evaluation of transmitted over-voltages through a power

7
2014 International Conference on Lightning Protection (ICLP), Shanghai, China Evaluation of Transmitted Over-Voltages through a Power Transformer Taking into Account Uncertainties on Lightning Parameters B. Jurisic, A. Xemard Electricité de France Clamart, France [email protected] I. Uglesic*, F. Paladian, S. Lallechere, P. Bonnet *University of Zagreb, Zagreb, Croatia Université Clermont Auvergne, Université Blaise Pascal, Institut Pascal, France AbstractLighting striking an overhead line is at the origin of high frequency over-voltages, which propagate along the line and through the power transformers located at its ends. To study the transmission of over-voltages through transformers, low frequency transformer models are not adapted. Therefore, in the past few decades, many high frequency transformer models were developed. Recently, in the CIGRE brochure 577, an overview of such models is given. In this paper the over-voltages caused by lightning strikes to a 20 kV overhead line are simulated to calculate the amplitudes of over-voltages in a 6.8 kV distribution grid, transmitted through a Yd11d11, 64 MVA, 24/6.8/6.8 kV transformer unit. A high frequency black box transformer model is used. This model is based on frequency response measurements, rational approximation and state space equations. Uncertainties on lightning parameters are taken into account by using the Monte Carlo and Stochastic Collocation methods. The aim of the paper is to present a methodology to evaluate the statistical variations of transmitted over-voltages. Keywords-Transformer; Black Box Model; Monte Carlo Method; Stochastic Collocation Method; Uncertainty Quantification; Electromagnetic Transient Program (EMTP) I. INTRODUCTION Lightning strikes generate high over-voltages in the electric power network. Consequently, apparatuses in the power network have to be protected against them. To determine the lightning withstand voltage of the power network’s equipment as well as surge arrester installations needs, it is necessary to conduct insulation coordination studies. These studies are usually based on Electromagnetic transient simulations (EMTP) and require a precise model for each component inside the power network. Traditional, low frequency models cannot be used for lightning studies since electrical devices like transformers at high frequencies exhibit a different behavior than at low frequencies. To represent high frequency electromagnetic transformer behavior in simple studies, capacitance divider models can be used, while for more detailed studies, special high frequency transformer models should be developed. In the case of a power transformer, it is very important to have a precise high frequency model which will allow an accurate evaluation of the transmitted over-voltages. However, high frequency transformer models are often too complex or require confidential information on transformer geometry. The lack of knowledge on transformer geometry data led to the development of black box transformer models which as an input require only data measured from the transformer terminals. That makes them suitable for usage in insulation coordination studies, especially for power utilitiesengineers. The transformer model, developed for the purpose of this paper is a state of the art black box model built from a transformer admittance matrix, measured with a standard sweep frequency response analyzer (FRA). It is based on a rational approximation with passivity enforcement and a state space representation compatible with an EMTP-like software program. The model is suitable to represent accurately enough transmitted over-voltages in the lightning frequency range, for which a power transformer behaves as a linear component. In this paper the over-voltages caused by lightning strikes to a 20 kV overhead line are simulated in order to evaluate the amplitudes of the over-voltages in the distribution grid, transmitted through a Yd11d11, 64 MVA, 24/6.8/6.8 kV transformer unit. Uncertainties regarding lightning parameters may be taken into account by using the well-known Monte Carlo method (MC) or more sophisticated stochastic approaches such as the Stochastic Collocation methods (SC) [1]-[3]. It should be noticed that the probability distributions of input parameters are taken into account based on data given in [4]. The aim of this paper is to calculate the mean and standard deviation of the amplitude of the transmitted over- voltages through the power transformer. II. TRANSFORMER HIGH FREQUENCY MODELLING In this section, the black box high frequency transformer model is presented. It is based only on measurements data.

Upload: others

Post on 20-Feb-2022

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Evaluation of Transmitted Over-Voltages through a Power

2014 International Conference on Lightning Protection (ICLP), Shanghai, China

Evaluation of Transmitted Over-Voltages through a

Power Transformer Taking into Account

Uncertainties on Lightning Parameters

B. Jurisic, A. Xemard

Electricité de France

Clamart, France

[email protected]

I. Uglesic*, F. Paladian, S. Lallechere, P. Bonnet

*University of Zagreb,

Zagreb, Croatia

Université Clermont Auvergne, Université Blaise Pascal,

Institut Pascal, France

Abstract— Lighting striking an overhead line is at the origin of

high frequency over-voltages, which propagate along the line and

through the power transformers located at its ends. To study the

transmission of over-voltages through transformers, low

frequency transformer models are not adapted. Therefore, in the

past few decades, many high frequency transformer models were

developed. Recently, in the CIGRE brochure 577, an overview of

such models is given.

In this paper the over-voltages caused by lightning strikes to a 20

kV overhead line are simulated to calculate the amplitudes of

over-voltages in a 6.8 kV distribution grid, transmitted through a

Yd11d11, 64 MVA, 24/6.8/6.8 kV transformer unit. A high

frequency black box transformer model is used. This model is

based on frequency response measurements, rational

approximation and state space equations. Uncertainties on

lightning parameters are taken into account by using the Monte

Carlo and Stochastic Collocation methods. The aim of the paper

is to present a methodology to evaluate the statistical variations

of transmitted over-voltages.

Keywords-Transformer; Black Box Model; Monte Carlo Method;

Stochastic Collocation Method; Uncertainty Quantification;

Electromagnetic Transient Program (EMTP)

I. INTRODUCTION

Lightning strikes generate high over-voltages in the electric

power network. Consequently, apparatuses in the power

network have to be protected against them. To determine the

lightning withstand voltage of the power network’s equipment

as well as surge arrester installations needs, it is necessary to

conduct insulation coordination studies. These studies are

usually based on Electromagnetic transient simulations

(EMTP) and require a precise model for each component

inside the power network.

Traditional, low frequency models cannot be used for

lightning studies since electrical devices like transformers at

high frequencies exhibit a different behavior than at low

frequencies. To represent high frequency electromagnetic

transformer behavior in simple studies, capacitance divider

models can be used, while for more detailed studies, special

high frequency transformer models should be developed. In

the case of a power transformer, it is very important to have a

precise high frequency model which will allow an accurate

evaluation of the transmitted over-voltages. However, high

frequency transformer models are often too complex or

require confidential information on transformer geometry. The

lack of knowledge on transformer geometry data led to the

development of black box transformer models which as an

input require only data measured from the transformer

terminals. That makes them suitable for usage in insulation

coordination studies, especially for power utilities’ engineers.

The transformer model, developed for the purpose of this

paper is a state of the art black box model built from a

transformer admittance matrix, measured with a standard

sweep frequency response analyzer (FRA). It is based on a

rational approximation with passivity enforcement and a state

space representation compatible with an EMTP-like software

program. The model is suitable to represent accurately enough

transmitted over-voltages in the lightning frequency range, for

which a power transformer behaves as a linear component.

In this paper the over-voltages caused by lightning strikes to

a 20 kV overhead line are simulated in order to evaluate the

amplitudes of the over-voltages in the distribution grid,

transmitted through a Yd11d11, 64 MVA, 24/6.8/6.8 kV

transformer unit. Uncertainties regarding lightning parameters

may be taken into account by using the well-known Monte

Carlo method (MC) or more sophisticated stochastic

approaches such as the Stochastic Collocation methods (SC)

[1]-[3]. It should be noticed that the probability distributions

of input parameters are taken into account based on data given

in [4]. The aim of this paper is to calculate the mean and

standard deviation of the amplitude of the transmitted over-

voltages through the power transformer.

II. TRANSFORMER HIGH FREQUENCY

MODELLING

In this section, the black box high frequency transformer

model is presented. It is based only on measurements data.

Page 2: Evaluation of Transmitted Over-Voltages through a Power

Transformer’s scattering parameters, admittance parameters,

impedance parameters or transfer function can be measured.

That makes the model suitable for practical applications in

power utility companies because they usually do not have

access to detailed transformer’s geometry data. To interact

with an EMTP-like software program, an admittance matrix is

calculated from the named measured parameters. Among

many different approaches to input the model’s admittance

matrix in an EMTP-like software program, the most used one

is to approximate the matrix elements with rational

expressions [5], [6]. As a final representation, usually the state

space equations are used [7]. State space equations are used to

represent a linear network. Therefore, they can be used to

represent a transformer, since transformer’s behavior can be

considered as linear at high frequencies.

For the purpose of this paper, to measure the admittance

matrix elements, a sweep frequency response analyzer (FRA)

measuring equipment is used. This is a standard equipment for

measuring the frequency response of a transformer as

suggested in the IEC standard [8]. The measurement

procedure is similar to the one described in [9]. A frequency

response analyzer, is capable of measuring the ratio (H)

between the input (Vin) and the output (Vout) voltages:

)f(V

)f(V)f(H

in

out

, where f stands for the frequency. Note that the

measurements are done at discrete frequency points. Since the

FRA measurement’s equipment is not normally used for

measuring Y matrix, a specific procedure for measuring is

established.

The measuring method stems from the following expression:

)f(U

)f(U

)f(U

)f(U

)f(Y)f(Y

)f(Y)f(Y

)f(I

)f(I

)f(I

)f(I

N

NNNN

N

N

N 1

2

1

1

111

1

2

1

Expression (2) is valid for a transformer with N terminals.

The measuring procedure includes N*N measurements as it is

shown in [10] and [11]. Note that the measuring methods

differ for off-diagonal and diagonal matrix elements.

Since the transformer model has to be built in an EMTP-like

software program, the results of the measurement have to be

prepared accordingly. This can be done by using a fitting

method to approximate each admittance matrix element Yij(f)

with a rational expression Yij,fit(s) of the type given below [5],

[12] :

ij

Np

n ij,n

ij,nfit,ijij d

as

c)s(Y)f(Y

1

In (3) an,ij represents the poles which can be either real or

complex conjugated pair, cn,ij represents the residues which

can also be either real or complex conjugated pair, dij are real

value constants. s stands for j2πf. Np is the number of poles

used for the approximation of each matrix element.

The rational functions (3) have to be both stable and passive

since the transformer is a passive component of the electric

grid. Stability is obtained by keeping only the poles which are

stable. Passivity is enforced by perturbation of the residues

and constants values in order to match the passivity criterion:

0 v)s(YvReP fit*

, in which Yfit(s) represents the matrix of the fitted rational

functions. Expression (4) means that the model will not

produce power for any complex vector v. The expression

above will be positive only if all the eigenvalues of the real

part of the Yfit(s) are positive:

0)))s(Y(Re(eig fit

By introducing the passivity criterion (4), the fitting problem

can be formulated as follows:

minimize i j

ij,fitij )s(Y)s(Y 2

passive )s(Y fit

The problem formulated with (6) and (7) is a non-convex

one (may have multiple feasible regions and multiple locally

optimal points within each region). To solve such a problem,

many algorithms have been developed [13]-[16]. These

algorithms can be separated into two groups: the ones using an

unconstrained minimization combined with a post processing

perturbation to enforce passivity such as Vector Fitting (VF)

combined with the Fast Residue Perturbation method (FRP

method) [13], [14] and the ones simultaneously enforcing

passivity during the fitting process by formulating a convex

optimization problem as the semi-definite programming

method (SDP method) [15], [16].

When fitted, the rational expression (3) allows using the

state space equations as shown below:

)s(UB)s(XA)s(sX

)s(UD)s(XC)s(I

Matrices A, B, C and D for the state space representation can

be input directly into the state space block in the EMTP-RV.

These matrices are obtained by using the values of poles and

residues of the rational functions (3) and constructing the

function given below:

)s(UDAIs

BC)s(U)s(Y)s(I

Page 3: Evaluation of Transmitted Over-Voltages through a Power

Expression (10), in which [I] is the identity matrix, can be

obtained from (8) and (9). It represents the relation between

the terminal’s currents and voltages of the transformer,

suitable to represent the rational functions given by (3).

The black box model in the EMTP-RV, built for the

transformer unit described in this paper has 10 terminals: 3

terminals of the HV windings, the neutral of the HV windings,

3 terminals per LV winding.

III. STATISTICAL ANALYSIS OF THE

TRANSMITTED OVER-VOLTAGES

In this section the case of a direct lightning strike to a 20 kV

overhead line, without shield wire is described. Uncertainties

regarding the lightning parameters are taken into account in

the time domain simulations. In this framework, two different

methods to include uncertainties are used: the Monte Carlo

and Stochastic Collocation techniques [1]-[3]. Since the

EMTP-RV does not have an inbuilt module for uncertainty

studies, one was developed in MATLAB. The interaction

between these two software packages is managed by using an

EDF’s in-house software program code as a link. This

approach allows to adjust the simulation parameters from

MATLAB, running the EMTP-RV simulations in parallel and

post-processing the simulation results in the MATLAB.

A. Case of the lightning strike to the 20 kV overhead line

In this section we consider that the Yd11d11, 64 MVA,

24/6.8/6.8 kV transformer unit is connected to the 20 kV

overhead line without shield wire. This is a purely academic

case aiming at presenting the method for taking lightning

parameters uncertainty into account in the time domain

simulations.

The case of a direct lightning strike to the second tower of

the 20 kV overhead line, observed from the transformer

primary side, is simulated. The primary side of the transformer

is connected to the 20 kV overhead line. The neutral of the

primary side of the transformer is grounded with a 1 kΩ

resistor. The transformer is intended to be connected inside a

plant for powering its distribution system. A surge arrester,

which is normally connected before the transformer, is not

represented in order to concentrate the study on the influence

of the transformer. It is assumed that the transformer internal

insulation will withstand over-voltages. The secondary

transformer windings are grounded through 250 nF capacitors

per phase, which represent the influence of the distribution

grid. These capacitances have a beneficial influence on the

transmitted over-voltages amplitude [17].

The transformer is simulated using the black box model. For

the fitting of the measured admittance matrix coefficients SDP

method with 40 poles is used. The fitting is done for the

frequency range from 10-500 kHz. Simulated transformer has

2 secondary 3 phase windings and their terminals names are

respectively: a1, b1, c1, a2, b2, c2. The 20 kV overhead line is

simulated using a frequency dependent line model, from the

EMTP-RV library. The line is simulated with 4 towers and 5

spans in order to avoid any unphysical reflections of the

travelling wave across the overhead line, as it can be seen in

figure 1. Data used for the line simulation is shown in table 1.

The line is not equipped with a shield wire and has

ungrounded reinforced concrete poles. Consequently the tower

footing is not considered in the simulation.

TABLE I. OVERHEAD LINE DATA

Span length

[m]

Conductor

height [m]

Horizontal

distance between

2 adjacent

conductors [m]

Vertical distance

between the

conductors [m]

100 8 1.5 0

Grounding

resistance [Ω]

Ground

return

resistivity

[Ωm]

External

diameter of the

conductor [mm]

Conductor’s

resistance

[Ω/km]

10000 (i.e. ungrounded)

1000 19.6 0.146

Each tower of the overhead line is simulated as one constant

parameter line, with a surge impedance equal to 106.35 Ω and

the propagation wave speed equal to 2.4*108 m/s. Tower arms

are modeled as inductances, whose lineic inductance is equal

to 1 µH/m, while the air gaps are simulated by using the equal

area criterion model [18], with the parameters given in table 2.

Span 1Span 2Span 4 Span 3Span 5

Tower 4 Tower 3 Tower 2 Tower 1Transformer

Capacitances (250 nF per phase)

Lighting strike

20 kV line to line sinus voltage

source

10 k tower grounding resistance

Air gap

Tower s arm

Figure 1. Direct lightning strikes the 20 kV overhead line simulation in the EMTP-RV.

Page 4: Evaluation of Transmitted Over-Voltages through a Power

TABLE II. AIR GAP PARAMETERS

10% flashover voltage of the insulation [kV] Air gap distance [mm]

112.5 305

Lightning, for the case described above, strikes the tower 2.

The lightning parameters of the CIGRE lightning current

source are respectively lightning current amplitude, If,

lightning front time, tf, lightning time to half, th and lightning

maximum slope, Sm. For the explanation of these parameters,

see figure 2.

I [kA]

t [μs]

If

tf

0.9*If

0.3*If

Sm

Figure 2. CIGRE concave shape [18].

These parameters are varied with the distributions given in

the CIGRE brochure 63 for the first negative downward stroke

[4]. Distributions used are the ones for the backflash domain

since the simulated overhead line does not have a shield wire.

These distributions are shown in table 3.

TABLE III. DISTRIBUTION OF THE LIGHTNING PARAMETERS

If [kA] tf [µs] Sm [kA/µs] th [µs]

log-N(33.3,

0.605)

log-N(0.906 If 0.411,

0.494)

log-N(6.5If 0.376,

0.554)

log-N(77.5,

0.577)

It is to be noted that the distributions for the lightning front

time and the lightning maximum slope value are conditional

ones. Therefore, in the scope of this paper we consider them as

deterministic variables and as such their values are calculated

from the expressions for their medians as a function of

lightning current amplitude value.

CIGRE brochure 63 does not include any condition which

should be fulfilled in order for the shape given in figure 2 to

exist:

f

fm

t

IS

However, condition (11) holds for the following study

without influencing the distribution of the lightning current

parameters.

Three other parameters which should be taken into account

in our uncertainty analysis are the angles of the sinus phase 20

kV voltage source. Since this source is considered as

symmetrical, only one angle parameter is independent, while

the other two are dependent. The probabilistic distribution law

considered for the phase voltage angle is U[-180, 180] without

any further information about this parameter.

To recap, in the simulation 3 parameters are considered as

independent, random variables (the lightning current

amplitude, the lightning time to half value and the phase

voltage angle) and 4 parameters are considered as dependent,

deterministic variables (the lightning front time, the lighting

maximum slope and the other two voltage phase angles). The

lightning current dependent parameters are determined by

taking condition (11) into account.

As an output data the maximum value of the induced over-

voltages of the two three phase 6.8 kV systems located on the

secondary side of the transformer are observed.

B. Statistical analysis with Monte Carlo method

Monte Carlo (MC) technique is based on repeatedly random

sampling and the application of the law of the large numbers.

According to this law the mean value of the results will

converge with the number of samples. Input parameters are

varied by taking into account the probability distributions

given in table 3. Due to hard drive space limitation (used for

storing the results data), the number of MC realizations was

imposed (no more than 10000 inputs). The log normal

distribution of the input parameter If is shown in figure 3. Each

column in the figure shows the number of the parameters If in

spans of approximately 10 kA.

Figure 3. Distribution of input parameter If.

The convergence of the output data is checked for the

maximum transmitted overvoltage in each phase of both 6.8

kV systems located on the secondary side of the transformer.

Page 5: Evaluation of Transmitted Over-Voltages through a Power

The convergence is obtained for the two first statistical

moments (i.e. mean and variance of each output parameter).

C. Statistical analysis with Stochastic Collocation method

In comparison to the Monte Carlo method, a great advantage

of the Stochastic Collocation (SC) method is to require fewer

input data to achieve a similar level of convergence. Another

key factor relies on the non-intrusiveness of SC method,

allowing a straightforward use of existing deterministic

calculation codes. Depending on the number of points

(collocation points) which are used to simulate the input data

distributions, levels of accuracy will differ. In this study

convergence is expected with only a few collocation points.

Consequently 3, 5, 7 and 9 points per independent input

parameter (i.e. lightning current amplitude, lightning time to

half, and phase voltage angle) are used. The number of

simulations needed can be calculated as follows: 3

independent parameters with 9 points per each leads to 93=729

simulations.

IV. RESULTS AND DISCUSSION

First of all, it is necessary to make a comment about the

convergence of the MC and SC methods. Figures 4 and 5 are

respectively devoted to the mean and variance of the

maximum of transmitted over-voltages in the phase a1, for the

MC method and the SC method with 3, 5, 7 and 9 points per

independent input parameter.

From the figures the MC method seems to converge when

the number of samples is around 10000. The same behavior

was observed for most of other output parameters.

Furthermore, it can be seen that the SC method needs

significantly smaller number of simulations (with 9 points per

input parameter, 729 in comparison of 10000 for MC) to

converge to the same value as MC method. To conclude, SC

methods reveal to be far more efficient than MC techniques

(decreasing the required number of realizations) with

comparable levels of accuracy for the studied case.

Figure 4. Convergence of MC method for mean value of maximum in the

phase a1.

Figure 5. Convergence of MC method for variance value of maximum OV in the phase a1.

In addition the convergence for the SC method versus the

number of points per independent parameter is shown.

Figure 6. Convergence of SC method for mean value of maximum OV at each phase.

From figure 6, it can be seen that the convergence of the SC

method is obtained with a small number of collocation points

per independent parameter.

The aim of this paper is to evaluate the probable amplitude

of the transmitted overvoltage through the power transformer

for all possible over-voltages caused by a lightning based on

data distributions given in table 3. Therefore, the results for

the maximum amplitude in all the phases of the transformer’s

secondary side are given in table 4, in terms of mean value, µ

and 2 standard deviations, σ both for the MC method and the

SC method with 9 points.

Page 6: Evaluation of Transmitted Over-Voltages through a Power

TABLE IV. RESULTS OF TRANSMITTED OV MAXIMUM AMPLITUDE IN

TERMS OF 2

a1

[kV]

b1

[kV]

c1

[kV]

a2

[kV]

b2

[kV]

c2

[kV]

µ+2σ with SC

16.69 18.51 18.37 17.74 19.31 19.33

µ-2σ with SC

9.46 9.95 11.44 10.76 10.84 12.10

µ+2σ with MC

16.67 18.47 18.47 17.72 19.27 19.43

µ-2σ with MC

9.40 10.03 11.36 10.71 10.91 12.03

Knowing the ranges shown in table 4, it is clear that the

transmitted overvoltage amplitude in all the phases of the

secondary side of the transformer will not exceed 19.43 kV (in

respect to 2 standard deviations), which is below the withstand

voltage of the 6.8 kV distribution grid (withstand voltage is 40

kV [19]).

Finally, the wave shapes of the transmitted over-voltages in

the phase c2 (in which the highest value of the overvoltage is

possible with the highest possibility among phases located on

transformer’s secondary side) are given in figure 7. The first

0.1 ms of time domain responses are given for each input set

of data (by using the 729 deterministic results from SC

points).

Figure 7. Wave shape of the transmitted OV amplitude in the phase c2.

It is interesting to note that the shapes of the transmitted

over-voltages are not significantly influenced by the lightning

impulse parameters. Therefore, we can conclude that the

shapes of the over-voltages are mostly a function of the

frequency behavior of the electric grid components such as the

transformer.

In the future, lightning data from lightning location systems

(LLS) could be used in studies similar to the one presented in

this paper. An experience with LLS has shown that lightning

strokes tend to have a lower crest value than the ones given in

the CIGRE brochure 63 [4]. Additionally, by using the LLS

data the local characteristics of the lightning can also be taken

into account.

V. CONCLUSION

In this paper an application of the state of the art high

frequency black box transformer model is shown. The case

studied in the paper simulates direct lightning striking the 20

kV overhead line and the maximum amplitudes of transmitted

over-voltages through the transformer are observed. Lightning

is a random phenomenon. Nowadays, several tools are

available to take these uncertainties into account when

performing insulation coordination studies. For the purpose of

the paper, a link between MATLAB and EMTP-RV is used to

adjust the simulation parameters in MATLAB, to run EMTP-

RV simulations in parallel and to post-process the simulation

results in MATLAB. Uncertainties regarding the lightning

parameters are considered by taking into account the

probabilistic distributions laws given in the CIGRE brochure

63 [4].

Two different methods are used to take lightning parameters

uncertainties into account: the Monte Carlo method and the

Stochastic Collocation method. Both methods gave similar

results. However, the Stochastic Collocation method requires

fewer simulations than the Monte Carlo method to achieve the

same accuracy for the studied case. This paper shows the

interest of taking into account uncertainties of the lightning

impulse and especially the advantage of the SC method for the

prediction of the induced over-voltages in the power network.

Additional simulation are necessary to confirm the higher

efficiency of the SC method comparing to the conventional

MC method.

ACKNOWLEDGMENT

The authors express their thanks to Siemens Končar Power

Transformers for providing the measurement results which

were used for the development and validation of the black box

transformer model presented in this paper. Furthermore, the

authors would like to thank Mr. Ali El-Akoum and Mr.

Manuel Martinez for allowing them to use their codes as the

link between MATLAB and EMTP-RV.

REFERENCES

[1] S. Lalléchère, P. Bonnet and F. Paladian, “Sensitivity analysis to compute

advanced stochastic problems in uncertain and complex electromagnetic environments”, Advanced Electromagnetics –Vol. 1, N°3, pp. 13-23, Oct.

2012. DOI: 10.7716/AEM.V1I3.43

[2] A. Xémard, A. Pagnetti, M. Martinez, P.D. Moreau, F. Paladian, P. Bonnet and C.A. Nucci, “Effect of uncertainties on the precision of

lightning studies”, International Colloquium on Lightning and Power

Systems, CIGRE, Lyon, 2014. DOI: 10.13140/2.1.4261.7601

[3] F. Paladian, P. Bonnet, S. Lalléchère, A. Xemard and C. Miry, “On the

numerical analysis of lightning effect on power installations”,

Page 7: Evaluation of Transmitted Over-Voltages through a Power

International Colloquium on Lightning and Power systems, Lyon, 2014.

DOI: 10.13140/2.1.4261.7601

[4] CIGRE brochure 63, “Guide to Procedures for Estimating the Lightning Performance of Transmission Lines”, 1991.

[5] E. C. Levy, “Complex-curve fitting”, IRE Transaction on Automatic Control, vol. AC-4, no.1, pp.37-43, 1958. DOI:

10.1109/TAC.1959.6429401

[6] B. Gustavsen, “Wide band modeling of power transformers”, IEEE Transactions on Power Delivery, vol. 19, pp. 414-422, 2004. DOI:

10.1109/TPWRD.2003.820197

[7] X. Legrand, A. Xemard, C.A. Nucci and P. Auriol, “A Method to

Interface Electromagnetic Models of Grounding Systems with Transients

Programs”, CIGRE C4 Colloquium on Power Quality and Lightning, Sarajevo, 2012.

[8] IEC Standard 60076-18: “Power Transformers – Part 18: Measurement of

frequency response”, First edition, 2012.

[9] A. Holdyk, B. Gustavsen, I. Arana and J. Holboell, "Wideband Modeling

of Power Transformers Using Commercial sFRA Equipment", IEEE

Transactions on Power Delivery, vol.29, no.3, pp.1446,1453, 2014. DOI:

10.1109/TPWRD.2014.2303174

[10] B. Jurisic, A. Xemard, I. Uglesic, F. Paladian and P. Guuinic, “Case Study on Transformer Models for Calculation of High Frequency

Transmitted Overvoltages”, CIGRE 3rd International Colloquium

"Transformer Research and Asset Management", Split, 2014.

[11] B. Jurisic, I. Uglesic, A. Xemard, F. Paladian and P. Guuinic,

“Difficulties in high frequency transformer modelling”, International Conference on Power System Transients (IPST 2015), Cavtat, 2015.

[12] B. Gustavsen and A. Semlyen, "Rational approximation of frequency domain responses by vector fitting", IEEE Transactions on Power

Delivery, vol.14, no.3, pp.1052-1061, 1999. DOI: 10.1109/61.772353

[13] B. Gustavsen, “Fast Passivity Enforcement for Pole-Residue Models by Perturbation of Residue Matrix Eigenvalues”, IEEE Transactions on

Power Delivery, vol. 23, no. 4, pp. 2278-2285, 2008. DOI:

10.1109/TPWRD.2008.919027

[14] B. Gustavsen, “Fast Passivity Enforcement for S-Parameter Models by

Perturbation of Residue Matrix Eigenvalues”, IEEE Transactions on Advanced Packaging, vol.33, no.1, pp.257-265, 2010. DOI:

10.1109/TADVP.2008.2010508

[15] C. Coelho, J. Phillips, and L. Silveira, “A convex programming approach for generating guaranteed passive approximations to tabulated frequency-

data”, IEEE Transactions on Computer-Aided Design of Integrated

Circuits and Systems, vol. 23, no. 2, pp. 293–301, 2004. DOI: 10.1109/TCAD.2003.822107

[16] Z. Ye, “pmm: A Matlab Toolbox for Passive Macromodeling in RF/mm-wave Circuit Design”, IEEE 10th International Conference on ASIC,

2013. DOI: 10.1109/ASICON.2013.6811857

[17] CIGRE Working Group A2/C4.39, “TB577: Electrical transient interaction between transformers and the power systems”, 2013.

[18] IEC Standard 60071-4: “Insulation co-ordination - Part 4: Computational guide to insulation co-ordination and modelling of electrical networks”,

2004.

[19] IEC Standard 60071-1: “Insulation co-ordination - Part 1: Definition, principles and rules”, 1993.