exchust fan information
TRANSCRIPT
-
8/2/2019 Exchust Fan information
1/52
Jun
20
Centrifugal Roof Downblast Exhaust Fans General Clean Air Light Contaminants
Seismic High Wind Variable Volume
Models G and GB
Performance data now included.
-
8/2/2019 Exchust Fan information
2/52
Contents
Model Comparison 3
Construction Features 4-5
Emergency Smoke Control 6
Seismic 6
High Wind & Hurricane 7
Vari-Green Motor and Controls 8-9
Demand Control Ventilation 9
Roo Curbs, Options, Accessories 10-11
Typical Installations 12-13
Model Number Code 13
PERFORMANCE AND DIMENSIONS:
Models G-060-095 14-17
Models G-097-G203 18-31
GB-071-200 18-32
Models GB-220-540 33-46
SPECIFICATIONS:
Vari-Green Motors and Controls 47
Direct Drive 48
High Wind & Hurricane, Seismic G Fan 49
Belt Drive 50
High Wind & Hurricane,Seismic & Smoke Control GB Fan 51
Quick Build Programs 52
Warranty 52
Models G and GBSpun Aluminum Downblast
Centriugal Roo Exhaust Fans
Codes and CertificationsGreenheck Fan Corporation certiies that the ModelsG and GB fans shown herein are licensed to bear theAMCA Seal. The ratings shown are based on testsand procedures performed in accordance with AMCAPublication 211 and Publication 311 and comply with therequirements o the AMCA Certiied Ratings ProgramThe certified ratings for Models G and GB are shown on
pages 14 - 46
G and GB models are listed or electrical(UL/cUL 705) File no E40001
GB models or Emergency Smoke Control Systems(UL/cUL Listed or 500F (260C) or 4 hours and1,000F (538C) or 15 minutes) File no MH17511
High Wind Certication
Miami-Dade NOA for high wind and hurricane zones
Seismic Certication
OSHPD No. 0148-10 - Ofce of Statewide Health
Planning and Development (Caliornia)
IBC 2006 and 2009 - International Building Code
*UL/cUL is optional
and must be specified
-
8/2/2019 Exchust Fan information
3/52
Models G and GBSpun Aluminum Downblast
Centriugal Roo Exhaust Fans
Greenheck models G and GB centriugal rooexhaust provide the industrys best perormance anddurability for general clean air applications where air is
discharged downward, toward the roof surface.
Broadest perormance in the industry, up to3.25 in. wg (810 Pa) and 45,000 cm (76,500 m3/hr)
Most advanced motor cooling o any an in its class
Performance as cataloged is assured. All fan sizes
are tested in our AMCA Accredited Laboratory, andall models are licensed to bear the AMCA Sound
and Air Perormance seals
UL Listed or electrical
Greenheck subjects these products to extensive lietesting, assuring you that the fans will provide years
o reliable perormance
Direct Drive, G
Use for short and/or low resistance ductwork
Belt Drive, GB
For average length and/or average
resistance ductwork High volume/average pressure
High Pressure, GB-HP and G-HP
For long and/or high resistance ductwork
Low volume/high pressure
3
Model Comparison
Model
Location Mounting Airow ApplicationDriveType
ImpellerType
Performance
RelativeCost
Outdoor
Indoor
RoofCurb
Base/Floor
Hanging
Wall
CeilingMounted
Exhaust
Supply
Reversible
Recirculate
General/CleanAir
ContaminatedAir
SparkResistant
Grease(UL762)
SmokeControl(UL)**
HighWind(150mph)*
ContinuousHighTemp
(above200F)
Belt
Direct
Centrifugal
Propeller/Axial
MixedFlow
MaximumVolume
(cfm)
MaximumStatic
Pressure
(in.wg)
G 6,308 15 $
GB 44,700 325 $
*High wind limited to sizes 300 and smaller
**Smoke Control available on models: 101, 101HP, 121, 131, 141, 141HP, 161, 161HP, 200, 240, 300, 360, 420 and 480
-
8/2/2019 Exchust Fan information
4/52
Construction FeaturesModels G and GB
4
Standard Construction Features
Wheel
An aluminum, backward-inclined, non-overloading centrifugal wheel is utilized togenerate high-eiciency and minimal sound Wheel cones are careully matched tothe venturi for maximum efficiency. Each wheel is robotically welded and staticallyand dynamically balanced or long lie and quiet operation
DisconnectSwitch
NEMA-1 switch is factory mounted and wiring is provided from the motor as standard(other switches are available). All wiring and electrical components comply with theNational Electrical Code (NEC) and are either UL Listed or Recognized.
Fan ShatPrecisely sized, ground and polished so the first critical speed is at least 25% overthe maximum operating speed. Where the shaft makes contact with bearings, tighttolerances result in longer bearing lie
Bearings100% factory tested and designed specifically for air handling applications with aminimum L10 lie in excess o 100,000 hours (L50 lie o 500,000 hours)
Motor Careully matched to the an load and is mounted out o the airstream
Motor CoverConstructed of aluminum, machine-punched, and attached with fasteners that provideor easy removal and access to motor compartment and drive assembly
Motor CoolingCooling fins located on top of the fan wheel draw outside air through a large spacebetween the fan shroud and the motor cover directly into the motor compartment.Positive motor cooling with fresh air results in maximum motor life.
Liting Points Various lifting points are located on the drive frame and bearing plate (on select sizes).
True VibrationIsolation
Vibration isolators, with no metal-to-metal contact, support the drive assembly andwheel for long life and quiet operation.
Drive AssemblyBelts, pulleys, and keys are oversized 150% of driven horsepower. Machined castpulleys are adjustable or inal system balancing Belts are static-ree and oil-resistant
Lower WindbandHeavy-gauge aluminum with formed edges for added strength and providesweather resistance.
Curb CapCurb cap (with integral deep spun venturi) is constructed of aluminum and is one-piece
for a weather-tight fit.Internal ConduitChase
A large diameter conduit for installing electrical wiring through the curb cap into themotor compartment
Nameplate Permanent stamped aluminum plate or exact model and serial number identiication
Galvanized
BirdscreenRigid wire protects the fan discharge from birds and small objects.
Fan ShroudOne-piece, heavy-gauge aluminum with a rolled bead for extra strength directsexhaust air downward.
Mounting Holes Curb cap has prepunched mounting holes to ensure correct attachment to the roo
6
1
2
3
4
5
7
8
9
10
11
12
13
14
15
16
17
High Wind Construction Features
Internal SupportsHeavy-gauge supports and bracing are added for additional strength to withstanda wind of 150 mph (75 ps)
ReinorcedWind Band
High wind fans include additional reinforcement for maximum strength.
Roo Curb(page 10)
High wind load fans are certified for use with Greenheck model SD, SDP, GPF orequivalent in high wing applications. Roof curbs ship separate for field installationwith attachment details provided.
18
19
-
8/2/2019 Exchust Fan information
5/525
Construction FeaturesModels G and GB
8
8
DRIVE FRAME(BELT DRIVE)
MODEL GDIRECT DRIVE
15
12
11
7
6
5
1
14
18
17
16
9
8
4
3
2
19
10
MODEL GBBELT DRIVE
13
-
8/2/2019 Exchust Fan information
6/52
With changes in building codes and standards more equipment isbeing required to be seismically certifed in areas o the country not
commonly thought of as being in seismically active zones.The International Building Code (IBC) is designed to provide modelcode regulations that saeguard public health and saety in all UScommunities This code is intended to improve the perormance anddesign o non-structural systems subject to seismic events
The State o Caliornia, one o the most active seismic areas in theUnited States, has the Ofce of Statewide Health Planning and
Development (OSHPD) to regulate the design and construction ohealthcare acilities to ensure they are sae and
capable o providing services to the public atera seismic event. OSHPD developed their own
unique certifcation process to incorporatethe IBC and ASCE testing standards toensure equipment remains operable ater aseismic event
ApplicationsG and GB models
6
SeismicTesting Criteria
All Greenheck seismically certiied models have been tested using the most severe seismic event thatis ound on the Spectral Response Map per IBC Figures 16135 (1-2) Our testing is perormed underthe worst case scenario using the highest mapped seismic load, highest level occupancy category,worst case site class, and highest code mandated importance factor, thereby allowing Greenhecks
seismically certified fans to be used anywhere in the United States under any conditions
Caliornia OSHPD
Test Protocols
The California Office of Statewide Health Planning and Development (OSHPD) requires all certifiedmodels be shake table tested in accordance with ICC ES AC-156, in which the fans are physically
subjected to the same or greater forces than they will see during a seismic event. SubjectingGreenheck model G and GB fans to this type of testing ensures the fans will operate withoutproblems ater a seismic event
OSHPD Certiication
No 0148-10The OSHPD certification numbers and supporting documents can be viewed on OSHPDs
website ensuring that the fan has been subjected to and passed rigorous testing standards.
State LicensedPE Calculations
When using the fans in applications which are not covered by California OSHPD standards,
Greenheck models G and GB have been certiied by a third party engineering irm to IBC 2006, 2009and ASCE 7-05 standards These engineers hold proessional engineering (PE) licenses in all 50states, so no matter where your job is located, you are backed by a P.E. signature for your state.
CertiiedIndependentThird-Party Testing
All Greenheck seismically certiied an models have gone through extensive testing proceduresGreenheck models G and GB have been certiied to IBC 2006, 2009, ASCE 7-05 and CaliorniaOSHPD standards through both engineering calculations and shake table testing o all models byindependent third party engineering irms
Seismic - G and GB
Protocols designed for seismic standards:
When you buy a Greenheckmodel GB with the smoke
control option, you receive a
fan with the industrys bestperormance and durability orsmoke control applications (asound in emergency smokecontrol systems)
UL/cUL Listed or 500F (260C) or 4 hours and1,000F (538C) or 15 minutes
Half the weight of traditional smoke control fans,
ideal choice or roo load concerns Low profile, height is less than half of traditional
smoke control ans, maximum o 5212 inches(1334 mm) rom curb cap to top o an
Multiple applications, capable o exhaustinggeneral clean air and satisying emergency smokecontrol regulations
Emergency Smoke Control - GB
GB smoke control models are:101, 101-HP, 121, 131, 141, 141-HP,161, 161-HP, 200, 240, 300, 360,420, 480
-
8/2/2019 Exchust Fan information
7/527
High Wind and Hurricane - G and GBGreenheck is leading the High Wind Standard or roo top ans andventilators. Forceful winds and wind-borne debris are the cause of
most hurricane damage. Hurricane winds start at 75 mph. At speeds
over 150 mph, wind can exert a force of 75 pounds per square foot
of pressure or over 900 pounds on a fan and curb. Forceful winds arenot the only problem, wind-borne debris can also cause detrimental
effects to objects and structures. High winds and extreme forces
are the cause of most storm damage. By analyzing calculations,
computer simulations, actual testing, and other standardsGreenheck developed the High Wind Standard
StructuralPerormance Load
A static load that is 15 times the design load (915 pounds per square oot o pressure) is appliedboth positively and negatively to simulate wind force loads in each direction. Structural Performanceper Dade County Protocol TAS-202 (ASTM-E330)
Miami-Dade CountyTest Protocols
Greenheck worked with Miami-Dade County to outline a High Velocity Hurricane Zone standard forrooftop fans. Greenheck model USGF was the first rooftop fan certified and approved by the Miami-
Dade Building Code Compliance oice and Texas Department o Insurance or use in hurricanezones. Models G and GB have been certified by an independent third party to the ASTM E-330 Static
Pressure Dierence Standard, Florida Building Code Test Protocol TAS-201 (large missile impact),202 (static pressure dierence) and 203 (cyclic pressure) Static Pressure Dierence
Miami-Dade NOANumbers
The certifications can be viewed on the Miami-Dade County website under the NOA numbers listedbelow. Models G and GB are the first downblast aluminum fans in the industry that have received
a Miami-Dade NOA for high wind (150 mph) and hurricane zones. Miami-Dade NOA 09-0624.09 for
models G and GB
Florida ProductApproval
Florida Product Approval ensures that products which have been approved can be used anywhere in
the State of Florida which are not governed by the Miami-Dade County high wind regulations. More
information can be found on the Florida Building Code website. Florida Product Approval FL13225.1
or models G and GB
State LicensedPE Calculations
Structural calculations perormed by a licensed Proessional Engineer (PE) on models G and GBinclude Finite Element Analysis (FEA) and a stamped PE report o the ans compliance to ASCE7-02 Minimum Design Loads or Buildings and Other Structures Standard and the Florida BuildingCode The ASCE 7-02 Standard meets the IBC, Florida and Miami-Dade codes The models havebeen proven to withstand winds in excess of 150 mph (75 psf).
Computational FluidDynamics (CFD)
All Greenheck high wind models have been analyzed using Computational Fluid Dynamics (CFD).CFD is computer software designed to simulate the flow of high speed (150 mph) winds over the
surface of objects. The software records the force profile exerted on the fan so it can be utilized
in Finite Element Analysis (FEA)
Finite ElementAnalysis (FEA)
Utilizing the results from CFD analysis, Greenheck can accurately predict the stress, strain,
and deflection resulting from high wind loads. Greenheck high wind units have been proven
to withstand 150 mph winds through Finite Element Analysis utilizing CFD results.
Protocols designedto protect against wind bornedebris and severe wind loads:
U.S. continentaveraged
tornado requency.
Atlantic, Gul and Pacifc history o major hurricane tracks.
ApplicationsG and GB models
-
8/2/2019 Exchust Fan information
8/52
Vari-Green Motor - Model G
Greenhecks electronically commutatedVari-Green (VG) motor combines motortechnology, controllability and energy-
efciency into one single low maintenance unit andis the industrys frst ully controllable motor Whencombined with Greenhecks G fans all the CFM
and static pressureranges o a belt drivecan be attained with
the benefts o adirect drive
The Vari-Greenmotor is available in115 volt single phasehorsepower; 1/4,
1/2, 3/4 and50/60 Hz power.
Benets
Operates on AC power thats converted to DC
providing a more efcient motor operation ascompared to an AC operation
The motor can attain up to 85% efciency and
reduce energy consumption
Watt savings of 30-70% depending on RPM.
Note:As motor speed is turned down, efciencystays constant as compared to an AC motor that
decreases dramatically.
Operates cooler than a standard AC motorA cooler motor has longer motor lie and reducesenergy consumption
80% usable RPM turndown vs. 30%,see chart
G fans with Vari-Green motors can provide all
the CFM and static pressure ranges o acomparable belt drive
Maintenance costs are reduced as there areno belts or bearings to replace and no pulleysto adjust
8
Options
$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
100
80
60
40
20
0%
Time of Day
HypotheticalVariable Volume - Load Shape
%o
fOperation
Series 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
100
80
60
40
20
0%
Time of Day
Constant Volume - Load Shape
%o
fOperation
Series 2
Demand controlled ventilation oers signiicant energy savings by
exhausting only the necessary amount o air throughout the day.
Variable VolumeVariable volume or demand ventilation oerssignifcant energy savings by only exhausting airwhen necessary throughout a day. This type of
application can greatly reduce the operating costsassociated with air conditioning and heating. Either
a Vari-Green motor or standard VFD compatiblemotor can function within a variable volume system
and help reduce energy consumption
600
500
400
300
200
100
0
0 350
50% 75% 100%
1750FAN SPEED (RPM)
INPUT
POWER(WATTS)
EnergySavings
G-123with PSC
Not recommended
GB-123Single Phase*
G-123 with
* GB is a belt driven fan
Length of each curve indicates the practicalturndown range. Data is for 1/2 hp motorswith load of 0.35 BHP at full speed.
E
S
The length o each curve indicates the practical turndown range.Data is or 1/2 hp motors with load o 0.35 Bhp at ull speed
Motor Turndown Comparison
Features
1 Vari-Green dial on motor controlA potentiometer (dial on motor control) ismounted right on the motor or easy speedadjustment or system balance Simply turn adial instead o adjusting belts and pulleys
2 Control wire inputsInputs provide a 0-10V DC signal to the motorrom Building Automated System sensors or othercontrols to adjust motor speed
Direct drive fans are often preferred where
maintenance access is difcult
The Vari-Green motor reduces noise and vibrationas well as providing solutions for variable volume
system balancing
1
2
-
8/2/2019 Exchust Fan information
9/529
Options
Fan Price VFD Price
Example: Initial Cost Comparison
Belt Drive vs. Direct Drive Vari-Green
$0 100 200 300 400 500 600 700
GB-121
G-123-VG
The diagram shows how the overall cost o a an with a directdrive Vari-Green motor is less than the cost to purchase a beltdrive and add a VFD to it.
Demand controlled systems reduce the energyconsumed by decreasing the speed o the an andenergy used by the motor The system controlswill lessen the amount of conditioned air that is
exhausted, urther reducing the total operating costs
A 0-10 VDC control signal is easily used inconjunction with:
BAS - Building Automation System
GreenVent System Controls - or constantpressure
CO2 Sensors - Monitors carbon dioxide levels
VOC Sensors - Monitors a range o volatileorganic compounds
Motion Detectors - Monitors occupancy
For additional inormation reer to the Vari-Green
Motor brochure.
$2,000-
1,750-
1,500-
1,250-
1,000-
750-
500-250-
$-
Variable Volume vs. Constant Volume
Variable Volume Constant Volume
Heating Cost ($/yr) Cooling Cost ($/yr) Fan Operating Cost
Example o
potential saving
based on a
northeast city in
the USA using a
GreenVent System.
Example
Cost/Savings
Comparisons
Demand Control Ventilationor multi-story buildings
Applications requiring constant pressurecontrol or variable volume as used inmulti-storied buildings such as hotels,multi-amily complexes, institutional
acilities, and high rise commercial buildings,may utilize G fans with Vari-Green motor and
Vari-Green control
The Vari-Green constant pressure controlis preprogrammed and easy to install orapplications that includeventing dryers,bathrooms, residential type kitchen space orindustrial process exhaust
Reer to the GreenVent Systems brochure ormore detailed inormation on beneits and
energy savings.
LEED information
Greenheck became one o the frstmanuacturers in the Air Movement andControl industry to join the LEED/greenmovement when they joined the United States
Green Building Council (USGBC) in 2005Greenheck has been actively researchingqualifcation requirements or our products tomeet LEED credits and prerequisites
The Vari-Green motor signifcantlyhelps qualifcation eorts or theEnergy and Atmosphere credits and
prerequisites specifcally credit one,Optimize Energy Performance and prerequisite
two, Minimum Energy Performance.
Vari-Green Controls
Remote mounted dial wall mounted dial allowsan to be controlled at point o use and includesa transducer
Two-speed control provides the ability topreset a high and low at the fan and control with a
timed position switch at the point of use.
Transformer reduces 115V power to 24V power
Constant pressure maintains negative pressure(-1.0 wg to = 1.0 wg) for applications such as
bathrooms, dryers, ilters, etc
-
8/2/2019 Exchust Fan information
10/52
Options and Accessories
10
Roo Curbs
Preabricated roo curbs reduce installation timeand costs by ensuring compatibility between
the an, the curb and roo opening All curbs areinsulated with fiberglass. A wide variety of roof
curbs are available, including: langed, pitched andsound-absorbing
Hinged Curb Cap with Cables (Field Installed)
Mounted to the curb cap, allows entire fan to tilt
away from curb for access to wheel and ductwork.
Includes restraint cables
Hinged Base(Factory Mounted)
Allows for easy
maintenance Hinge andrestraining cables areactory mounted to asubbase attached directlyto curb without additional
height added
Curb Seal
Rubber seal between fan and curb to assure proper
sealing when attached to a curb.
Curb Extensions
Extensions raisethe an dischargeabove the roolineand provide anaccessible mountinglocation or dampers Insect screenbases, constructed with a removable fine mesh, are
recommended for applications where insect entry
must be prevented
High Wind and Severe Duty Roo Curbs
Provided as an option with models G and GB. The
severe-duty roo curb models can ship separatelyto allow for final finishing of the roof prior to the fan
arrival and installation
Model GPF This roo curb is used on an modelsG/GB and specifically designed for high windapplications up to 75 ps Curbs are minimum18 gauge construction in a standard height o12 inches (305 mm), with fully-welded straight sidesand a 5-inch lashing lange GPF is available up to24 inches (460 mm) in height to meet greater heightrequirements
Models SD and SDP These severe-duty curbsor an models G and GB are speciically designedfor high wind applications up to 150 mph, maximum
design load o 130 ps Model SD is or use onlat roos and model SDP or pitched roos Theyare attached directly to the building structure with
extremely high structural design load requirementsThe severe duty curbs are 12 gauge coated steelwith a 134-inch lip on the top and a 4-inch lange onthe bottom Available heights include 1224 inchesHeights greater than 18 inches are reinorced in theinterior with 12 gauge x 2-inch angles.
Mounting details or the roo curb to the roosubstrate and the fan to the curb are included with
each model G and GB installation manualFor additional inormation reer to the Greenheck
High Wind brochure.
Tie-Down PointsFour brackets located onthe shroud or securingthe fan in high wind
applications Cables andanchors by others
-
8/2/2019 Exchust Fan information
11/521
Speed Controllers orStandard Motors
Available for use with shaded
pole and permanent splitcapacitor (PSC) open motorson model G ans They providean economical means o systembalancing with direct drive fans.
Disconnect Switches
A wide selection of NEMA rated
switches are available for positive
electrical shuto and saety,including: dust-tight, rainproo,and corrosion-resistantSwitches may be internally
or externally mounted
Dampers
Designed to preventoutside air rom enteringback into the buildingwhen fan is off. Includes
gravity and motorized
dampers. Damper sizes
are shown on each
perormance data page
Birdscreen
Galvanized mesh is standard,
optional aluminum or stainlesssteel rigid wire are also available.
Options and Accessories
G and GB models are Listed or electrical (UL/cUL 705)File no E40001
GB models or Emergency Smoke Control Systems
(UL/cUL Listed or 500F (260C) or 4 hours and1,000F (538C) or 15 minutes) File no MH17511
Note: UL/cUL is optional and must be speciied.
Coatings
A wide variety of coatings and colors are available.
Greenheck coatings and resistance charts can beound in the Perormance Coatings Commercialand Industrial Fans catalog and in our Product
Application GuidePerormance Coatings orVentilation Products
Primer is applied at the factory to allowor fnal fnish in the feld
Permatector is our standard coatingTypically used or applications thatrequire corrosion resistance in indoorand outdoor environments
Hi-Pro Polyester is resistant to saltwater, chemical fumes and moisture
in more corrosive atmospheres
Typically used or applications thatrequire superior chemical resistance,excellent abrasion and outdoor UVprotection This coating exceedsprotective qualities o Air DriedHeresite and Air Dry Phenolic
Baked Enamel Decorative Coatingsare heat cured enamels appliedeither as wet paints or electrostatic
powders. Customers can choose from
16 standard decorative colors or colormatch any color
PERMATECTORTM
HI-PRO
POLYESTER
PRIMER
-
8/2/2019 Exchust Fan information
12/5212
Typical InstallationsModels G and GB
Note: The typical installations shown are recommendations
based on national codes. Local authority may supersede these
recommendations.
General Clean Air(igure 1)
Models G and GB exhaust ans are designed tomeet the needs o general clean air applicationsTests were conducted to assure safe, rugged and
reliable ans
Due to the varying types o airstreams encounteredin commercial ventilation, system designers mustbe aware of national, state, and local codes and
guidelines governing these installations Local codeauthorities should be consulted beore proceedingwith any ventilation project.
When rooing materials extend to the top o thecurb, roo curbs should be 112 inches (34 inch oneach side) less than the unit curb cap to allow
or rooing and lashing
For recommended duct size, damper size, and
roo opening dimensions, reer to theperormance data pages (starting on t 14)
Installation must include a means or inspecting,cleaning and servicing the exhaust an
High Wind, Hurricane and Seismic (igure 2)
Rooing materials can extend to the top o thecurb, roo curbs should be 1 inch(25 mm) total,or 12 inch (13 mm) on each side, less than the unitcurb cap to allow for roofing and flashing.
RecommendedDuct and
Damper Size
RecommendedRoof Opening
11/4in.(32 mm)
3/4 in.(19 mm)
Factory Wiredfrom Motor toDisconnect
Wiring by
Others
8 or 12 in.(203 or 305 mm)
Damper
11/4in.(32 mm)
Recommended
Duct and
Damper Size
Recommended
Roof Opening
11/4in. (32 mm)
1/2 in. (13 mm)
Wiring by
Others
8 - 24 in.
(203 - 610 mm)
GPF or SD Curb
Damper
11/4in. (32 mm)
1/4 in. (6 mm)
Fastener
4 in. (102 mm)
From Curb Edge
Wheel Rotation
Direction of rotation is very critical. Rotation in the wrong direction will result
in excessive horsepower, possible motor burnout, and increased noise levels.
Check rotation by energizing the unit only momentarily. The rotation should bethe same as the rotation decals afxed to the unit and is clockwise when viewed
rom the top o the unit
Clockwise
igure 1
igure 2
-
8/2/2019 Exchust Fan information
13/521
VG = Vari-Green(Direct Drive only)
Motor HP(Belt Drive only)6 = 1/6 10 = 1 50 = 54 = 1/4 15 = 1 75 = 73 = 1/3 20 = 2 100 = 105 = 1/2 30 = 3 150 = 157 = 3/4
Motor RPM(Direct Drive only)A = 1725 D = 1550B = 1140 E = 1050C = 860 G = 1300
International(See CAPS or perormance)
K= 950 RPM J = 1475 RPM
Fan Inlet Connections
In order to assure proper an perormance, cautionmust be exercised in an placement and connectionto the ventilation system Obstructions, transitions,poorly designed elbows, improperly selecteddampers, etc, can cause reduced perormance,excessive noise, and increased mechanical stressFor perormance to be as published, the systemmust provide uniform and stable airow into the fan.
Provide uniform airflow at fan inlet to assure
optimum perormance
Provide uniform airflow at fan inlet and
through the damper to assure optimumperormance
Dampers must open fully. Use motorized
dampers in low airflow applications to
reduce losses
Avoid sharp turns or entrance conditionswhich cause uneven flow. Use turning vanes
in elbows to reduce adverse effects.
Typical InstallationsModels G and GB
Good
Good
PoorPoor
A
C D
B
Model Number Code
The model number code system is designed to completely identiy the an The correct code lettersmust be speciied to designate belt or direct drive The remainder o the model code is determinedby the size and performance.
A
C
D
B
Fan Size
060 through 540
Wheel Pressure LevelHP - High Pressure
GB - 240 HP - VG/5/A - X
ConigurationG - Direct Drive
GB - Belt Drive
X = UL 705F = UL 762
Smoke Control Systems
-
8/2/2019 Exchust Fan information
14/52
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
3Volume (m/hr )
RPM (Direct)
Density 0.075 lb/ft3
Density 1.2 kg/m3
14
Roof Downblast - ExhaustDirect DriveG-060 G-065
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Damper Size = 8 x 8 (203 x 203)Roof Opening = 10 x 10 (267 x 267)
Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 15 lbs. (7 kg)
All dimensions in inches (millimeters) *May be greater depending on motor^Weight shown is largest cataloged Open Drip-Proof motor.
MotorHP
FanRPM
Static Pressure in Inches wg
0 005 01 0125 015 02 025 03 0375 04060
E-1/200 1050CFM 138 116 90 73 53BHP 000 000 001 001 001
Sones 17 17 17 17 17
G-1/100 1300CFM 170 153 135 125 113 85BHP 001 001 001 001 001 001
Sones 29 28 28 27 27 26
D-1/60 1550CFM 203 188 173 166 158 140 120 92BHP 001 001 001 001 002 002 002 02
Sones 42 39 38 38 38 37 37 36065
E-1/100 1050CFM 187 161 130 110 87BHP 001 001 001 001 001
Sones 22 21 19 18 17
G-1/60 1300CFM 231 211 189 178 163 130 92BHP 001 001 001 001 001 001 001
Sones 32 31 30 29 29 28 27
D-1/30 1550CFM 276 259 241 232 223 201 176 145 96BHP 002 002 002 002 002 002 002 002 002
Sones 49 46 45 45 44 43 43 41 40
E-1050-RPM G-1300-RPM D-1550-RPM
134(44)
1938(492)
*1218(308)
17(432)
3 (76)
Direct Drive RPM
-
8/2/2019 Exchust Fan information
15/521
MotorHP
FanRPM
Static Pressure in Inches wg
0 005 01 0125 015 02 025 03 0375 04070
E-1/100 1050CFM 253 226 195 179 152BHP 001 001 001 001 001
Sones 27 21 17 15 12
G-1/60 1300CFM 314 292 269 257 244 214 171BHP 001 001 002 002 002 002 002
Sones 41 37 34 33 32 29 26
D-1/30 1550
CFM 374 356 337 327 317 297 274 244 190BHP 002 002 002 003 003 003 003 003 003
Sones 56 54 52 52 51 49 47 45 41075
E-1/80 1050CFM 297 260 222 200 176BHP 001 001 001 001 001
Sones 36 31 29 28 26
G-1/50 1300CFM 367 338 309 293 277 241 195BHP 002 002 002 002 002 002 002
Sones 41 39 37 37 37 36 35
D-1/25 1550CFM 438 413 389 377 364 337 309 277 214BHP 003 003 03 004 004 004 004 004 003
Sones 61 58 56 54 53 51 49 49 48
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
3Volume (m/hr )
RPM (Direct)
Density 0.075 lb/ft3
Density 1.2 kg/m3
Damper Size = 8 x 8 (203 x 203)Roof Opening = 10 x 10 (267 x 267)
Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 15 lbs. (7 kg)
All dimensions in inches (millimeters) *May be greater depending on motor^Weight shown is largest cataloged Open Drip-Proof motor.
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Roof Downblast - ExhaustDirect DriveG-070 G-075
E-1050-RPM G-1300-RPM D-1550-RPM
134(44)
1938(492)
*1218(308)
17(432)
3 (76)
Direct Drive RPM
-
8/2/2019 Exchust Fan information
16/52
0 100 200 300 400 500 600 700 800 900 1000
0
20
40
60
80
100
120
140
160
180
200
220
0 100 200 300 400 500 6000.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
085-E
085-G
085-D
085-VG
080-VG
080-D
080-G
080-E
RPM (Direct Drive)
RPM (Vari Green)
Density 0.075 lb/ft3
StaticPressure(in.wg)
Volume (cfm)
m3/hr
StaticPressure(Pa)
Volume ( )
DO
NOT
SELECTTOTHELEFT
OFTHIS
SY
STEM
CURVE
Density 1.2 kg/m3
16
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Damper Size = 10 x 10 (254 x 254)Roof Opening = 12 x 12 (318 x 318)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 19 lbs. (9 kg)
All dimensions in inches (millimeters) *May be greater depending on motor^Weight shown is largest cataloged Open Drip-Proof motor.
Roof Downblast - ExhaustDirect DriveG-080 G-085
DirectDrive
MotorHP
FanRPM
Static Pressure in Inches wg
0 01 0125 015 02 025 03 0375 05 0625080
E-1/40 1050CFM 335 268 249 230 189 134BHP 001 002 002 002 002 002
Sones 38 37 36 37 39 42
G-1/30 1300CFM 415 361 348 333 303 272 239 174BHP 002 003 003 003 003 003 003 003
Sones 54 54 54 54 54 55 56 59
D-1/20 1550CFM 495 450 439 427 404 379 354 314 237BHP 004 004 004 005 005 005 005 006 006
Sones 73 73 73 73 73 72 73 73 76
1725CFM 551 511 501 490 469 449 426 392 332 260BHP 005 006 006 006 006 007 007 007 008 008
Sones 91 91 91 91 9 89 89 89 91 94085
E-1/40 1050CFM 398 326 307 286 240 179BHP 001 002 002 002 002 002
Sones 4 39 39 39 41 43
G-1/30 1300CFM 493 436 420 405 375 340 302 233BHP 002 003 003 003 003 004 004 004
Sones 55 53 53 53 53 53 54 55
D-1/20 1550CFM 588 541 528 515 490 464 439 394 308 168BHP 004 004 005 005 005 005 006 006 006 006
Sones 76 74 74 74 74 74 74 74 76 81
1725CFM 654 612 602 590 567 544 521 486 419 340BHP 005 006 006 006 007 007 007 008 008 009
Sones 95 94 94 93 93 93 93 93 94 94
E-1050-RPM G-1300-RPM D-1550-RPM VG-1725-RPM
VG - Vari-Green is a direct drive brushless DC motor.
134(44)
2134(552)
*1458(371)
17(432)
4 (102)
Direct Drive RPM
VG-1/4
VG-1/4
-
8/2/2019 Exchust Fan information
17/52
0 500 1000 1500 2000
0
50
100
150
200
0 200 400 600 800 1000 12000.0
0.2
0.4
0.6
0.8
1.0
095-E
095-G
095-D
095-VG090-VG
090-D
090-G
090-E
RPM
RPM (Vari Green)
Density 0.075 lb/ft3
StaticPressure(in.
wg)
Volume (cfm)
Volume ( )
Static
Pressure(
Pa)
m3/hr
DON
OTSELE
CT
TOTH
ELEFT
OFTHIS
SYSTEM
CU
RVE
Density 1.2 kg/m3
1
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
DirectDrive
MotorHP
FanRPM
Static Pressure in Inches wg
0 01 0125 015 02 025 03 0375 05 0625090
E-1/40 1050CFM 520 441 420 398 351 293BHP 001 002 002 002 002 002
Sones 4 39 39 4 41 42
G-1/25 1300CFM 644 580 565 549 515 478 440 373BHP 003 003 004 004 004 004 004 005
Sones 54 54 54 54 54 55 55 56
D-1/15 1550CFM 768 714 701 688 662 633 605 557 473 338BHP 005 005 006 006 006 006 007 007 008 007
Sones 76 75 75 75 75 74 74 74 74 78
1725CFM 855 806 794 782 759 735 709 671 600 522BHP 006 007 007 008 008 008 009 009 010 011
Sones 97 95 95 95 95 94 94 92 91 91095
E-1/30 1050CFM 717 606 570 534 468 389 290BHP 003 003 004 004 004 004 003
Sones 54 45 45 45 44 45 46
G-1/12 1300CFM 888 802 780 754 695 640 586 493 184BHP 006 006 006 006 007 007 007 007 005
Sones 76 68 67 66 65 64 64 64 68
D-1/8 1550CFM 1059 987 969 950 912 863 814 745 623 474BHP 010 010 010 011 011 011 011 012 012 011
Sones 96 94 93 92 9 88 87 87 87 87
1725CFM 1179 1114 1098 1081 1048 1013 969 903 800 688BHP 013 014 014 014 015 015 015 016 016 016
Sones 114 114 114 115 114 112 11 109 113 113
E-1050-RPM G-1300-RPM D-1550-RPM VG-1725-RPM
VG - Vari-Green is a direct drive brushless DC motor.
Damper Size = 10 x 10 (254 x 254)Roof Opening = 12 x 12 (318 x 318)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 22 lbs. (10 kg)
All dimensions in inches (millimeters) *May be greater depending on motor^Weight shown is largest cataloged Open Drip-Proof motor.
Roof Downblast - ExhaustDirect DriveG-090 G-095
134(44)
2134(552)
*1458(371)
17(432)
4 (102)
Direct Drive RPM
VG-1/4
VG-1/4
-
8/2/2019 Exchust Fan information
18/52
DONOT
SELECTT
OTHELEFT
OF
THIS
SYSTEMCU
RVE
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
3Volume (m/hr )
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
18
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Motor HP FanRPM
Static Pressure in Inches wg
Belt Direct 0 0125 025 0375 05 0625 075 0875 1 1125071 097
1/6
or
1/8
VG-Var
i-GreenisadirectdrivebrushlessDCmotor.
720CFM 157 107BHP 001 001
Sones 18 20
790CFM 172 128 70BHP 001 001 001
Sones 23 23 22
C-1/8 860CFM 187 148 101BHP 002 002 002
Sones 28 27 27
930CFM 203 166 124BHP 002 002 002
Sones 33 34 32
1000CFM 218 184 146 100BHP 003 003 003 002
Sones 39 40 39 36
1070CFM 233 202 167 130BHP 003 003 003 003
Sones 46 47 45 42
B-1/6 1140CFM 248 220 187 152 109BHP 004 004 004 004 003
Sones 53 54 51 49 47
1285CFM
280 255 228 197 166 127BHP 006 006 006 005 005 005Sones 68 67 66 63 60 59
1435CFM 313 292 265 240 212 185 151BHP 008 008 008 008 008 007 007
Sones 80 80 79 76 73 71 69
1580CFM 344 324 302 281 255 230 205 177 140BHP 010 010 010 010 010 010 010 009 009
Sones 95 95 94 91 88 85 83 81 79
A-1/4 1725CFM 376 356 339 316 297 273 250 227 205 171BHP 013 013 013 013 013 013 013 013 012 012
Sones 113 112 112 108 105 102 99 97 95 93
VG-1/4
C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM
Roof Downblast ExhaustBelt & Direct DriveGB-071 G-097
Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 54/60 lbs. (24/27 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
MAXIMUM BHP AT A GIVEN RPM = (RPM/3371)3
MAXIMUM RPM - GB-071=1710, G-097=1725TIP SPEED (ft/min) = RPM x 2.929
MAXIMUM MOTOR FRAME SIZE = 56
134(44)
2438(619)
438(111)
*2334(603)
19(483)
Direct Drive RPM
-
8/2/2019 Exchust Fan information
19/52
DONOT
SELECT
TO
THE
LEFT
OFTHIS
SYSTEM
CURVE
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
3Volume (m/hr )
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
1
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Roof Downblast ExhaustBelt & Direct DriveGB-081 G-098
Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)
Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 54/60 lbs. (24/27 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
134(44)
2438(619)
438 (111)
*2334(603)
19(483)
Motor HP FanRPM
Static Pressure in Inches wg
Belt Direct 0 0125 025 0375 05 0625 075 0875 1 1125081 098
1/6
VG-Vari-GreenisadirectdrivebrushlessDCmotor.
720CFM 361 272BHP 001 001
Sones 30 27
790CFM 396 315 181BHP 002 002 002
Sones 35 32 3
C-1/8 860CFM 431 358 261BHP 002 002 002
Sones 40 37 34
930CFM 466 399 323BHP 003 003 003
Sones 46 44 40
1000CFM 501 439 372 259BHP 003 004 004 004
Sones 53 51 47 44
1070CFM 536 478 416 338BHP 004 004 005 005
Sones 59 58 54 50
B-1/6 1140CFM 571 517 460 396 283BHP 005 005 006 006 005
Sones 66 65 61 57 55
1315CFM 659 612 564 513 456 362BHP 008 008 008 009 009 008
Sones 83 81 78 74 70 69
1490CFM 746 706 663 621 574 525 452 353BHP 011 012 012 012 012 012 012 011
Sones 101 99 98 93 89 86 85 84
1670CFM 836 800 763 725 686 645 603 550 466 377BHP 016 016 016 017 017 017 017 018 017 016
Sones 120 119 117 114 110 107 104 101 100 99
1/4 A-1/4 1725CFM 864 829 793 756 719 679 640 592 527 441BHP 017 018 018 018 019 019 019 019 019 018
Sones 127 125 123 121 117 114 111 108 106 105
MAXIMUM BHP AT A GIVEN RPM = (RPM/2985)3
MAXIMUM RPM - GB-081=1710, G-098=1725TIP SPEED (ft/min) = RPM x 2.929
MAXIMUM MOTOR FRAME SIZE = 56
C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM
VG-1/4
Direct Drive RPM
-
8/2/2019 Exchust Fan information
20/52
DONOT
SELECT
TOTH
EL
EFT
OF
THIS
SYSTEM
CUR
VE
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
3Volume (m /hr )
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.0 75 lb/ft3
Density 1.2 kg/m3
20
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)
Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 54/61 lbs. (24/28 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
134(44)
2438(619)
438(111)
*2334(603)
19(483)
Motor HP FanRPM
Static Pressure in Inches wg
Belt Direct 0 0125 025 0375 05 0625 075 0875 1 1125091 099
1/4
VG-Vari-GreenisadirectdrivebrushlessDCmotor.
720CFM 546 403BHP 002 002
Sones 36 35
790CFM 599 471 291BHP 002 002 002
Sones 42 41 39
C-1/8 860CFM 652 536 400BHP 003 003 003
Sones 49 47 45
930CFM 705 598 481BHP 004 004 004
Sones 56 55 51
1000CFM 758 659 552 414BHP 004 005 005 005
Sones 64 62 58 56
1070CFM 811 718 621 512BHP 005 006 006 006
Sones 73 71 67 63
B-1/6 1140CFM 864 777 687 590 457BHP 007 007 007 007 007
Sones 83 81 76 71 68
1285CFM 974 897 819 736 647 526BHP 009 010 010 010 011 010
Sones 95 94 90 85 82 79
1435CFM 1087 1018 949 877 801 721 615 404BHP 013 014 014 014 015 015 015 012
Sones 107 106 104 100 96 93 90 84
1580CFM 1197 1135 1072 1009 941 872 799 707 583BHP 017 018 019 019 019 020 020 020 019
Sones 121 120 119 115 112 109 106 103 98
A-1/4 1725CFM 1307 1250 1192 1135 1076 1013 949 883 806 707BHP 023 023 024 024 025 025 026 026 026 025
Sones 136 135 134 132 129 126 123 120 118 115
C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM
Roof Downblast ExhaustBelt & Direct DriveGB-091 G-099
MAXIMUM BHP AT A GIVEN RPM = (RPM/2703)3
MAXIMUM RPM - GB-091=1710, G-099=1725TIP SPEED (ft/min) = RPM x 2.929
MAXIMUM MOTOR FRAME SIZE = 56VG-1/4
Direct Drive RPM
-
8/2/2019 Exchust Fan information
21/52
DONOT
SE
LECT
TO
THELEFTOFTHIS
SYSTEM
CURVE
1350
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
3Volume (m /hr )
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.07 5 lb/ft3
Density 1.2 kg/m3
2
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: f ree inlet hemispherical sone levels.
Motor HP FanRPM
Static Pressure in Inches wg
Belt Direct 0 0125 025 0375 05 0625 075 0875 1 125101 103
1/4
VG-Vari-GreenisadirectdrivebrushlessDCmotor.
720CFM 610 477BHP 002 002
Sones 38 27
C-1/8 860CFM 729 623 473BHP 003 004 004
Sones 46 37 29
1000CFM 848 753 654 481BHP 005 005 006 005
Sones 55 48 44 34
B-1/6 1140CFM 966 883 805 702 507BHP 007 008 009 009 008
Sones 66 60 57 52 41
1245CFM 1055 978 908 824 715BHP 010 010 011 011 011
Sones 75 70 67 63 57
1350CFM 1144 1073 1006 938 851 731BHP 012 013 013 014 014 014
Sones 85 81 78 77 72 67
1450CFM 1229 1162 1099 1041 965 878 750BHP 015 016 016 017 017 017 017
Sones 93 90 87 84 80 75 69
1555CFM 1318 1255 1196 1140 1079 1005 917 791BHP 019 019 020 021 022 022 022 021
Sones 102 100 97 94 89 84 80 75
1660CFM 1407 1348 1292 1238 1187 1122 1050 963 841BHP 023 023 024 025 026 026 026 026 025
Sones 114 111 107 104 101 96 91 87 81
1/3
A-1/4 1725CFM 1462 1405 1351 1298 1250 1193 1126 1052 955BHP 025 026 027 028 029 029 029 029 029
Sones 122 119 115 112 109 103 100 95 90
1800CFM 1525 1471 1419 1368 1321 1270 1209 1142 1065 793BHP 029 030 030 031 033 033 033 033 033 030
Sones 133 128 125 124 122 114 109 106 102 93
Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 54/61 lbs. (24/28 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
134(44)
2438(619)
438(111)
*2334(603)
19(483)
MAXIMUM BHP AT A GIVEN RPM = (RPM/2593)3
MAXIMUM RPM = 1800TIP SPEED (ft/min) = RPM x 2.913
MAXIMUM MOTOR FRAME SIZE = 56
Roof Downblast ExhaustBelt & Direct DriveGB-101 G-103
C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM
VG-1/4
Direct Drive RPM
-
8/2/2019 Exchust Fan information
22/52
DO
NOT
SELECTTOTH
ELEFT
OFTHIS
SYSTEMCURVE
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
22
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Motor HP FanRPM
Static Pressure in Inches wg
Belt Direct 0 025 05 075 1 125 15 175 2 225101HP 103HP
1/4
VG
-Vari-GreenisadirectdrivebrushlessDCmotor.
1300CFM 571 477 342BHP 006 006 007
Sones 66 57 53
1445CFM 635 553 449 243BHP 008 009 009 008
Sones 84 75 7 63
1590CFM 699 626 537 417BHP 010 011 012 012
Sones 104 95 91 83
A-1/4 1725CFM 758 692 613 521 364BHP 013 014 015 016 015
Sones 114 107 106 101 10
1880CFM 826 767 697 618 518 337BHP 017 018 019 020 020 018
Sones 127 122 119 12 114 119
2025CFM 890 836 772 702 622 515 313BHP 021 023 024 024 026 025 022
Sones 142 136 133 132 126 12 114
1/3
2137CFM 939 889 830 765 693 607 474BHP 025 026 028 028 029 030 028
Sones 154 148 144 142 134 131 121
2229CFM
979 931 875 814 748 674 574 406BHP 028 030 031 032 033 035 033 031Sones 158 154 148 145 141 137 132 120
1/2
2336CFM 1026 981 928 871 809 742 661 543 358BHP 033 034 036 036 037 039 040 037 034
Sones 164 16 154 149 147 14 141 135 136
2500CFM 1098 1056 1008 956 901 840 775 695 583 416BHP 040 042 043 045 045 046 048 048 046 042
Sones 178 174 169 167 158 155 148 152 157 166
2550CFM 1120 1078 1032 982 928 869 807 735 639 497BHP 043 044 046 047 047 049 051 052 050 047
Sones 182 179 174 172 163 161 151 156 162 172
Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 58/63 lbs. (26/29 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
134(44)
2438(619)
438(111)
*2334(603)
19(483)
MAXIMUM BHP AT A GIVEN RPM = (RPM/3165)3
MAXIMUM RPM = 2550TIP SPEED (ft/min) = RPM x 2.978
MAXIMUM MOTOR FRAME SIZE = 56
Roof Downblast ExhaustBelt & Direct DriveGB-101HP G-103HP
A-1725 RPM VG-2550-RPM
VG-1/2
Direct Drive RPM
-
8/2/2019 Exchust Fan information
23/52
DONOTS
ELEC
TTO
THE
LEFT
OF
THIS
SYSTEM
CURVE
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
3
Volume (m /hr )
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.07 5 lb/ft3
Density 1.2 kg/m3
2
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)
Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 58/66 lbs. (26/30 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
134(44)
2438(619)
438(111)
*2334(603)
19(483)
Roof Downblast ExhaustBelt & Direct DriveGB-121 G-123
Motor HP FanRPM
Static Pressure in Inches wg
Belt Direct 0 0125 025 0375 05 0625 075 1 125 15121 123
1/4
VG-Vari-GreenisadirectdrivebrushlessDCmotor.
580CFM 704 515BHP 002 002
Sones 32 33
720CFM 873 735 523BHP 003 004 004
Sones 42 43 41
C-1/8 860CFM 1043 932 796 580BHP 005 006 006 006
Sones 54 55 52 52
1000CFM 1213 1119 1013 883 694BHP 008 009 009 010 009
Sones 67 68 67 64 64
B-1/6 1140CFM 1383 1300 1213 1112 993 831BHP 012 013 014 014 014 014
Sones 84 84 84 81 79 78
1265CFM 1535 1460 1384 1299 1204 1093 950BHP 016 017 018 019 019 020 019
Sones 102 101 101 99 97 96 94
1395CFM 1692 1625 1557 1484 1404 1315 1214 907BHP 021 023 024 025 026 026 026 024
Sones 125 124 123 122 120 117 115 113
1/3
1475CFM 1789 1726 1661 1594 1521 1441 1356 1132BHP 025 027 028 029 030 031 031 031
Sones 135 134 133 132 130 127 124 120
1550CFM 1880 1820 1759 1696 1629 1555 1475 1289 974BHP 029 031 032 033 034 035 036 036 033
Sones 146 145 143 142 140 138 135 129 124
1/2
1635CFM 1983 1926 1868 1810 1747 1680 1608 1446 1231BHP 034 036 037 039 040 041 042 043 041
Sones 159 158 156 154 153 150 148 139 134
A-1/2 1725CFM 2093 2038 1984 1928 1871 1810 1743 1600 1426 1180BHP 040 042 044 045 046 047 048 050 050 047
Sones 174 172 170 168 167 164 162 155 149 140
C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM
MAXIMUM BHP AT A GIVEN RPM = (RPM/2170)3
MAXIMUM RPM = 1725TIP SPEED (ft/min) = RPM x 3.420
MAXIMUM MOTOR FRAME SIZE = 56VG-1/2
Direct Drive RPM
-
8/2/2019 Exchust Fan information
24/52
A
DONOTSEL
ECTTO
THELE
FTOF
THIS
SYSTEM
CURVE
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
3
Volume (m /hr )
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.0 75 lb/ft3
Density 1.2 kg/m3
24
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Roof Downblast - ExhaustBelt & Direct DriveGB-131 G-133
134(44)
Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 62/67 lbs. (28/30 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
2838(721)
4 (102)
*2334(603)
19(483)
Motor HP FanRPM
Static Pressure in Inches wg
Belt Direct 0 0125 025 0375 05 0625 075 1 125 15131 133
1/4
VG-Va
ri-GreenisadirectdrivebrushlessDCmotor.
580CFM 823 626BHP 002 002
Sones 45 45
720CFM 1022 879 650BHP 004 004 004
Sones 54 54 52
C-1/8 860CFM 1221 1106 962 727BHP 006 007 007 007
Sones 66 65 63 60
1000CFM 1419 1323 1213 1075 867BHP 010 011 011 012 011
Sones 81 80 77 74 70
B-1/6 1140CFM 1618 1535 1444 1340 1211 1031BHP 015 016 016 017 017 017
Sones 100 98 96 92 88 85
1250CFM 1774 1698 1617 1528 1426 1133BHP 019 02 021 022 023 022
Sones 120 117 113 110 105 97
1315CFM 1866 1794 1718 1637 1545 1435 1305BHP 022 023 024 025 026 026 026
Sones 132 128 125 121 117 112 109
1/3 1440CFM 2044 1978 1911 1838 1759 1674 1571 1299BHP 029 031 032 033 034 034 035 034
Sones 150 150 151 151 145 139 134 125
1/2
1600CFM 2271 2212 2152 2088 2023 1873 1783 1686 1425BHP 040 042 043 044 045 047 047 048 047
Sones 162 160 158 156 153 146 142 139 132
1685CFM 2391 2335 2279 2219 2158 2020 1946 1857 1654 1312BHP 047 048 050 051 052 054 055 056 056 052
Sones 169 166 163 160 157 151 148 145 139 135
3/4 A-1/2 1725CFM 2448 2393 2338 2281 2220 2159 2089 1935 1746 1474BHP 050 052 053 055 056 057 058 059 060 058
Sones 174 170 167 163 159 156 154 149 143 138
C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM
MAXIMUM BHP AT A GIVEN RPM = (RPM/2047)3
MAXIMUM RPM - GB-131=1725, G-133=1725TIP SPEED (ft/min) = RPM x 3.436
MAXIMUM MOTOR FRAME SIZE = 56VG-3/4
Direct Drive RPM
-
8/2/2019 Exchust Fan information
25/52
DONOT
SELEC
TTO
THELEFT
OF
THIS
SYSTEM
CURVE
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
2
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Roof Downblast - ExhaustBelt & Direct DriveGB-141 G-143
134(44)
Damper Size = 16 x 16 (406 x 406)Roof Opening = 18 x 18 (470 x 470)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 77/86 lbs. (35/39 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
2838(721)
4 (102)
*2334(603)
22(559)
Motor HP FanRPM
Static Pressure in Inches wg
Belt Direct 0 0125 025 0375 05 075 1 125 15 175141 143
1/4
V
G-Vari-GreenisadirectdrivebrushlessDCmotor.
580CFM 1076 855BHP 004 004
Sones 47 47
720CFM 1336 1169 938BHP 007 008 008
Sones 58 59 52
C-1/8 860CFM 1595 1457 1304 1085BHP 012 013 013 013
Sones 71 70 66 61
950CFM 1762 1636 1506 1344 1085BHP 016 017 018 018 017
Sones 81 80 76 71 65
1075CFM 1994 1882 1771 1647 1490BHP 024 025 026 026 026
Sones 100 99 94 89 84
1/3 B-1/3 1140CFM 2115 2008 1905 1792 1660 1233BHP 028 030 031 031 031 029
Sones 110 109 104 99 94 82
1/2
1265CFM 2347 2250 2158 2062 1955 1677 1048BHP 039 040 041 042 042 042 035
Sones 129 127 123 119 114 104 88
1360
CFM 2523 2433 2347 2259 2166 1943 1602BHP 048 050 051 052 052 053 051
Sones 146 143 139 135 131 122 110
3/4
1450CFM 2690 2606 2524 2443 2358 2165 1905 1501BHP 058 060 061 063 063 064 063 059
Sones 162 159 156 152 147 138 129 117
1550CFM 2875 2797 2719 2644 2566 2396 2191 1910 1297BHP 071 073 074 076 077 078 079 076 065
Sones 177 180 174 172 168 150 148 148 149
1 A-1 1725CFM 3200 3129 3059 2991 2923 2782 2619 2427 2184 1815BHP 098 100 102 103 105 107 107 109 106 100
Sones 200 210 200 199 196 185 172 170 168 167
C-860-RPM B-1140-RPM A-1725-RPM VG-1550-RPM
MAXIMUM BHP AT A GIVEN RPM = (RPM/1676)3
MAXIMUM RPM - GB-141=1725, G-143=1725TIP SPEED (ft/min) = RPM x 3.829
MAXIMUM MOTOR FRAME SIZE = 145TVG-3/4
Direct Drive RPM
-
8/2/2019 Exchust Fan information
26/52
DONOT
SELECTTOTHELEFTOF
THIS
SYSTEM
CURV
E
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
3
Volume (m /hr )
RPM (Belt)
RPM (Direct)
RPM (Vari-Green)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
2200
Motor HP FanRPM
Static Pressure in Inches wg
Belt Direct 5 75 1 125 15 175 2 225 25 275141HP 143HP
1/4
VG-Vari-GreenisadirectdrivebrushlessDCmotor.
1020CFM 488BHP 008
Sones 63
B-1/4 1140CFM 645 413BHP 011 011
Sones 77 76
1320CFM 837 700 486BHP 017 018 017
Sones 103 98 99
1500CFM 1009 903 774 592BHP 024 026 026 025
Sones 131 123 122 124
1/3 1655CFM 1151 1064 959 833 668BHP 032 034 035 035 034
Sones 150 141 133 131 136
1/2
A-1/2 1725CFM 1213 1132 1035 932 784 588BHP 036 038 039 039 039 037
Sones 162 154 147 142 143 149
1812CFM 1289 1213 1127 1030 911 763 545BHP 041 043 045 046 045 045 041
Sones 178 172 166 158 156 159 166
1900CFM 1366 1294 1218 1127 1033 901 753BHP 047 049 051 053 053 052 051
Sones 190 184 180 174 168 167 170
3/4
2050CFM 1495 1430 1361 1285 1200 1113 991 857 672BHP 058 061 063 065 066 066 066 065 061
Sones 210 200 198 193 188 186 183 183 186
2170CFM 1598 1536 1472 1407 1328 1248 1163 1045 919 757BHP 068 071 073 076 077 078 079 078 077 074
Sones 220 220 210 210 210 210 210 200 197 198
2200CFM 1623 1562 1500 1436 1360 1281 1200 1088 968 834BHP 071 074 076 078 080 082 082 081 080 079
230 220 220 220 210 210 210 210 200 200
26
Roof Downblast - Belt DriveSize- : GB H-GB
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Roof Downblast - ExhaustBelt & Direct DriveGB-141HP G-143HP
Damper Size = 16 x 16Roof Opening = 18 x 18 (470 x 470)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 75/83 lbs. (34/38 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
MAXIMUM BHP AT A GIVEN RPM = (RPM/2351)3
MAXIMUM RPM - GB-141HP=2200, G-143HP=2200TIP SPEED (ft/min) = RPM x 3.829
MAXIMUM MOTOR FRAME SIZE = 145T
134(44)
4 (102)
*2334(603)
22(559)
2838(721)
B-1140-RPM A-1725-RPM VG-2200-RPM
VG-3/4
Direct Drive RPM
-
8/2/2019 Exchust Fan information
27/522
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
DONOTS
ELEC
TTO
THE
LEFT
OF
THIS
SYSTEM
CURVE
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
3Volume (m/hr )
RPM (Belt)
RPM (Direct)
HP
Density 0.07 5 lb/ft3
Density 1.2 kg/m3
Roof Downblast - ExhaustBelt & Direct DriveGB-161 G-163
Damper Size = 16 x 16Roof Opening = 18 x 18 (470 x 470)
Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 101/88 lbs. (46/40 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
134(44)
2838(619)
4 (102)
*2334(603)
22(559)
Motor HP FanRPM
Static Pressure in Inches wg
Belt Direct 0 0125 025 0375 05 075 0875 1 125 15161 163
1/4
580CFM 1713 1417 970BHP 007 008 007
Sones 58 56 53
720CFM 2127 1893 1632 1243BHP 014 015 015 014
Sones 78 75 72 68
C-1/4 860CFM 2540 2344 2145 1913 1596BHP 023 024 025 026 024
Sones 105 100 96 93 87
1/3 945CFM 2791 2612 2434 2236 2010BHP 031 032 033 034 034
Sones 126 120 115 112 107
1/2
1050CFM 3102 2940 2782 2616 2429 1937 1582BHP 042 044 045 046 047 044 041
Sones 144 138 132 129 126 116 107
1100CFM 3249 3095 2943 2787 2615 2198 1900BHP 048 050 052 053 053 052 050
Sones 153 147 141 138 135 125 120
3/4
B-1/2 1140CFM 3367 3219 3072 2922 2761 2382 2125 1808BHP 054 056 057 058 059 059 057 054
Sones 159 154 149 145 142 133 129 121
1250CFM 3692 3557 3422 3289 3149 2838 2658 2444BHP 071 073 075 076 077 079 078 076
Sones 179 174 170 166 163 156 152 149
1 1375CFM 4062 3938 3815 3694 3571 3304 3161 3007 2609 2073BHP 095 097 099 101 102 104 105 104 101 093
Sones 210 200 196 192 189 184 180 176 172 154
1-1/2 1575CFM 4652 4545 4437 4330 4225 4007 3894 3769 3512 3198BHP 142 145 147 149 151 154 156 156 157 154
Sones 260 250 250 240 240 240 230 230 220 220
C-860-RPM B-1140-RPM A-1725-RPM
MAXIMUM BHP AT A GIVEN RPM = (RPM/1355)3
MAXIMUM RPM - GB-161=1575, G-163=1725TIP SPEED (ft/min) = RPM x 4.352
MAXIMUM MOTOR FRAME SIZE = 145T
Direct Drive RPM
-
8/2/2019 Exchust Fan information
28/5228
Roof Downblast - Belt DriveSize- : GB H-GB
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Damper Size = 16 x 16 (406 x 406)Roof Opening = 18 x 18 (470 x 470)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 88 lbs. (40 kg)
All dimensions in inches (millimeters) *May be greater depending on motor^Weight shown is largest cataloged Open Drip-Proof motor.
Roof Downblast - ExhaustBelt DriveGB-161HP
MotorHP
FanRPM
Static Pressure in Inches wg
05 0625 075 1 125 15 175 2 225 25161HP
1/4
825CFM 702BHP 011
Sones 65
960CFM 1093 919 585BHP 018 017 015
Sones 77 76 80
1095CFM 1380 1271 1139 589BHP 026 026 026 021
Sones 90 90 89 95
1/3 1210CFM 1606 1514 1416 1149BHP 034 035 035 034
Sones 106 103 104 103
1/2
1270CFM 1718 1636 1545 1333 949BHP 039 040 040 041 037
Sones 114 112 111 111 114
1330CFM 1829 1753 1668 1483 1204BHP 044 045 046 047 045
Sones 123 121 119 121 120
1390CFM 1938 1865 1789 1619 1399 1032BHP 050 051 052 053 053 048
Sones 133 130 128 127 127 131
3/4
1485CFM
2109 2041 1973 1822 1654 1416 1012BHP 060 061 063 064 065 063 057Sones 149 147 144 138 137 140 147
1580CFM 2275 2214 2150 2016 1868 1704 1447 1034BHP 072 073 075 077 077 0791 075 067
Sones 167 167 164 155 147 148 154 166
1
1660CFM 2414 2357 2297 2175 2037 1887 1702 1441 996BHP 082 084 085 089 089 091 090 086 075
Sones 183 188 183 167 162 158 158 171 20
1740CFM 2551 2497 2442 2325 2200 2066 1917 1714 1452 987BHP 094 096 097 101 103 103 105 103 098 085
Sones 20 21 21 184 175 172 168 172 192 28
DO
NOT
SELECTTOTHELEFT
OF
THIS
SYSTEMCURVE
StaticPressure(in.wg
)
StaticPressure(Pa)
Volume (cfm)
3Volume (m/hr)
RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
MAXIMUM BHP AT A GIVEN RPM = (RPM/1708)3
MAXIMUM RPM = 1740TIP SPEED (ft/min) = RPM x 4.352
MAXIMUM MOTOR FRAME SIZE = 145T
134(44)
4 (102)
*2334(603)
22(559)
2838(721)
-
8/2/2019 Exchust Fan information
29/522
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
DONOT
SEL
ECT
TO
THE
LEFTOF
THIS
SYSTEM
CURVE
StaticPressure(in.wg)
StaticPressure(Pa )
Volume (cfm)
3Volume (m/hr )
RPM (Belt)
RPM (Direct)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
Roof Downblast - ExhaustBelt & Direct DriveGB-180 G-183
Damper Size = 18 x 18 (457 x 457)Roof Opening = 20 x 20 (521 x 521)Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 108/142 lbs. (49/64 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
134(44)
3512(902)
512(140)
*28(711)
30(762)
Motor HP FanRPM
Static Pressure in Inches wg
Belt Direct 0 0125 025 05 075 1 125 15 175 2180 183
1/4
495CFM 1925 1646 1150BHP 0067 0078 0075
Sones 43 47 41
730CFM 2839 2668 2469 1882BHP 021 023 025 025
Sones 74 87 72 67
1/3 810CFM 3150 2997 2832 2375BHP 029 031 033 035
Sones 88 99 87 82
1/2
825CFM 3208 3059 2899 2458BHP 031 032 035 037
Sones 91 102 90 86 85
C-1/2 860CFM 3344 3202 3049 2647 2015BHP 035 036 039 042 04
Sones 101 108 98 91 81
940CFM 3655 3527 3388 3052 2601BHP 046 047 049 054 054
Sones 127 128 12 111 103
3/4 1055CFM 4102 3990 3867 3596 3252 2811BHP 065 067 068 074 077 077
Sones 162 157 149 14 129 124
1
B-1 1140CFM 4433 4329 4216 3980 3684 3328 2856BHP 081 084 085 093 096 098 095
Sones 179 174 168 16 151 143 136
1185CFM 4608 4508 4401 4179 3900 3575 3178 2499BHP 091 094 096 103 107 11 109 099
Sones 19 184 178 171 162 154 147 137
1-1/2 1335CFM 5191 5102 5010 4814 4599 4344 4052 3713 3262BHP 131 133 136 141 149 154 157 156 151
Sones 22 22 21 21 199 192 187 182 176
2 1460CFM 5677 5596 5514 5336 5155 4938 4699 4426 4123 3765BHP 171 174 177 181 193 197 203 205 205 202
Sones 26 25 24 24 23 23 22 22 22 21
C-860-RPM B-1140-RPM
MAXIMUM BHP AT A GIVEN RPM = (RPM/1149)3
MAXIMUM RPM = 1460TIP SPEED (ft/min) = RPM x 4.843
MAXIMUM MOTOR FRAME SIZE = 184T
Direct Drive RPM
-
8/2/2019 Exchust Fan information
30/5230
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Damper Size = 18 x 18 (457 x 457)Roof Opening = 20 x 20 (521 x 521)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 142 lbs. (64 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
Roof Downblast - ExhaustBelt DriveGB-180HP
MotorHP
FanRPM
Static Pressure in Inches wg
05 075 1 125 15 175 2 225 25 275180HP
1/4
795CFM 1547BHP 022
Sones 86
845CFM 1759BHP 026
Sones 91
1/3 935CFM 2114 1686BHP 035 035
Sones 103 96
1/2 1075CFM 2601 2316 1920BHP 051 053 052
Sones 129 121 116
3/4
1150CFM 2847 2607 2298 1811BHP 061 064 065 062
Sones 146 131 126 123
1225CFM 3088 2880 2610 2277 1711BHP 073 077 078 078 072
Sones 163 147 139 133 132
1 1350CFM 3485 3296 3095 2840 2540 2059BHP 096 100 104 105 105 099
Sones 195 176 164 158 150 151
112
1445CFM
3782 3604 3428 3213 2969 2670 2216BHP 116 121 125 128 129 128 121Sones 22 20 188 178 173 164 166
1540CFM 4076 3909 3744 3576 3353 3119 2827 2407BHP 139 144 149 153 155 156 155 148
Sones 25 22 21 20 196 189 181 183
2
1620CFM 4319 4163 4005 3848 3663 3450 3223 2923 2512BHP 160 166 171 176 179 181 182 180 172
Sones 27 25 24 23 22 21 20 197 198
1700CFM 4560 4414 4263 4114 3964 3764 3560 3340 3037 2642BHP 184 190 196 201 206 208 210 211 207 199
Sones 30 27 26 25 24 23 22 22 21 21
DONOT
SELECT
TO
THE
LEFT
OF
THIS
SY
STEM
CUR
VE
StaticPressure(in.wg
)
StaticPressure(Pa)
Volume (cfm)
3Volume (m /hr )
RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
MAXIMUM BHP AT A GIVEN RPM = (RPM/1325)3
MAXIMUM RPM = 1700TIP SPEED (ft/min) = RPM x 4.843
MAXIMUM MOTOR FRAME SIZE = 184T
134(44)
512(140)
*28(711)
30(762)
3512(902)
-
8/2/2019 Exchust Fan information
31/523
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Roof Downblast - ExhaustBelt & Direct DriveGB-200 G-203
Damper Size = 18 x 18 (457 x 457)Roof Opening = 20 x 20 (521 x 521)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 119/144 lbs. (54/65 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
134(44)
3512(902)
512(140)
*28(711)
30(762)
Motor HP FanRPM
Static Pressure in Inches wg
Belt Direct 0 0125 025 0375 05 075 10 125 15 175200 203
1/4
440CFM 2435 1976BHP 01 01
Sones 65 58
600CFM 3320 2984 2637 2089BHP 025 026 026 025
Sones 85 79 73 61
1/3 665CFM 3680 3378 3085 2706 2087BHP 034 034 035 035 033
Sones 96 9 85 77 67
1/2
718CFM 3973 3700 3422 3109 2684BHP 043 043 045 045 044
Sones 108 10 96 9 83
770CFM 4261 4013 3744 3477 3141BHP 052 053 055 055 055
Sones 121 11 107 102 98
3/4 C-3/4 860CFM 4759 4548 4289 4068 3811 3085BHP 073 074 075 077 077 074
Sones 141 133 129 124 118 111
1 965CFM 5340 5158 4927 4720 4520 4015 3240BHP 103 104 105 108 109 108 102
Sones 167 16 154 15 145 137 13
1-1/2
1028
CFM 5689 5517 5309 5101 4918 4488 3911 2941BHP 125 126 127 129 131 132 128 114
Sones 185 178 172 168 164 156 147 146
1090CFM 6032 5870 5682 5473 5301 4925 4450 3751BHP 149 15 151 152 156 156 156 148
Sones 20 196 189 184 181 175 168 158
2
B-2 1140CFM 6308 6154 5980 5779 5606 5267 4832 4287 3439BHP 17 171 172 174 177 179 179 175 161
Sones 22 21 21 20 197 191 185 175 165
1200CFM 6640 6494 6336 6145 5969 5651 5274 4829 4177 3077BHP 199 2 201 202 204 209 209 208 199 169
Sones 24 23 23 22 22 21 21 199 186 167
DONOT
SELECT
TO
THELEFTOFTHIS
SYSTEM
CURVE
StaticPressure(in.wg
)
StaticPressure(Pa)
Volume (cfm)
3Volume (m/hr )
RPM (Belt)
RPM (Direct)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
C-860-RPM B-1140-RPM
MAXIMUM BHP AT A GIVEN RPM = (RPM/938)3
MAXIMUM RPM = 1200TIP SPEED (ft/min) = RPM x 5.596
MAXIMUM MOTOR FRAME SIZE = 184T
Direct Drive RPM
-
8/2/2019 Exchust Fan information
32/5232
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Damper Size = 18 x 18 (457 x 457)Roof Opening = 20 x 20 (521 x 521)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 166 lbs. (75 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
Roof Downblast - ExhaustBelt DriveGB-220HP
DONOT
SELECTT
OT
HELEFTOF
THIS
SYSTEMC
URVE
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm)
3Volume (m /hr)
RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
MotorHP
FanRPM
Static Pressure in Inches wg
05 075 1 125 15 2 25 275 3 325200HP
1/2
740CFM 1961BHP 030
Sones 87
895CFM 2809 2331 1424BHP 052 053 045
Sones 114 109 103
3/4
958CFM 3116 2715 2153BHP 063 065 063
Sones 128 121 116
1020CFM 3409 3050 2602 1857BHP 075 077 078 071
Sones 141 136 131 126
1 1125CFM 3885 3584 3243 2804 2136BHP 099 102 104 104 097
Sones 169 164 155 153 152
112
1205CFM 4229 3967 3663 3314 2884BHP 119 124 127 129 127
Sones 188 179 172 165 164
1285CFM 4569 4343 4070 3770 3416 2278BHP 143 149 152 155 157 140
Sones 21 20 191 181 178 189
2
1350CFM
4843 4638 4384 4109 3811 2996BHP 165 171 175 178 181 176Sones 23 22 21 198 193 191
1415CFM 5114 4919 4692 4442 4169 3492 2250BHP 188 195 200 204 207 207 178
Sones 24 24 23 22 21 197 23
3
1520CFM 5550 5368 5182 4952 4713 4166 3458 2850 2046BHP 231 238 245 250 253 258 253 238 206
Sones 27 27 27 26 24 23 22 22 22
1625CFM 5982 5812 5642 5448 5233 4767 4196 3859 3377 2725BHP 280 288 295 302 306 313 316 312 301 276
Sones 32 31 31 29 28 27 25 24 23 22
MAXIMUM BHP AT A GIVEN RPM = (RPM/1106)3
MAXIMUM RPM = 1625TIP SPEED (ft/min) = RPM x 5.596
MAXIMUM MOTOR FRAME SIZE = 184T
134(44)
512(140)
*28(711)
30(762)
3512(902)
-
8/2/2019 Exchust Fan information
33/523
Roof Downblast - ExhaustBelt DriveGB-220
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
134(44)
Damper Size = 24 x 24 (610 x 610)Roof Opening = 26 x 26 (673 x 673)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 164 lbs. (74 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
DONOT
SEL
ECTTO
THE
LEFT
OF
THISSYSTEM
CURVE
StaticPressure(in.w
g)
StaticPressure(Pa
)
Volume (cfm x 1000)
3Volume (m/hr x 1000)
RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
MotorHP
FanRPM
Static Pressure in Inches wg
0 0125 025 0375 05 0625 075 1 125 15220
1/4
425CFM 3230 2879 2296BHP 014 016 016
Sones 74 72 69
465CFM 3533 3219 2758 1951BHP 018 020 021 019
Sones 81 78 74 70
500CFM 3799 3512 3132 2542BHP 023 025 026 026
Sones 88 84 79 75
1/3 550CFM 4179 3924 3629 3158 2526BHP 030 032 034 035 033
Sones 100 96 89 84 80
1/2 640CFM 4863 4654 4403 4120 3702 3208BHP 048 050 053 054 055 054
Sones 130 128 121 112 105 97
3/4 710CFM 5395 5206 4990 4762 4459 4077 3633BHP 065 068 071 073 074 075 074
Sones 150 149 144 136 128 121 112
1
755CFM 5737 5559 5362 5148 4920 4579 4206 3095BHP 079 082 084 087 089 090 090 082
Sones 157 156 152 146 140 134 127 112
800CFM
6079 5911 5732 5530 5326 5049 4716 3929BHP 093 097 100 102 105 106 107 105Sones 166 164 161 156 152 146 142 125
112
848CFM 6444 6286 6122 5932 5741 5540 5236 4566 3542BHP 111 115 118 121 123 126 127 127 117
Sones 178 175 172 169 165 162 157 145 134
895CFM 6801 6651 6501 6323 6142 5960 5723 5122 4401BHP 131 134 138 141 144 147 149 150 147
Sones 194 191 188 185 182 180 176 169 155
2 985CFM 7485 7349 7212 7062 6898 6734 6568 6107 5548 4883BHP 174 178 182 186 189 192 195 199 200 196
Sones 23 23 23 22 22 22 22 21 20 190
MAXIMUM BHP AT A GIVEN RPM = (RPM/782)3
MAXIMUM RPM = 985TIP SPEED (ft/min) = RPM x 6.283
MAXIMUM MOTOR FRAME SIZE = 184T
4234(1086)
*3112(800)
534(146)
34(864)
-
8/2/2019 Exchust Fan information
34/5234
Roof Downblast - ExhaustBelt DriveGB-220HP
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.
134(44)
Damper Size = 24 x 24 (610 x 610)Roof Opening = 26 x 26 (673 x 673)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 186 lbs. (84 kg)
All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.
DONOT
SELE
CT
TO
THE
LEFT
OFTHIS
SYSTEM
CUR
VE
StaticPressure(in.wg)
StaticPressure(Pa)
Volume (cfm x 1000)
3Volume (m/hr x 1000)
RPM (Belt)
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
534(146)
*3112(800)
34(864)
MotorHP
FanRPM
Static Pressure in Inches wg
05 0625 075 1 125 15 175 2 225 25220HP
1/2
650CFM 2952 2555 1892BHP 047 046 042
Sones 89 85 83
680CFM 3215 2871 2440BHP 053 053 052
Sones 94 92 89
3/4
728CFM 3614 3312 2974BHP 065 065 065
Sones 106 103 99
775CFM 3973 3719 3424 2643BHP 077 079 079 075
Sones 120 115 111 105
1 850CFM 4532 4317 4083 3536 2648BHP 100 102 104 103 095
Sones 150 138 135 127 120
112
913CFM 4975 4791 4590 4119 3545 2557BHP 122 125 127 129 127 113
Sones 167 160 153 144 135 130
975CFM 5400 5245 5060 4660 4185 3602BHP 146 150 153 157 156 153
Sones 187 182 175 163 154 148
2
1025CFM 5740 5591 5432 5075 4643 4157 3492BHP 168 172 176 181 182 1804 174
Sones 21 20 194 182 171 164 156
1075CFM 6076 5935 5794 5459 5082 4649 4136 3346BHP 193 197 201 206 210 210 207 193
Sones 23 22 21 20 187 183 177 164
3
1127CFM 6422 6289 6154 5852 5520 5124 4703 4173 3299BHP 220 224 229 236 241 242 241 237 217
Sones 24 24 23 22 21 20 193 186 177
1230CFM 7100 6981 6858 6611 6316 6009 5649 5263 4812 4265BHP 282 287 292 301 308 314 315 314 310 302
Sones 28 27 27 27 25 25 23 22 22 22
MAXIMUM BHP AT A GIVEN RPM = (RPM/838)3
MAXIMUM RPM = 1230TIP SPEED (ft/min) = RPM x 6.414
MAXIMUM MOTOR FRAME SIZE = 184T
4234(1086)
-
8/2/2019 Exchust Fan inform