    Centrifugal Roof Downblast Exhaust Fans General Clean Air Light Contaminants

    Seismic High Wind Variable Volume

    Models G and GB

    Performance data now included.

  • 8/2/2019 Exchust Fan information

    2/52

    Contents

    Model Comparison 3

    Construction Features 4-5

    Emergency Smoke Control 6

    Seismic 6

    High Wind & Hurricane 7

    Vari-Green Motor and Controls 8-9

    Demand Control Ventilation 9

    Roo Curbs, Options, Accessories 10-11

    Typical Installations 12-13

    Model Number Code 13

    PERFORMANCE AND DIMENSIONS:

    Models G-060-095 14-17

    Models G-097-G203 18-31

    GB-071-200 18-32

    Models GB-220-540 33-46

    SPECIFICATIONS:

    Vari-Green Motors and Controls 47

    Direct Drive 48

    High Wind & Hurricane, Seismic G Fan 49

    Belt Drive 50

    High Wind & Hurricane,Seismic & Smoke Control GB Fan 51

    Quick Build Programs 52

    Warranty 52

    Models G and GBSpun Aluminum Downblast

    Centriugal Roo Exhaust Fans

    Codes and CertificationsGreenheck Fan Corporation certiies that the ModelsG and GB fans shown herein are licensed to bear theAMCA Seal. The ratings shown are based on testsand procedures performed in accordance with AMCAPublication 211 and Publication 311 and comply with therequirements o the AMCA Certiied Ratings ProgramThe certified ratings for Models G and GB are shown on

    pages 14 - 46

    G and GB models are listed or electrical(UL/cUL 705) File no E40001

    GB models or Emergency Smoke Control Systems(UL/cUL Listed or 500F (260C) or 4 hours and1,000F (538C) or 15 minutes) File no MH17511

    High Wind Certication

    Miami-Dade NOA for high wind and hurricane zones

    Seismic Certication

    OSHPD No. 0148-10 - Ofce of Statewide Health

    Planning and Development (Caliornia)

    IBC 2006 and 2009 - International Building Code

    *UL/cUL is optional

    and must be specified

  • 8/2/2019 Exchust Fan information

    3/52

    Models G and GBSpun Aluminum Downblast

    Centriugal Roo Exhaust Fans

    Greenheck models G and GB centriugal rooexhaust provide the industrys best perormance anddurability for general clean air applications where air is

    discharged downward, toward the roof surface.

    Broadest perormance in the industry, up to3.25 in. wg (810 Pa) and 45,000 cm (76,500 m3/hr)

    Most advanced motor cooling o any an in its class

    Performance as cataloged is assured. All fan sizes

    are tested in our AMCA Accredited Laboratory, andall models are licensed to bear the AMCA Sound

    and Air Perormance seals

    UL Listed or electrical

    Greenheck subjects these products to extensive lietesting, assuring you that the fans will provide years

    o reliable perormance

    Direct Drive, G

    Use for short and/or low resistance ductwork

    Belt Drive, GB

    For average length and/or average

    resistance ductwork High volume/average pressure

    High Pressure, GB-HP and G-HP

    For long and/or high resistance ductwork

    Low volume/high pressure

    3

    Model Comparison

    Model

    Location Mounting Airow ApplicationDriveType

    ImpellerType

    Performance

    RelativeCost

    Outdoor

    Indoor

    RoofCurb

    Base/Floor

    Hanging

    Wall

    CeilingMounted

    Exhaust

    Supply

    Reversible

    Recirculate

    General/CleanAir

    ContaminatedAir

    SparkResistant

    Grease(UL762)

    SmokeControl(UL)**

    HighWind(150mph)*

    ContinuousHighTemp

    (above200F)

    Belt

    Direct

    Centrifugal

    Propeller/Axial

    MixedFlow

    MaximumVolume

    (cfm)

    MaximumStatic

    Pressure

    (in.wg)

    G 6,308 15 $

    GB 44,700 325 $

    *High wind limited to sizes 300 and smaller

    **Smoke Control available on models: 101, 101HP, 121, 131, 141, 141HP, 161, 161HP, 200, 240, 300, 360, 420 and 480

  • 8/2/2019 Exchust Fan information

    4/52

    Construction FeaturesModels G and GB

    4

    Standard Construction Features

    Wheel

    An aluminum, backward-inclined, non-overloading centrifugal wheel is utilized togenerate high-eiciency and minimal sound Wheel cones are careully matched tothe venturi for maximum efficiency. Each wheel is robotically welded and staticallyand dynamically balanced or long lie and quiet operation

    DisconnectSwitch

    NEMA-1 switch is factory mounted and wiring is provided from the motor as standard(other switches are available). All wiring and electrical components comply with theNational Electrical Code (NEC) and are either UL Listed or Recognized.

    Fan ShatPrecisely sized, ground and polished so the first critical speed is at least 25% overthe maximum operating speed. Where the shaft makes contact with bearings, tighttolerances result in longer bearing lie

    Bearings100% factory tested and designed specifically for air handling applications with aminimum L10 lie in excess o 100,000 hours (L50 lie o 500,000 hours)

    Motor Careully matched to the an load and is mounted out o the airstream

    Motor CoverConstructed of aluminum, machine-punched, and attached with fasteners that provideor easy removal and access to motor compartment and drive assembly

    Motor CoolingCooling fins located on top of the fan wheel draw outside air through a large spacebetween the fan shroud and the motor cover directly into the motor compartment.Positive motor cooling with fresh air results in maximum motor life.

    Liting Points Various lifting points are located on the drive frame and bearing plate (on select sizes).

    True VibrationIsolation

    Vibration isolators, with no metal-to-metal contact, support the drive assembly andwheel for long life and quiet operation.

    Drive AssemblyBelts, pulleys, and keys are oversized 150% of driven horsepower. Machined castpulleys are adjustable or inal system balancing Belts are static-ree and oil-resistant

    Lower WindbandHeavy-gauge aluminum with formed edges for added strength and providesweather resistance.

    Curb CapCurb cap (with integral deep spun venturi) is constructed of aluminum and is one-piece

    for a weather-tight fit.Internal ConduitChase

    A large diameter conduit for installing electrical wiring through the curb cap into themotor compartment

    Nameplate Permanent stamped aluminum plate or exact model and serial number identiication

    Galvanized

    BirdscreenRigid wire protects the fan discharge from birds and small objects.

    Fan ShroudOne-piece, heavy-gauge aluminum with a rolled bead for extra strength directsexhaust air downward.

    Mounting Holes Curb cap has prepunched mounting holes to ensure correct attachment to the roo

    6

    1

    2

    3

    4

    5

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    High Wind Construction Features

    Internal SupportsHeavy-gauge supports and bracing are added for additional strength to withstanda wind of 150 mph (75 ps)

    ReinorcedWind Band

    High wind fans include additional reinforcement for maximum strength.

    Roo Curb(page 10)

    High wind load fans are certified for use with Greenheck model SD, SDP, GPF orequivalent in high wing applications. Roof curbs ship separate for field installationwith attachment details provided.

    18

    19

  • 8/2/2019 Exchust Fan information

    5/525

    Construction FeaturesModels G and GB

    8

    8

    DRIVE FRAME(BELT DRIVE)

    MODEL GDIRECT DRIVE

    15

    12

    11

    7

    6

    5

    1

    14

    18

    17

    16

    9

    8

    4

    3

    2

    19

    10

    MODEL GBBELT DRIVE

    13

  • 8/2/2019 Exchust Fan information

    6/52

    With changes in building codes and standards more equipment isbeing required to be seismically certifed in areas o the country not

    commonly thought of as being in seismically active zones.The International Building Code (IBC) is designed to provide modelcode regulations that saeguard public health and saety in all UScommunities This code is intended to improve the perormance anddesign o non-structural systems subject to seismic events

    The State o Caliornia, one o the most active seismic areas in theUnited States, has the Ofce of Statewide Health Planning and

    Development (OSHPD) to regulate the design and construction ohealthcare acilities to ensure they are sae and

    capable o providing services to the public atera seismic event. OSHPD developed their own

    unique certifcation process to incorporatethe IBC and ASCE testing standards toensure equipment remains operable ater aseismic event

    ApplicationsG and GB models

    6

    SeismicTesting Criteria

    All Greenheck seismically certiied models have been tested using the most severe seismic event thatis ound on the Spectral Response Map per IBC Figures 16135 (1-2) Our testing is perormed underthe worst case scenario using the highest mapped seismic load, highest level occupancy category,worst case site class, and highest code mandated importance factor, thereby allowing Greenhecks

    seismically certified fans to be used anywhere in the United States under any conditions

    Caliornia OSHPD

    Test Protocols

    The California Office of Statewide Health Planning and Development (OSHPD) requires all certifiedmodels be shake table tested in accordance with ICC ES AC-156, in which the fans are physically

    subjected to the same or greater forces than they will see during a seismic event. SubjectingGreenheck model G and GB fans to this type of testing ensures the fans will operate withoutproblems ater a seismic event

    OSHPD Certiication

    No 0148-10The OSHPD certification numbers and supporting documents can be viewed on OSHPDs

    website ensuring that the fan has been subjected to and passed rigorous testing standards.

    State LicensedPE Calculations

    When using the fans in applications which are not covered by California OSHPD standards,

    Greenheck models G and GB have been certiied by a third party engineering irm to IBC 2006, 2009and ASCE 7-05 standards These engineers hold proessional engineering (PE) licenses in all 50states, so no matter where your job is located, you are backed by a P.E. signature for your state.

    CertiiedIndependentThird-Party Testing

    All Greenheck seismically certiied an models have gone through extensive testing proceduresGreenheck models G and GB have been certiied to IBC 2006, 2009, ASCE 7-05 and CaliorniaOSHPD standards through both engineering calculations and shake table testing o all models byindependent third party engineering irms

    Seismic - G and GB

    Protocols designed for seismic standards:

    When you buy a Greenheckmodel GB with the smoke

    control option, you receive a

    fan with the industrys bestperormance and durability orsmoke control applications (asound in emergency smokecontrol systems)

    UL/cUL Listed or 500F (260C) or 4 hours and1,000F (538C) or 15 minutes

    Half the weight of traditional smoke control fans,

    ideal choice or roo load concerns Low profile, height is less than half of traditional

    smoke control ans, maximum o 5212 inches(1334 mm) rom curb cap to top o an

    Multiple applications, capable o exhaustinggeneral clean air and satisying emergency smokecontrol regulations

    Emergency Smoke Control - GB

    GB smoke control models are:101, 101-HP, 121, 131, 141, 141-HP,161, 161-HP, 200, 240, 300, 360,420, 480

  • 8/2/2019 Exchust Fan information

    7/527

    High Wind and Hurricane - G and GBGreenheck is leading the High Wind Standard or roo top ans andventilators. Forceful winds and wind-borne debris are the cause of

    most hurricane damage. Hurricane winds start at 75 mph. At speeds

    over 150 mph, wind can exert a force of 75 pounds per square foot

    of pressure or over 900 pounds on a fan and curb. Forceful winds arenot the only problem, wind-borne debris can also cause detrimental

    effects to objects and structures. High winds and extreme forces

    are the cause of most storm damage. By analyzing calculations,

    computer simulations, actual testing, and other standardsGreenheck developed the High Wind Standard

    StructuralPerormance Load

    A static load that is 15 times the design load (915 pounds per square oot o pressure) is appliedboth positively and negatively to simulate wind force loads in each direction. Structural Performanceper Dade County Protocol TAS-202 (ASTM-E330)

    Miami-Dade CountyTest Protocols

    Greenheck worked with Miami-Dade County to outline a High Velocity Hurricane Zone standard forrooftop fans. Greenheck model USGF was the first rooftop fan certified and approved by the Miami-

    Dade Building Code Compliance oice and Texas Department o Insurance or use in hurricanezones. Models G and GB have been certified by an independent third party to the ASTM E-330 Static

    Pressure Dierence Standard, Florida Building Code Test Protocol TAS-201 (large missile impact),202 (static pressure dierence) and 203 (cyclic pressure) Static Pressure Dierence

    Miami-Dade NOANumbers

    The certifications can be viewed on the Miami-Dade County website under the NOA numbers listedbelow. Models G and GB are the first downblast aluminum fans in the industry that have received

    a Miami-Dade NOA for high wind (150 mph) and hurricane zones. Miami-Dade NOA 09-0624.09 for

    models G and GB

    Florida ProductApproval

    Florida Product Approval ensures that products which have been approved can be used anywhere in

    the State of Florida which are not governed by the Miami-Dade County high wind regulations. More

    information can be found on the Florida Building Code website. Florida Product Approval FL13225.1

    or models G and GB

    State LicensedPE Calculations

    Structural calculations perormed by a licensed Proessional Engineer (PE) on models G and GBinclude Finite Element Analysis (FEA) and a stamped PE report o the ans compliance to ASCE7-02 Minimum Design Loads or Buildings and Other Structures Standard and the Florida BuildingCode The ASCE 7-02 Standard meets the IBC, Florida and Miami-Dade codes The models havebeen proven to withstand winds in excess of 150 mph (75 psf).

    Computational FluidDynamics (CFD)

    All Greenheck high wind models have been analyzed using Computational Fluid Dynamics (CFD).CFD is computer software designed to simulate the flow of high speed (150 mph) winds over the

    surface of objects. The software records the force profile exerted on the fan so it can be utilized

    in Finite Element Analysis (FEA)

    Finite ElementAnalysis (FEA)

    Utilizing the results from CFD analysis, Greenheck can accurately predict the stress, strain,

    and deflection resulting from high wind loads. Greenheck high wind units have been proven

    to withstand 150 mph winds through Finite Element Analysis utilizing CFD results.

    Protocols designedto protect against wind bornedebris and severe wind loads:

    U.S. continentaveraged

    tornado requency.

    Atlantic, Gul and Pacifc history o major hurricane tracks.

    ApplicationsG and GB models

  • 8/2/2019 Exchust Fan information

    8/52

    Vari-Green Motor - Model G

    Greenhecks electronically commutatedVari-Green (VG) motor combines motortechnology, controllability and energy-

    efciency into one single low maintenance unit andis the industrys frst ully controllable motor Whencombined with Greenhecks G fans all the CFM

    and static pressureranges o a belt drivecan be attained with

    the benefts o adirect drive

    The Vari-Greenmotor is available in115 volt single phasehorsepower; 1/4,

    1/2, 3/4 and50/60 Hz power.

    Benets

    Operates on AC power thats converted to DC

    providing a more efcient motor operation ascompared to an AC operation

    The motor can attain up to 85% efciency and

    reduce energy consumption

    Watt savings of 30-70% depending on RPM.

    Note:As motor speed is turned down, efciencystays constant as compared to an AC motor that

    decreases dramatically.

    Operates cooler than a standard AC motorA cooler motor has longer motor lie and reducesenergy consumption

    80% usable RPM turndown vs. 30%,see chart

    G fans with Vari-Green motors can provide all

    the CFM and static pressure ranges o acomparable belt drive

    Maintenance costs are reduced as there areno belts or bearings to replace and no pulleysto adjust

    8

    Options

    $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

    100

    80

    60

    40

    20

    0%

    Time of Day

    HypotheticalVariable Volume - Load Shape

    %o

    fOperation

    Series 1

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

    100

    80

    60

    40

    20

    0%

    Time of Day

    Constant Volume - Load Shape

    %o

    fOperation

    Series 2

    Demand controlled ventilation oers signiicant energy savings by

    exhausting only the necessary amount o air throughout the day.

    Variable VolumeVariable volume or demand ventilation oerssignifcant energy savings by only exhausting airwhen necessary throughout a day. This type of

    application can greatly reduce the operating costsassociated with air conditioning and heating. Either

    a Vari-Green motor or standard VFD compatiblemotor can function within a variable volume system

    and help reduce energy consumption

    600

    500

    400

    300

    200

    100

    0

    0 350

    50% 75% 100%

    1750FAN SPEED (RPM)

    INPUT

    POWER(WATTS)

    EnergySavings

    G-123with PSC

    Not recommended

    GB-123Single Phase*

    G-123 with

    * GB is a belt driven fan

    Length of each curve indicates the practicalturndown range. Data is for 1/2 hp motorswith load of 0.35 BHP at full speed.

    E

    S

    The length o each curve indicates the practical turndown range.Data is or 1/2 hp motors with load o 0.35 Bhp at ull speed

    Motor Turndown Comparison

    Features

    1 Vari-Green dial on motor controlA potentiometer (dial on motor control) ismounted right on the motor or easy speedadjustment or system balance Simply turn adial instead o adjusting belts and pulleys

    2 Control wire inputsInputs provide a 0-10V DC signal to the motorrom Building Automated System sensors or othercontrols to adjust motor speed

    Direct drive fans are often preferred where

    maintenance access is difcult

    The Vari-Green motor reduces noise and vibrationas well as providing solutions for variable volume

    system balancing

    1

    2

  • 8/2/2019 Exchust Fan information

    9/529

    Options

    Fan Price VFD Price

    Example: Initial Cost Comparison

    Belt Drive vs. Direct Drive Vari-Green

    $0 100 200 300 400 500 600 700

    GB-121

    G-123-VG

    The diagram shows how the overall cost o a an with a directdrive Vari-Green motor is less than the cost to purchase a beltdrive and add a VFD to it.

    Demand controlled systems reduce the energyconsumed by decreasing the speed o the an andenergy used by the motor The system controlswill lessen the amount of conditioned air that is

    exhausted, urther reducing the total operating costs

    A 0-10 VDC control signal is easily used inconjunction with:

    BAS - Building Automation System

    GreenVent System Controls - or constantpressure

    CO2 Sensors - Monitors carbon dioxide levels

    VOC Sensors - Monitors a range o volatileorganic compounds

    Motion Detectors - Monitors occupancy

    For additional inormation reer to the Vari-Green

    Motor brochure.

    $2,000-

    1,750-

    1,500-

    1,250-

    1,000-

    750-

    500-250-

    $-

    Variable Volume vs. Constant Volume

    Variable Volume Constant Volume

    Heating Cost ($/yr) Cooling Cost ($/yr) Fan Operating Cost

    Example o

    potential saving

    based on a

    northeast city in

    the USA using a

    GreenVent System.

    Example

    Cost/Savings

    Comparisons

    Demand Control Ventilationor multi-story buildings

    Applications requiring constant pressurecontrol or variable volume as used inmulti-storied buildings such as hotels,multi-amily complexes, institutional

    acilities, and high rise commercial buildings,may utilize G fans with Vari-Green motor and

    Vari-Green control

    The Vari-Green constant pressure controlis preprogrammed and easy to install orapplications that includeventing dryers,bathrooms, residential type kitchen space orindustrial process exhaust

    Reer to the GreenVent Systems brochure ormore detailed inormation on beneits and

    energy savings.

    LEED information

    Greenheck became one o the frstmanuacturers in the Air Movement andControl industry to join the LEED/greenmovement when they joined the United States

    Green Building Council (USGBC) in 2005Greenheck has been actively researchingqualifcation requirements or our products tomeet LEED credits and prerequisites

    The Vari-Green motor signifcantlyhelps qualifcation eorts or theEnergy and Atmosphere credits and

    prerequisites specifcally credit one,Optimize Energy Performance and prerequisite

    two, Minimum Energy Performance.

    Vari-Green Controls

    Remote mounted dial wall mounted dial allowsan to be controlled at point o use and includesa transducer

    Two-speed control provides the ability topreset a high and low at the fan and control with a

    timed position switch at the point of use.

    Transformer reduces 115V power to 24V power

    Constant pressure maintains negative pressure(-1.0 wg to = 1.0 wg) for applications such as

    bathrooms, dryers, ilters, etc

  • 8/2/2019 Exchust Fan information

    10/52

    Options and Accessories

    10

    Roo Curbs

    Preabricated roo curbs reduce installation timeand costs by ensuring compatibility between

    the an, the curb and roo opening All curbs areinsulated with fiberglass. A wide variety of roof

    curbs are available, including: langed, pitched andsound-absorbing

    Hinged Curb Cap with Cables (Field Installed)

    Mounted to the curb cap, allows entire fan to tilt

    away from curb for access to wheel and ductwork.

    Includes restraint cables

    Hinged Base(Factory Mounted)

    Allows for easy

    maintenance Hinge andrestraining cables areactory mounted to asubbase attached directlyto curb without additional

    height added

    Curb Seal

    Rubber seal between fan and curb to assure proper

    sealing when attached to a curb.

    Curb Extensions

    Extensions raisethe an dischargeabove the roolineand provide anaccessible mountinglocation or dampers Insect screenbases, constructed with a removable fine mesh, are

    recommended for applications where insect entry

    must be prevented

    High Wind and Severe Duty Roo Curbs

    Provided as an option with models G and GB. The

    severe-duty roo curb models can ship separatelyto allow for final finishing of the roof prior to the fan

    arrival and installation

    Model GPF This roo curb is used on an modelsG/GB and specifically designed for high windapplications up to 75 ps Curbs are minimum18 gauge construction in a standard height o12 inches (305 mm), with fully-welded straight sidesand a 5-inch lashing lange GPF is available up to24 inches (460 mm) in height to meet greater heightrequirements

    Models SD and SDP These severe-duty curbsor an models G and GB are speciically designedfor high wind applications up to 150 mph, maximum

    design load o 130 ps Model SD is or use onlat roos and model SDP or pitched roos Theyare attached directly to the building structure with

    extremely high structural design load requirementsThe severe duty curbs are 12 gauge coated steelwith a 134-inch lip on the top and a 4-inch lange onthe bottom Available heights include 1224 inchesHeights greater than 18 inches are reinorced in theinterior with 12 gauge x 2-inch angles.

    Mounting details or the roo curb to the roosubstrate and the fan to the curb are included with

    each model G and GB installation manualFor additional inormation reer to the Greenheck

    High Wind brochure.

    Tie-Down PointsFour brackets located onthe shroud or securingthe fan in high wind

    applications Cables andanchors by others

  • 8/2/2019 Exchust Fan information

    11/521

    Speed Controllers orStandard Motors

    Available for use with shaded

    pole and permanent splitcapacitor (PSC) open motorson model G ans They providean economical means o systembalancing with direct drive fans.

    Disconnect Switches

    A wide selection of NEMA rated

    switches are available for positive

    electrical shuto and saety,including: dust-tight, rainproo,and corrosion-resistantSwitches may be internally

    or externally mounted

    Dampers

    Designed to preventoutside air rom enteringback into the buildingwhen fan is off. Includes

    gravity and motorized

    dampers. Damper sizes

    are shown on each

    perormance data page

    Birdscreen

    Galvanized mesh is standard,

    optional aluminum or stainlesssteel rigid wire are also available.

    Options and Accessories

    G and GB models are Listed or electrical (UL/cUL 705)File no E40001

    GB models or Emergency Smoke Control Systems

    (UL/cUL Listed or 500F (260C) or 4 hours and1,000F (538C) or 15 minutes) File no MH17511

    Note: UL/cUL is optional and must be speciied.

    Coatings

    A wide variety of coatings and colors are available.

    Greenheck coatings and resistance charts can beound in the Perormance Coatings Commercialand Industrial Fans catalog and in our Product

    Application GuidePerormance Coatings orVentilation Products

    Primer is applied at the factory to allowor fnal fnish in the feld

    Permatector is our standard coatingTypically used or applications thatrequire corrosion resistance in indoorand outdoor environments

    Hi-Pro Polyester is resistant to saltwater, chemical fumes and moisture

    in more corrosive atmospheres

    Typically used or applications thatrequire superior chemical resistance,excellent abrasion and outdoor UVprotection This coating exceedsprotective qualities o Air DriedHeresite and Air Dry Phenolic

    Baked Enamel Decorative Coatingsare heat cured enamels appliedeither as wet paints or electrostatic

    powders. Customers can choose from

    16 standard decorative colors or colormatch any color

    PERMATECTORTM

    HI-PRO

    POLYESTER

    PRIMER

  • 8/2/2019 Exchust Fan information

    12/5212

    Typical InstallationsModels G and GB

    Note: The typical installations shown are recommendations

    based on national codes. Local authority may supersede these

    recommendations.

    General Clean Air(igure 1)

    Models G and GB exhaust ans are designed tomeet the needs o general clean air applicationsTests were conducted to assure safe, rugged and

    reliable ans

    Due to the varying types o airstreams encounteredin commercial ventilation, system designers mustbe aware of national, state, and local codes and

    guidelines governing these installations Local codeauthorities should be consulted beore proceedingwith any ventilation project.

    When rooing materials extend to the top o thecurb, roo curbs should be 112 inches (34 inch oneach side) less than the unit curb cap to allow

    or rooing and lashing

    For recommended duct size, damper size, and

    roo opening dimensions, reer to theperormance data pages (starting on t 14)

    Installation must include a means or inspecting,cleaning and servicing the exhaust an

    High Wind, Hurricane and Seismic (igure 2)

    Rooing materials can extend to the top o thecurb, roo curbs should be 1 inch(25 mm) total,or 12 inch (13 mm) on each side, less than the unitcurb cap to allow for roofing and flashing.

    RecommendedDuct and

    Damper Size

    RecommendedRoof Opening

    11/4in.(32 mm)

    3/4 in.(19 mm)

    Factory Wiredfrom Motor toDisconnect

    Wiring by

    Others

    8 or 12 in.(203 or 305 mm)

    Damper

    11/4in.(32 mm)

    Recommended

    Duct and

    Damper Size

    Recommended

    Roof Opening

    11/4in. (32 mm)

    1/2 in. (13 mm)

    Wiring by

    Others

    8 - 24 in.

    (203 - 610 mm)

    GPF or SD Curb

    Damper

    11/4in. (32 mm)

    1/4 in. (6 mm)

    Fastener

    4 in. (102 mm)

    From Curb Edge

    Wheel Rotation

    Direction of rotation is very critical. Rotation in the wrong direction will result

    in excessive horsepower, possible motor burnout, and increased noise levels.

    Check rotation by energizing the unit only momentarily. The rotation should bethe same as the rotation decals afxed to the unit and is clockwise when viewed

    rom the top o the unit

    Clockwise

    igure 1

    igure 2

  • 8/2/2019 Exchust Fan information

    13/521

    VG = Vari-Green(Direct Drive only)

    Motor HP(Belt Drive only)6 = 1/6 10 = 1 50 = 54 = 1/4 15 = 1 75 = 73 = 1/3 20 = 2 100 = 105 = 1/2 30 = 3 150 = 157 = 3/4

    Motor RPM(Direct Drive only)A = 1725 D = 1550B = 1140 E = 1050C = 860 G = 1300

    International(See CAPS or perormance)

    K= 950 RPM J = 1475 RPM

    Fan Inlet Connections

    In order to assure proper an perormance, cautionmust be exercised in an placement and connectionto the ventilation system Obstructions, transitions,poorly designed elbows, improperly selecteddampers, etc, can cause reduced perormance,excessive noise, and increased mechanical stressFor perormance to be as published, the systemmust provide uniform and stable airow into the fan.

    Provide uniform airflow at fan inlet to assure

    optimum perormance

    Provide uniform airflow at fan inlet and

    through the damper to assure optimumperormance

    Dampers must open fully. Use motorized

    dampers in low airflow applications to

    reduce losses

    Avoid sharp turns or entrance conditionswhich cause uneven flow. Use turning vanes

    in elbows to reduce adverse effects.

    Typical InstallationsModels G and GB

    Good

    Good

    PoorPoor

    A

    C D

    B

    Model Number Code

    The model number code system is designed to completely identiy the an The correct code lettersmust be speciied to designate belt or direct drive The remainder o the model code is determinedby the size and performance.

    A

    C

    D

    B

    Fan Size

    060 through 540

    Wheel Pressure LevelHP - High Pressure

    GB - 240 HP - VG/5/A - X

    ConigurationG - Direct Drive

    GB - Belt Drive

    X = UL 705F = UL 762

    Smoke Control Systems

  • 8/2/2019 Exchust Fan information

    14/52

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    3Volume (m/hr )

    RPM (Direct)

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    14

    Roof Downblast - ExhaustDirect DriveG-060 G-065

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Damper Size = 8 x 8 (203 x 203)Roof Opening = 10 x 10 (267 x 267)

    Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 15 lbs. (7 kg)

    All dimensions in inches (millimeters) *May be greater depending on motor^Weight shown is largest cataloged Open Drip-Proof motor.

    MotorHP

    FanRPM

    Static Pressure in Inches wg

    0 005 01 0125 015 02 025 03 0375 04060

    E-1/200 1050CFM 138 116 90 73 53BHP 000 000 001 001 001

    Sones 17 17 17 17 17

    G-1/100 1300CFM 170 153 135 125 113 85BHP 001 001 001 001 001 001

    Sones 29 28 28 27 27 26

    D-1/60 1550CFM 203 188 173 166 158 140 120 92BHP 001 001 001 001 002 002 002 02

    Sones 42 39 38 38 38 37 37 36065

    E-1/100 1050CFM 187 161 130 110 87BHP 001 001 001 001 001

    Sones 22 21 19 18 17

    G-1/60 1300CFM 231 211 189 178 163 130 92BHP 001 001 001 001 001 001 001

    Sones 32 31 30 29 29 28 27

    D-1/30 1550CFM 276 259 241 232 223 201 176 145 96BHP 002 002 002 002 002 002 002 002 002

    Sones 49 46 45 45 44 43 43 41 40

    E-1050-RPM G-1300-RPM D-1550-RPM

    134(44)

    1938(492)

    *1218(308)

    17(432)

    3 (76)

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    15/521

    MotorHP

    FanRPM

    Static Pressure in Inches wg

    0 005 01 0125 015 02 025 03 0375 04070

    E-1/100 1050CFM 253 226 195 179 152BHP 001 001 001 001 001

    Sones 27 21 17 15 12

    G-1/60 1300CFM 314 292 269 257 244 214 171BHP 001 001 002 002 002 002 002

    Sones 41 37 34 33 32 29 26

    D-1/30 1550

    CFM 374 356 337 327 317 297 274 244 190BHP 002 002 002 003 003 003 003 003 003

    Sones 56 54 52 52 51 49 47 45 41075

    E-1/80 1050CFM 297 260 222 200 176BHP 001 001 001 001 001

    Sones 36 31 29 28 26

    G-1/50 1300CFM 367 338 309 293 277 241 195BHP 002 002 002 002 002 002 002

    Sones 41 39 37 37 37 36 35

    D-1/25 1550CFM 438 413 389 377 364 337 309 277 214BHP 003 003 03 004 004 004 004 004 003

    Sones 61 58 56 54 53 51 49 49 48

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    3Volume (m/hr )

    RPM (Direct)

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    Damper Size = 8 x 8 (203 x 203)Roof Opening = 10 x 10 (267 x 267)

    Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 15 lbs. (7 kg)

    All dimensions in inches (millimeters) *May be greater depending on motor^Weight shown is largest cataloged Open Drip-Proof motor.

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Roof Downblast - ExhaustDirect DriveG-070 G-075

    E-1050-RPM G-1300-RPM D-1550-RPM

    134(44)

    1938(492)

    *1218(308)

    17(432)

    3 (76)

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    16/52

    0 100 200 300 400 500 600 700 800 900 1000

    0

    20

    40

    60

    80

    100

    120

    140

    160

    180

    200

    220

    0 100 200 300 400 500 6000.0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0.9

    085-E

    085-G

    085-D

    085-VG

    080-VG

    080-D

    080-G

    080-E

    RPM (Direct Drive)

    RPM (Vari Green)

    Density 0.075 lb/ft3

    StaticPressure(in.wg)

    Volume (cfm)

    m3/hr

    StaticPressure(Pa)

    Volume ( )

    DO

    NOT

    SELECTTOTHELEFT

    OFTHIS

    SY

    STEM

    CURVE

    Density 1.2 kg/m3

    16

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Damper Size = 10 x 10 (254 x 254)Roof Opening = 12 x 12 (318 x 318)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 19 lbs. (9 kg)

    All dimensions in inches (millimeters) *May be greater depending on motor^Weight shown is largest cataloged Open Drip-Proof motor.

    Roof Downblast - ExhaustDirect DriveG-080 G-085

    DirectDrive

    MotorHP

    FanRPM

    Static Pressure in Inches wg

    0 01 0125 015 02 025 03 0375 05 0625080

    E-1/40 1050CFM 335 268 249 230 189 134BHP 001 002 002 002 002 002

    Sones 38 37 36 37 39 42

    G-1/30 1300CFM 415 361 348 333 303 272 239 174BHP 002 003 003 003 003 003 003 003

    Sones 54 54 54 54 54 55 56 59

    D-1/20 1550CFM 495 450 439 427 404 379 354 314 237BHP 004 004 004 005 005 005 005 006 006

    Sones 73 73 73 73 73 72 73 73 76

    1725CFM 551 511 501 490 469 449 426 392 332 260BHP 005 006 006 006 006 007 007 007 008 008

    Sones 91 91 91 91 9 89 89 89 91 94085

    E-1/40 1050CFM 398 326 307 286 240 179BHP 001 002 002 002 002 002

    Sones 4 39 39 39 41 43

    G-1/30 1300CFM 493 436 420 405 375 340 302 233BHP 002 003 003 003 003 004 004 004

    Sones 55 53 53 53 53 53 54 55

    D-1/20 1550CFM 588 541 528 515 490 464 439 394 308 168BHP 004 004 005 005 005 005 006 006 006 006

    Sones 76 74 74 74 74 74 74 74 76 81

    1725CFM 654 612 602 590 567 544 521 486 419 340BHP 005 006 006 006 007 007 007 008 008 009

    Sones 95 94 94 93 93 93 93 93 94 94

    E-1050-RPM G-1300-RPM D-1550-RPM VG-1725-RPM

    VG - Vari-Green is a direct drive brushless DC motor.

    134(44)

    2134(552)

    *1458(371)

    17(432)

    4 (102)

    Direct Drive RPM

    VG-1/4

    VG-1/4

  • 8/2/2019 Exchust Fan information

    17/52

    0 500 1000 1500 2000

    0

    50

    100

    150

    200

    0 200 400 600 800 1000 12000.0

    0.2

    0.4

    0.6

    0.8

    1.0

    095-E

    095-G

    095-D

    095-VG090-VG

    090-D

    090-G

    090-E

    RPM

    RPM (Vari Green)

    Density 0.075 lb/ft3

    StaticPressure(in.

    wg)

    Volume (cfm)

    Volume ( )

    Static

    Pressure(

    Pa)

    m3/hr

    DON

    OTSELE

    CT

    TOTH

    ELEFT

    OFTHIS

    SYSTEM

    CU

    RVE

    Density 1.2 kg/m3

    1

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    DirectDrive

    MotorHP

    FanRPM

    Static Pressure in Inches wg

    0 01 0125 015 02 025 03 0375 05 0625090

    E-1/40 1050CFM 520 441 420 398 351 293BHP 001 002 002 002 002 002

    Sones 4 39 39 4 41 42

    G-1/25 1300CFM 644 580 565 549 515 478 440 373BHP 003 003 004 004 004 004 004 005

    Sones 54 54 54 54 54 55 55 56

    D-1/15 1550CFM 768 714 701 688 662 633 605 557 473 338BHP 005 005 006 006 006 006 007 007 008 007

    Sones 76 75 75 75 75 74 74 74 74 78

    1725CFM 855 806 794 782 759 735 709 671 600 522BHP 006 007 007 008 008 008 009 009 010 011

    Sones 97 95 95 95 95 94 94 92 91 91095

    E-1/30 1050CFM 717 606 570 534 468 389 290BHP 003 003 004 004 004 004 003

    Sones 54 45 45 45 44 45 46

    G-1/12 1300CFM 888 802 780 754 695 640 586 493 184BHP 006 006 006 006 007 007 007 007 005

    Sones 76 68 67 66 65 64 64 64 68

    D-1/8 1550CFM 1059 987 969 950 912 863 814 745 623 474BHP 010 010 010 011 011 011 011 012 012 011

    Sones 96 94 93 92 9 88 87 87 87 87

    1725CFM 1179 1114 1098 1081 1048 1013 969 903 800 688BHP 013 014 014 014 015 015 015 016 016 016

    Sones 114 114 114 115 114 112 11 109 113 113

    E-1050-RPM G-1300-RPM D-1550-RPM VG-1725-RPM

    VG - Vari-Green is a direct drive brushless DC motor.

    Damper Size = 10 x 10 (254 x 254)Roof Opening = 12 x 12 (318 x 318)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 22 lbs. (10 kg)

    All dimensions in inches (millimeters) *May be greater depending on motor^Weight shown is largest cataloged Open Drip-Proof motor.

    Roof Downblast - ExhaustDirect DriveG-090 G-095

    134(44)

    2134(552)

    *1458(371)

    17(432)

    4 (102)

    Direct Drive RPM

    VG-1/4

    VG-1/4

  • 8/2/2019 Exchust Fan information

    18/52

    DONOT

    SELECTT

    OTHELEFT

    OF

    THIS

    SYSTEMCU

    RVE

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    3Volume (m/hr )

    RPM (Belt)

    RPM (Direct)

    RPM (Vari-Green)

    HP

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    18

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Motor HP FanRPM

    Static Pressure in Inches wg

    Belt Direct 0 0125 025 0375 05 0625 075 0875 1 1125071 097

    1/6

    or

    1/8

    VG-Var

    i-GreenisadirectdrivebrushlessDCmotor.

    720CFM 157 107BHP 001 001

    Sones 18 20

    790CFM 172 128 70BHP 001 001 001

    Sones 23 23 22

    C-1/8 860CFM 187 148 101BHP 002 002 002

    Sones 28 27 27

    930CFM 203 166 124BHP 002 002 002

    Sones 33 34 32

    1000CFM 218 184 146 100BHP 003 003 003 002

    Sones 39 40 39 36

    1070CFM 233 202 167 130BHP 003 003 003 003

    Sones 46 47 45 42

    B-1/6 1140CFM 248 220 187 152 109BHP 004 004 004 004 003

    Sones 53 54 51 49 47

    1285CFM

    280 255 228 197 166 127BHP 006 006 006 005 005 005Sones 68 67 66 63 60 59

    1435CFM 313 292 265 240 212 185 151BHP 008 008 008 008 008 007 007

    Sones 80 80 79 76 73 71 69

    1580CFM 344 324 302 281 255 230 205 177 140BHP 010 010 010 010 010 010 010 009 009

    Sones 95 95 94 91 88 85 83 81 79

    A-1/4 1725CFM 376 356 339 316 297 273 250 227 205 171BHP 013 013 013 013 013 013 013 013 012 012

    Sones 113 112 112 108 105 102 99 97 95 93

    VG-1/4

    C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM

    Roof Downblast ExhaustBelt & Direct DriveGB-071 G-097

    Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 54/60 lbs. (24/27 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    MAXIMUM BHP AT A GIVEN RPM = (RPM/3371)3

    MAXIMUM RPM - GB-071=1710, G-097=1725TIP SPEED (ft/min) = RPM x 2.929

    MAXIMUM MOTOR FRAME SIZE = 56

    134(44)

    2438(619)

    438(111)

    *2334(603)

    19(483)

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    19/52

    DONOT

    SELECT

    TO

    THE

    LEFT

    OFTHIS

    SYSTEM

    CURVE

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    3Volume (m/hr )

    RPM (Belt)

    RPM (Direct)

    RPM (Vari-Green)

    HP

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    1

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Roof Downblast ExhaustBelt & Direct DriveGB-081 G-098

    Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)

    Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 54/60 lbs. (24/27 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    134(44)

    2438(619)

    438 (111)

    *2334(603)

    19(483)

    Motor HP FanRPM

    Static Pressure in Inches wg

    Belt Direct 0 0125 025 0375 05 0625 075 0875 1 1125081 098

    1/6

    VG-Vari-GreenisadirectdrivebrushlessDCmotor.

    720CFM 361 272BHP 001 001

    Sones 30 27

    790CFM 396 315 181BHP 002 002 002

    Sones 35 32 3

    C-1/8 860CFM 431 358 261BHP 002 002 002

    Sones 40 37 34

    930CFM 466 399 323BHP 003 003 003

    Sones 46 44 40

    1000CFM 501 439 372 259BHP 003 004 004 004

    Sones 53 51 47 44

    1070CFM 536 478 416 338BHP 004 004 005 005

    Sones 59 58 54 50

    B-1/6 1140CFM 571 517 460 396 283BHP 005 005 006 006 005

    Sones 66 65 61 57 55

    1315CFM 659 612 564 513 456 362BHP 008 008 008 009 009 008

    Sones 83 81 78 74 70 69

    1490CFM 746 706 663 621 574 525 452 353BHP 011 012 012 012 012 012 012 011

    Sones 101 99 98 93 89 86 85 84

    1670CFM 836 800 763 725 686 645 603 550 466 377BHP 016 016 016 017 017 017 017 018 017 016

    Sones 120 119 117 114 110 107 104 101 100 99

    1/4 A-1/4 1725CFM 864 829 793 756 719 679 640 592 527 441BHP 017 018 018 018 019 019 019 019 019 018

    Sones 127 125 123 121 117 114 111 108 106 105

    MAXIMUM BHP AT A GIVEN RPM = (RPM/2985)3

    MAXIMUM RPM - GB-081=1710, G-098=1725TIP SPEED (ft/min) = RPM x 2.929

    MAXIMUM MOTOR FRAME SIZE = 56

    C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM

    VG-1/4

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    20/52

    DONOT

    SELECT

    TOTH

    EL

    EFT

    OF

    THIS

    SYSTEM

    CUR

    VE

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    3Volume (m /hr )

    RPM (Belt)

    RPM (Direct)

    RPM (Vari-Green)

    HP

    Density 0.0 75 lb/ft3

    Density 1.2 kg/m3

    20

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)

    Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 54/61 lbs. (24/28 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    134(44)

    2438(619)

    438(111)

    *2334(603)

    19(483)

    Motor HP FanRPM

    Static Pressure in Inches wg

    Belt Direct 0 0125 025 0375 05 0625 075 0875 1 1125091 099

    1/4

    VG-Vari-GreenisadirectdrivebrushlessDCmotor.

    720CFM 546 403BHP 002 002

    Sones 36 35

    790CFM 599 471 291BHP 002 002 002

    Sones 42 41 39

    C-1/8 860CFM 652 536 400BHP 003 003 003

    Sones 49 47 45

    930CFM 705 598 481BHP 004 004 004

    Sones 56 55 51

    1000CFM 758 659 552 414BHP 004 005 005 005

    Sones 64 62 58 56

    1070CFM 811 718 621 512BHP 005 006 006 006

    Sones 73 71 67 63

    B-1/6 1140CFM 864 777 687 590 457BHP 007 007 007 007 007

    Sones 83 81 76 71 68

    1285CFM 974 897 819 736 647 526BHP 009 010 010 010 011 010

    Sones 95 94 90 85 82 79

    1435CFM 1087 1018 949 877 801 721 615 404BHP 013 014 014 014 015 015 015 012

    Sones 107 106 104 100 96 93 90 84

    1580CFM 1197 1135 1072 1009 941 872 799 707 583BHP 017 018 019 019 019 020 020 020 019

    Sones 121 120 119 115 112 109 106 103 98

    A-1/4 1725CFM 1307 1250 1192 1135 1076 1013 949 883 806 707BHP 023 023 024 024 025 025 026 026 026 025

    Sones 136 135 134 132 129 126 123 120 118 115

    C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM

    Roof Downblast ExhaustBelt & Direct DriveGB-091 G-099

    MAXIMUM BHP AT A GIVEN RPM = (RPM/2703)3

    MAXIMUM RPM - GB-091=1710, G-099=1725TIP SPEED (ft/min) = RPM x 2.929

    MAXIMUM MOTOR FRAME SIZE = 56VG-1/4

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    21/52

    DONOT

    SE

    LECT

    TO

    THELEFTOFTHIS

    SYSTEM

    CURVE

    1350

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    3Volume (m /hr )

    RPM (Belt)

    RPM (Direct)

    RPM (Vari-Green)

    HP

    Density 0.07 5 lb/ft3

    Density 1.2 kg/m3

    2

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: f ree inlet hemispherical sone levels.

    Motor HP FanRPM

    Static Pressure in Inches wg

    Belt Direct 0 0125 025 0375 05 0625 075 0875 1 125101 103

    1/4

    VG-Vari-GreenisadirectdrivebrushlessDCmotor.

    720CFM 610 477BHP 002 002

    Sones 38 27

    C-1/8 860CFM 729 623 473BHP 003 004 004

    Sones 46 37 29

    1000CFM 848 753 654 481BHP 005 005 006 005

    Sones 55 48 44 34

    B-1/6 1140CFM 966 883 805 702 507BHP 007 008 009 009 008

    Sones 66 60 57 52 41

    1245CFM 1055 978 908 824 715BHP 010 010 011 011 011

    Sones 75 70 67 63 57

    1350CFM 1144 1073 1006 938 851 731BHP 012 013 013 014 014 014

    Sones 85 81 78 77 72 67

    1450CFM 1229 1162 1099 1041 965 878 750BHP 015 016 016 017 017 017 017

    Sones 93 90 87 84 80 75 69

    1555CFM 1318 1255 1196 1140 1079 1005 917 791BHP 019 019 020 021 022 022 022 021

    Sones 102 100 97 94 89 84 80 75

    1660CFM 1407 1348 1292 1238 1187 1122 1050 963 841BHP 023 023 024 025 026 026 026 026 025

    Sones 114 111 107 104 101 96 91 87 81

    1/3

    A-1/4 1725CFM 1462 1405 1351 1298 1250 1193 1126 1052 955BHP 025 026 027 028 029 029 029 029 029

    Sones 122 119 115 112 109 103 100 95 90

    1800CFM 1525 1471 1419 1368 1321 1270 1209 1142 1065 793BHP 029 030 030 031 033 033 033 033 033 030

    Sones 133 128 125 124 122 114 109 106 102 93

    Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 54/61 lbs. (24/28 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    134(44)

    2438(619)

    438(111)

    *2334(603)

    19(483)

    MAXIMUM BHP AT A GIVEN RPM = (RPM/2593)3

    MAXIMUM RPM = 1800TIP SPEED (ft/min) = RPM x 2.913

    MAXIMUM MOTOR FRAME SIZE = 56

    Roof Downblast ExhaustBelt & Direct DriveGB-101 G-103

    C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM

    VG-1/4

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    22/52

    DO

    NOT

    SELECTTOTH

    ELEFT

    OFTHIS

    SYSTEMCURVE

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    RPM (Belt)

    RPM (Direct)

    RPM (Vari-Green)

    HP

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    22

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Motor HP FanRPM

    Static Pressure in Inches wg

    Belt Direct 0 025 05 075 1 125 15 175 2 225101HP 103HP

    1/4

    VG

    -Vari-GreenisadirectdrivebrushlessDCmotor.

    1300CFM 571 477 342BHP 006 006 007

    Sones 66 57 53

    1445CFM 635 553 449 243BHP 008 009 009 008

    Sones 84 75 7 63

    1590CFM 699 626 537 417BHP 010 011 012 012

    Sones 104 95 91 83

    A-1/4 1725CFM 758 692 613 521 364BHP 013 014 015 016 015

    Sones 114 107 106 101 10

    1880CFM 826 767 697 618 518 337BHP 017 018 019 020 020 018

    Sones 127 122 119 12 114 119

    2025CFM 890 836 772 702 622 515 313BHP 021 023 024 024 026 025 022

    Sones 142 136 133 132 126 12 114

    1/3

    2137CFM 939 889 830 765 693 607 474BHP 025 026 028 028 029 030 028

    Sones 154 148 144 142 134 131 121

    2229CFM

    979 931 875 814 748 674 574 406BHP 028 030 031 032 033 035 033 031Sones 158 154 148 145 141 137 132 120

    1/2

    2336CFM 1026 981 928 871 809 742 661 543 358BHP 033 034 036 036 037 039 040 037 034

    Sones 164 16 154 149 147 14 141 135 136

    2500CFM 1098 1056 1008 956 901 840 775 695 583 416BHP 040 042 043 045 045 046 048 048 046 042

    Sones 178 174 169 167 158 155 148 152 157 166

    2550CFM 1120 1078 1032 982 928 869 807 735 639 497BHP 043 044 046 047 047 049 051 052 050 047

    Sones 182 179 174 172 163 161 151 156 162 172

    Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 58/63 lbs. (26/29 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    134(44)

    2438(619)

    438(111)

    *2334(603)

    19(483)

    MAXIMUM BHP AT A GIVEN RPM = (RPM/3165)3

    MAXIMUM RPM = 2550TIP SPEED (ft/min) = RPM x 2.978

    MAXIMUM MOTOR FRAME SIZE = 56

    Roof Downblast ExhaustBelt & Direct DriveGB-101HP G-103HP

    A-1725 RPM VG-2550-RPM

    VG-1/2

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    23/52

    DONOTS

    ELEC

    TTO

    THE

    LEFT

    OF

    THIS

    SYSTEM

    CURVE

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    3

    Volume (m /hr )

    RPM (Belt)

    RPM (Direct)

    RPM (Vari-Green)

    HP

    Density 0.07 5 lb/ft3

    Density 1.2 kg/m3

    2

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)

    Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 58/66 lbs. (26/30 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    134(44)

    2438(619)

    438(111)

    *2334(603)

    19(483)

    Roof Downblast ExhaustBelt & Direct DriveGB-121 G-123

    Motor HP FanRPM

    Static Pressure in Inches wg

    Belt Direct 0 0125 025 0375 05 0625 075 1 125 15121 123

    1/4

    VG-Vari-GreenisadirectdrivebrushlessDCmotor.

    580CFM 704 515BHP 002 002

    Sones 32 33

    720CFM 873 735 523BHP 003 004 004

    Sones 42 43 41

    C-1/8 860CFM 1043 932 796 580BHP 005 006 006 006

    Sones 54 55 52 52

    1000CFM 1213 1119 1013 883 694BHP 008 009 009 010 009

    Sones 67 68 67 64 64

    B-1/6 1140CFM 1383 1300 1213 1112 993 831BHP 012 013 014 014 014 014

    Sones 84 84 84 81 79 78

    1265CFM 1535 1460 1384 1299 1204 1093 950BHP 016 017 018 019 019 020 019

    Sones 102 101 101 99 97 96 94

    1395CFM 1692 1625 1557 1484 1404 1315 1214 907BHP 021 023 024 025 026 026 026 024

    Sones 125 124 123 122 120 117 115 113

    1/3

    1475CFM 1789 1726 1661 1594 1521 1441 1356 1132BHP 025 027 028 029 030 031 031 031

    Sones 135 134 133 132 130 127 124 120

    1550CFM 1880 1820 1759 1696 1629 1555 1475 1289 974BHP 029 031 032 033 034 035 036 036 033

    Sones 146 145 143 142 140 138 135 129 124

    1/2

    1635CFM 1983 1926 1868 1810 1747 1680 1608 1446 1231BHP 034 036 037 039 040 041 042 043 041

    Sones 159 158 156 154 153 150 148 139 134

    A-1/2 1725CFM 2093 2038 1984 1928 1871 1810 1743 1600 1426 1180BHP 040 042 044 045 046 047 048 050 050 047

    Sones 174 172 170 168 167 164 162 155 149 140

    C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM

    MAXIMUM BHP AT A GIVEN RPM = (RPM/2170)3

    MAXIMUM RPM = 1725TIP SPEED (ft/min) = RPM x 3.420

    MAXIMUM MOTOR FRAME SIZE = 56VG-1/2

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    24/52

    A

    DONOTSEL

    ECTTO

    THELE

    FTOF

    THIS

    SYSTEM

    CURVE

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    3

    Volume (m /hr )

    RPM (Belt)

    RPM (Direct)

    RPM (Vari-Green)

    HP

    Density 0.0 75 lb/ft3

    Density 1.2 kg/m3

    24

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Roof Downblast - ExhaustBelt & Direct DriveGB-131 G-133

    134(44)

    Damper Size = 12 x 12 (305 x 305)Roof Opening = 14 x 14 (368 x 368)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 62/67 lbs. (28/30 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    2838(721)

    4 (102)

    *2334(603)

    19(483)

    Motor HP FanRPM

    Static Pressure in Inches wg

    Belt Direct 0 0125 025 0375 05 0625 075 1 125 15131 133

    1/4

    VG-Va

    ri-GreenisadirectdrivebrushlessDCmotor.

    580CFM 823 626BHP 002 002

    Sones 45 45

    720CFM 1022 879 650BHP 004 004 004

    Sones 54 54 52

    C-1/8 860CFM 1221 1106 962 727BHP 006 007 007 007

    Sones 66 65 63 60

    1000CFM 1419 1323 1213 1075 867BHP 010 011 011 012 011

    Sones 81 80 77 74 70

    B-1/6 1140CFM 1618 1535 1444 1340 1211 1031BHP 015 016 016 017 017 017

    Sones 100 98 96 92 88 85

    1250CFM 1774 1698 1617 1528 1426 1133BHP 019 02 021 022 023 022

    Sones 120 117 113 110 105 97

    1315CFM 1866 1794 1718 1637 1545 1435 1305BHP 022 023 024 025 026 026 026

    Sones 132 128 125 121 117 112 109

    1/3 1440CFM 2044 1978 1911 1838 1759 1674 1571 1299BHP 029 031 032 033 034 034 035 034

    Sones 150 150 151 151 145 139 134 125

    1/2

    1600CFM 2271 2212 2152 2088 2023 1873 1783 1686 1425BHP 040 042 043 044 045 047 047 048 047

    Sones 162 160 158 156 153 146 142 139 132

    1685CFM 2391 2335 2279 2219 2158 2020 1946 1857 1654 1312BHP 047 048 050 051 052 054 055 056 056 052

    Sones 169 166 163 160 157 151 148 145 139 135

    3/4 A-1/2 1725CFM 2448 2393 2338 2281 2220 2159 2089 1935 1746 1474BHP 050 052 053 055 056 057 058 059 060 058

    Sones 174 170 167 163 159 156 154 149 143 138

    C-860-RPM B-1140-RPM A-1725-RPM VG-1725-RPM

    MAXIMUM BHP AT A GIVEN RPM = (RPM/2047)3

    MAXIMUM RPM - GB-131=1725, G-133=1725TIP SPEED (ft/min) = RPM x 3.436

    MAXIMUM MOTOR FRAME SIZE = 56VG-3/4

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    25/52

    DONOT

    SELEC

    TTO

    THELEFT

    OF

    THIS

    SYSTEM

    CURVE

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    RPM (Belt)

    RPM (Direct)

    RPM (Vari-Green)

    HP

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    2

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Roof Downblast - ExhaustBelt & Direct DriveGB-141 G-143

    134(44)

    Damper Size = 16 x 16 (406 x 406)Roof Opening = 18 x 18 (470 x 470)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 77/86 lbs. (35/39 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    2838(721)

    4 (102)

    *2334(603)

    22(559)

    Motor HP FanRPM

    Static Pressure in Inches wg

    Belt Direct 0 0125 025 0375 05 075 1 125 15 175141 143

    1/4

    V

    G-Vari-GreenisadirectdrivebrushlessDCmotor.

    580CFM 1076 855BHP 004 004

    Sones 47 47

    720CFM 1336 1169 938BHP 007 008 008

    Sones 58 59 52

    C-1/8 860CFM 1595 1457 1304 1085BHP 012 013 013 013

    Sones 71 70 66 61

    950CFM 1762 1636 1506 1344 1085BHP 016 017 018 018 017

    Sones 81 80 76 71 65

    1075CFM 1994 1882 1771 1647 1490BHP 024 025 026 026 026

    Sones 100 99 94 89 84

    1/3 B-1/3 1140CFM 2115 2008 1905 1792 1660 1233BHP 028 030 031 031 031 029

    Sones 110 109 104 99 94 82

    1/2

    1265CFM 2347 2250 2158 2062 1955 1677 1048BHP 039 040 041 042 042 042 035

    Sones 129 127 123 119 114 104 88

    1360

    CFM 2523 2433 2347 2259 2166 1943 1602BHP 048 050 051 052 052 053 051

    Sones 146 143 139 135 131 122 110

    3/4

    1450CFM 2690 2606 2524 2443 2358 2165 1905 1501BHP 058 060 061 063 063 064 063 059

    Sones 162 159 156 152 147 138 129 117

    1550CFM 2875 2797 2719 2644 2566 2396 2191 1910 1297BHP 071 073 074 076 077 078 079 076 065

    Sones 177 180 174 172 168 150 148 148 149

    1 A-1 1725CFM 3200 3129 3059 2991 2923 2782 2619 2427 2184 1815BHP 098 100 102 103 105 107 107 109 106 100

    Sones 200 210 200 199 196 185 172 170 168 167

    C-860-RPM B-1140-RPM A-1725-RPM VG-1550-RPM

    MAXIMUM BHP AT A GIVEN RPM = (RPM/1676)3

    MAXIMUM RPM - GB-141=1725, G-143=1725TIP SPEED (ft/min) = RPM x 3.829

    MAXIMUM MOTOR FRAME SIZE = 145TVG-3/4

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    26/52

    DONOT

    SELECTTOTHELEFTOF

    THIS

    SYSTEM

    CURV

    E

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    3

    Volume (m /hr )

    RPM (Belt)

    RPM (Direct)

    RPM (Vari-Green)

    HP

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    2200

    Motor HP FanRPM

    Static Pressure in Inches wg

    Belt Direct 5 75 1 125 15 175 2 225 25 275141HP 143HP

    1/4

    VG-Vari-GreenisadirectdrivebrushlessDCmotor.

    1020CFM 488BHP 008

    Sones 63

    B-1/4 1140CFM 645 413BHP 011 011

    Sones 77 76

    1320CFM 837 700 486BHP 017 018 017

    Sones 103 98 99

    1500CFM 1009 903 774 592BHP 024 026 026 025

    Sones 131 123 122 124

    1/3 1655CFM 1151 1064 959 833 668BHP 032 034 035 035 034

    Sones 150 141 133 131 136

    1/2

    A-1/2 1725CFM 1213 1132 1035 932 784 588BHP 036 038 039 039 039 037

    Sones 162 154 147 142 143 149

    1812CFM 1289 1213 1127 1030 911 763 545BHP 041 043 045 046 045 045 041

    Sones 178 172 166 158 156 159 166

    1900CFM 1366 1294 1218 1127 1033 901 753BHP 047 049 051 053 053 052 051

    Sones 190 184 180 174 168 167 170

    3/4

    2050CFM 1495 1430 1361 1285 1200 1113 991 857 672BHP 058 061 063 065 066 066 066 065 061

    Sones 210 200 198 193 188 186 183 183 186

    2170CFM 1598 1536 1472 1407 1328 1248 1163 1045 919 757BHP 068 071 073 076 077 078 079 078 077 074

    Sones 220 220 210 210 210 210 210 200 197 198

    2200CFM 1623 1562 1500 1436 1360 1281 1200 1088 968 834BHP 071 074 076 078 080 082 082 081 080 079

    230 220 220 220 210 210 210 210 200 200

    26

    Roof Downblast - Belt DriveSize- : GB H-GB

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Roof Downblast - ExhaustBelt & Direct DriveGB-141HP G-143HP

    Damper Size = 16 x 16Roof Opening = 18 x 18 (470 x 470)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 75/83 lbs. (34/38 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    MAXIMUM BHP AT A GIVEN RPM = (RPM/2351)3

    MAXIMUM RPM - GB-141HP=2200, G-143HP=2200TIP SPEED (ft/min) = RPM x 3.829

    MAXIMUM MOTOR FRAME SIZE = 145T

    134(44)

    4 (102)

    *2334(603)

    22(559)

    2838(721)

    B-1140-RPM A-1725-RPM VG-2200-RPM

    VG-3/4

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    27/522

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    DONOTS

    ELEC

    TTO

    THE

    LEFT

    OF

    THIS

    SYSTEM

    CURVE

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    3Volume (m/hr )

    RPM (Belt)

    RPM (Direct)

    HP

    Density 0.07 5 lb/ft3

    Density 1.2 kg/m3

    Roof Downblast - ExhaustBelt & Direct DriveGB-161 G-163

    Damper Size = 16 x 16Roof Opening = 18 x 18 (470 x 470)

    Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 101/88 lbs. (46/40 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    134(44)

    2838(619)

    4 (102)

    *2334(603)

    22(559)

    Motor HP FanRPM

    Static Pressure in Inches wg

    Belt Direct 0 0125 025 0375 05 075 0875 1 125 15161 163

    1/4

    580CFM 1713 1417 970BHP 007 008 007

    Sones 58 56 53

    720CFM 2127 1893 1632 1243BHP 014 015 015 014

    Sones 78 75 72 68

    C-1/4 860CFM 2540 2344 2145 1913 1596BHP 023 024 025 026 024

    Sones 105 100 96 93 87

    1/3 945CFM 2791 2612 2434 2236 2010BHP 031 032 033 034 034

    Sones 126 120 115 112 107

    1/2

    1050CFM 3102 2940 2782 2616 2429 1937 1582BHP 042 044 045 046 047 044 041

    Sones 144 138 132 129 126 116 107

    1100CFM 3249 3095 2943 2787 2615 2198 1900BHP 048 050 052 053 053 052 050

    Sones 153 147 141 138 135 125 120

    3/4

    B-1/2 1140CFM 3367 3219 3072 2922 2761 2382 2125 1808BHP 054 056 057 058 059 059 057 054

    Sones 159 154 149 145 142 133 129 121

    1250CFM 3692 3557 3422 3289 3149 2838 2658 2444BHP 071 073 075 076 077 079 078 076

    Sones 179 174 170 166 163 156 152 149

    1 1375CFM 4062 3938 3815 3694 3571 3304 3161 3007 2609 2073BHP 095 097 099 101 102 104 105 104 101 093

    Sones 210 200 196 192 189 184 180 176 172 154

    1-1/2 1575CFM 4652 4545 4437 4330 4225 4007 3894 3769 3512 3198BHP 142 145 147 149 151 154 156 156 157 154

    Sones 260 250 250 240 240 240 230 230 220 220

    C-860-RPM B-1140-RPM A-1725-RPM

    MAXIMUM BHP AT A GIVEN RPM = (RPM/1355)3

    MAXIMUM RPM - GB-161=1575, G-163=1725TIP SPEED (ft/min) = RPM x 4.352

    MAXIMUM MOTOR FRAME SIZE = 145T

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    28/5228

    Roof Downblast - Belt DriveSize- : GB H-GB

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Damper Size = 16 x 16 (406 x 406)Roof Opening = 18 x 18 (470 x 470)Shroud Thickness = 0.051 (1.3)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 88 lbs. (40 kg)

    All dimensions in inches (millimeters) *May be greater depending on motor^Weight shown is largest cataloged Open Drip-Proof motor.

    Roof Downblast - ExhaustBelt DriveGB-161HP

    MotorHP

    FanRPM

    Static Pressure in Inches wg

    05 0625 075 1 125 15 175 2 225 25161HP

    1/4

    825CFM 702BHP 011

    Sones 65

    960CFM 1093 919 585BHP 018 017 015

    Sones 77 76 80

    1095CFM 1380 1271 1139 589BHP 026 026 026 021

    Sones 90 90 89 95

    1/3 1210CFM 1606 1514 1416 1149BHP 034 035 035 034

    Sones 106 103 104 103

    1/2

    1270CFM 1718 1636 1545 1333 949BHP 039 040 040 041 037

    Sones 114 112 111 111 114

    1330CFM 1829 1753 1668 1483 1204BHP 044 045 046 047 045

    Sones 123 121 119 121 120

    1390CFM 1938 1865 1789 1619 1399 1032BHP 050 051 052 053 053 048

    Sones 133 130 128 127 127 131

    3/4

    1485CFM

    2109 2041 1973 1822 1654 1416 1012BHP 060 061 063 064 065 063 057Sones 149 147 144 138 137 140 147

    1580CFM 2275 2214 2150 2016 1868 1704 1447 1034BHP 072 073 075 077 077 0791 075 067

    Sones 167 167 164 155 147 148 154 166

    1

    1660CFM 2414 2357 2297 2175 2037 1887 1702 1441 996BHP 082 084 085 089 089 091 090 086 075

    Sones 183 188 183 167 162 158 158 171 20

    1740CFM 2551 2497 2442 2325 2200 2066 1917 1714 1452 987BHP 094 096 097 101 103 103 105 103 098 085

    Sones 20 21 21 184 175 172 168 172 192 28

    DO

    NOT

    SELECTTOTHELEFT

    OF

    THIS

    SYSTEMCURVE

    StaticPressure(in.wg

    )

    StaticPressure(Pa)

    Volume (cfm)

    3Volume (m/hr)

    RPM (Belt)

    HP

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    MAXIMUM BHP AT A GIVEN RPM = (RPM/1708)3

    MAXIMUM RPM = 1740TIP SPEED (ft/min) = RPM x 4.352

    MAXIMUM MOTOR FRAME SIZE = 145T

    134(44)

    4 (102)

    *2334(603)

    22(559)

    2838(721)

  • 8/2/2019 Exchust Fan information

    29/522

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    DONOT

    SEL

    ECT

    TO

    THE

    LEFTOF

    THIS

    SYSTEM

    CURVE

    StaticPressure(in.wg)

    StaticPressure(Pa )

    Volume (cfm)

    3Volume (m/hr )

    RPM (Belt)

    RPM (Direct)

    HP

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    Roof Downblast - ExhaustBelt & Direct DriveGB-180 G-183

    Damper Size = 18 x 18 (457 x 457)Roof Opening = 20 x 20 (521 x 521)Shroud Thickness = 0.064 (1.6)

    Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 108/142 lbs. (49/64 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    134(44)

    3512(902)

    512(140)

    *28(711)

    30(762)

    Motor HP FanRPM

    Static Pressure in Inches wg

    Belt Direct 0 0125 025 05 075 1 125 15 175 2180 183

    1/4

    495CFM 1925 1646 1150BHP 0067 0078 0075

    Sones 43 47 41

    730CFM 2839 2668 2469 1882BHP 021 023 025 025

    Sones 74 87 72 67

    1/3 810CFM 3150 2997 2832 2375BHP 029 031 033 035

    Sones 88 99 87 82

    1/2

    825CFM 3208 3059 2899 2458BHP 031 032 035 037

    Sones 91 102 90 86 85

    C-1/2 860CFM 3344 3202 3049 2647 2015BHP 035 036 039 042 04

    Sones 101 108 98 91 81

    940CFM 3655 3527 3388 3052 2601BHP 046 047 049 054 054

    Sones 127 128 12 111 103

    3/4 1055CFM 4102 3990 3867 3596 3252 2811BHP 065 067 068 074 077 077

    Sones 162 157 149 14 129 124

    1

    B-1 1140CFM 4433 4329 4216 3980 3684 3328 2856BHP 081 084 085 093 096 098 095

    Sones 179 174 168 16 151 143 136

    1185CFM 4608 4508 4401 4179 3900 3575 3178 2499BHP 091 094 096 103 107 11 109 099

    Sones 19 184 178 171 162 154 147 137

    1-1/2 1335CFM 5191 5102 5010 4814 4599 4344 4052 3713 3262BHP 131 133 136 141 149 154 157 156 151

    Sones 22 22 21 21 199 192 187 182 176

    2 1460CFM 5677 5596 5514 5336 5155 4938 4699 4426 4123 3765BHP 171 174 177 181 193 197 203 205 205 202

    Sones 26 25 24 24 23 23 22 22 22 21

    C-860-RPM B-1140-RPM

    MAXIMUM BHP AT A GIVEN RPM = (RPM/1149)3

    MAXIMUM RPM = 1460TIP SPEED (ft/min) = RPM x 4.843

    MAXIMUM MOTOR FRAME SIZE = 184T

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    30/5230

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Damper Size = 18 x 18 (457 x 457)Roof Opening = 20 x 20 (521 x 521)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 142 lbs. (64 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    Roof Downblast - ExhaustBelt DriveGB-180HP

    MotorHP

    FanRPM

    Static Pressure in Inches wg

    05 075 1 125 15 175 2 225 25 275180HP

    1/4

    795CFM 1547BHP 022

    Sones 86

    845CFM 1759BHP 026

    Sones 91

    1/3 935CFM 2114 1686BHP 035 035

    Sones 103 96

    1/2 1075CFM 2601 2316 1920BHP 051 053 052

    Sones 129 121 116

    3/4

    1150CFM 2847 2607 2298 1811BHP 061 064 065 062

    Sones 146 131 126 123

    1225CFM 3088 2880 2610 2277 1711BHP 073 077 078 078 072

    Sones 163 147 139 133 132

    1 1350CFM 3485 3296 3095 2840 2540 2059BHP 096 100 104 105 105 099

    Sones 195 176 164 158 150 151

    112

    1445CFM

    3782 3604 3428 3213 2969 2670 2216BHP 116 121 125 128 129 128 121Sones 22 20 188 178 173 164 166

    1540CFM 4076 3909 3744 3576 3353 3119 2827 2407BHP 139 144 149 153 155 156 155 148

    Sones 25 22 21 20 196 189 181 183

    2

    1620CFM 4319 4163 4005 3848 3663 3450 3223 2923 2512BHP 160 166 171 176 179 181 182 180 172

    Sones 27 25 24 23 22 21 20 197 198

    1700CFM 4560 4414 4263 4114 3964 3764 3560 3340 3037 2642BHP 184 190 196 201 206 208 210 211 207 199

    Sones 30 27 26 25 24 23 22 22 21 21

    DONOT

    SELECT

    TO

    THE

    LEFT

    OF

    THIS

    SY

    STEM

    CUR

    VE

    StaticPressure(in.wg

    )

    StaticPressure(Pa)

    Volume (cfm)

    3Volume (m /hr )

    RPM (Belt)

    HP

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    MAXIMUM BHP AT A GIVEN RPM = (RPM/1325)3

    MAXIMUM RPM = 1700TIP SPEED (ft/min) = RPM x 4.843

    MAXIMUM MOTOR FRAME SIZE = 184T

    134(44)

    512(140)

    *28(711)

    30(762)

    3512(902)

  • 8/2/2019 Exchust Fan information

    31/523

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Roof Downblast - ExhaustBelt & Direct DriveGB-200 G-203

    Damper Size = 18 x 18 (457 x 457)Roof Opening = 20 x 20 (521 x 521)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight G/GB = 119/144 lbs. (54/65 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    134(44)

    3512(902)

    512(140)

    *28(711)

    30(762)

    Motor HP FanRPM

    Static Pressure in Inches wg

    Belt Direct 0 0125 025 0375 05 075 10 125 15 175200 203

    1/4

    440CFM 2435 1976BHP 01 01

    Sones 65 58

    600CFM 3320 2984 2637 2089BHP 025 026 026 025

    Sones 85 79 73 61

    1/3 665CFM 3680 3378 3085 2706 2087BHP 034 034 035 035 033

    Sones 96 9 85 77 67

    1/2

    718CFM 3973 3700 3422 3109 2684BHP 043 043 045 045 044

    Sones 108 10 96 9 83

    770CFM 4261 4013 3744 3477 3141BHP 052 053 055 055 055

    Sones 121 11 107 102 98

    3/4 C-3/4 860CFM 4759 4548 4289 4068 3811 3085BHP 073 074 075 077 077 074

    Sones 141 133 129 124 118 111

    1 965CFM 5340 5158 4927 4720 4520 4015 3240BHP 103 104 105 108 109 108 102

    Sones 167 16 154 15 145 137 13

    1-1/2

    1028

    CFM 5689 5517 5309 5101 4918 4488 3911 2941BHP 125 126 127 129 131 132 128 114

    Sones 185 178 172 168 164 156 147 146

    1090CFM 6032 5870 5682 5473 5301 4925 4450 3751BHP 149 15 151 152 156 156 156 148

    Sones 20 196 189 184 181 175 168 158

    2

    B-2 1140CFM 6308 6154 5980 5779 5606 5267 4832 4287 3439BHP 17 171 172 174 177 179 179 175 161

    Sones 22 21 21 20 197 191 185 175 165

    1200CFM 6640 6494 6336 6145 5969 5651 5274 4829 4177 3077BHP 199 2 201 202 204 209 209 208 199 169

    Sones 24 23 23 22 22 21 21 199 186 167

    DONOT

    SELECT

    TO

    THELEFTOFTHIS

    SYSTEM

    CURVE

    StaticPressure(in.wg

    )

    StaticPressure(Pa)

    Volume (cfm)

    3Volume (m/hr )

    RPM (Belt)

    RPM (Direct)

    HP

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    C-860-RPM B-1140-RPM

    MAXIMUM BHP AT A GIVEN RPM = (RPM/938)3

    MAXIMUM RPM = 1200TIP SPEED (ft/min) = RPM x 5.596

    MAXIMUM MOTOR FRAME SIZE = 184T

    Direct Drive RPM

  • 8/2/2019 Exchust Fan information

    32/5232

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Damper Size = 18 x 18 (457 x 457)Roof Opening = 20 x 20 (521 x 521)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 166 lbs. (75 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    Roof Downblast - ExhaustBelt DriveGB-220HP

    DONOT

    SELECTT

    OT

    HELEFTOF

    THIS

    SYSTEMC

    URVE

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm)

    3Volume (m /hr)

    RPM (Belt)

    HP

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    MotorHP

    FanRPM

    Static Pressure in Inches wg

    05 075 1 125 15 2 25 275 3 325200HP

    1/2

    740CFM 1961BHP 030

    Sones 87

    895CFM 2809 2331 1424BHP 052 053 045

    Sones 114 109 103

    3/4

    958CFM 3116 2715 2153BHP 063 065 063

    Sones 128 121 116

    1020CFM 3409 3050 2602 1857BHP 075 077 078 071

    Sones 141 136 131 126

    1 1125CFM 3885 3584 3243 2804 2136BHP 099 102 104 104 097

    Sones 169 164 155 153 152

    112

    1205CFM 4229 3967 3663 3314 2884BHP 119 124 127 129 127

    Sones 188 179 172 165 164

    1285CFM 4569 4343 4070 3770 3416 2278BHP 143 149 152 155 157 140

    Sones 21 20 191 181 178 189

    2

    1350CFM

    4843 4638 4384 4109 3811 2996BHP 165 171 175 178 181 176Sones 23 22 21 198 193 191

    1415CFM 5114 4919 4692 4442 4169 3492 2250BHP 188 195 200 204 207 207 178

    Sones 24 24 23 22 21 197 23

    3

    1520CFM 5550 5368 5182 4952 4713 4166 3458 2850 2046BHP 231 238 245 250 253 258 253 238 206

    Sones 27 27 27 26 24 23 22 22 22

    1625CFM 5982 5812 5642 5448 5233 4767 4196 3859 3377 2725BHP 280 288 295 302 306 313 316 312 301 276

    Sones 32 31 31 29 28 27 25 24 23 22

    MAXIMUM BHP AT A GIVEN RPM = (RPM/1106)3

    MAXIMUM RPM = 1625TIP SPEED (ft/min) = RPM x 5.596

    MAXIMUM MOTOR FRAME SIZE = 184T

    134(44)

    512(140)

    *28(711)

    30(762)

    3512(902)

  • 8/2/2019 Exchust Fan information

    33/523

    Roof Downblast - ExhaustBelt DriveGB-220

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    134(44)

    Damper Size = 24 x 24 (610 x 610)Roof Opening = 26 x 26 (673 x 673)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 164 lbs. (74 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    DONOT

    SEL

    ECTTO

    THE

    LEFT

    OF

    THISSYSTEM

    CURVE

    StaticPressure(in.w

    g)

    StaticPressure(Pa

    )

    Volume (cfm x 1000)

    3Volume (m/hr x 1000)

    RPM (Belt)

    HP

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    MotorHP

    FanRPM

    Static Pressure in Inches wg

    0 0125 025 0375 05 0625 075 1 125 15220

    1/4

    425CFM 3230 2879 2296BHP 014 016 016

    Sones 74 72 69

    465CFM 3533 3219 2758 1951BHP 018 020 021 019

    Sones 81 78 74 70

    500CFM 3799 3512 3132 2542BHP 023 025 026 026

    Sones 88 84 79 75

    1/3 550CFM 4179 3924 3629 3158 2526BHP 030 032 034 035 033

    Sones 100 96 89 84 80

    1/2 640CFM 4863 4654 4403 4120 3702 3208BHP 048 050 053 054 055 054

    Sones 130 128 121 112 105 97

    3/4 710CFM 5395 5206 4990 4762 4459 4077 3633BHP 065 068 071 073 074 075 074

    Sones 150 149 144 136 128 121 112

    1

    755CFM 5737 5559 5362 5148 4920 4579 4206 3095BHP 079 082 084 087 089 090 090 082

    Sones 157 156 152 146 140 134 127 112

    800CFM

    6079 5911 5732 5530 5326 5049 4716 3929BHP 093 097 100 102 105 106 107 105Sones 166 164 161 156 152 146 142 125

    112

    848CFM 6444 6286 6122 5932 5741 5540 5236 4566 3542BHP 111 115 118 121 123 126 127 127 117

    Sones 178 175 172 169 165 162 157 145 134

    895CFM 6801 6651 6501 6323 6142 5960 5723 5122 4401BHP 131 134 138 141 144 147 149 150 147

    Sones 194 191 188 185 182 180 176 169 155

    2 985CFM 7485 7349 7212 7062 6898 6734 6568 6107 5548 4883BHP 174 178 182 186 189 192 195 199 200 196

    Sones 23 23 23 22 22 22 22 21 20 190

    MAXIMUM BHP AT A GIVEN RPM = (RPM/782)3

    MAXIMUM RPM = 985TIP SPEED (ft/min) = RPM x 6.283

    MAXIMUM MOTOR FRAME SIZE = 184T

    4234(1086)

    *3112(800)

    534(146)

    34(864)

  • 8/2/2019 Exchust Fan information

    34/5234

    Roof Downblast - ExhaustBelt DriveGB-220HP

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effectsof a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.Values shown are for installation type A: free inlet hemispherical sone levels.

    134(44)

    Damper Size = 24 x 24 (610 x 610)Roof Opening = 26 x 26 (673 x 673)Shroud Thickness = 0.064 (1.6)Motor Cover Thickness = 0.040 (1.0)Curb Cap Thickness = 0.064 (1.6)^Approximate Unit Weight = 186 lbs. (84 kg)

    All dimensions in inches (millimeters) *May be greater depending onmotor. ^Weight shown is largest cataloged Open Drip-Proof motor.

    DONOT

    SELE

    CT

    TO

    THE

    LEFT

    OFTHIS

    SYSTEM

    CUR

    VE

    StaticPressure(in.wg)

    StaticPressure(Pa)

    Volume (cfm x 1000)

    3Volume (m/hr x 1000)

    RPM (Belt)

    HP

    Density 0.075 lb/ft3

    Density 1.2 kg/m3

    534(146)

    *3112(800)

    34(864)

    MotorHP

    FanRPM

    Static Pressure in Inches wg

    05 0625 075 1 125 15 175 2 225 25220HP

    1/2

    650CFM 2952 2555 1892BHP 047 046 042

    Sones 89 85 83

    680CFM 3215 2871 2440BHP 053 053 052

    Sones 94 92 89

    3/4

    728CFM 3614 3312 2974BHP 065 065 065

    Sones 106 103 99

    775CFM 3973 3719 3424 2643BHP 077 079 079 075

    Sones 120 115 111 105

    1 850CFM 4532 4317 4083 3536 2648BHP 100 102 104 103 095

    Sones 150 138 135 127 120

    112

    913CFM 4975 4791 4590 4119 3545 2557BHP 122 125 127 129 127 113

    Sones 167 160 153 144 135 130

    975CFM 5400 5245 5060 4660 4185 3602BHP 146 150 153 157 156 153

    Sones 187 182 175 163 154 148

    2

    1025CFM 5740 5591 5432 5075 4643 4157 3492BHP 168 172 176 181 182 1804 174

    Sones 21 20 194 182 171 164 156

    1075CFM 6076 5935 5794 5459 5082 4649 4136 3346BHP 193 197 201 206 210 210 207 193

    Sones 23 22 21 20 187 183 177 164

    3

    1127CFM 6422 6289 6154 5852 5520 5124 4703 4173 3299BHP 220 224 229 236 241 242 241 237 217

    Sones 24 24 23 22 21 20 193 186 177

    1230CFM 7100 6981 6858 6611 6316 6009 5649 5263 4812 4265BHP 282 287 292 301 308 314 315 314 310 302

    Sones 28 27 27 27 25 25 23 22 22 22

    MAXIMUM BHP AT A GIVEN RPM = (RPM/838)3

    MAXIMUM RPM = 1230TIP SPEED (ft/min) = RPM x 6.414

    MAXIMUM MOTOR FRAME SIZE = 184T