ez zone · the york international corporation’s ez zone controls system was first introduced in...
TRANSCRIPT
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
Meridian
COOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YO
RK
1
4
2
5
3
6
9
8
07
Enter
Esc
*
Min
us
Menu
Cle
ar
Dec.
Ala
rm
Com
munic
ation
Overr
ide
MANAGER
SYSTEM
Auto-Z
onePlus
09/20/0
003:3
8PMW
ED
OCCUPIED
NOALARM
S
WATTM
ASTERCONTROLS
INC.
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
Meridian
COOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YO
RK
EZ ZoneEZ ZoneEZ ZoneEZ ZoneEZ Zone
TTTTTooooo
AAAAAuto-Zoneuto-Zoneuto-Zoneuto-Zoneuto-Zone
UpgUpgUpgUpgUpgrrrrradeadeadeadeadeGuideGuideGuideGuideGuide
8500 NW River Park Drive • Parkville , MO 64152PH: (816) 505-1100 • FX: (816) 505-1101 • E-mail: [email protected] our website at www.wattmaster.comForm: WM-AEZ-UG-01C Copyright 2000 WattMaster Controls, Inc.Auto-Zone & System Manager are registered trademarks of WattMaster Controls, Inc.EZ Zone is a registered trademark of York International Corp.
WattMaster Controls assumes no responsibility for errors, or omissions.This document is subject to change without notice. All rights reserved.
Table of ContentsIntroduction ........................................................................................................................................ 4EZ Zone Upgrade Overview .............................................................................................................. 5Component Descriptions .................................................................................................................... 6Upgrade Package Selection ................................................................................................................ 7Example #1 - EZ Zone Stand Alone To AZ Basic ..................................................................... 8 & 9Example #2 - EZ Zone Stand Alone To AZ Plus................................................................... 10 & 11Example #3 - Networked EZ Zone To AZ Plus ..................................................................... 12 & 13Optional Controllers And Accessories ................................................................................... 14 & 15EZ Zone Wiring ................................................................................................................................ 16Auto-Zone Basic Wiring .................................................................................................................. 17Auto-Zone Plus Wiring .................................................................................................................... 18Auto-Zone Plus Address Switches ................................................................................................... 19HVAC Staging Connections ............................................................................................................. 20Sensor Connections .......................................................................................................................... 21Bypass Damper Connections ........................................................................................................... 22Honeywell Economizer Actuators ................................................................................................... 23System Manager Installation ........................................................................................................... 24CommLink II Installation ................................................................................................................ 25Modem Linc Central EPROM Replacement ................................................................................ 26Master Interface EPROM Replacement ........................................................................................ 27Zone Controller EPROM Replacement.......................................................................................... 28EPROM Installation Procedures..................................................................................................... 29Ribbon Cable Installation ................................................................................................................ 30Upgrade Parts List Summary .......................................................................................................... 31Additional Information .................................................................................................................... 32
Table of FiguresFigure 1: Existing EZ Zone Master Controller Wiring ................................................................ 16Figure 2: New Auto-Zone Basic Controller Wiring ...................................................................... 17Figure 3: Existing Auto-Zone Plus Controller Wiring .................................................................. 18Figure 4: New Auto-Zone Plus Address Switch Setting ................................................................ 19Figure 5: Existing EZ Zone HVAC Wiring .................................................................................... 20Figure 6: New Auto-Zone HVAC Wiring ....................................................................................... 20Figure 7: Existing EZ Zone Master Controller Sensor Wiring .................................................... 21Figure 8: New AZ Zone Manager Sensor Wiring.......................................................................... 21Figure 9: Existing EZ Zone Bypass Damper Wiring .................................................................... 22Figure 10: New Auto-Zone Bypass Damper Wiring...................................................................... 22Figure 11: Honeywell Economizer Actuators Wiring Information.............................................. 23Figure 12: System Manager Wiring ................................................................................................ 24Figure 13: CommLink II Wiring ..................................................................................................... 25Figure 14: EZ Zone Modem Linc Central EPROM Location ...................................................... 26Figure 15: EZ Zone Master Interface Board EPROM Location ................................................. 27Figure 16: EZ Zone Zone Controller EPROM Location .............................................................. 28Figure 17: EPROM Removal & Installation .................................................................................. 29Figure 18: 3 Connector Ribbon Cable Installation ....................................................................... 30
EZ Zone/Auto-Zone
4 Upgrade
The York International Corporation’s EZ Zone ControlsSystem was first introduced in the early nineties. TheEZ Zone Controls System was designed for York, byWattMaster Controls, as a simple zone control systemfor York’s line of commercial unitary roof top and splitsystem HVAC units. Since its original design and in-troduction, the York EZ Zone Control System haschanged very little.
Introduction
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
Meridian
COOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YO
RK
The Auto-Zone Controls System was created from theoriginal EZ Zone Control System concept by redesign-ing, enhancing and expanding the original systems ca-pabilities under the new Auto-Zone Controls Systemname.
WattMaster’s Auto-Zone Control Systems have contin-ued in the York EZ Zone tradition of keeping the con-trols simple to install and use while enhancing the sys-tem to make it more applicable and in line with the needsof the current marketplace. In addition to offering anexcellent control system for zoning applications, theAuto-Zone Control System has been expanded to al-low control of multiple single zone constant volumeunits and other devices such as lighting, exhaust fans,and unit heaters.
Upgrading your EZ Zone system to the Auto-Zone Con-trols system allows you and your customer to take ad-vantage of the many improvements that have been madein the Auto-Zone Controls system without having toreplace all the EZ Zone system components that areinstalled on your job.
This guide is intended to provide you with simpleinstructions on upgrading an existing EZ Zone systemto an Auto-Zone Control System.
1
4
2
5
3
6
9
8
07
Enter
Esc
*
Min
us
Menu
Cle
ar
Dec.
Ala
rm
Com
munic
ation
Overr
ide
MANAGER
SYSTEM
Auto-Z
onePlus
09/20/0
003:3
8PMW
ED
OCCUPIED
NOALARM
S
WATTM
ASTERCONTROLS
INC.
EZ Zone/Auto-Zone
Upgrade 5
The basic steps required to upgrade your EZZone system to an Auto-Zone system are:
Determine what EZ Zone componentsare currently installed on the system.
Replace the existing EZ-Zone MasterController board with an Auto-ZoneZone Manager controller board
Replace the existing EZ ZoneEPROM’s in each Zone Controllerwith a new Auto-Zone EPROM.
Install return air and outside airtemperature sensors
EZ Zone to Auto-Zone upgrade allows you toretain:
All existing wiring
Master Controller enclosure withkeypad and display
Existing supply air and static pressuresensors
Existing bypass damper
All Zone Dampers
* All Zone Controllers
Room sensors
* Modem Link Central
* All Master Interface Boards
All Fan Terminal Controllers
EZ Zone Upgrade Overview
After upgrading your system from EZ Zone toAuto-Zone, you will be able to take advantageof many new enhancements including:
Damper actuators can be programmedfor direct or reverse operation
Full modulating economizer controlcapability including optional wetbulbeconomizer control
Outside air temperature sensor provideslockout function for both heating andcooling. When converted to Auto-ZonePlus system only one outside air sensoris required for the entire system
Contact closure input for dirty filterstatus
Global and individual zone overridemodes
Zones can be set for voting ornonvoting status
Room sensor slide can be programmed ± 0° F to ± 5° F adjustmentfrom setpoint
Staging delays, minimum off times,and changeover intervals areprogrammable
Sensor offset calibration to correctsensor errors due to poor location
ZoneView enhanced graphical computerfront end software available whenCommLink and a PC are used
System Manager operator interfaceallows all controllers to be accessed fromone central location
* These controllers can be retained but they will re-quire an EPROM chip upgrade to be compatiblewith the Auto-Zone System.
EZ Zone/Auto-Zone
6 Upgrade
Component Descriptions
The general architecture of the EZ Zone and the Auto-Zone Systems are very similar making the upgrade pro-cess relatively easy.
There are some changes in the component descriptionsbetween the EZ Zone system and the Auto-Zone sys-tem. It is important to understand these differencesbefore you begin the upgrade process.
Many of these components look similar, however, insome cases they do not function in an identical fashion.Having the wrong component installed can cause im-proper system operation.
The chart below depicts the difference in descriptionsfor the various comparable system components in theEZ Zone and Auto-Zone Systems.
Master Controller Zone Manager
Fan TerminalController
Master Interface BoardMiniLink
CommunicationsInterface
Modem Linc Central CommLink II
Zone Controller Zone Controller
EZ
Zon
e C
ompo
nent
s
Aut
o-Z
one
Com
pone
ntsRelay Expansion
Board
Must Be Replaced Improved Hardware & Software
Replacement Not Required
EPROM Replacement Required
EPROM Replacement Required
EPROM Replacement Required
Same As Existing Fan Terminal Controller
Improved Software
Improved Software
Improved Software
EZ Zone/Auto-Zone
Upgrade 7
Upgrade Package Selection
There are basically 3 possible EZ Zone to Auto-Zoneupgrade scenarios you may encounter. We have out-lined these below to assist you in deciding which op-tion is best for your application.
Please see the Auto-Zone upgrade selection chart be-low to help determine which example best fits yourneeds.
Upgrade A Simple EZ Zone Stand AloneSystem(s) To The Auto-Zone Basic System• Each Existing Master Controller Has It’s Own Display
And Keypad And Is Treated As A Separate System
• No Communications Cable Between Existing MasterControllers
• No Central Display Or Computer Interface Is Desired
See Example #1On
Pages 8 & 9
See Example #2On
Pages 10 & 11
See Example #3On
Pages 12 & 13
Upgrade A Simple EZ Zone Stand AloneSystem(s) To The Auto-Zone Plus System• Two Or More Existing Master Controllers On The Job.
• No Communications Cable Between Existing MasterControllers
• The Customer Wants To Connect The MasterControllers So That They Are Part Of A NetworkedSystem And/Or Install Constant Volume UnitControllers Or Other Controller Boards On TheirSystem
Upgrade A Networked EZ Zone System ToThe Auto-Zone Plus System• Two Or More Existing Master Controllers That Are
Networked Together With A Modem Linc Central
• The Customer May Want To Add Constant VolumeUnit Controllers Or Other Controller Boards To TheirSystem
EZ Zone/Auto-Zone
8 Upgrade
Example #1:Your project has a single EZ Zone Master Panel andit’s associated Zone Controllers. This is a typical EZZone system. The upgrade will essentially convert thisto an Auto-Zone Basic System. Please see the requiredupgrade components to be ordered in the list below.
To upgrade your existing EZ Zone System to the Auto-Zone Basic System the following procedure will be re-quired.
Warning: All removal and installation proceduresmust be done with the power to the controllersturned off. Failure to do so can cause severe dam-age to the controller boards.
1) All power and input/output wiring will need to bedisconnected from the board. Remove the enclosurecover and disconnect the keypad & display cable byunplugging the cable connector at the board connec-tion.
2) The new Return Air Sensor should be installed inthe return air stream in a location upstream of the pointthat the bypass duct connects to the return duct.
3) Install the new Outdoor Air Sensor in a location onthe exterior of the building that provides shade and pro-
tection from the weather. See the mounting instructionsincluded with the sensor for detailed mounting instruc-tions.
4) Remove the existing EZ Zone Master ControllerBoard from the EZ Zone enclosure. This will requirethe removal of 4 screws securing the board to the en-closure base.
5) Install the new Zone Manager board onto the exist-ing enclosure base. The new board installation requires6 plastic standoffs be inserted between the back of thenew board and the existing standoffs. Secure the boardto 4 of the threaded standoffs (one in each corner of theboard) with the mounting screws provided.
6) Connect the input, output and power wiring per theAuto-Zone Basic wiring diagram (See Figure 2 on page17). Connect the keypad display connector of the exist-ing EZ Zone enclosure cover to the new Auto-Zone ZoneManager board and secure the existing enclosure coverto the enclosure base with the existing screws.
7) Remove and replace each EPROM on all the exist-ing EZ-Zone Zone Controllers. See Figures 16 & 17 onpages 28 & 29 for detailed EPROM Replacement in-formation.
To Upgrade To The AZ Basic System Order the Following:(1) (OE751) EZ Zone to Auto-Zone Basic Upgrade Kit
(Includes: Zone Manager Board w/ Mounting Screws, Plastic Standoff Kit for Zone Manager,Return Air Sensor, Upgrade Label, Installation Instructions.
(1) (OE250) Outside Air Sensor(X) (OE752) EPROM (Replaces EZ Zone, Zone Controller EPROM) (One Required Per Controller)
Note: When ordering be sure to specify Fahrenheit or Celsius operation for your system
For optional components list and information see pages 14 & 15 of this manual.
EZ Zone/Auto-Zone
Upgrade 9
EZ Zone Stand Alone to AZ Basic
Zone Air DampersUp to 16 Zone Air Dampers Allowed
SupplyAir TempSensor
To HVAC UnitControl Panel
MasterController
Bypass AirDamper
StaticPressureSensor
#1 #16
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
EZ-ZONECOOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YORK
®
Zone Air DampersUp to 16 Zone Air Dampers Allowed
SupplyAir TempSensor
To HVAC UnitControl Panel
Zone Manager
Bypass AirDamper
StaticPressureSensor
#1 #16
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
EZ-ZONECOOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YORK
®
ReturnAir TempSensor
OutsideAir TempSensor
8
9
7
4
5
6
3
2
1
#
0*
Remote Link(Optional)
CommLink IISingle Loop
(Optional)
W
C
LI
ATTMASTER
ONTRO
S,NC
CO
MM
LINK
II
CO
MM
LINK
II
L
C
M
M
O
O
O
O
M
D
P
PE
Computer(Optional - By Others)
SychronousData
Link
C
O
N
T
R
O
L
S
SIG
DE
T
RD
Y
SN
D
RE
C
PW
R
Telephone Line(Required ForRemote Link)
Upgraded System
Existing System
EZ Zone/Auto-Zone
10 Upgrade
Example #2:Your project has multiple EZ Zone Master Panels andtheir associated Zone Controllers. This upgrade willconvert this to an Auto-Zone Plus System.
To upgrade your existing EZ Zone System to the Auto-Zone Plus System the following procedures will berequired.
Warning: All removal and installation proceduresmust be done with the power to the controllersturned off. Failure to do so can cause severe dam-age to the controller boards.
1) All power and input/output wiring will need to bedisconnected from the existing Master Controller board.Disconnect the keypad & display cable from the boardby unplugging its connector from the board and the dis-play on the existing enclosure cover.
2) The new Return Air Sensor should be installed inthe return air stream in a location upstream of the pointthat the bypass duct connects to the return duct.
3) Install the new Outdoor Air Sensor in a location onthe exterior of the building that provides shade andprotection from the weather. Only one OA sensor isrequired for the entire system. See the mounting instruc-tions included with the sensor for detailed mountinginstructions.
4) Connect the CommLink to the network communica-
tions loop and wire in 24VAC power (See Figure 13 onpage 25).
5) Remove the existing EZ Zone Master ControllerBoard from the EZ Zone enclosure. This will requirethe removal of 4 screws securing the board to the en-closure base.
6) Install the new Zone Manager board onto the exist-ing enclosure base. The MiniLink should then bemounted to the Zone Manager board using the stand-offs and screws included with the MiniLink. The newZone Manager board installation requires 6 plasticstandoffs be inserted between the back of the new boardand the existing standoffs. Secure the board to 4 of thethreaded standoffs (one in each corner of the board)with the screws that were included with the new ZoneManager board.
7) Connect the input, output and power wiring per theAuto-Zone Plus wiring diagram (See Figure 3 on page18). Connect the new 3 Connector Ribbon Cable key-pad display connector to the existing EZ Zone enclo-sure cover and to the new Auto-Zone Zone Managerboard (See Figure 18 on page 30). Secure the existingenclosure cover to the enclosure base with the existingscrews.
8) Remove and replace each EPROM on all the exist-ing EZ-Zone Zone Controllers. See Figures 16 & 17 onpages 28 & 29 for detailed EPROM Replacement in-formation.
To Upgrade To The Auto-Zone Plus System Order the Following:(X) (OE753) EZ Zone to Auto-Zone Plus Upgrade Kit (One Required Per Existing Master Controller)
(Includes: Zone Manager Board w/ Mounting Screws, Plastic Standoff Kit for Zone Manager,MiniLink w/ Mounting Hardware, Return Air Sensor, 3 Way Display/Keypad Connector cable,Upgrade Label, Installation Instructions).
(1) (OE361-04-CLMA) CommLink II Kit (Includes: Cables, Power Supply, Installation Instructions)(1) (OE250) Outside Air Sensor (Only One Required For Entire System)(X) (OE752) EPROM (Replaces EZ Zone, Zone Controller EPROM) (One Required Per Controller)(1) (OE392-01-AZSYSM) System Manager (Not Required if Using Optional Computer)
Note: When ordering be sure to specify Fahrenheit or Celsius operation for your system
For optional components list and information see pages 14 & 15 of this manual.
EZ Zone/Auto-Zone
Upgrade 11
EZ Zone Stand Alone to AZ Plus
Zone Air Dampers
Zone Air Dampers
Up to 16 Zone Air Dampers Allowed
Up to 16 Zone Air Dampers Allowed
SupplyAir TempSensor
SupplyAir TempSensor
To HVAC UnitControl Panel
To HVAC UnitControl Panel
MasterController
MasterController
Bypass AirDamper
Bypass AirDamper
StaticPressureSensor
StaticPressureSensor
#1
#1
#16
#16
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
EZ-ZONECOOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YORK
®
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
EZ-ZONECOOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YORK
®
Zone Air Dampers
Zone Air Dampers
Up to 16 Zone Air Dampers Allowed
Up to 16 Zone Air Dampers Allowed
SupplyAir TempSensor
SupplyAir TempSensor
To Other Zone Managers(Up to 30 Allowed On System)
To HVAC UnitControl Panel
Network Loop
Network Loop
Local Loop
Zone Manager
Zone Manager
To HVAC UnitControl Panel
Bypass AirDamper
Bypass AirDamper
StaticPressureSensor
StaticPressureSensor
#1
#1
#16
#16
ReturnAir TempSensor
OutsideAir TempSensor
ReturnAir TempSensor
Only One OASensor IsRequiredFor EntireSystem
8
9
7
4
5
6
3
2
1
#
0*
Remote Link(Optional)
CommLink IIMultiple Loop
W
C
LI
ATTMASTER
ONTRO
S,NC
CO
MM
LINKII
CO
MM
LINK
II
L
C
M
M
O
O
O
O
M
D
P
PE
Computer(Optional - By Others)
SychronousData
Link
C
O
N
T
R
O
L
S
SIG
DE
T
RD
Y
SN
D
RE
C
PW
R
Telephone Line(Required For Remote Link)
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
Meridian
COOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YO
RK
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
Meridian
COOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YO
RK
1
4
2
5
3
6
9
8
07
Enter
Esc
*
Min
us
Menu
Cle
ar
Dec.
Ala
rm
Com
munic
ation
Overr
ide
MANAGER
MANAGER
SYSTEM
Auto-Z
onePlus
01/01/9
703:3
8PMW
ED
OCCUPIED
NOALARM
S
SystemManager
(Optional If Computer Front End Used)
Other Controllers(Optional - Up to 13 On Each Loop))
Upgraded System
Existing System
EZ Zone/Auto-Zone
12 Upgrade
Example #3:Your project has a Networked EZ Zone System that youwant to convert to the Auto-Zone Plus system. Pleasesee the required upgrade components list below for thenecessary parts to be ordered.
To upgrade your existing Networked EZ Zone Systemto the Auto-Zone Plus System the following procedureswill be required.
Warning: All removal and installation proceduresmust be done with the power to the controllersturned off. Failure to do so can cause severe dam-age to the controller boards.
1) All power and input/output wiring will need to bedisconnected from the existing Master Controller board.Disconnect the keypad & display cable from the boardby unplugging its connector from the board.
2) The new Return Air Sensor should be installed inthe return air stream in a location upstream of the pointthat the bypass duct connects to the return duct.
3) Install the new Outdoor Air Sensor in a location onthe exterior of the building that provides shade andprotection from the weather. Only one OA sensor isrequired for the entire system. See the mounting instruc-tions included with the sensor for detailed mountinginstructions.
4) Take the cover off of the Modem Link Central, re-move the old EPROM and replace with the newCommLink EPROM. See Figures 14 & 17 on pages 25
& 27 for detailed EPROM installation instructions.
5) Remove the existing EZ Zone Master ControllerBoard from the EZ Zone enclosure. This will requirethe removal of 4 screws securing the board to the en-closure base. Remove the existing Master InterfaceBoard from the old Master Controller board. Removethe old EPROM from the Master Interface board andinstall the new MiniLink upgrade EPROM to the Mas-ter Interface board. See Figures 15 & 17 on pages 26 &27 for detailed EPROM installation instructions.
6) Install the upgraded Master Interface board to thenew Zone Manager board using the existing mountinghardware. Install the new Zone Manager board onto theexisting enclosure base. The new Zone Manager boardinstallation requires 6 plastic standoffs be inserted be-tween the back of the new board and the existing stand-offs. Secure the board to 4 of the threaded standoffs(one in each corner of the board) with the screws thatwere included with the new Zone Manager board.
7) Connect the input, output and power wiring per theAuto-Zone Plus wiring diagram (See Figure 3 on page18). Connect the existing 3 Connector Ribbon Cablekeypad display connector to the existing EZ Zone en-closure cover and to the new Auto-Zone Zone Managerboard (See Figure 18 on page 30). Secure the existingenclosure cover to the enclosure base with the existingscrews.
8) Remove and replace each EPROM on all the exist-ing EZ-Zone Zone Controllers. See Figures 16 & 17 onpages 28 & 29 for detailed EPROM Replacement in-formation.
To Upgrade To The Auto-Zone Plus System Order the Following:(X) (OE751) EZ Zone to AZ Basic Upgrade Kit (One Required Per Existing Master Controller)
(Includes: Zone Manager Board w/ Mounting Screws, Plastic Standoff Kit for Zone Manager,Return Air Sensor, Upgrade Label, Installation Instructions)
(1) (OE755) Modem Link Central to CommLink II Upgrade Kit(Includes: ComLink EPROM Upgrade Chip, Upgrade Label)
(1) (OE754) Master Interface Board to MiniLink Upgrade Kit(Includes: MiniLink EPROM Upgrade Chip, Upgrade Label)
(1) OE250 Outside Air Sensor (Only One Required Per System)(X) (OE752) EPROM (Replaces EZ Zone, Zone Controller EPROM) (One Required Per Controller)(1) (OE392-01-AZSYSM) System Manager (Not Required if Using Optional Computer)
Note: When ordering be sure to specify Fahrenheit or Celsius operation for your system
For optional components list and information see pages 14 & 15 of this manual.
EZ Zone/Auto-Zone
Upgrade 13
Networked EZ Zone To AZ Plus
Zone Air Dampers
Zone Air Dampers
Up to 16 Zone Air Dampers Allowed
Up to 16 Zone Air Dampers Allowed
SupplyAir TempSensor
SupplyAir TempSensor
To Other Master Controllers(Up to 30 Allowed On System)
To HVAC UnitControl Panel
Network Loop
Network Loop
Local Loop
To HVAC UnitControl Panel
Bypass AirDamper
Bypass AirDamper
StaticPressureSensor
StaticPressureSensor
#1
#1
#16
#16
8
9
7
4
5
6
3
2
1
#
0*
Modem(Optional)
Modem Link Central
24VAC
24VAC
W
C
LI
ATTMASTER
ONTRO
S,NC
CO
MM
LINK
II
CO
MM
LINK
II
L
C
M
M
O
O
O
O
M
D
P
PE
Computer(Optional)
Telephone Line
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
Meridian
COOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YO
RK
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
Meridian
COOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YO
RK
MasterController
MasterController
Zone Air Dampers
Zone Air Dampers
Up to 16 Zone Air Dampers Allowed
Up to 16 Zone Air Dampers Allowed
SupplyAir TempSensor
SupplyAir TempSensor
To OtherZone Managers(Up to 30 Allowed On System)
To HVAC UnitControl Panel
Network Loop
Network Loop
Local Loop
To HVAC UnitControl Panel
Bypass AirDamper
Bypass AirDamper
StaticPressureSensor
StaticPressureSensor
#1
#1
#16
#16
8
9
7
4
5
6
3
2
1
#
0*
Modem(Optional)
UpgradedModem Link Central
24VAC
24VAC
W
C
LI
ATTMASTER
ONTRO
S,NC
CO
MM
LINK
II
CO
MM
LINK
II
L
C
M
M
O
O
O
O
M
D
P
PE
Computer(Optional)
Telephone Line
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
Meridian
COOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YO
RK
FAN
COO
L1
COO
L2
HEAT1
HEAT2
BYPASSO
PEN
BYPASSCLO
SE
COM
MUNIC
ATION
ALARM
A=
ALLZO
NES
B=
EACHZO
NE
C=
HVACUNIT
/CLEAR
D=
ALARMS
#=
STEP/ENTER
* =DECIM
AL
+
+
+
+
Meridian
COOL
MODE
04-08-96
03:48PMFRI
OCCUPIED
NOALARMS
2
8
5
0
A
C
B
D
1
7
4
*
3
9
6
#
YO
RK
ZoneManager
ZoneManager
ReturnAir TempSensor
OutsideAir TempSensor
ReturnAir TempSensor
Only One OASensor IsRequiredFor EntireSystem
1
4
2
5
3
6
9
8
07
Enter
Esc
*
Min
us
Menu
Cle
ar
Dec.
Ala
rm
Com
munic
ation
Overr
ide
MANAGER
SYSTEM
Auto-Z
onePlus
01/01/9
703:3
8PMW
ED
OCCUPIED
NOALARM
S
SystemManager
(Optional If Computer Front End Used)
Other Controllers(Optional - Up to 13 On Each Loop))
Upgraded System
Existing System
EZ Zone/Auto-Zone
14 Upgrade
Optional Controllers and Accessories
In addition to the standard Zone Manager and ZoneControllers, WattMaster offers many other controllersand accessories to enhance your new Auto-Zone Sys-tem. Optional Controllers that are available for use withthe Auto-Zone Plus system include the CV, CV-C, GPC,Optimal Start Scheduler, Lighting Panel Controller andWetbulb Module. These controllers are not availablefor use with the Auto-Zone Basic System. To utilizeany of the optional controllers you must upgrade yoursystem to the Auto-Zone Plus configuration. Accesso-
ries that are available for use with either the Auto-ZonePlus or Basic System include the CommLink II Com-munications Interface, Remote Link, Room Sensors,Round Zone Dampers and Rectangular Zone Dampers.WattMaster also offers Communication Cable that iscolor coded and labeled for the network communica-tions loop and local communications loop.
Following are brief descriptions of the optional con-trollers and accessories that are available.
CV Controller
The CV Controller provides control of single zone con-stant volume rooftop or split system HVAC equipment.CV controllers have four configurable relay outputs forheating/cooling staging, a 0-10VDC output for econo-mizer control, on board time clock for scheduling/nightsetback functions and built in alarming features.The CV Controller can be used with the Auto Zone
Plus System only. The CV can be programmed andmonitored from the either the System Manager or froma personal computer which has the ZoneView Com-puter front end software installed. Up to 13 CV con-trollers can be installed on each local communicationsloop of your Auto-Zone Plus system.
CV-C Controller
The CV-C Controller is a field configurable constantvolume unit controller that provides additional featureswhich are not available with the standard CV control-ler. CV-C controllers can be configured for applicationsrequiring CO2/IAQ economizer control, modulating HWand CW control valves and dehumidification. The CV-C relay outputs can be expanded via a plug-in expan-sion board for use in applications requiring additionalheating/cooling staging control.
The CV-C Controller can be used with the Auto-ZonePlus System only. The System Manager cannot be usedto program or monitor the CV-C controller. CV-C con-trollers require that a personal computer which has theZoneView computer front end software installed be usedfor all programming and monitoring. Up to 13 CV-Ccontrollers can be installed on each local communica-tions loop of your Auto-Zone Plus system.
GPC ControllerThe GPC (General Purpose Controller) is a very versa-tile controller that can be used for a variety of controlapplications that are outside the function of our stan-dard HVAC unit controllers. Each GPC controller has(5) Universal Inputs that can accept contact closures,thermistor temperature sensors, or 4-20mA/2-10VDCsignals. The controller has (5) digital outputs for on/offcontrol and (1) 0-10VDC analog output to modulate avalve or damper. These inputs and outputs can be con-figured in a variety of ways using And/Or logic func-tions, time schedules, setpoints, etc. to perform manydifferent tasks.
The GPC can be used for many applications including,but not limited to:
• Control of Unit Heaters• Control of Boilers• Control of Exhaust Fans• Monitoring of Temperature• Monitoring of Humidity• Monitoring of Status Contacts
The GPC Controller can be used with the Auto-ZonePlus System only. The System Manager cannot be usedto program or monitor the GPC controller. GPC con-trollers require that a personal computer which has theZoneView computer front end software installed be usedfor all programming and monitoring.
EZ Zone/Auto-Zone
Upgrade 15
Lighting Panel ControllerAdds building lighting control capability to the Auto-Zone System. The Lighting Panel Controller providesup to (7) Independent time schedules and light levelsfor control of up to (7) lighting circuits. The LightingPanel Controller relay outputs can be set for on/off re-lay or pulsed relay control depending on the lightingsystem control contactor requirements. Pushbutton over-ride is available for each lighting circuit by connectinga momentary pushbutton to the Lighting Panel Con-troller board.
The Lighting Panel Controller can be used with the AutoZone Plus System only. The System Manager cannotbe used to program or monitor the Lighting Panel Con-troller. Light Panel Controllers require that a personalcomputer which has the ZoneView computer front endsoftware installed be used for all programming andmonitoring.
Optimal Start SchedulerProvides expanded scheduling capabilities beyond thoseincorporated with the standard Auto-Zone controllers.The Optimal Start Scheduler provides for optimalStart/Stop and up to (7) independent schedules with 2Start/Stop events per day and (14) Start/Stop holidayevents per schedule.
The Optimal Start Scheduler can be used with the AutoZone Plus System only. The System Manager cannotbe used to program or monitor the Optimal Start Sched-uler Controller. This controller requires that a personalcomputer which has the ZoneView computer front endsoftware installed be used for all programming andmonitoring.
Wetbulb Module
Provides wetbulb temperature monitoring for controlof all economizer equipped units on the Auto-Zonesystem. The Wetbulb Module includes an Outside AirHumidity Sensor for measuring outside air relativehumidity and utilizes the installed Outdoor Air Sensoron the Auto-Zone System to calculate the wetbulbtemperature. This temperature is used by the economizercontrol portion of the unit controller to provide accurate
economizer operation. The Wetbulb Module can be usedwith the Auto-Zone Basic and Plus Zone Systems. TheWetbulb Module can be monitored and programmedfrom either the System Manager or from a personalcomputer which has the ZoneView computer front endsoftware installed.
AccessoriesWattMaster offers a complete line of accessories foryour Auto-Zone system. For part ordering informationand a complete list of accessories please see the Auto-Zone Product List Pricing manual and the Auto-Zone
Replacement Parts List Pricing Catalogs. Following isa brief list of some of the accessories that are offeredfor the Auto-Zone system.
• Remote Link - 14,400 baud modem forremote access to any Auto-Zone system
• CommLink II - Required to connect theAuto Zone Basic system to a personalcomputer
• Round Air Dampers - Air damper with aZone Controller and actuator mounted in acontrol enclosure. Available in pressuredependent and pressure independent models.Available in round duct sizes of 6”, 8”, 10”,12”, 14” and 16” diameter.
• Rectangular Air Dampers - Rectangular,aluminum frame opposed blade dampers.Available in rectangular duct sizes from 8” x8” to 24” x 36” in 2” increments of height andwidth
• Rectangular Air Damper Kit - ZoneController and actuator mounted in a controlenclosure for use with Rectangular AirDampers
• ZoneView Computer Front End SoftwareFree when ordered with an EZ Zone to Auto-Zone upgrade
EZ Zone/Auto-Zone
16 Upgrade
EZ Zone Wiring
The wiring diagram below depicts a typical existingEZ Zone Master Controller wiring. This diagram isshown for reference only. It’s intent is to show the dif-ference between the EZ Zone system wiring and the
Auto-Zone system wiring. All wiring should be con-nected per the specific Auto-Zone system wiring dia-grams on the following pages.
StaticPick-up
StaticPressureSensor
Supply AirTemp Sensor
Splice AsRequired
LO HI
HV
AC
Un
it
24VAC Only
R
G
Y1
Y2
W1
W2
LineVoltage
GND
24VAC
Actuator WiringInterface
Feedback (BK)
Close (GR)
Open (YL)
Gnd (WH)
Bypass Air DamperActuator
Re
d
Blk
Grn
RS-485Communication cableto Zone Controllers
Master Controller Board
75
90
60
45
Figure 1: Existing EZ Zone Master Controller Wiring
EZ Zone/Auto-Zone
Upgrade 17
Auto-Zone Basic Wiring
Zone Manager
Feedback (BK)
Close (GR)
Open (YL)
Gnd (WH)
Notes:
1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.
3.)All Communication Wiring To Be 18Ga. Minimum, 2 Conductor TwistedPair With Shield. Belden #82760 OrEquivalent.
4.)For Individual Component Wiring SeeSpecific Component Wiring Diagram.
5.)It Is Recommended That AllControllers Address Switches AreSet Before Installation.
2.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
RS-485Communications To Zone
Controllers
Return Air Temp.Sensor
Supply Air Temp.Sensor
LineVoltage
HV
AC
Un
it
24VAC Only
Re
d
Blk
To Relief / Exhaust Fans
Grn
StaticPick-up
StaticPressureSensor
Splice AsRequired
LO HI
GND
24VAC
Belimo Actuator Wiring Shown.Consult Factory For Other
Models Of Economizer Actuators.Some Actuators Require IsolationTransformers In Order To PreventDamage To The Controller Board.
WARNING!
Use Extreme Care When WiringEconomizer Actuators
Never Connect Or DisconnectWiring With Power Applied!
Never Apply Power If TheGnd ( 1 Com ) Terminal On The
Actuator Is Not Connected.
See Note 1 &2
Outdoor Air Temp.Sensor
Aux3Forced
OccupiedMode
Aux1Economizer
Disable
Aux2FilterAlarm
Auxiliary Inputs( Dry Contacts )
R
G
Y1
Y2
W1
W2
Economizer Actuator
133 IN-LB
AF24-SR
1 COM
2 +
3 Y1
4 Y2
5 UBELIMO
Actuator WiringInterface
Bypass Air DamperActuator
C987
CABLE
R6
R5
HEAT 2 SW
1
W2
W1
Y2
HEAT2
HEAT1
COOL2
COOL1
FAN
HEAT 1
COOL 2
COOL 1
C 1992
1
1632
BNET
248
AD
D
COMM DRIVER
RS-485
75176
MADE IN U.S.A.
D1
7
D1
8
D1
9
D2
0
D2
1
D2
2
D2
3
D2
4
0* # D
R
SH
T
COMM
C1C2
+
P1
RIBBON
GN
D
06/11/95 03:48PM FRIAuto-Zone COOL MODE
G
Y1V6
V5
CLOSE
V4
V3
OPEN
GND
FDBK
FAN
CLOSE
OPEN
+
REC
+
GND
NE5090
4 5 6
KEYPAD
1 2 3
B
A
NO ALARM(S)OCCUPIED
LCD DISPLAY
&
++
24VAC
TB2
POWER
+
++
ADJUST
5.11V
PJ1
++PRESSU
RE
SEN
SO
RJA
CK
+5
V
SIG
BUSS
EXP
TB2
A2
G
OUTPUTS
ANALOG
A1
N.O.
CONTACTS
EXHAUST
AUX3
GND
GND
AUX2
AUX1
ANALOG
SAT
OAT
RAT
INPUTS
+12V
TB1
2
BYPASS
BYPASS
Local Loop
Address Switch Must Always Be SetTo Address 0 on Zone Manager Board
As Shown
Zone ManagerAddress Switch
These Switches Must BeIn The OFF PositionAs Shown
ADD
12
481632B
NET
AD
D
32
BNE
T
16 8 4 12
OF
F>
OF
F>
RockerDown
RockerDown
75
90
60
45
Figure 2: New Auto-Zone Basic Controller Wiring
Figure 2 below depicts the wiring schematic that shouldbe used for the Auto-Zone Basic System upgrade asdescribed in Example 1 on pages 8 and 9 of this manual.
Be sure to pay strict attention to all warnings and cau-tions listed on the schematic.
Warning:See Figure 11 in this manual forimportant wiring instructionsregarding HoneywellEconomizer Actuators
EZ Zone/Auto-Zone
18 Upgrade
Zone Manager
Notes:
1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.
3.)All Communication Wiring To Be 18Ga. Minimum, 2 Conductor TwistedPair With Shield. Belden #82760 OrEquivalent.
5.)For Individual Component Wiring SeeSpecific Component Wiring Diagram.
2.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.
RS-485Communications To ZoneControllers, CV ControllersAnd/Or System Manager
Return Air Temp.Sensor
Supply Air Temp.Sensor
LineVoltage
HV
AC
Unit
24VAC Only
Red
Blk
To Relief / Exhaust Fans
Grn
StaticPick-up
StaticPressureSensor
Splice AsRequired
LO HI
GND
24VAC
Belimo Actuator Wiring ShownConsult Factory For Other
Models Of Economizer ActuatorsSome Actuators Require IsolationTransformers In Order To PreventDamage To The Controller Board.
WARNING!
Use Extreme Care When WiringEconomizer Actuators
Never Connect Or DisconnectWiring With Power Applied!
Never Apply Power If TheGnd ( 1 Com ) Terminal On The
Actuator Is Not Connected.
See Note 1 &2
+
+
++
+
++
+ +
HEAT2
HEAT1
COOL2
COOL1
FAN
R
2
8C
SW
1
16AB 24
AD
D
LOCALLOOP
Local Loop
T
SH
RTB3
COMM
T
SH
R
32
16
8
4
1
2
MINILINK
R9
R10
R8
I CEXP
PORT
PWR
V4
V3
CLOSE
OPEN
FDBK
REC
GND
GND
24VAC
AUX1
OPEN
K1
NETWORKLOOP
Network Loop RS-48519200 Baud
To Other ZoneManagers and/or
CommLink onSystem
SH
R
T
CLOSEK
2
NE5090
ANALOGOUTPUTS
A2
G
TB2
A1
N.O.
EXHAUSTCONTACTS
GND
GND
AUX3
AUX2
7824
D2
5
U1
4
VR
3
R4
0
ADJUST5.11V
C2
7
7812 C2
6V
R2
D1
D3
D4
D2
PJ1
PR
ES
SU
RE
SE
NS
OR
JA
CK
+5V
R7
OAT
RAT
+12V
SAT
ANALOGINPUTS
GN
D
SIG
T
R
SHIELD
T
R
SHIELD
Outdoor Air Temp.Sensor
(See Note 4)
Aux3Forced
OccupiedMode
Aux1Economizer
Disable
Aux2FilterAlarm
Auxiliary Inputs( Dry Contacts )
R
G
Y1
Y2
W1
W2
Economizer Actuator
133 IN-LB
AF24-SR
1 COM
2 +
3 Y1
4 Y2
5 UBELIMO
Actuator WiringInterface
Bypass Air DamperActuator
4.)Only One Outside Air Sensor IsRequired Per System. It May BeConnected To Any CV Controller OrZone Manager On The System. If AWetbulb Module Controller Is Used TheOA Sensor Must Be Connected To TheWetbulb Module.
75
90
60
45
Auto-Zone Plus Wiring
Figure 3: Existing Auto-Zone Plus Controller Wiring
Figure 3 below depicts the wiring schematic that shouldbe used for the Auto-Zone Plus System upgrade as de-scribed in Example 2 on pages 10 and 11 of this manual.This schematic is also used for wiring of Example 3 on
pages 12 & 13 of this manual. Be sure to pay strict at-tention to all warnings and cautions listed on the sche-matic.
Warning:See Figure 11 in this manual forimportant wiring instructionsregarding Honeywell economizeractuators
EZ Zone/Auto-Zone
Upgrade 19
1632
8421
Caution!The MiniLinks Must Have Address Switches Set Between 1And 30 (Up To 30 MiniLinks (Mounted on Zone Managers)Are Allowed Per Auto-Zone Plus System). The MiniLinksShould Be Addressed In Consecutive Order Starting WithAddress #1. Address #1 Must Be Present On The Loop ForThe System To Function.
Address Switch Shown IsSet For Address 1
Address Switch Must Always Be SetTo Address 17 on Zone Manager Board
As Shown
Address Switch Shown IsSet For Address 4
Zone ManagerAddress Switch
MiniLinkAddress Switch
These Switches Must BeIn The OFF PositionAs Shown
These Switches Must BeIn The OFF PositionAs Shown
Caution:The Power To The Zone Manager Must BeRemoved And Reconnected After Changing TheMiniLink Or Zone Manager Address Switch SettingsIn Order For Any Changes To Take Effect.
Caution:Disconnect All Communication Loop Wiring FromThe Zone Manger Before Removing Power.Reconnect Power And Then ReconnectCommunication Loop Wiring To Zone Manager.
ADD
ADD
ADD
12
481632B
NET
ADD
All Zone Managers On System Must BeAddressed As 17
Network Switch As ShownMust Be ON
The Address For Each MiniLinkMust Be Unique To The Other MiniLinksOn The Network Loop. Loop #1 MiniLink
Should Be Addressed As #1Loop #2 MiniLink Should Be Addressed
As #2 Etc..
ADD
AD
D
AD
D
32
32
32
B
B
NE
T
NE
T
16
16
16
8
88
4
4
4
1
1
1
2
2
2
OFF >
OF
F>
OF
F>
Rocker
Dow
n
RockerDown
RockerDown
HEAT2
HEAT1
COOL2
COOL1
FAN
R
LOCALLOOPT
SH
RTB3
COMM
T
SH
R
MINILINKV4
V3
CLOSE
OPEN
FDBK
GND
OPEN
K1
NETWORKLOOP
SH
R
T
CLOSE
K2
ANALOGOUTPUTS
A2
G
TB2
A1
Zone Manager Board(Under MiniLink Board)
MiniLink Address Switch Setting
Zone Manager Address Switch Setting
MiniLink Board(Mounted On Top Of Zone Manager Board)
Auto-Zone Plus Address Switches
Figure 4: New Auto-Zone Plus Address Switch Setting
The Auto-Zone Plus Zone Manager has two differentaddress switches. One is located on the main ZoneManager board and one is located on the MiniLink boardthat is located on the top of the Zone Manager board.The Zone Manager board address should always be setto address 17 on an Auto-Zone Plus system. The
MiniLink board should be addressed with a unique num-ber for each Zone Manager on the system. It is recom-mended that you start with address 1 and address eachZone Manager consecutively. See Figure 4 below fordetailed information.
EZ Zone/Auto-Zone
20 Upgrade
HVAC Staging Connections
Figure 6: New Auto-Zone HVAC Wiring
Figure5 below shows the EZ Zone Master Controllerwiring. Figure 6 below depicts the wiring schematicthat should be used for wiring of all Auto-Zone ZoneManagers boards. As can be seen below, the Auto-Zone
OUT1
OUT2
OUT3
OUT4
OUT5
FAN
COOL1
COOL2
HEAT1
HEAT2
24 VAC - R
Fan - G
Cool - Y1
Cool - Y2
Heat - W1
Heat - W2
HEAT2
HEAT1
COOL2
COOL1
FAN
R
Fan - GCool - Y1Cool - Y2Heat - W1Heat - W2
24 VAC -R
Figure 5: Existing EZ Zone HVAC Wiring
The EZ Zone Master Con-troller relay outputs consistof a series of five double poleterminal blocks. Wire jump-ers between terminal blocksare required to the commonof each relay.
The Auto-Zone Zone Man-ager wiring has been simpli-fied. There is only one termi-nal block with connectionsclearly marked for ease of in-stallation. Jumpers are nolonger required since thecommons are tied togetherwithin the circuit board.
Zone Manager wiring is much simpler than the EZ ZoneMaster Controller wiring. Be sure to pay strict atten-tion to all warnings and cautions listed on the sche-matic.
EZ Zone/Auto-Zone
Upgrade 21
Sensor Connections
Figure 8: New AZ Zone Manager Sensor Wiring
ANALOGINPUTS
+V
+V12345678GG
PRESSURESENSOR
+5
V
SIG
GN
D
TB12
StaticPick-up
StaticPressureSensor
Splice AsRequired
LO HI
Red
Blk
Grn
Supply AirSensor
To BypassActuator Feedback
++
+ +
R9
R10
C4
C4
R8
AUX1
ANALOGOUTPUTS
A2
G
TB5
TB4
TB3
A1
N.O.CONTACTS
EXHAUST
GND
GND
AUX3
AUX2
D3
D4
D5
D6
D8
D2
PR
ES
SU
RE
SE
NS
OR
JA
CK
+5
V
R7 INPUTS
OAT
RAT
+12V
SAT
ANALOG
GN
D
SIG
TB
1
PJ1
Return Air Temp.Sensor
Supply Air Temp.Sensor
Outdoor Air Temp.Sensor
StaticPick-up
StaticPressureSensor
Splice AsRequired
LO HI
Figure 7: Existing EZ Zone Master Controller Sensor Wiring
The EZ Zone Master Controller sensor connec-tions are located on the right side of the board.Only a supply air temperature sensor and thebypass actuator feedback are connected here.
The Auto-Zone Zone Manager includes termi-nals for connecting the following sensors:
• Supply Air Temperature• Return Air Temperature• Outside Air Temperature
The terminals are marked SAT, RAT, and OATfor ease of wiring. Auxiliary input terminalsAUX1, AUX2 and AUX3 are used for Econo-mizer Disable, Dirty Filter Alarm and ForcedOccupied Mode. Bypass damper feedback hasbeen relocated (see next page).
EZ Zone/Auto-Zone
22 Upgrade
Figure 10: New Auto-Zone Bypass Damper Wiring
ANALOGINPUTS
+V
+V12345678GG
PRESSURESENSOR
+5
V
SIG
GN
D
TB12
OUT6
OUT7
BYPASS
OPEN
BYPASSCLOSE
FeedbackGnd
OpenClose
Actuator WiringInterface
24 VAC
V4
V3
REC
CLOSE
OPENK1
K2
NE
TW
OR
K
SH
R
T
NE5090
FDBK
GND
OPEN
CLOSE
Feedback (Bk)Ground (Wh)
Open (Yl)
Close (Gr)
Actuator InterfaceWiring
Figure 9: Existing EZ Zone Bypass Damper Wiring
The EZ Zone Master Con-troller has two double poleterminal blocks for the by-pass actuator connections.These terminal blocks mustbe tied together by an exter-nal jumper. In addition, thefeedback connection from theactuator must be terminatedon the other side of the con-troller .
The Auto-Zone Zone Man-ager wiring has been simpli-fied. There is only one termi-nal block with connectionsclearly marked for ease ofinstallation. The actuator“feedback” connection isnow terminated at the samelocation as all the connec-tions. Jumpers are no longerrequired since the commonsare tied together within thecircuit board.
Bypass Damper Connections
EZ Zone/Auto-Zone
Upgrade 23
Honeywell Economizer Actuators
TR
T1
P
P1
24VAC24VAC
Zone Manager
Wiring OE266-01 Actuator Interface Module Kit To Zone Manager (Basic & Plus Systems)
Installing MS000204 Interface Module To Honeywell M7415 Or 7405 Actuator
Q769C1007 Interface Module(WM # MS002004)
Warning:
!
An Isolation TransformerMust Be Used For Connection ToActuator Or Serious Damage WillResult
+
TR1
T
-
A1
G
TB2
A2
G
OUTPUTSANALOG
A1
N.O.CONTACTS
EXHAUST
AUX3
GND
GND
AUX2
AUX1
ANALOG
SAT
OAT
RAT
INPUTS+12V
Honeywell Series M7415Or M7405 Actuator
24VA
C
24VA
C
T1 T1
TR TR
T T
P
P1
TR1
TR1
SEN
SO
R
SEN
SO
R
MINPO
SN
M7415A1014
025-26250
M7415A1014
025-26250
24 VAC - Isolation Transformer(WM # WP000019)
Honeywell M7415 ActuatorWithout Interface Module
Honeywell M7415 Actuator WithQ769C1007 (WM # MS000204)Interface Module Installed
Place Interface Module OnTerminals P1 and P
Figure 11: Honeywell Economizer Actuators Wiring Information
When the HVAC units that are being upgraded tothe Auto-Zone system are equipped with either theHoneywell M7415 or M7405 economizer actua-tors, an interface module and a isolation transformerare required in order to connect and use the econo-mizer outputs on the Auto-Zone system. The inter-face module converts the Honeywell actuator from0-5VDC operation to 0-10VDC operation. An iso-lation transformer is also required for this installa-tion to prevent voltage feedback to the control sys-tem. The OE266-01 Actuator Interface Module kit
is available from WattMaster. This kit includes boththe MS000204 Interface Module and a 24VAC Iso-lation Transformer.
Warning: Both the interface module and a 24VACisolation transformer must be installed as shownbelow when connecting to the Honeywell M7415or M7405 actuator. Failure to install these com-ponents as shown can result in serious damage tothe Auto-Zone controller board.
EZ Zone/Auto-Zone
24 Upgrade
To MiniLink Local Loop Terminals (Recommended)Or Local Loop Terminals Of Any Device On
Local Loop
To Next DeviceOn Local Loop
(If Desired - Not Required)
YS101716 REV. 1
SYSTEM MANAGER POWER SUPPLY
SHLD
COMMUNICATIONS
RS-485
R
T
GND
24VAC
POWER
WATTMASTER CONTROLS INC.
Override
Communication
Alarm
987
CLEAR0DEC. MINUS
ENTER
NO ALARM(S)
03/11/98 03:38PM WED
Auto-Zone v.X.XX
2
54
1
6
3
OCCUPIED
MENU ESC
Line Voltage
See Note 1
See Note 3
24VAC
Required VA For TransformerSystem Manager = 25VA Max.
The Ideal Recommended Location For The System Manager Is As TheFirst Device On The Local Loop, (Connect To MiniLink Local Loop Terminals)Although The System Manager May Be Connected To Any Local Loop AtAny Point On The Local Loop.The System Manager Will Not Operate Correctly If Attached To The Network Loop.
DO NOT CONNECT TO THE NETWORK LOOP.
The Ideal Recommended Location For The System Manager Is As TheFirst Device On The Local Loop, (Connect To MiniLink Local Loop Terminals)Although The System Manager May Be Connected To Any Local Loop AtAny Point On The Local Loop.The System Manager Will Not Operate Correctly If Attached To The Network Loop.
DO NOT CONNECT TO THE NETWORK LOOP.
System Manager
Notes:
1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.
3.) All Communication Wiring To Be2 Conductor Twisted Pair WithShield. Use Belden #82760 OrEquivalent.
2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes And Specifications.
Figure 12: System Manager Wiring
System Manager Installation
EZ Zone/Auto-Zone
Upgrade 25
Commlink II Communications Interface
(Jumper Set For Multiple Loop)
Caution: Use The “Molded Cable” ToConnect To The Computer (DCE) Connector.This Cable Is Only To Be Used To ConnectFrom The CommLink (DTE) Connection ToThe Modem (When Used).
Do Not
Caution:Disconnect All Communication Loop WiringFrom The CommLink Before Removing PowerFrom The CommLink. Reconnect Power And ThenReconnect Communication Loop Wiring.
Use 25 Pin Or 9 Pin Connector AsRequired By Available Serial (COM) PortOn Computer.
Caution: Use The “25 Pin Or 9 Pin Cable” ToConnect To The Modem (DTE) Connector.. ThisCable Is Only To Be Used To Connect From TheCommLink (DCE) Connection To The Computer
Serial Port (COM) Connection.
Do Not
(When Used) Note:Place Jumper BetweenPins 1 & 2 for MultipleLoop Applications &Between Pins 2 & 3 forSingle Loop Applications
COMM DRIVER CHIP( U1 )PIN 1
MULTI
SINGLE
12
3
CommLink Jumper Switch Settings
Notes:
R
SH
T
R
SH
T
R
SH
T
R
SH
T
All Communication LoopWiring Is Straight Through
Connect To First ZoneManager On Network Loop
Network LoopRS-485
19200 Baud(See Note 3).
Line Voltage
See Note 1
24VAC
Required VA For TransformerCommLink = 14VA Max.
CommLink Is Supplied With 110/24VAC Power Supply.If Desired A Transformer (By Others)
May Be Wired To The CommLink Instead
Molded Modem Cable.Part #HZ000098
Supplied With CommLink
(DTE)MODEMMODEM
485 LOOP485 LOOP
COMPUTER(DCE)
GT R
G2
V4
DN
POWER
4 Piece ComputerCable Kit.Part # HZ000112Supplied WithCommLink
Connect To Modem .Modem Is Part # OE419-02
Only
9P
inF
em
ale
9 PinFemale
25 PinFemale
9P
inF
em
ale
120/24 VacTransformer
Part # PX000015
25 PinMale
Part #CLMA19A1
Connect Supplied RJ12 Modular Phone CableTo Supplied 9 Pin Or 25 Pin Connector As ReqdBy Your Computer Com Port Connection
1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.
2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes And Specifications.
3.)All Communication Wiring To Be2 Conductor Twisted Pair WithShield. Use Belden #82760 OrEquivalent.
Figure 13: CommLink II Wiring
CommLink II Installation
Note:For Auto-Zone Basic System (See Example 1 page 8& 9) jumper must be set for single loop operation asshown above.For Auto-Zone Plus System (See Example 2 page 10& 11) jumper must be set for multiple loop operationas shown above.
EZ Zone/Auto-Zone
26 Upgrade
EPROM LocationSee Figure 17 ForRemoval AndInstallation Instructions
Figure 14: EZ Zone Modem Linc Central EPROM Location
Modem Linc Central EPROM Replacement
The EZ Zone Modem Linc Cen-tral EPROM chip must be re-placed with the Auto-ZoneCommLink upgrade EPROMchip part #OE754. ThisEPROM chip is factory pro-grammed with the new Auto-Zone to EZ Zone software. Thischip must be replaced or theModem Linc Central will notfunction with the Auto-Zonesystem.
CAUTION:Power must be removed from theModem Linc Central during re-moval of the old EPROM chipand installation of the newEPROM chip. It is also impera-tive that the old EPROM chip isremoved gently to avoid damageto the circuit board. Installationof the new EPROM chip mustalso be done with care to preventdamage to the pins on the newchip. See Figure 17 for detailedchip removal and installation in-formation.
Notch
EZ Zone/Auto-Zone
Upgrade 27
LO
OP
NE
TW
OR
K
T
SH
R
24VAC
GND
T
SH
R
32
16
8
4
1
2
1
2
3
4
7
5
6
8
OFF>
Ro
cke
rD
ow
n
EPROM LocationSee Figure 17 ForRemoval AndInstallation Instructions
Figure 15: EZ Zone Master Interface Board EPROM Location
The EZ Zone Master InterfaceBoard EPROM chip must be re-placed with the Auto-ZoneMiniLink upgrade EPROM chippart # OE755. This EPROMchip is factory programmed withthe new Auto-Zone to EZ Zonesoftware. This chip must be re-placed or the Master InterfaceBoard will not function with theAuto-Zone system.
CAUTION:Power must be removed from theMaster Interface Board duringremoval of the old EPROM chipand installation of the newEPROM chip. It is also impera-tive that the old EPROM chip isremoved gently to avoid damageto the circuit board. Installationof the new EPROM chip mustalso be done with care to preventdamage to the pins on the newchip. See Figure 17 for detailedchip removal and installation in-formation.
Master Interface EPROM Replacement
Notch
EZ Zone/Auto-Zone
28 Upgrade
Figure 16: EZ Zone Zone Controller EPROM Location
Zone Controller EPROM Replacement
CX
6
SW
1
U10
75176
EX
PA
N
SIO
N
Q3
Q2
D3
VR
17824
GND
24VAC
M
7824C
T
MC340
64A9936
R17
R16
U7
C7
R15
PO
WE
RR
21
RE
V.2
YS
101
562
MDL
F1
250D4
R26
LD3
L1
SCAN REC
R12
C6
R11
TOKEN
NET
LD
2
32
R14
R13
R100
LD
1
C5
D1
K1
V2
24VDC
CONTACT:
UL / CSA 5A250VAC
K2
D2
AC
TU
A
TO
R
24VDC
CONTACT:
UL / CSA 5A250VAC
R10
R9
PJ2
V1
C4
74H
C573N
B31920P
S
TC
U3
2K
2V
9936
MS
6264L-7
0P
C
EPROM
VR
EF
AD
J
R23
C10
PC
B80C
552-5
-16W
P
500650=
1/3
DF
D9940S
M
PH
ILIP
S
EW
DO
G
CO
MM
D7
CX10
R25
R28
T'STA
T U11
C15
R20
C11
R24
8
16
2
4
ADDRE
SS ADD
1 U6
93C
46
U5
R19
PH
ILIP
S
U9CX9
R32
D5
C14
P.U.
R22
C13
LM
C662
R27
D5
RAM
C9
C8
80C55
2
CX
5P
J1
C3
R8
R7
R5
R6
R4
C2
C1
X1 74H
C259
B31920P
S
U2
R1
R2
R3
CX2
Q1
16L8
32K
R34FLOW
U8
1
RN1
CX8 U4
R18 CX4
8KRAM
U3
CX3
U1
CX1
The EZ Zone Zone ControllerEPROM chip must be replacedwith the Auto-Zone ZoneContoller upgrade EPROM chippart # OE752. This EPROMchip is factory programmed withthe new Auto-Zone to EZ Zonesoftware. This chip must be re-placed or the zone controller willnot function with the Auto-Zonesystem.
CAUTION:Power must be removed from theZone Controller board during re-moval of the old EPROM chipand installation of the newEPROM chip. It is also impera-tive that the old EPROM chip isremoved gently to avoid damageto the circuit board. Installationof the new EPROM chip mustalso be done with care to preventdamage to the pins on the newchip. See the next page for de-tailed chip removal and instal-lation information.
EPROM LocationSee Figure 17 ForRemoval AndInstallation Instructions
Notch
EZ Zone/Auto-Zone
Upgrade 29
EPROM Installation Procedures
Small FlatheadScrewdriver
Chip
Chip
Printed CircuitBoard
Printed CircuitBoard
Printed CircuitBoard
Chip
WARNING!
Direction Of Pull
Notch
Dot
Pin1
Be sure the chip you have selected to replace is asocketed chip. Not all driver chips on the boardsare field replaceable. Only socketed chips may beremoved and replaced in the field. All other chipsthat are not socketed will require sending the boardto the WattMaster factory for repair.
Once you have determined that thechip needing replacement is indeed a socketed chipplease proceed in the following manner.
Remove the communications loop connector andthen the 24VAC power connector on the controllerbefore attempting to change any components.
will occur if components are removed orinstalled with power applied.
If you are unsure how to safely remove the chip orabout the correct pin placement, please consult thefactory before proceeding.
Use extreme care to avoid inserting the screwdriveror I.C. Puller under the socket. You must insert the tipof the screwdriver or ends of the I.C. Puller betweenthe body of the chip and the chip socket.
Each chip be installed with Pin 1 in the correctlocation. Installing the chip “backwards” will in mostcases destroy the device when power is reapplied.
Pin 1 can be located by looking for the notch in the endof the chip. Pin 1 on "some" chips is identified with a dot.
Be certain that pins are lined up in the socketbefore pressing the chip in. Failure to properly lineup the pins will result in damage to the chip.This is a common error -
Only after confirming that the chip has been correctlyinstalled with Pin 1 in the proper position and that thepins are lined up and none are bent or out of the socket,should communication or power wiring be reconnectedto the board. Tp prevent possible damage alwaysreconnect the power wiring first and then thecommunication wiring.
If you try toremove a chip that is not socketed it will destroythe circuit board.
DAMAGE
Damage to the board caused by failure to correctlyremove or install the chip is not covered by theWattMaster warranty.
MUST
ALL
VERY BE CAREFUL.
Using I.C. Puller To Remove Socketed Chip
Using Screwdriver To Remove Socketed Chip
End View Of Socketed Chip AssemblyTop View Of Socketed Chip Assembly
I.C. Puller
Chip Socket
Chip Socket
Chip Socket
Gently Rock Chip Side To Side And ThenLift Straight Up To Remove Chip FromChip Socket.
Gently Lift The Chip On One End And Rock ChipBack And Forth With Screwdriver As Shown.Repeat This Process On The Other End Of Chip.Alternate This Process On Both Ends Of Chip UntilThe Chip Is Free From The Chip Socket.
Pin 1
Dot
Socket
PrintedCircuitBoard
Typical RS-485 CommunicationsDriver Chip Detail
Figure 17: EPROM Removal And Installation
EZ Zone/Auto-Zone
30 Upgrade
Minilink Board
Zone Manager Board
Keypad And DisplayCircuit Board
3- Connector Ribbon CableTo KeyPad & Display BoardSee Connection Detail Below
Cable Connection Detail
+
+
++
+
++
+ +
HEAT2
HEAT1
COOL2
COOL1
FAN
R
2
8C
SW
1
16AB 24
AD
D
LOCALLOOPT
SH
RTB3
COMM
T
SH
R
32
16
8
4
1
2
MINILINK
R9
R10
R8
I CEXP
PORT
PWR
V4
V3
CLOSE
OPEN
FDBK
REC
GND
GND
24VAC
AUX1
OPEN
K1
NETWORKLOOP
SH
R
T
CLOSE
K2
NE5090
ANALOGOUTPUTS
A2
G
TB2
A1
N.O.
EXHAUSTCONTACTS
GND
GND
AUX3
AUX2
7824
D25
U14
VR
3
R40
ADJUST5.11V
C27
7812 C26
VR
2
D1
D3
D4
D2
PJ1
PR
ES
SU
RE
SE
NS
OR
JA
CK
+5V
R7
OAT
RAT
+12V
SAT
ANALOGINPUTS
GN
D
SIG
Use 3-Connector Ribbon Cable When ConnectingAuto-Zone Plus Zone Manager BoardTo EZ Zone Keypad & Display Board
USE CARE TO ROUTE THE RIBBON CABLE SO THAT IT IS NOT CRIMPED AND SOIT IS CLEAR OF ENCLOSURE COVER SCREWS WHEN INSTALLED
CAUTION!
Figure 18: 3 Connector Ribbon Cable Installation
Note:The 3 Connector Ribbon Cable Is Only RequiredWhen Connecting A System As Shown InExample #2 On Pages 10 & 11 Of This Guide.
Ribbon Cable Installation
EZ Zone/Auto-Zone
Upgrade 31
Upgrade Parts List Summary
All the standard and components that are required oravailable for the Auto-Zone to EZ Zone upgrades aresummarized below. See the upgrade examples on pages8 through 13 of this manual for the parts lists that arerequired for your specific application. For other Auto-
Zone products such as CV Unit Controllers, LightingPanel Controllers etc., please see pages 14 & 15 or con-sult the factory to see if these are available for yourspecific application.
Part No Description
OE392-01-ZSYSM System Manager (Used on Plus Systems)Includes: System Manager Only.
OE751 EZ Zone To Auto-Zone Basic Upgrade KitIncludes: Zone Manager Board w/ Mounting Screws, Plastic Standoff Kit forZone Manager, Return Air Sensor, Upgrade Label, Installation Instructions.
OE753 EZ Zone To Auto-Zone Plus Upgrade KitIncludes: Zone Manager Board w/ Mounting Screws, Plastic Standoff Kit forZone Manager, MiniLink w/ Mounting Hardware, Return Air Sensor, 3 WayDisplay/Keypad Connector cable, Upgrade Label, Installation Instructions.
OE231 Duct Temperature Sensor(10kohm with 12” Probe, used for Return or Supply Air Sensor)Includes: Duct Temperature Sensor, 2 Wire with 12” Long Probe.
OE250 Outside Air Temperature Sensor (10kohm)Includes: Temperature Sensor Mounted in Weatherproof Handy Box.
OE419-03 Remote Data Link (Modem- External -14,400 Baud )Includes: Modem and 120/9 VAC Power Supply.
OE361-04 CommLink II (Used on Basic & Plus Systems )Includes: CommLink II, Power Supply & Cables for Connection to Computer andRemote Link are Included.
OE752 Replacement EPROM ChipContains Auto-Zone software to replace EZ Zone software in Zone ControllerIncludes: EPROM Chip
OE755 Modem Linc Central To CommLink II Upgrade KitIncludes: ComLink II EPROM Upgrade Chip, Upgrade Label
OE754 Master Interface Board To MiniLink Upgrade KitIncludes: MiniLink EPROM Upgrade Chip, Upgrade Label
EC101600-3 Blank Enclosure CoverUsed to replace EZ Zone Master Controller Cover when Keypad & Display arenot Desired. Includes: Metal Enclosure Cover Only
SP500 ZoneView AZ SoftwareWindows Based Software for Accessing System using a PCIncludes: 3.5” Floppy Installation Diskettes and Operations Manual.
EZ Zone/Auto-Zone
32 Upgrade
For further technical information regarding the Auto-Zone products please refer to the appropriate Installa-tion, Operation and Maintenance manual included with
Additional Information
your upgrade package. Additional technical assistanceis available by contacting the WattMaster technical sup-port group at the numbers listed below.
WattMaster Controls Inc.Phone: (816) 505-1100Fax: (816) 505-1101E-mail: [email protected]
Thank you for choosing WattMaster Controls!
EZ Zone/Auto-Zone
Upgrade 33
Notes:
Form: WM-EZA-UG-01C Printed in the USA October 2000All rights reserved Copyright 2000WattMaster Controls Inc. • 8500 NW River Park Drive • Parkville MO • 64152Phone (816) 505-1100 E-mail: [email protected] Fax (816) 505-1101