Estimating Peak Water Demands in Buildings with Efficient Fixtures: Progress and Prognosis Steven Buchberger Emerging Water Technology Symposium May 15, 2018

Upload: others

Post on 23-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Estimating Peak Water Demands in Buildings with Efficient Fixtures: Progress and Prognosis

Steven Buchberger

Emerging Water Technology Symposium

May 15, 2018

Page 2: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

The Problem

The Progress

The Prognosis

2

Page 3: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Hour

Flow

(L/m

in) Friday, May 16

0 4 8 12 16 20 24

0

20

40

60

80

100

Time History of Water Demand (21 units)

3

Page 4: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

4

Page 5: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

3 Key Fixture Characteristics (n,p,q,)

5

Fixture Flow Rateq:

Fixture Countn:1 2 3 . . . x . . . . . n

Fixture Probability of Usep: itp

T=

Page 7: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

n=100, p=0.20

BUSY FIXTURES

Binomial Distribution

0 20 40 60 80 100

0

0.02

0.04

0.06

0.08

0.1

pro

ba

bil

ity

7

A Building with n=100 Flush Tanks

Binomial Distribution

Page 8: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

n=100, p=0.20

BUSY FIXTURES

Binomial Distribution

0 20 40 60 80 100

0

0.02

0.04

0.06

0.08

0.1

pro

ba

bil

ity

8

Hunter’s Criterion: Design for 99th Percentile

30simultaneous demands

99th Percentile

Page 9: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

9

BUSY FIXTURES

n=100, p=0.20n=100, p=0.40

Binomial Distribution

0 20 40 60 80 100

0

0.02

0.04

0.06

0.08

0.1

pro

ba

bil

ity

Building with 100 flush tanks + 100 red fixtures

Q(0.99) → 30 busy fixturesQ(0.99) → 52 busy fixtures

Page 10: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Hunter’s Curve Predicts Peak Flow (99th percentile)

Fixture Units

GPM

10

Hunter’s 1940 Curve has withstood the test of time; it is the basis for plumbing codes around the globe today.

(Hunter .vs. Moody)

Page 11: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Today Hunter’s Curve is often faulted for overly conservative design….Why?

[1] Simplicity is seductive. Hunter’s curve has been applied to many situations for which it was not intended.

[2] Times have changed. Water use fixtures (hot and cold) have become much more efficient since Hunter’s pioneering work. Water use habits have changed, too.

Main Issues

11

Page 12: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Hunter’s Approach Assumed “Congestion”

12

Page 13: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Modified Hunter’s Curve(s)

13http://www.armstronginternational.com/files/products/wheaters/pdf/sizing%20chart.pdf

Different curve for

different end users

Page 14: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Consequences of Obsolete Guidelines

Obsolete design guidelines produce over-sized premise plumbingand improperly-sized water meters, heaters and softeners.

This, in turn, leads to a host of water/energy problems including: inflated costs of construction, inaccurate metering and water billing, wasted energy and lost water through inefficient water heating, and increased potential health hazards from risk of microbial contamination (Legionella) (ANSI/ASHRAE 2015)

14

Page 15: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

The Problem

The Progress

The Prognosis

15

Page 16: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

16

Daniel Cole, Chair , IAPMO, Mokena, IL Jason Hewitt, CB Engineers, San Francisco, CA

Timothy Wolfe, TRC Worldwide Engineering MEP, Indianapolis, IN Toritseju Omaghomi, College Engr & Applied Science, Univ of Cincinnati, Cincinnati , OH Steven Buchberger, College Engr & Applied Science, Univ of Cincinnati, Cincinnati, OH

Task Group Sponsors and Members

Page 17: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

IAPMO Task Group Orders

“….will work singularly to develop the probability model to predict peak demands based on the number of plumbing fixtures of different kinds installed in one system.”

17

Bring Hunter into 21st Century

Page 18: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

WATER USE DATABASE

18

Page 19: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Database: Location of Homes

❖ Survey 1996-2011❖ MS database

❖ 62 cities

❖ 9 states

❖ 1,038 households

❖ 2,800 residents

❖ 11,350 home-days ❖ 863,000 events

19

Page 20: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

20

FIXTURE GROUP

DESIGN

P-VALUE (%)

MAXIMUM DESIGN

FLOW RATE (GPM)

Bar Sink 2.0 1.5

Bathtub 1.0 5.5

Bidet 1.0 2.0

Clothes Washer 5.5 3.5

Combination Bath/Shower 5.5 5.5

Dishwasher 0.5 1.3

Kitchen Faucet 2.0 2.2

Laundry Faucet 2.0 2.0

Lavatory Faucet 2.0 1.5

Shower, per head 4.5 2.0

Water Closet, 1.28 GPF Gravity Flush Tank 1.0 3.0

Recommended p-values and q-values

20; 4.0

6.7; 8.0

Hunter 1940

Page 21: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Hunter Number: H(n,p) =Σnkpk

21

Page 22: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Fixture Count: n = 100 Probability of Use: p = 0.20Hunter Number: H = np = 20

22

Dimensionless Hunter Number, H

H is “expected number” of flush tanks in simultaneous use during the peak demand period.

Page 23: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Hunter Number H(n,p) = ΣHk = Σnkpk k=1,2,…K

Prob[zero demand] = P0 exp[-H(n,p)]

23

Peak Period Probability of Stagnation

Page 24: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

24

P0=0.78 P0=0.29 P0=0.01

Page 25: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

25

Algorithm for Zone D: Wistort Method (1994)

Page 26: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

n=100, p=0.20

BUSY FIXTURES

Binomial Distribution

0 20 40 60 80 100

0

0.02

0.04

0.06

0.08

0.1

pro

ba

bil

ity

26

Algorithm for Zone D: Wistort Method (1994)[n=100, p=0.20, H(n,p)=20]

Design for the 99th percentile!

30simultaneous demands

( )99

2

99

1 1

1K K

k k k k k

k k

k kn p z n p pQ q q= =

= + −

Page 27: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

n=100, p=0.20

BUSY FIXTURES

Binomial Distribution

0 20 40 60 80 100

0

0.02

0.04

0.06

0.08

0.1

pro

ba

bil

ity

27

Algorithm for Zone D: Wistort Method (1994)[n=100, p=0.20, H(n,p)=20]

Design for the 99th percentile!

30simultaneous demands

Normal approximation for binomial distribution

( )99

2

99

1 1

1K K

k k k k k

k k

k kn p z n p pQ q q= =

= + −

Page 28: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

28

P0=0.78 P0=0.29 P0=0.01

Page 29: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

29

Zones A&B Algorithm: Exhaustive Enumeration

Page 30: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

30

Algorithm for Zones A&B: Exhaustive Enumeration

n=1 fixture2 outcomes0a

EXEN Outcomes Grows as 2n

n=2 fixtures4 outcomes0a, ba+b

n=3 fixtures8 outcomes0a, b, ca+b, a+c, b+ca+b+c

a a a

b cb

n=7 fixtures128 outcomes0a, b, c, d, e, f, ga+b, a+c, a+d …..…….etc…….a+b+c+d+e+f+g

c

e

a

b

d

f g

Page 31: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

31

Example CDF from EXEN for n=4 Fixtures

Page 32: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Plot of Number of Outcomes vs Fixture Count

0 2 4 6 8 10

Fixture Count

0

200

400

600

800

1000

Nu

mb

er

of

Ou

tco

mes

32

Exhaustive Enumeration Grows as 2n

Page 33: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

33

P0=0.78 P0=0.29 P0=0.01

Page 34: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

34

Algorithm for Zone A only: Q1+Q3

a a a

b cb c

e

a

b

d

f g

STEP 1: Rank fixture demands from maximum to minimum.STEP 2: Add rank 1 and rank 3 demands (largest and 3rd largest).

“Q1+Q3” works reasonably well in single family homes (n 12).

Page 35: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

35

• Limiting Case is Deterministic (n=1)• Discrete Random Variables• Single Family Homes• Small Hunter’s Number, H(n,p)• High chance of stagnation P[0]• One water fixture can have a big influence

• Limiting Case is Stochastic (n>>1)• Continuous Random Variables• Multi-Family Developments• Large Hunter’s Number, H(n,p)• Little chance of stagnation, P[0]• One water fixture has little (if any) influence

Transition from One to Many Fixtures

ONE MANY

Page 36: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

WDC: Water Demand Calculator-1

BasicTemplate

36

Page 37: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

WDC: Water Demand Calculator-2

12Fixtures

UPC gives18.2 gpm

40% reduction

1” line↓

¾” line

37

Zone AExample:

Single Family Home

Page 38: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

WDC: Water Demand Calculator-3

1200Fixtures

1200Fixtures

UPC gives397 gpm

62% reduction

5” line↓

3” line

38

Zone DExample:

Multi-Family

Complex

Page 39: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Precautionary Note on Fixture Retrofits

39

Method Peak Flow (gpm)

Pipe Size (inch)

Velocity (fps)

UPC 397 5 6.5

WDC 155 3 7.0

UPC, WDC 155 5 2.5

Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing system. This almost certainly implies longer residence time for water in the premise plumbing system since the volume of water use also drops following retrofit.

Page 40: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

The Problem

The Progress

The Prognosis

40

Page 41: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Design Flow Comparison: School (site 7)

41

Data

M22163 gpm

UPC294 gpm

Flow (gpm)

Pro

bability

WDC 50 gpm

99th Percentile

Page 42: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Design Flow Comparison: Apartments (site 14)

42

Flow (gpm)

Pro

bability

WDC15 gpm

UPC80 gpm

M2240 gpm

99th PercentileData

Page 43: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

BIM: Building Information Model

43

Page 44: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

44

Page 45: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Archive Fixture Values: (p,q)

Fixture Group Kp = 0.05

q = 1.2 gpmFixture Group …

p = 0.05q = 1.2 gpm

Fixture Group 2p = 0.05

q = 1.2 gpmFixture Group 1

p = 0.05q = 1.2 gpm

45

Page 46: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Hunter Number, H

Dim

en

sio

nle

ss

De

ma

nd

99th Percentile

0 5 10 15 20 25 30 35 40 45 50

0

10

20

30

40

50

60

70

(From Omaghomi and Buchberger, 2014).

Universal Dimensionless Design Curve

46

Page 47: Estimating Peak Water Demands in Buildings with Efficient … · 2019-01-30 · Velocity ratio 6.5/2.5 = 2.6 times slower moving water after retrofitting the original premise plumbing

Summary / Conclusions

❖ Introduced a new framework to estimate peak water demand in single/multi-family dwellings.

❖ Replaced fixture units with fixture counts.

❖ Runs on a spreadsheet.

❖ Recommended fixture p and q values.

❖ Can be applied to a wide spectrum of buildings.

❖ WDC is an appendix in the 2018 Code

❖ Approach is amendable to BIM platforms.

47