exterior wall systems nfpa 285 - industries.ul.com · exterior wall systems – why do we test? a...

24
UL and the UL logo are trademarks of UL LLC © 2014 Exterior Wall Systems NFPA 285 Presented by: David Hintz Senior Project Engineer

Upload: ngotruc

Post on 27-Sep-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

UL and the UL logo are trademarks of UL LLC © 2014

Exterior Wall Systems –

NFPA 285

Presented by:

David Hintz Senior Project Engineer

Exterior Wall Systems – Why Do We Test?

A broad range of components that are commonly used in exterior

wall construction happen to be very flammable. This can be

catastrophic when they are not protected properly.

• Insulations (foam plastics, batts and

blankets)

• Metal Composite and Aluminum

Composite Cladding (MCM/ACM)

• High Pressure Laminates (HPL)

• Water resistive and Air Barriers

(WRB)

Combustible Exterior

Insulation (Foam Plastic)

Combustible Air/Weather

Barrier over Exterior

Sheathing

Combusible Stud

Cavity Insulation

(Foam Plastic)

Exterior Wall Systems – Why Do We Test?

Torch Building Fire – Dubai

Exterior Wall Systems – Why Do We Test?

Torch Building Fire – Dubai

Exterior Wall Systems – Why Do We Test?

Monte Carlo Casino Fire – Las Vegas,

Exterior Wall Systems – Why Do We Test?

Water Club Tower Fire –

Atlantic City Mermoz Tower – France

Exterior Wall Systems

7

“Fire Hazards of Exterior Wall Assemblies Containing Combustible Components”

- Fire Protection Research Foundation

NFPA 285 – FIRE PROPAGATION

ANSI/NFPA 285 – investigates the ability of a wall

assembly to:

1. Resist flame propagation over the exterior face of the

wall assembly,

2. Resist vertical flame propagation within the combustible

core or within other combustible components from one

story to the next,

3. Resist vertical flame propagation over the interior

surface of the wall assembly from one story to the next,

and

4. Resist lateral flame propagation from the compartment

of fire origin to adjacent compartments or spaces.

NFPA 285 – FIRE PROPAGATION

APPARATUS

• Two-story steel framed test

apparatus with rooms

opening to the front at each

floor.

• Each test room is app. 10 ft. x

10 ft. x 7 ft. high

• Two gas-fired burners

One inside the first story

room (burn room)

One underneath the header

of the first story window

opening

NFPA 285 – FIRE PROPAGATION

TEST PROCEDURE

• Burners are ignited to deliver same gas flows as determined

by calibration procedure. Adjustments are not made to those

gas flows, regardless of sample performance.

• 30 minute test duration.

• First 5 minutes – Interior first

floor room burner only.

• 5 – 30 mins – Interior first floor

room burner and exterior

window burner are in operation.

NFPA 285 – EXAMPLE ASSEMBLY CONSTRUCTION

Step 1 – Stud Construction Step 2 – Exterior Gypsum

and Joint Treatment

NFPA 285 – EXAMPLE ASSEMBLY CONSTRUCTION

Step 2 – Joint Treatment

Complete

Step 3 – Weather Barrier

Installation

NFPA 285 – EXAMPLE ASSEMBLY CONSTRUCTION

Step 3 – Weather Barrier

Install Complete

Step 4 – Exterior Insulation

and Brick Ties

NFPA 285 – EXAMPLE ASSEMBLY CONSTRUCTION

Step 5 – Stud Cavity

Insulation Install

NFPA 285 – EXAMPLE ASSEMBLY CONSTRUCTION

Step 6 – Brick

Veneer

Construction

NFPA 285 – EXAMPLE ASSEMBLY CONSTRUCTION

Step 7 – Test It!

NFPA 285 – Post Test Analysis

Step 8 – Post

Test Analysis

NFPA 285 – FIRE PROPAGATION

CONDITIONS OF ACCEPTANCE

• Temperatures at exterior of wall

must not exceed 1000 F at a

height of 10 ft. above the window

opening

• Exterior flames must not extend

vertically more than 10 ft. above

the window opening

• Exterior flames must not extend

horizontally more than 5 ft. from

the centerline of the window

opening

(red hatched area shows allowable

extents of flame propagation)

Agenda: Exterior Wall Systems – NFPA 285

• Why Do We Test Exterior Wall Assemblies?

• NFPA 285 – Testing and Requirements

• UL’s Certification Program for Exterior Wall

Assemblies & Components

Exterior Wall Systems & Components

20

UL launched two new certification categories also known as

Category Codes (CCN):

Exterior Wall Systems (FWFO)

- All Components within a system design

Exterior Wall System Components (FWFX)

- The System Design (EWS) incorporates all

components and description of components

Where can this be found? UL’s Online Directory and Building

Materials Directory

NFPA 285 – FWFX Components

UL MARK

Product identity: Exterior Wall System Component (FWFX)

The Certification Mark for these products includes the UL

symbol, the words "CERTIFIED" and "SAFETY," the

geographic identifier(s), file number, and the statement:

ANSI/NFPA 285

SYSTEM EWS0001

UL Online Certifications Directory

No charge to access

No passwords

Updated daily

Searchable

Keyword

Manufacturer

UL File Number

Standard used for evaluation

www.ul.com/database

22

Exterior Wall Systems (FWFO)

Contact Us

David Hintz, Senior Project Engineer

PH: (847) 664-1285

E-mail: [email protected]

Dwayne Sloan, Principal Engineer

PH: (919) 549-1676

Email: [email protected]