HubnetColloquiumStrathclydeUniversity–Glasgow,Scotland(UK)
December7th2016
ExtrudedCableSystemsfor
HVDCTransmissionProf.GiovanniMazzan*
Dept.Electrical,Electronic&Informa5onEngineering“GuglielmoMarconi”AlmaMaterStudiorum-UniversityofBologna,Italy
1
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
![Page 2: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/2.jpg)
Introducingmyself…
1) MD(1986)andPhDinElectrotechnicalEngineering(1992)atUNIBO
2) Since1992withDEl-UNIBO.Since2004AssociateProfessorofPowerQualityandHVEngineering.Researchfields:insulaVonaging(lifemodels,SC),RES,EMF
3) Since2009ConsultantofTERNA(ItalianTSO).HVDCprojects:SAPEI,SACOI, ITA-FRA(Piemont-Savoie),ITA-MON
4) CoauthorofG.MazzanV,M.Marzino]o,ExtrudedCablesforHighVoltageDirectCurrentTransmission:AdvancesinResearchandDevelopment,PowerEngineeringSeries-Wiley-IEEEPress,2013
5) Since 2012 Chairman of IEEE DEIS TC “HVDC cable systems (cables, joints &terminaQons)”.Since2015ChairmanofIEEEDEISWG“HVDCcablesystems”fordeveloping IEEE Standard P1732: “Recommended prac5ce for space chargemeasurementsinHVDCextrudedcablesforratedvoltagesupto550kV” 2
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
![Page 3: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/3.jpg)
3
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
SUMMARY
1) FundamentalsofHVDCextrudedcabletransmission[chp.1-2I-B]
2) Designparameters:HVDCvsHVACcabledesign[chp.3I-B]
3) MainrealizaVonsworldwide[chp.7I-B]
![Page 4: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/4.jpg)
4
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
1) FundamentalsofHVDCextrudedcabletransmission[chp.1-2I-B]
2) Designparameters:HVDCvsHVACcabledesign[chp.3I-B]
3) MainrealizaVonsworldwide[chp.7I-B]
![Page 5: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/5.jpg)
Historyofpowertransmission:fromDCtoACØ PowerT&DstartedwithDC:
-1879: (T.A.Edison) incandescent lamp+useofdynamo⇒1882,PearlStreetStaVon,NYC(6x100-kW“jumbodynamos”+30kmu.g.cables)
-1882:50-km2-kVDClineMiesbach-MunichinGermany
Ø From DC to AC (Tesla & WesQnghouse) ⇒ transformers andinducVonmotors⇒ACdominantingeneraQon,T&D,uQlizaQon
Ø ACsystemvoltageconversionissimple:• transformer (high power and insulaVon, low losses, li]le
maintenance)• 3-φsynchronousgeneratorsuperiortoDCgenerator 5
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
![Page 6: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/6.jpg)
DisadvantagesofHVACpowertransmissionØ ACpowertransmissionhasalsodisadvantages,e.g.
1) NoconnecQonbetweenACsystemswithdifferentfrequencies
2) Weak connecQon between independent AC systems ⇒ systeminstability(DOMINOEFFECT)orundesirablepowerflow
3) InducVve & capaciVve elements of OHLs and cables⇒ limits totransmission capacity and distance. Strong limitaVon for HVACcables:inthe40-100kmrange(~70kmat220kV,~40kmat400kV)increasingto50-150kmwithopVmizedreacVvecompensaVon
6
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
![Page 7: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/7.jpg)
Fig.2.1–Cabletypologiesusedvs.length,powerandvoltage(aQer[7.2.I-B])7
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
![Page 8: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/8.jpg)
AdvantagesoftransmissionwithHVDCcables(1)1) lowerlosseswithsamecurrent(conductor≡noskin&proximityeff.,
metallicsheath&armoring≡nolosses,dielectric≅nolosses)2) higheraverageelectricfield⇒highercableuQlizaQon
8
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
![Page 9: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/9.jpg)
AdvantagesoftransmissionwithHVDCcables(2)
3) conductor and insulaVon savings ⇒ HVDC cables cheaper thanHVACcablesforsamepowerraVng⇒lowerp.u.l.linecosts
4) cable lengths not limited by reacVve power (no reacVvecompensaVonatendstaVonsand/orintermediatepoints)
5) DC transmission ≡ asynchronous link with ≈ no increase in faultlevel
6) powerfloweasilyandquicklycontrollable⇒DC linkcan improveACsystemstability
7) uniqueusageofHVDCcables:subseapowerlinksonlongdistances9
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
![Page 10: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/10.jpg)
Ø HVDCtransmissiondisadvantages:AC/DCconvertercosts&losses⇒breakevendistance(BD)≡savingsinlinecostsoffsetconvertercosts
Ø Total (line + losses) cost ⇒ DC-lesssteepthanAC-curvesdueto• lower p.u.l. line investment
cost (OHL: narrow ROW &sm a l l t owe r s , 2 v s . 3conductors ; cab les : lowconductor&insulaVoncost,noreacVvecompensaVon)
• lower capitalized losses cost(noAClosses)
10
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
ACvs.DCtransmission:economiccomparison
Fig. 2.8 - HVAC vs. HVDC transmission system costs (after [4.2.I-B])
Ø At500kV:BD≈500kmforOHLs,≈40kmforcables(seeabove)
![Page 11: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/11.jpg)
• highpowerandvoltageraVngs• lowlosses• highreliability• acceptablecosts• goodperformances
11
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
AC/DCconvertersØ DCtransmissionrequiresAC/DCconverterswith(ideally):
Ø TwoconvertersmainlyusedforDCtransmission:
• Line-CommutatedCurrent-SourceConverters(LCC)
• Self-CommutatedVoltage-SourceConverters(VSC)
![Page 12: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/12.jpg)
12
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
AC/DCconverters:LCC(1)Ø Firstdeveloped:LCC(=tradiVonalDCtransmission,HVDCClassicTM)
Fig. 2.11 - LCC with SCR valves arrangement (after [5.2.I-B])
![Page 13: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/13.jpg)
Ø LCCdevelopment:
1) MercuryarcrecQfiersinthe1930’s⇒LCCdesignpossible
2) Silicon Controlled RecQfiers (SCR, or thyristors) in the late1970’s:oil-immersed,parallel/seriesconnecVon
3) State of the art: air-insulated water-cooled Light-TriggeredThyristors(LTT):highercurrent&voltage,lesscomponentspervalve⇒higherreliability⇒highestpower&voltageraQngs
Ø Power flow reversal: by reversing voltage polarity⇒ criQcal forHVDCextrudedcableinsulaQon!
13
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
AC/DCconverters:LCC(2)
![Page 14: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/14.jpg)
14
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
AC/DCconverters:VSC(1)Ø Morerecent(late1990s)thanLCC,VSC(HVDCLightTM,HVDCPlusTM)
Fig. 2.12 - VSC with IGBT valves arrangement (after [5.2.I-B])
![Page 15: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/15.jpg)
15
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
AC/DCconverters:VSC(2)
Fig. 2.7 – Operating range for HVDC VSC (after [5.2.I-B])
Ø MaincharacterisVcsofVSC:
• semiconductors with turn-offcapability:IGBT
• four-quadrantoperaQon• highlosses• powerupto≈1000MW
Ø Power flow reversal: byreversing current flow⇒ novoltagepolarityreversal⇒okfor HVDC extruded cableinsulaQon!
![Page 16: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/16.jpg)
1) DisadvantagesofLCC:1) reacQvepowerdemandfromACnodes2) injecVonofcurrentandvoltageharmonics⇒capacitorbanksonACside&harmonicfiltersonACandDCside
2) DisadvantagesofVSC:lessexperience,lowervoltage/powerraVngs
AC/DCconverters:LCCvsVSC
16
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
Fig. 2.6 – HVDC with VSC (after [5.2.I-B]) Fig. 2.5 – HVDC with LCC (after [5.2.I-B])
![Page 17: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/17.jpg)
17
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
DevelopmentofLCCandVSCØ Since VSC-HVDC started (1990s), the increase of voltage &
powerforIGBT-VSChasparalleledthatofSCR-LCCin1970s
Fig. 2.13 – Solid-state converter development (after [5.2.I-B])
![Page 18: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/18.jpg)
(From [LW2013]:MarcoMarelli, “Achievement and experience in service of long lengthHVDC electricallinks by insulated power cables”, LaVnAmericanWorkshop 2013, Foz do Iguaçu – September 6th, 2013.CourtesyofPrysmian)
ACvsDCCableTransmissionSystems
18
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
![Page 19: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/19.jpg)
1)ground/seaelectrodes2) “metallic return”:MVcable grounded at 1converterstaVon3) midpoint grounded12-pulse conv. + 2 1/2-voltagepoles(nogroundcurrent)
19
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
HVDCcablelineconfiguraQons:(1)monopolar
Fig.2.11-HVDCconfiguraVonsandoperaVngmodes(axer[5.2.I-B])
Ø Monopolarsystems:simplestandcheapestformoderatepower:2convertersand1HVpoleonly.
Ø AlternaVvesforreturncurrent:
![Page 20: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/20.jpg)
Ø OperaQngmodes:1) Normal (balanced)
⇒ 0 g r o u n dcurrent
2) Monopolar groundreturn:1poleoutage3) Opposite pole formetallicreturn:outageof1converter(ateachend pole/converterbypassswitch) 20
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
HVDCcablelineconfiguraQons:(2)bipolarØ Bipolarsystems:mostcommon,one12-pulseconverterperpole
andterminal⇒2independentcircuits(1/2capacityeach)Fig.2.11-HVDCconfiguraVonsandoperaVngmodes(axer[5.2.I-B])
![Page 21: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/21.jpg)
Ø ClassificaQonbasedontheinsulaQontype:
q Oil-paperinsulated- Mass-ImpregnatedNon-Draining(MIND)- oilfilled(OF)
o LowpressureOF(LPOF,SCOF,SCFF)o HighpressureOF(HPOF)
q Polypropylene-LaminatePaper(PPLP)orPolypropylenePaperLaminate(PPL)
q Gasfilledcables
q Extruded(XLPE,thermoplasQc)21
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
HVDCcabletypes
![Page 22: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/22.jpg)
Ø Usedinmanylinks,highestvoltages&longestlengths: up to 500-600 kV, 1000 MW in 1cable, depths under sea up to 1640 m,≈unlimitedlengths.Structure:1) compactstranded/segmentedCu/Alconductor2) carbon-loadedpaperconductorsemicon3) InsulaVon(Kraxpapertapesimpregnated
withhigh-viscositymineraloils)4) carbon-loadedpaperinsulaVonsemicon5) metallic(leadalloy)sheath6) thermoplasVcjacket7) steeltapereinforcement(subseacables)8) bedding(subseacables)9) armorofsteelround/flatwires(subseacables)
Ø Conductortemperature:max.55°C⇒limittocapacity 22
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
HVDCcabletypes:MIND(1)
Fig.2.16(a)-MINDHVDCdeepwatercableforSAPEIsubsealink(aQer[I-B],courtesyofPrysmian)
![Page 23: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/23.jpg)
23
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
HVDCcabletypes:Oil-Filled(OF)Ø InsulaVon: paper + low-viscosity oil. Conductor
with longitudinal duct for oil flow along thecable.Otherlayersare≈sameasabove
Ø Oil-filledcablesokforACandDCvoltages:DCvoltagesupto600kV,greatseadepths
Ø Oil flow along cable⇒ lengths limited to<100km,riskofoilleakageintheenvironment
Ø Oil-filledcablesdividedinto:i)single-coreoilfilled(SCOF)=lowpressureoilii)highpressureoilfilled(HPOF)=cableslaidinapipefilledwithhighpressureoil
Fig.2.16(b)SCOFHVDCcable(aQer[I-B],courtesyof
Prysmian)
![Page 24: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/24.jpg)
24
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
HVDCcabletypes:PPLPØ Polypropylene Paper Laminate (PPL or PPLP) =
LappedThinFilmInsulaVon
Ø OF-PPLP = impregnated with non-viscous oil ⇒similartoSCOFcables
Ø MI-PPLP=impregnatedwithviscous(non-draining)oil⇒ similar toMINDcables: ok for long&deepsubsealinks
Ø Claimedtooperatewithconductorat80-90°Candupto60%higherelectricalstressthanMIND
Ø Technology under development for DC-cables (KiiChannel,Westernlink:England-Scotland)
Fig.2.16(c)–MI-PPLP
HVDCcable(aQer[I-B],courtesyofPrysmian).
![Page 25: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/25.jpg)
25
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
Fig.3.4–StructureofHVDCXLPE-insulatedcablesforland(leQ)andsea(right)usagewithVSCconverters
(aQer[I-B],courtesyofABB)
Conductor Copper or aluminium
Conductor Aluminium or Copper
Conductor screen Semi-conductive polymer
Conductor screen Semi-conductive polymer
Insulation Dry cured polymer
Insulation Dry cured polymer
Insulation screen Semi-conductive polymer
Insulation screen Semi-conductive polymer
Swelling tape
Swelling tape Lead alloy sheath
Metallic screen Copper wires
Swelling tape Inner jacket Polyethylene
Aluminium laminate Outer covering Polyethylene
Swelling tape
Tensile armour Galvanized steel wires
Outer covering
Polypropylene yarn
HVDCcabletypes:extruded(1)
![Page 26: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/26.jpg)
26
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
(a) (b)Fig.2.19–TwotypesofHVDCXLPE-insulatedcable:
(a)landcable(aQer[25.2.I-B]);(b)submarinecable(aQer[I-B],courtesyofPrysmian)
HVDCcabletypes:extruded(2)
![Page 27: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/27.jpg)
Ø Extrusion:uniformcompact layerofpolymer laidaroundconductorbetween2semiconlayers
Ø Besttodate:• tripleextrusionofinsulaQonthickness+inner&outersemicons• X-linkingof insulaVon (if needed,XLPE): dryenvironment (N2) +
DCP X-linking agent⇒ X-linking by-products that store SC⇒degassing--->thisaxernoon
Ø TripleExtrusionLine:1) conductorentersTripleExtrusionCrossHead2) output:insulatedconductor⇒entersX-linkingpipe,catenaryor
verVcal≡highp&T,longenoughforthermo-chemicalX-linking3) finishedcablecoreviaconVnuousproducVon 27
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
HVDCextrudedinsulaQontechnology:extrusion
![Page 28: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/28.jpg)
Ø ExtrudedXLPEinsulaVonadvantagesvs.oil-papercables:• lowercosts• easier(faster,cheaper)joinQng• environmentalcompaQbility(nooilleakage)• conductortemperature>MINDcables:
o HVACXLPE:conductortemperature=90°C(service),250°C(shortcircuit)o HVDCXLPEconductortemperature=70°C(Hokkaido-Honshulink90°C)
Ø ExtrudedXLPEinsulaVondisadvantagesvs.oil-papercables:• weakpoints(defects)--->thisaxernoon• suffers space charges (SC) and polarity reversals ---> this
axernoon• lessserviceexperience&lowervoltages--->thisaxernoon
28
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
Extrudedvs.oil-paperDCcables:pros&cons
![Page 29: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/29.jpg)
29
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
1) FundamentalsofHVDCextrudedcabletransmission[chp.1-2I-B]
2) Designparameters:HVDCvsHVACcabledesign[chp.3 I-B]
3) MainrealizaVonsworldwide[chp.7I-B]
![Page 30: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/30.jpg)
30
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
DesignofACcables:(1)thermaldesign
θc=designconductortemperature[known]θa=ambienttemperature[known]Pd=dielectriclosses[notofmainsignificance,preliminaryevaluaVonfromU0,Eave]γ=addiVonallossesinmetalliclayers(screen,armors)Ti=thermalresistancesofcablelayers(T1,T2,T3)+environment(T4).Mainrole:T4[known]Rca=ACelectricalresistanceofconductoratdesigntemperature∝1/conductorX-secVon⇒conductorX-secQon⇒conductorradiusri
P=3U0Iaccosϕ
(5.3ac)
(5.5ac)
Ø Maindesignparameter=maximumtransmissionacQvepowerP
Ø U0=Un/√3=ratedφ-to-groundvoltageofcablesystem⇒Iac=ampacityofunipolarcable⇒thermaldesignaxerIEC60287,seeeq.(5.3ac):
Ø U0+conductorradiusri⇒electricaldesign⇒insulaQonthicknessfromACelectricfield
)])(1([)()(
321
321
TTTRTTTPI
ca
dacac +γ++
++β−θ−θ=
![Page 31: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/31.jpg)
31
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
DesignofACcables:(2)electricaldesign
⎟⎟⎠
⎞⎜⎜⎝
⎛=
i
oAC
rr
r
UrE
ln)( 0
(3.1)
EAC(r)=ACelectricfieldatradiusrU0=designvoltage(AC:φ-to-ground)[known]ri=insulaVoninnerradius[known]r=genericradiuswithininsulaVonro=insulaVonouterradiusEMAX=maximumfieldEMIN=minimumfieldØ fieldprofile• EMAXalwaysatconductor-insulaQon• EMINalwaysatinsulaQon-screen
Fig.3.5–ElectricfieldinACcableinsulaVon:“Laplace”,or“capaciVve”,or“ε-dependent”field(axer[I-B])
Ø ACvoltagewithstandproperQesofinsulaQon⇒EMAX⇒outerinsulaQonradiusro⇒insulaQonthicknessd=ro-ri
![Page 32: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/32.jpg)
32
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
DesignofACcables:≈completedØ Known:
• conductorradiusfromthermaldesign• insulaQonthicknessfromelectricaldesign
Ø Thesetwodesigns≈donotinteractwitheachother⇒needed
onlyarefinedevaluaVonofampacityfrom:
• refinedevaluaVonofdielectriclosses• “finetuning”ofcablelayers(screen/sheath,jacket,etc.)• deeperstudyofenvironment(route,soil,etc.)
Ø Ampacityupdated
Ø ACcabledesigncompleted
![Page 33: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/33.jpg)
33
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
DesignofDCcables:(1)samestarQngpoint…
θc=designconductortemperatureθa=ambienttemperatureTi=thermalresistancesofcablelayers(T1,T2,T3)+environment(T4).Mainrole:T4[known]Rdc=DCelectricalresistanceofconductoratdesigntemperature∝1/conductorX-secVon⇒conductorX-secQon⇒conductorradiusri
P=2U0Idc(bipolarsystem)
(5.3)
(5.5)
Ø Maindesignparameter=maximumtransmissionpowerP
Ø 1stchoice(non-trivial≡inv.costs,losses,etc.):ratedpole-to-groundvoltageU0⇒Idc=ampacityofpolecable⇒preliminarythermaldesignaxerIEC60287,seeeq.(5.3):
)()(
4321 TTTTRI
dc
acdc +++
θ−θ=
Ø U0+conductorradiusri⇒electricaldesign⇒inprinciple,insulaQonthicknessfromDCfield.Problem:DCfieldofcablesdiffersbymuchfromACfield!
![Page 34: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/34.jpg)
34
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
DesignofDCcables(2):…butmanydifferences!Ø Maindifference:Maxwell’sequaVons⇒
1) DCelectricfieldEDCaffectedbyelectricalconducQvityσofinsulaVon,affectedinturnbytemperatureandfield⇒EDCdependsoninsulaQontemperaturedropΔT(∝conductorlossesWc∝cablecurrent∝load)⇒fieldprofileinversionbetweenmin.andmax.loadpossible⇒designfield/insulaQonthicknessforoneloadcondiVon(e.g.zero)notokforanother(e.g.maximum)
2) ampacityaffectsEDC⇒selecVonofvoltage,ampacity(losses),field,insulaQonthicknessinherentlyinterlinked
Ø 2nddifference:EDCinsteady-stateisnotthesameasintransients
Ø 3rddifference:Maxwell’sequaQons⇒spacecharge(SC)altersEDC---->thisaxernoon
![Page 35: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/35.jpg)
35
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
Noloadvsunder-loadcondiVonsinHVDC:1) cableenergizedatzeroload⇒temperaturedropacrossinsulaVon
ΔT=0⇒EDC“quasi-Laplacian”or“quasi-capaciVve”(≈geometricalvariaVononly,similartoEACinFig.3.5)
2) cableenergizedunderagivenload⇒equilibriumvalueofΔT≠0:
ElectricfieldofDCcablesinsteady-state(1)
)]()(exp[),( 000 EEbTTaET −+−=σσ (3.10)
])/)((exp[),( 000γσσ EETTaET −=
σ(T,E) = σ0 exp(-Ga/kBT) sinh(cE)/E
(3.11)
(3.12)
⎟⎟⎠
⎞⎜⎜⎝
⎛
πλ=−=Δ
i
o
T
Coi r
rWrTrTT ln2
)()(
⇒“Poissonian”EDCdependsonΔTviaσ.
Experimentalexpressionsforσvs.EandTinDC-XLPE:
(3.14)
Mostused
![Page 36: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/36.jpg)
36
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
Ø Maxwelleqns.inS.S.+(3.10)+simplifyinghypotheses⇒Eoll’sformula:
(3.29)
[inversioncoefficient]
(3.27)
⎥⎥⎦
⎤
⎢⎢⎣
⎡⎟⎟⎠
⎞⎜⎜⎝
⎛−
⎟⎟⎠
⎞⎜⎜⎝
⎛
=
−
δ
δ
δ
o
io
o
rrr
rrU
rE
1
)(
1
0
( )
( )
( )
( )io
o
io
o
io
io
o
io
o
dT
c
rrbU
rrbU
rrTa
rrbU
rrbUaW
−+
−+
Δ
=
−+
−+
πλ=δ
1
)/ln(
1
2 ,
Ø (3.29)vs.(3.1)⇒steadyDCfieldfarmorecomplexthanACfield
Ø From(3.29),(3.27)steadyDCfielddependsnotonTbutonΔTonly⇒onJoulelossesintheconductorWC
ElectricfieldofDCcablesinsteady-state(2)
![Page 37: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/37.jpg)
ElectricfieldofDCcables:steadyfieldprofiles
37
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
Reference“standard”cable:U0=450kV,1600mm2Cuconductor,ri=23.2mm,ro=42.4mm,ρ0=1x1016ΩmatT0=293K,E0~0kV/mm,a=0.11/°C,b=0.03mm/kV.Underload,inversioncoefficientδ>1fortemperaturedropΔT=10,15,20°C⇒fieldinversion!!
Fig.3.9(b)–SteadyDCfieldprofilesunderno-loadfor“standardcable”using(3.29)(aQer[I-B])
Fig.3.16(b)-SteadyDCfieldprofilesunderloadvs.ΔTfor“standardcable”using(3.29).Inversioncoefficientδ>1⇒fieldinversionoccurs(aQer[I-B])
![Page 38: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/38.jpg)
38
Combinedelectro-thermallifemodel:loadcyclesØ [GMDC]:24-hloadcyclestd,givendependenceI(≡load current)=f(t), t∈[0,td] ⇒cumul.damageMiner’slawforDCcableinsulaVonatradiusr:
LFDC(r)=loss-of-life fraction within td KDC(r)=number of “cycles-to-failure”
1)()()()(0
==∫ rLFrKrdLFrK DCDC
t
DCDC
d
( ) ( )[ ] )(/1,,,/)()(00
rKtrTtrELdtrdLFrLF DC
t
DC
t
DCDC
dd
=∫∫ ==
Ø DCcablelifefromKDC,min=minimumnumberof“cycles-to-failure”KDC(r)withininsulaVon:
( ) ( ) ( ) )41.6(),('exp)(/),())(),,(( ),('00
0 trTBrEtrEtTtrE trTbnDCt
ET −= −−αα
]}[),(min{ ,min, oiDCdDCdDC rrrrKtKtL ∈×=×=
0 5 10 15 20 2520
22
24
26
28
30
Time of the daily cycle [h]
Elec
tric
field
[kV/
mm
]
inner insulation surface25% insulation thickness50% insulation thickness75% insulation thicknessouter insulation surface
Inner insul. 25% insul. 50% insul. 75% insul. Outer insul.0
5
10
15
20
25
30
Loss
-of-l
ife fr
actio
n [%
]
ZL period (120 days)HL periods (80 days)LC periods (160 days)
Loss-of-lifefracVonsfor360-kV,2000mm2Al,20mmDC-XLPEcableinLC,HL,ZLperiodsandwhole360daysofPQtestsatsame5locaVons(axer[GMDC])
T
E
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
![Page 39: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/39.jpg)
39
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
1) FundamentalsofHVDCextrudedcabletransmission[chp.1-2I-B]
2) Designparameters:HVDCvsHVACcabledesign[chp.3I-B]
3) MainrealizaQonsworldwide[chp.7I-B]
![Page 40: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/40.jpg)
40
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
(From[LW2013].CourtesyofPrysmian)
Ø ExponenQalincreaseofHVDCcablemarket!Ø Paper-oilcablesruledunQl2000,thenextrudedcablestookoff!
HVDCcablemarket
![Page 41: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/41.jpg)
41
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
41
Table7.1–MainHVDCextrudedcablesystemsinserviceworldwide(aQer[I-B])MainrealizaQonsworldwide(end2012)
Project Customer Country Sea/land Year Length(km) U0(kV) Power(MW) Cond.(mm2)
Hokkaido-Honshu EPDC Japan Sea 2012 44 ±250 600 600
East-WestInterc. EirGrid Ireland-Wales Land 2012 75 ±200 500 -
East-WestInterc. EirGrid Ireland-Wales Sea 2012 186 ±200 500 -
Valhall BP Norway Sea 2011 292 150 78 -
BorWin1 Transpower Germany Sea 2011 243.3 ±150 400 1200
BorWin1 Transpower Germany Sea 2011 22.6 ±150 400 1600
BorWin1 Transpower Germany Land 2011 155.3 ±150 400 2300
TransBay CaliforniaTSO USA Sea 2010 160 ±200 400 1100
TransBay CaliforniaTSO USA Land 2010 10 ±200 400 1100
Estlink NordicEnergyLink Estonia-Finland Sea 2006 150 ±150 350 1000
Estlink NordicEnergyLink Estonia-Finland Land 2006 62 ±150 350 2000
Troll-A Statoil Norway Sea 2004 284 ±80 2x41 300
Cross-Sound Transenergie-US USA Sea 2002 83.2 ±150 330 1300
Murraylink Transenergie-US Australia Land 2002 223.2 ±150 220 1200
Murraylink Transenergie-US Australia Land 2002 136.8 ±150 220 1400
DirectLink Transenergie-US Australia Land 1999 390 ±84 3x60 630
GotLight GotlandEnergy Sweden Land 1998 140 ±80 50 340
![Page 42: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/42.jpg)
42
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
SummaryofmainrealizaQonsworldwide(end2012)
Totalinstalledlengthofsubmarinecables(km) 1237
Totalinstalledlengthoflandcables(km) 1119
Grandtotalofinstalledlengthofcables(km) 2356
![Page 43: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/43.jpg)
43
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
TransBayProject(commissioned2010):thesubmarinecable
Fig. 5.11 - Trans Bay cable design (after [I-B], courtesy of Prysmian)
Ø ±200kV,400MW,∼2x83km,SanFranciscoBay(USA),commissioned2010(firstextruded200kV-DCattheVme).Cablestructure:
![Page 44: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/44.jpg)
44
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
TransBayProject:thecablesystem
Fig. 7.16 - Cross Section of HVDC Cable for the Trans Bay Cable Project (after [I-B], courtesy of Prysmian)
Ø ±200kV,400MW,1100mm2Cuconductor,VSCMMC
![Page 45: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/45.jpg)
45
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
TransBayProject:thecableroute
Fig. 7.13 – The Trans Bay Project route
(after [I-B], courtesy of Prysmian).
Fig. 1.4(a) – Sketch of cable interconnections of the Trans Bay Cable Project (after [I-B], courtesy of Prysmian).
![Page 46: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/46.jpg)
46
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
Example,TransBayProject:layingacQviQesFig.7.15–Facili*esusedforthelayingac5vi5esoftheTransBayCableinSanFranciscoBay,USA:b)turntableaboardtheshipGiulioVerne(after [I-B], courtesyofPrysmian)d)Hydroplow(after [I-B], courtesyofPrysmian)
![Page 47: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/47.jpg)
Ø ±250kV,600MW,commissionedattheendof2012.Mainfeatures:
47
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
SubmarinecableforHokkaido–HonshuinterQe(commis.2012)
Fig.7.17.±250kV,600MWHokkaido–Honshuinter5e,Japan:(a)route;(b)powercable(aQer[I-B],courtesyofElectricPower
DevelopmentCo.Ltd.&J-PowerSystemsCorpora5on)
• Max.conductorT=90°C• okforpolarityreversal
• DC-XLPEcompound(PolarizedinorganicnanofillersforsuppressingSC,keepingel.resisVvityhighathighT,improveDCbreakdownstrength)
• SuccessfullypassedqualificaVonaxerCIGRÉ219
• lightningimpulsewithstand±750kV,withsuperimposedDCvoltage±530kV
(UDC=250kV)∓
![Page 48: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/48.jpg)
48
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
RecentlyinserviceorongoingHVDCextr.cablesys.projectsTable7.2.a-HVDCLightTMextrudedcablesystems(aQer[22.7.I-B],courtesyofABB)
(from[PryRL],courtesyofPrysmian)
![Page 49: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/49.jpg)
49
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
GermanNorthSeaOffshoreWindFarmProjects
(From[LW2013].CourtesyofPrysmian)
![Page 50: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/50.jpg)
50
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
InterconnecQonSpain-France320kVDC«INELFE»
(From[LW2013].CourtesyofPrysmian)
![Page 51: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/51.jpg)
(From[LW2013].CourtesyofPrysmian) 51
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
UK:EastWestInterconnector
![Page 52: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/52.jpg)
52
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
UK:NemoLinkØ “NemoLink”:
• 1st400-kVratedXLPE-insulatedHVDCcablesystem• Bipolarlink,1000-MWratedpower
Ø Cablecontractor:JPS,contractawardedin2015,overallprojectvalue≈500M€
Ø Cableroute:• betweenRichboroughEnergyParkinKent(UK)andZeebrugge(Belgium)• 130-kmsubsea• 11.5-kmland
![Page 53: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/53.jpg)
53
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
UK:WesternLinkØ HVDCWesternLinkbetweenScotlandandEngland:
• HVDCbi-polarcablelink• MI-PPLPcableinsulaVon
Ø Cablecontractor:Prysmian,contractawardedin2012,overallcablesystemvalue≈800M€(highestattheVme)
Ø Cableroute:• 400km,mostlysubmarine• ShortlandsecVoninScotland• LongerlandsecVoninEngland-Wales
![Page 54: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/54.jpg)
[I-B]G.MazzanV,M.Marzino]o,ExtrudedCablesforHighVoltageDirectCurrentTransmission:AdvancesinResearchandDevelopment,PowerEngineeringSeries-Wiley-IEEEPress,2013.[4.2.I-B]HighVoltageDirectCurrenttransmission:proventechnologyforpowerexchange,SiemensAG–PowerTransmissionandDistribuVon:HighVoltageDivision,Erlangen,Germany,2003.[5.2.I-B]M.P.Bahrman,B.K.Johnson,“TheABCsofHVDCtransmissiontechnologies”,IEEEPowerandEnergyMagazine,Vol.5,N.2,pp.32-44,March-April2007.[7.2.I-B]A.Orini,M.Marelli,E.Zaccone,“IcollegamenVincavoHVDC:statodell’arteeprospe�vefuture”,AEITWorkshop-HVDCTransmission:Technology,StateoftheArtandPracVcalExperiences,Rome(Italy),November27th2008(inItalian).[10.2.I-B]M.Jeroense,“HVDC,thenextgeneraVonoftransmission.Highlightswithfocusonextrudedcablesystems”,Proc.2008InternaVonalSymposiumonElectricalInsulaVngMaterials(ISEIM2008),pp.10-15,Yokkaichi,Japan,Sept.7th-11th2008.[LW2013]M.Marelli,“AchievementandexperienceinserviceoflonglengthHVDCelectricallinksbyinsulatedpowercables”,LaVnAmericanWorkshop2013,FozdoIguaçu–September6th,2013.[25.2.I-B]R.N.Hampton,“SomeoftheconsideraVonsformaterialsoperaVngunderhigh-voltage,direct-currentstresses”,IEEEElectricalInsula5onMagazine,Vol.24,No.1,pp.5-13,Jan.-Feb.2008.[22.7.I-B]DolWin2–900MWHVDCLighttransmissionTheworld’slargestwindpowergridconnecVon,ABBABGridSystems–HVDC,POW-0075rev.0.[PryRL]Reference_List_HVDC_2016_03_17_rev_01.pdf[GMDC]G.MazzanV,“LifeesVmaVonofHVDCcablesundertheVme-varyingelectro-thermalstressassociatedwithloadcycles”,IEEETrans.PowerDelivery,Vol.30,N.2,pp.931–939,Apr.2015[NEMO]h]p://www.jpowers.co.jp/pr/150608/150608e.pdf. 54
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
REFERENCES
![Page 55: Extruded Cable Systems for HVDC Transmission - · PDF fileExtruded Cable Systems for HVDC Transmission ... Ø OF-PPLP = impregnated with non-viscous oil ⇒ ... uniform compact layer](https://reader034.vdocuments.us/reader034/viewer/2022050807/5ab5d86e7f8b9ab7638d3aca/html5/thumbnails/55.jpg)
55
HubnetColloquium-StrathclydeUniversity,Glasgow,Scotland(UK)-December7th2016
THANKYOUFORYOURATTENTION!