SubStation Hardened Ethernet Copper to Fiber Links For Reliable Substation Communications Technical Description DYMEC models 3340, 3350, 3344 and 3354 are hardened fiber optic links that convert 10Base-T Ethernet from twisted pair copper to 10Base-FL or Single-mode fiber optics. models 3440, 3450, 3442, 3452, 3444 and 3454 are hardened fiber optic links that convert 100Base-T Ethernet from twisted pair copper to 100Base-FX, 100Base-SX or Single-mode fiber optics. These links are stand-alone mounted and require no programming or set up. Simply mount the Link in an appropriate location and connect power. DYMEC Links are powered from various sources. The standard models accept 90 to 250 Volts ac or dc. Optionally, these Links can also be ordered for 12 or 24 to 48 Volts dc. The power supplies are surge withstand protected to both IEC 63000 and IEEE C37.90 standards. § IEEE 802.3 compatible § 2 RJ45 connectors eliminates the worry over crossover or straight cables § Automatic Polarity detection and correction § Auto adapts to Half or Full Duplex mode DYMEC Features and Benefits § Link Pulse Pass Through or Link Pulse Shut Down Modes are user selectable § Conformal coated PC Boards § Powered from Station Battery Bus to C37.90 or 12 Vdc § Operates reliably at temperatures of -40°C to 85°C with no fans. § Extended distances of 2 km over Multi-mode fiber and 12 km over Single-mode fiber. (Restrictions apply when connecting via hubs into networks) § Multiple Mounting choices with built-in mounting brackets and optional mounting shelf § Packaged in rugged, industrial- quality Galva Neal and powder coated shells § Each data channel has its own diagnostic LEDs for easier debug of installation § 5- year warranty Model 3340 Model 3350 Model 3440 Model 3450 TECHNICAL BULLETIN TB3340

Upload: maxdcruz

Post on 11-Dec-2015

225 views

Category:

Documents


0 download

DESCRIPTION

Garrettocm

TRANSCRIPT

Page 1: Ethernet Links Ds

SubStation Hardened Ethernet

Copper to Fiber Links

For Reliable Substation Communications Technical Description

DYMEC models 3340, 3350, 3344 and 3354 are hardened fiber optic links that convert 10Base-T Ethernet from twisted pair copper to 10Base-FL or Single-mode fiber optics.

models 3440, 3450, 3442, 3452, 3444 and 3454 are hardened fiber optic links that convert 100Base-T Ethernet from twisted pair copper to 100Base-FX, 100Base-SX or Single-mode fiber optics.

These links are stand-alone mounted and require no programming or set up. Simply mount the Link in an appropriate location and connect power. DYMEC Links are powered from various sources. The standard models accept 90 to 250 Volts ac or dc. Optionally, these Links can also be ordered for 12 or 24 to 48 Volts dc. The power supplies are surge withstand protected to both IEC 63000 and IEEE C37.90 standards.

§ IEEE 802.3 compatible

§ 2 RJ45 connectors eliminates the worry over crossover or straight cables

§ Automatic Polarity detection and correction

§ Auto adapts to Half or Full Duplex mode

DYMEC

Features and Benefits

§ Link Pulse Pass Through or Link Pulse Shut Down Modes are user selectable

§ Conformal coated PC Boards

§ Powered from Station Battery Bus to C37.90 or 12 Vdc

§ O p e r a t e s r e l i a b l y a t

temperatures of -40°C to 85°C with no fans.

§ Extended distances of 2 km over Multi-mode fiber and 12 km over Single-mode fiber. (Restrictions apply when connecting via hubs into networks)

§ Multiple Mounting choices with built-in mounting brackets and optional mounting shelf

§ Packaged in rugged, industrial-quality Galva Neal and powder coated shells

§ Each data channel has its own diagnostic LEDs for easier debug of installation

§ 5- year warranty

Model 3340

Model 3350

Model 3440

Model 3450

TECHNICAL BULLETIN TB3340

Page 2: Ethernet Links Ds

Ethernet Link Specifications

3340/3350 10 Base Ethernet 3440/3450 100 Base Ethernet Optical Parameters @ Maximum Temp Multimode Single-Mode Multimode Single-Mode Optical Budget Minimum 13.5 dB 8.6 dB 9.0 dB 8.6 dB Output power Minimum -16 dBm peak -19.9 dBm peak -19 dBm peak -19.9 dBm peak Receiver Sensitivity Minimum -29.5 dBm peak -28.5 dBm peak -28 dBm peak -28.5 dBm peak (62.5µ/125 Multimode) (9µ/125 Single-mode) (62.5µ/125 Multimode) (9µ/125 Single-mode) Wavelength 850nm 1310nm 1300nm 1310nm Connector Type ST Compatible Fiber Type Multimode (50-200µm) Single-Mode (9-13µm) Multimode (50-200µm) Single-Mode (9-13µm) Configuration (Switches) Link Pass-Through/ Link Fail Data Rate 10Mbs 100Mbs Data Transmission Half or Full Duplex Transmission Distance up to 2000 meters up to 10K meters up to 2000 meters up to 10K meters

(62.5µ/125 Cable

@3dB/km) (9µ/125 Cable @0.5dB/km)

(62.5µ/125 Cable @3dB/km)

(9µ/125 Cable @0.5dB/km)

Bit Error Rate 10-E9 Max. Point to Point Latency 100 nsec

Electrical Parameters

Inputs I/O Data Format 802.3 Ethernet 802.3 Ethernet Data Connector 2 RJ45 2 RJ45

Ambient Temperature Operating Temperatures -40 to +85 C -40 to +70 C -40 to +85 C -40 to +70 C Storage Temperature -40 to +85 C Power Required

3X50 5.4 Watts 60 mA @ 90-250 V 300 mA @ 18-60 V

3X40 4.0 Watts 333 mA @ 12Vdc Power Dissipation BTU/H

3X50 18.4 BTU 3X40 13.7 BTU

Physical Parameters Weight

3X50 17 Ozs. 3X40 9 Ozs.

Dimensions Inches 3X50 4.1W X 5.1L X 1.3H 3X40 2.0W X 5.1L X 1.3H

Indicators Power Fiber Link Electrical Link Fiber Data Electrical Data Specifications Subject to Change Without Notice

Page 3: Ethernet Links Ds

DYMEC, Inc. * 25 Commerce Way #1 * North Andover, MA 01845 Tel: 978.688.8807 * Fax: 978.688.8771 * www.dymec.com

Link Pass Through Mode

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

XLPX

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

XLPXLP XPOWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

The Diagram above shows the operation of the 3340-3350 10Base Ethernet Links when the Link Pulse option is set to Pass-through mode (Switch marked ONE/FULL set to ONE). The Bottom diagram shows the 3340 links diagnostic LED's in normal operation. The Data LED's both Fiber and TP will flash when data is actually passing and be off when no data is being transmitted. The Link LED's both Fiber and TP should be on Solid as long as the Power LED is also on. The Middle diagram shows the 3340 links diagnostic LED's when the TP input cable of one of the links is open or damaged. Both of the 3340's show loss of received Link Pulses (one shows Fiber and one shows TP. The 3340 link on the opposite end of the fiber will not be transmitting TP link pulses to the connected IED). The Top diagram shows the 3340 links diagnostic LED's when one of the fiber cables from one of the 3340 links is open or damaged. Only One of the 3340 links show loss of received Link Pulses (The receive fiber of the 3340 link on the opposite end of the break. That 3340 links TP port will not be transmitting link pulses to the connected IED).

Link Fail Mode

XXLPXLP

XLP XLP

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

XLP

XLPXLP

X

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

The Diagram above shows the operation of the 3340-3350 10Base Ethernet Links when the Link Pulse option is set to Fail mode(Switch marked ONE/FULL set to FULL). The Bottom diagram shows the 3340 links diagnostic LED's in normal operation. The Data LED's both Fiber and TP will flash when data is actually passing and be off when no data is being transmitted. The Link LED's both Fiber and TP should be on Solid as long as the Power LED is also on. The Middle diagram shows the 3340 links diagnostic LED's when the TP input cable of one of the 3304 links is open or damaged. Both of the 3340's show loss of received Link Pulses (Both of the 3340 links TP ports will not be transmitting link pulses to the connected IEDs). The Top diagram shows the 3340 links diagnostic LED's when one of the fiber cables from one of the 3340 links is open or damaged. Both of the 3340 links show loss of received Link Pulses (Both of the 3340 links TP ports will not be transmitting link pulses to the connected IEDs).

Page 4: Ethernet Links Ds

Ordering Information

DOC. NO. 3-45-0009-00 REV. AD

Model Input Fiber Type Input Power Rating 802.3 Standard 3340HRT 10 Base-T Multimode 9 - 15 Vdc 10Base-FL

3350HRT-H 10 Base-T Multimode 90-250 Vdc/ 90-250 Vac 10Base-FL 3350HRT-L 10 Base-T Multimode 24 to 48 Vdc 10Base-FL 3344HRT 10 Base-T Single-Mode 9 - 15 Vdc Single-Mode

3354HRT-H 10 Base-T Single-Mode 90-250 Vdc/ 90-250 Vac Single-Mode 3354HRT-L 10 Base-T Single-Mode 24 to 48 Vdc Single-Mode 3440HRT 100 Base-TX Multimode 9 - 15 Vdc 100Base-SX

3450HRT-H 100 Base-TX Multimode 90-250 Vdc/ 90-250 Vac 100Base-SX 3450HRT-L 100 Base-TX Multimode 24 to 48 Vdc 100Base-SX 3442HRT 100 Base-TX Multimode 9 - 15 Vdc 100Base-FX

3452HRT-H 100 Base-TX Multimode 90-250 Vdc/ 90-250 Vac 100Base-FX 3452HRT-L 100 Base-TX Multimode 24 to 48 Vdc 100Base-FX 3444HRT 100 Base-TX Single-Mode 9 - 15 Vdc Single-Mode

3454HRT-H 100 Base-TX Single-Mode 90-250 Vdc/ 90-250 Vac Single-Mode 3454HRT-L 100 Base-TX Single-Mode 24 to 48 Vdc Single-Mode

Accessories ACC-LCS Optional Mounting Bracket

Outline Drawings

Model 3340 Model 3440

Model 3350 Model 3450

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

DYMEC MODEL 3340 LINK10Base-T/10Base-FL

SW ITCH ACCESS

MADE IN U.S.A.

5 .14

2 .061 .25

.17

1 .26

RE MO V A BLE A CCE S S P LA TE

2 RJ45 ConnectorsW ired MDI and MDIX

.50

12 VO LTS DC

#6-32 THRE A D SS T

.34

TY PE "S T"F.O. CO NNE CTOR

G ND S TUD

4 .14

4 .64

NO TE : D IME NS IONS A RE IN INCHE S.

W ITH MA LE CO NN.S UPP LIE D

M ODEL 3340

TR

N OTE: D IMEN SION S AR E IN IN C H ES.

MO DE L 3350

.50

90-250 Vdc/Vac -H24-48 Vdc -L

W ITH MALE C ON N .SU PPLIED

1.25

.46

#6-32 TH R EAD SST

4.14

5.14

2.00 4.12

TR

M ODEL 3350 LINK

E THE RNE T 10 B T / 10 B FL

S W IT CH A CCE S S

M A DE IN U.S .A .

.17R EMOVABLE AC C ESS PLATE

2 R J45 C onnec to rsC onfigured MD I and MD IX

TYPE "ST"F.O . CON N EC TOR

4.64GNDST D

POWER

FIBER LINK

FIBER DATA

TP DATA

TP LINK

DYMEC