RTU500 series Environmental data Data sheet General The RTU500 series telecontrol equipment family has been de- signed to meet the requirements for environmental conditions and performance of network control, substation automation sys- tems and process industries. The telecontrol systems RTU560, RTU540, RTU520 and RTU511 and its products manufactured by ABB are type tested. They fulfill the requirements specified and described. The RTUs meet and achieve the requirements listed in the following tables. The requirements can be put into the following categories: Electrical interfaces: Power supply and insulation Electro-magnetic compatibility (EMC) Immunity Emission Environmental conditions: Temperature and humidity Mechanical influences Safety Performance requirements: Reliability, availability, maintenance Time quality for process signals Electrical interfaces The immunity and emission tests are made according to the re- quested IEC standards. The list of tests needed for the RTU500 series is taken from the IEC 60870-2-1 standard. The RTU fulfills the requested level, specified in IEC 60870-2-1. The rules for cable routing and grounding have strictly to be ful- filled, to reach the requested level. This has to be taken into con- sideration for engineering and commissioning. Power supply and insulation applying to IEC 60255-5, IEC 60870-2-1 and IEEE C37.90-1989 Environmental phenomena Required and verified data / values Verified according to test standard AC voltage tolerances of power supply -20 % … +15 % IEC 60870-2-1 Frequency tolerances of power supply ± 5 % IEC 60870-2-1 DC voltage tolerances of power supply -20 % … +15 % IEC 60870-2-1 Immunity to voltage interruption -100 %: 50 ms IEC 61000-4-29 AC power frequency withstand 2,5 kV AC, 50 Hz, 1 min EN 60255-5 Impulse voltage withstand 5 kV DC, 1,2 µs / 50 µs EN 60255-5 Insulation resistance > 100 MΩ at 500 V DC EN 60255-5 EMC Emission applying to IEC 61000-6-4 Environmental phenomena Required and verified data / values Verified according to test standard Enclosure radio interference field strength 30 dB (30 – 230 MHz) 37 dB (230 – 1000 MHz) IEC/CISPR 11 / EN 50011 Power supply radio interference voltage 79 dB (0,15 – 0,5 MHz) 73 dB (0,5 – 30 MHz) IEC/CISPR 11 / EN 50011

Upload: duongcong

Post on 19-Jul-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Environmental data Data sheet - caner62.com Series/CMUs/500ENVI_DS… · The telecontrol systems RTU560, RTU540, RTU520 and RTU511 and its products manufactured by ABB are type tested

RTU500 series

Environmental data Data sheet

General

The RTU500 series telecontrol equipment family has been de-signed to meet the requirements for environmental conditionsand performance of network control, substation automation sys-tems and process industries.

The telecontrol systems RTU560, RTU540, RTU520 andRTU511 and its products manufactured by ABB are type tested.They fulfill the requirements specified and described. The RTUsmeet and achieve the requirements listed in the following tables.

The requirements can be put into the following categories:

Electrical interfaces:– Power supply and insulation– Electro-magnetic compatibility (EMC)

– Immunity– Emission

Environmental conditions:– Temperature and humidity– Mechanical influences– Safety

Performance requirements:– Reliability, availability, maintenance– Time quality for process signals

Electrical interfaces

The immunity and emission tests are made according to the re-quested IEC standards. The list of tests needed for the RTU500series is taken from the IEC 60870-2-1 standard. The RTU fulfillsthe requested level, specified in IEC 60870-2-1.

The rules for cable routing and grounding have strictly to be ful-filled, to reach the requested level. This has to be taken into con-sideration for engineering and commissioning.

Power supply and insulation applying to IEC 60255-5, IEC 60870-2-1 and IEEE C37.90-1989

Environmental phenomena Required and verified data / values Verified according to test standard

AC voltage tolerances of power supply -20 % … +15 % IEC 60870-2-1

Frequency tolerances of power supply ± 5 % IEC 60870-2-1

DC voltage tolerances of power supply -20 % … +15 % IEC 60870-2-1

Immunity to voltage interruption -100 %: 50 ms IEC 61000-4-29

AC power frequency withstand 2,5 kV AC, 50 Hz, 1 min EN 60255-5

Impulse voltage withstand 5 kV DC, 1,2 µs / 50 µs EN 60255-5

Insulation resistance > 100 MΩ at 500 V DC EN 60255-5

EMC Emission applying to IEC 61000-6-4

Environmental phenomena Required and verified data / values Verified according to test standard

Enclosure radio interference field strength 30 dB (30 – 230 MHz)

37 dB (230 – 1000 MHz)

IEC/CISPR 11 / EN 50011

Power supply radio interference voltage 79 dB (0,15 – 0,5 MHz)

73 dB (0,5 – 30 MHz)

IEC/CISPR 11 / EN 50011

Page 2: Environmental data Data sheet - caner62.com Series/CMUs/500ENVI_DS… · The telecontrol systems RTU560, RTU540, RTU520 and RTU511 and its products manufactured by ABB are type tested

2 | 1KGT 150 400 V009 1 - Environmental data

EMC Immunity applying to IEC 60255, IEC 60870-2-1, IEC 61000-6-2, IEC 61000-6-5, IEC 61850-3 and IEEE C37.90.1-2002

Environmental phenomena Required and verified data / values Verified according to test standard

Electrostatic discharge (ESD) Cubicle 15/8 kV

Modules 8/6 kV

IEC 61000-4-2 level 4

Radiated electromagnetic field 10 V/m IEC 61000-4-3 level 3

Electrical fast transient / Burst 4 kV IEC 61000-4-4 level 4

Surge 2 kV

4 kV (23BE40, 23BA40)

IEC 61000-4-5 level 3

IEC 61000-4-5 level 4

Conducted disturbance included by radio-frequency fields 10 V IEC 61000-4-6 level 3

Power frequency magnetic field 30 A/m IEC 61000-4-8 level 4

Damped oscillatory wave 2,5 kV / 1 kV IEC 61000-4-12 level 3

Mains frequency interference 50 Hz 30 / 300 V EN 61000-4-16 level 4

AC ripple on DC power supply 12 % EN 61000-4-17 level 3

Voltage dips on DC power supply -30 %, 100 ms

-60 %, 100 ms

IEC 61000-4-29

Voltage short interruptions on DC power supply -100 %, 50 ms IEC 61000-4-29

Environmental conditions

The tests were made with a typical RTU560 telecontrol stationin a standard cubicle (IP 55 / DIN 40050). RTU540, RTU520 andRTU511 are tested without cubicle. The functionality was per-manently verified during and after the tests, with typical 60 %active input signals.

The shock values express a shock strain, which may occur dur-ing transportation.

The results of the vibration and shock tests are mainly influencedby the used cubicle and mounting methods. The test results arevalid for the RTU560 standard cubicles and mounting methods.

Temperature and humidity applying to IEC 60870-2-2 and IEEE C37.90-1989

Parameter Required and verified data / values Verified according to test standard

Operating temperature -25 °C ... 55 °C

-13 °F … 131 °F

IEC 60068-2-1 / 2

Storage temperature -25 °C ... 55 °C

-13 °F … 131 °F

IEC 60068-2-1 / 2

Temperature-Humidity (cyclic test) 5 … 95% (non condensing) IEC 60068-2-30

Rate of change of temperature 0,5 °C / min

32,9 °F / min

IEC 60870-2-2 class C1

Atmospheric pressure 70 … 106 kPa IEC 60870-2-2 class C1

Altitude (operation) <= 3000 m IEC 60870-2-2 class C1

Mechanical influences applying to IEC 60255-21 and IEC 60870-2-2

Influence Required and verified data / values Verified according to test standard

Vibration (sinusoidal) response test 0,5 g (10 Hz … 150 Hz) IEC 60068-2-6

Vibration (sinusoidal) seismic test 3,5 mm (3 Hz … 9 Hz) IEC 60068-2-6

Page 3: Environmental data Data sheet - caner62.com Series/CMUs/500ENVI_DS… · The telecontrol systems RTU560, RTU540, RTU520 and RTU511 and its products manufactured by ABB are type tested

Environmental data - 1KGT 150 400 V009 1 | 3

Influence Required and verified data / values Verified according to test standard

Vibration (sinusoidal) enduration test 1 g (9 Hz … 200 Hz) IEC 60068-2-6

Vibration (sinusoidal) high frequency test 1,5 g (200 Hz … 500 Hz) IEC 60068-2-6

Shock (half sine) 15 g / 11 ms,

25 g / 10 ms

IEC 60068-2-27

Bump (half sine) 10 g / 16 ms / 1000 pulses IEC 60068-2-29

Safety

The safety of the RTU560, RTU540, RTU520 and RTU511 asdescribed before is verified according to IEC 60950-1 and cer-tificated based on the IECEE CB scheme.

The differences to Australian / New Zealand, Canadian, Chinese,Israeli, Japanese, Korean, Singapore and US national require-ments to safety are also verified.

Performance requirementsPerformance Classes according IEC 60870-4

Performance characteristic Required data / value Class IEC 60870-4

Reliability MTBF MTBF ≥ 8.760 h R3

Availability A A ≥ 99.95 % A3

Maintainability MTTR MTTR ≤ 12 h M3

Mean repair time MRT MRT ≤ 1 h

(depends on strategy)

RT4

Data integrity classes IE IE ≤ 10-10 I2

Time separation capability SP SP ≤ 10 ms (between stations)

SP ≤ 5 ms (within a station)

SP2

SP3

Time resolution TR TR ≤ 1 ms TR4

Analogue overall accuracy E E ≤ 0.5 % A4

Reliability

The reliability of a RTU500 series is calculated on the base of atypical RTU station. The size is the experience of several hundredsupplied substations.

The calculation for RTU560 is based on the following data:

– 48 analogue measured information (AMI)– 100 single point information (SPI)– 64 double point information (DPI)– 8 integrated total information (ITI)– 80 double command output (DCO)– 1 command supervision board (1 out of n)– 3 sub-racks with power supply– 1 FSK modem

The typical reliability for such a substation is approximately33.000 hours. The reliability is defined by a serial structure. Thismeans a failure of one board/unit is defined as a system failure,

even if the other boards are operating well. The calculation isshown in Fig. 2. This sheet may also be used for calculation ofany other RTU560 configuration.

For RTU540, RTU520 and RTU511 also typical configurationsare selected (see Fig. 3 to see "Fig. 5: RTU511 Reliability Val-ues").

The mean repair time (MRT) of a RTU500 series will be typically1 hour. The RTU500 series concept has several supervision anddiagnostic capabilities, which assist the debugging and mainte-nance activities, when needed:

– Permanent online diagnostic of all I/O boards– LEDs on all boards indicating internal/external errors– None or only a few configuration settings onboard neces-

sary– PC based diagnostic tools

Page 4: Environmental data Data sheet - caner62.com Series/CMUs/500ENVI_DS… · The telecontrol systems RTU560, RTU540, RTU520 and RTU511 and its products manufactured by ABB are type tested

4 | 1KGT 150 400 V009 1 - Environmental data

The main telecontrol transmission protocols are based on formatclass FT1.2 (IEC 60870-5-1). In addition, the transmission pro-tocol allows for commands the ‘Select and Execute Command’strategy, which essentially decreases the residual information er-ror possibility in command direction.

The performance of time separating is given by the time syn-chronization quality of the network control system. The RTU500series has the possibility to be synchronized via communicationlines from the Network Control Centre (NCC), by sntp or by aDCF77 or GPS clock. The scan cycle for binary input signals is1 ms, executed by the microcontroller on each input board. Theboards are synchronized by the communication unit (CMU) ofthe RTU560. This allows a time resolution within a station of 1ms for binary inputs.

The overall accuracy for analogue signals is given by the totalerror of the 23AE23 analogue input board. For the real overallerror of the analogue output board 23AA21 see the hardwaredata sheet.

NCC

CommunicationSub-rack

ExtensionSub-rack

ExtensionSub-rack

Figure 1: Typical RTU560 telecontrol station

Page 5: Environmental data Data sheet - caner62.com Series/CMUs/500ENVI_DS… · The telecontrol systems RTU560, RTU540, RTU520 and RTU511 and its products manufactured by ABB are type tested

Environmental data - 1KGT 150 400 V009 1 | 5

Figure 2: RTU560 Reliability Values

Page 6: Environmental data Data sheet - caner62.com Series/CMUs/500ENVI_DS… · The telecontrol systems RTU560, RTU540, RTU520 and RTU511 and its products manufactured by ABB are type tested

6 | 1KGT 150 400 V009 1 - Environmental data

Figure 3: RTU540 Reliability Values

Figure 4: RTU520 Reliability Values

Page 7: Environmental data Data sheet - caner62.com Series/CMUs/500ENVI_DS… · The telecontrol systems RTU560, RTU540, RTU520 and RTU511 and its products manufactured by ABB are type tested

Environmental data - 1KGT 150 400 V009 1 | 7

Figure 5: RTU511 Reliability Values

Page 8: Environmental data Data sheet - caner62.com Series/CMUs/500ENVI_DS… · The telecontrol systems RTU560, RTU540, RTU520 and RTU511 and its products manufactured by ABB are type tested

8 | 1KGT 150 400 V009 1 - Environmental data

ABB AGPower Systems DivisionP.O. Box 10 03 5168128 Mannheim, Germany

www.abb.com/substationautomation

Note:

The specifications, data, design or other information contained in this document

(the “Brochure”) - together: the “Information” - shall only be for information pur-

poses and shall in no respect be binding. The Brochure does not claim to be ex-

haustive. Technical data in the Information are only approximate figures. We re-

serve the right at any time to make technical changes or modify the contents of

this document without prior notice. The user shall be solely responsible for the

use of any application example or information described within this document.

The described examples and solutions are examples only and do not represent

any comprehensive or complete solution. The user shall determine at its sole

discretion, or as the case may be, customize, program or add value to the ABB

products including software by creating solutions for the end customer and to

assess whether and to what extent the products are suitable and need to be ad-

justed or customized.

This product is designed to be connected to and to communicate information

and data via a network interface. It is the users sole responsibility to provide and

continuously ensure a secure connection between the product and users or end

customers network or any other network (as the case may be). The user shall es-

tablish and maintain any appropriate measures (such as but not limited to the in-

stallation of firewalls, application of authentication measures, encryption of da-

ta, installation of anti-virus programs, etc) to protect the product, the network,

its system and the interface against any kind of security breaches, unauthorized

access, interference, intrusion, leakage and/or theft of data or information. ABB

AG is not liable for any damages and/or losses related to such security breaches,

any unauthorized access, interference, intrusion, leakage and/or theft of data or

information.

ABB AG shall be under no warranty whatsoever whether express or implied and

assumes no responsibility for the information contained in this document or for

any errors that may appear in this document. ABB AG's liability under or in con-

nection with this Brochure or the files included within the Brochure, irrespective

of the legal ground towards any person or entity, to which the Brochure has been

made available, in view of any damages including costs or losses shall be exclud-

ed. In particular ABB AG shall in no event be liable for any indirect, consequen-

tial or special damages, such as – but not limited to – loss of profit, loss of pro-

duction, loss of revenue, loss of data, loss of use, loss of earnings, cost of cap-

ital or cost connected with an interruption of business or operation, third party

claims. The exclusion of liability shall not apply in the case of intention or gross

negligence. The present declaration shall be governed by and construed in ac-

cordance with the laws of Switzerland under exclusion of its conflict of laws rules

and of the Vienna Convention on the International Sale of Goods (CISG).