEC ezPAC SA330 bay controllers are used on lower level to collect digital, analogue information as well as to control switchgear.

Bay controllers RTU SA300-330

Page 17: ezPAC SA320/330

SA330 functions

Page 18: ezPAC SA320/330

PM175

Power Quality Analysis (EN50160, IEEE 1159 and GOST 13109-97)

Time Of Use (TOU) Accuracy Class 0.2S RTC and 10-year calendar Full galvanic isolation Non-volatile memory Registration of parameters on

set-point or time

Page 19: ezPAC SA320/330

ezPAC IEC 61850 Protocols

IEC 61850-7-2,3,4– Basic communication structure for substation and

feeder equipment – Abstract communication service interface (ACSI), Common Data classes, Compatible logical node classes and data classes

IEC 61850-8-1– Specific Communication Service Mapping (SCSM) –

Mappings to MMS (ISO 9506-1 and ISO 9506-2) and to ISO/IEC 8802-3

IEC 61850-10– Conformance testing

Page 20: ezPAC SA320/330

Implementation in NPT Expert SAS

IEC 61850 configurator and system driver allow: IED configuration reading Data receiving via read

requests and via event reports referenced by Report Control Blocks

Files downloading (in particular COMTRADE files)

Data Sets configuration Report Control Blocks and

GOOSE Control Blocks configuration

Page 21: ezPAC SA320/330
Page 22: ezPAC SA320/330

SATECEmpowering the Smart Grid

www.satec-global.com