The Savant SmartLighting Transorb Board (ENC-TRANS), Quick Reference Guide provides installation information. Box Contents (1) Transorb Board (ENC-TRANS-00) (2) Screws 6-32 x 0.375 in (039-5150-600) (1) Quick Reference Guide (this document) Required Accessories Two Module Enclosure (ENC-2000-xx) Four Module Enclosure (ENC-4000-xx) Specifications Environmental Temperature 32° to 95° F (0° to 35° C) - Ambient Operating Dimensions and Weight Height 2.20 in/5.59 cm Width 2.20 in/5.59 cm Weight 1.0 lb/ 0.45 kg (shipping weight) Compliance RoHS Compliant Module Bus Connector RJ-45 Ports r OUT IN Transorb Board Installation Transorb Board Four-Module Enclosure CAUTION: Before removing or installing a Transorb board in the Enclosure, disconnect all the power. To install the Transorb board do the following: 1. Remove theTransorb board from the anti-static bag . 2. Place the Transorb board in the enclosure. 3. Using the screws supplied, screw the Transorb board into the Enclosure with a Phillips head screwdriver. Grounding Procedure To avoid damage from electrostatic discharge (ESD) when handling boards, use a grounding strap as shown below: Observe the following precautions to prevent ESD discharge damage: 1. Use an approved ESD wrist grounding strap or an approved wrist or ankle strap. Ensure the grounding strap makes good skin contact. 2. Before installing or removing a Savant Transorb board, connect the clip end of the ground strap to a grounded surface. If you plan to return a replaced Transorb board to Savant Systems LLC: While wearing the grounded strap, place the board in the anti-static bag that it was originally shipped in or any static shielding bag to avoid ESD damage to the board. NOTE: The wrist strap only protects the component from ESD voltages on the body; ESD voltages on clothing can still cause damage. CAUTION: Keep these wires on their respective side of the enclosure. Do not cross over or under the voltage barrier with wires. Additional Documentation Additional Documentation is available at: dealers.SavantSystems.com Knowledge Base > Savant Hardware > Lighting Control > Enclosures SmartLighting Transorb Board (ENC-TRANS) Quick Reference Guide 009-0815-01 ENC-TRANS-00 120612 Copyright © 2012 Savant Systems, LLC. SAVANT and RacePoint Blueprint are trademarks of Savant Systems, LLC. All brand names, product names and trademarks are the property of their respective owners. Savant Systems, LLC reserves the right to change product specifications without notice.

Upload: truongdiep

Post on 31-Mar-2018

216 views

Category:

Documents


3 download

TRANSCRIPT

The Savant SmartLighting Transorb Board (ENC-TRANS), Quick Reference Guide provides installation information.

Box Contents(1) Transorb Board (ENC-TRANS-00)(2) Screws 6-32 x 0.375 in (039-5150-600)(1) Quick Reference Guide (this document)

Required Accessories Two Module Enclosure (ENC-2000-xx)Four Module Enclosure (ENC-4000-xx)

SpecificationsEnvironmentalEnvironmental

Temperature 32° to 95° F (0° to 35° C) - Ambient Operating

Dimensions and WeightDimensions and Weight

Height 2.20 in/5.59 cm

Width 2.20 in/5.59 cm

Weight 1.0 lb/ 0.45 kg (shipping weight)ComplianceCompliance

RoHS Compliant

!"#$%&&'$()'**+ !"#$%&&'()$*+,-./'0,12,"*"$#

62 LiteTouch Installation and Troubleshooting Manual

Plug a data cable into the five-pin connector on the transorb board, and plug the other end into the DATA IN port on the first module.

2. Connect another data cable to the DATA OUT port on the first module and to the DATA IN port on the second module.

3. Continue to connect a cable to the DATA OUT port of one module and the DATA IN port of the next module until all control modules in the enclosure are connected.

!"#$ ! !"#"$%&'&()$*+,-$(+#$.+((,.#$#+$/+%,'$-0//1&,-2$3+3,(#"'4$.+(#".#$*"#"$&(/0#$3+*01,-2$+'$3"&(#"&(,*$.+(#".#$*"#"$&(/0#$3+*01,-5$611$3+*01,-$#7"#$30-#$8,$&(.10*,*$&($#7,$*"#"$%&'&()$7"9,$!6:6$;<$"(*$!6:6$=>:$/+'#-5$

When finished, all control modules in each enclosure should be connected in a string to the first module (top module), which is connected to the tran-sorb board via the 5-pin connector.

,$-."/'0"1&2#3-)#42/)$()-

In large installations (more than eight enclosures), or when you have mul-tiple enclosure locations, you can string enclosures together to reduce the number of data homeruns to the CCU. While this helps to simplify the wiring, you should be aware that an early circuit breaker failure in the

Module Bus Connector

RJ-45 Ports

!"#$%&&'()$*+,-./'0,12,"*"$# !"#$%&&'$()'**+

LiteTouch Installation and Troubleshooting Manual 63

string leaves all modules beyond the failure without communication to the CCU.

!"#$ ! !"#$%"&#'($)&*#$+(*,&-$)&*#.$&-$/"#$(,/,$0,1'#$23%/$1#$04--#0/#($/4$#,0"$24(53'#6$/4$#,0"$/*,-%4*1$14,*(6$,-($/4$/"#$7789$:/$%#*;#%$,%$,$<*43-($*#=#*#-0#$=4*$04223-&0,/&4-%9

LiteTouch number 08-2105-01 wire is recommended for data wiring. It contains two twisted-pair, 22-gauge wires and an insulated bare shield wire. The cable is shielded with mylar. The table below shows LiteTouch wire colors. The cable color used for data wiring is green.

6800-202

UL®

LISTED71TO

IND. CONT. EQ.® LR50210

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 268-8 668 • FAX (801) 268 -9200 • TECH HOT LINE 1-800-527- 5527

WARNINGA SHO RTED LOA D WILL DAMAGE MODULE..

THIS IS NOT CO VERED BY WA RRANTY.

TO A VOID POSSIBLE DAMAGE TO MODULEAC POWER MUST BE REMOVED BEFORE

CONNECTING O R DISCONNECTING LOA DS.

®

Rated 2 Amps 15 Volts Max.Neutral

120 VA C60 HZ

Neutral

120 VA C60 HZ

WIRE RANGE 10-16 AW G. / TO RQUE 10-12 IN. L BS. / 60 c MIN. CO PPER WI RE ONL Y

POWER

DC Pos.

DC Com.

FUSE A GC 5 Amp.

NOT USE D

POWER

DC Pos.

DC Com.

FUSE A GC 5 Amp.

NOT USE D

Power

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

® ®

LISTED71TO

IND. CONT. EQ.

1 st DIGIT

2 nd DIGIT

ADDRESSSWITCHES

ADDRESS

RATED 2 0 AM PS TOTAL, 12 0 V OLTS TUNGSTENNOT TO EXCEED 1 6 AM PS ON A NY SINGLE OUTPUT

CAUTION R ISK OF ELECTRICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT FROM POWER BEFORE SERVICING.

®

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE LOADLEDS

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL BLOW FUSE

AND CAN DAMAGE M ODULE.THIS IS NOT COVERED BY WARRANTY.

WIRE RA NGE 1 0-16 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLYUSE FAST A CTING 2 0 AM P FUSES.

12345678

MANUALOFF ON

SERIAL NO. ____________________________________

POWER

12345678

REMOTEMANUAL

ON

COMM ON

C

Dimm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

® ®

LISTED71TO

IND. CONT. EQ.

1 st DIGIT

2 nd DIGIT

ADDRESSSWITCHES

ADDRESS

RATED 2 0 AM PS TOTAL, 12 0 V OLTS TUNGSTENNOT TO EXCEED 1 6 AM PS ON A NY SINGLE OUTPUT

CAUTION R ISK OF ELECTRICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT FROM POWER BEFORE SERVICING.

®

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE LOADLEDS

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL BLOW FUSE

AND CAN DAMAGE M ODULE.THIS IS NOT COVERED BY WARRANTY.

WIRE RA NGE 1 0-16 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLYUSE FAST A CTING 2 0 AM P FUSES.

12345678

MANUALOFF ON

SERIAL NO. ____________________________________

POWER

12345678

REMOTEMANUAL

ON

COMM ON

C

Dimm er

LISTED71TO

IND. CONT. EQ.

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

1 st DIGIT

2 st DIGIT

POWER

ADDRESSSWITCHES

NEUTRAL 1

LINE 1

LOAD 1

LINE 2

LOAD 2

LINE 3

LOAD 3

LINE 4

LOAD 4

LINE 5

LOAD 5

LINE 6

LOAD 6

LINE 7

LOAD 7

LINE 8

LOAD 8

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

123456789

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE

LOAD

LED'S

INTERRLOCK

SWITCHES

REMOTE

MANUAL

ON

COMM ON

MANUAL

ON

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL DAMAGE M ODULE.

THIS IS NOT COVERED BY WARRANTY.TO TEST FOR SHORT, CONNECT LINE TO

LOADS AND A PPLY POWER BEFORECONNECTING LOADS TO SSC M ODULE.

TO AV OID POSSIBLE DAMAGE TO M ODULEAC POWER M UST BE R EMOVED BEFORE

CONNECTING OR DISCONNECTING LOADS.

WIRE RA NGE 12 -22 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLY

®

UL®UL®

SERIAL NO.

RELAY RATINGS

VOLTAGE

INC.

FLUOR.

LV.

LOAD TYPE RATING8.3A @ 120/250V AC

12A @ 120/250V AC

12A @ 120/250V AC

AC60 Hz

1/2 HP @ 120VAC1 HP @ 240VACMOTOR

SERIAL NO. _________________

C

12

34

56

78

Relay

6800-202

UL®

LISTED71TO

IND. CONT. EQ.® LR50210

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 268-8 668 • FAX (801) 268-9200 • TECH HOT LINE 1-800 -527-5527

WARNINGA SHO RTED LOA D WILL DAMAGE MODULE..

THIS IS NOT CO VERED BY WA RRANTY.

TO A VOID POSSIBLE DAMAGE TO MODULEAC POWER MUST BE REMOVED BEFORE

CONNECTING O R DISCONNECTING LOA DS.

®

Rated 2 Amps 15 Volts Max.Neutral

120 VA C60 HZ

Neutral

120 VA C60 HZ

WIRE RANGE 10-16 AW G. / TO RQUE 10-12 IN. L BS. / 60 c MIN. CO PPER WI RE ONL Y

POWER

DC Pos.

DC Com.

FUSE A GC 5 Amp.

NOT USE D

POWER

DC Pos.

DC Com.

FUSE A GC 5 Amp.

NOT USE D

Power

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

® ®

LISTED71TO

IND. CONT. EQ.

1 st DIGIT

2 nd DIGIT

ADDRESSSWITCHES

ADDRESS

RATED 2 0 AM PS TOTAL, 12 0 V OLTS TUNGSTENNOT TO EXCEED 1 6 AM PS ON A NY SINGLE OUTPUT

CAUTION R ISK OF ELECTRICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT FROM POWER BEFORE SERVICING.

®

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE LOADLEDS

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL BLOW FUSE

AND CAN DAMAGE M ODULE.THIS IS NOT COVERED BY WARRANTY.

WIRE RA NGE 1 0-16 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLYUSE FAST A CTING 2 0 AM P FUSES.

12345678

MANUALOFF ON

SERIAL NO. ____________________________________

POWER

12345678

REMOTEMANUAL

ON

COMM ON

C

Dimm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

® ®

LISTED71TO

IND. CONT. EQ.

1 st DIGIT

2 nd DIGIT

ADDRESSSWITCHES

ADDRESS

RATED 2 0 AM PS TOTAL, 12 0 V OLTS TUNGSTENNOT TO EXCEED 1 6 AM PS ON A NY SINGLE OUTPUT

CAUTION R ISK OF ELECTRICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT FROM POWER BEFORE SERVICING.

®

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE LOADLEDS

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL BLOW FUSE

AND CAN DAMAGE M ODULE.THIS IS NOT COVERED BY WARRANTY.

WIRE RA NGE 1 0-16 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLYUSE FAST A CTING 2 0 AM P FUSES.

12345678

MANUALOFF ON

SERIAL NO. ____________________________________

POWER

12345678

REMOTEMANUAL

ON

COMM ON

C

Dimm er

LISTED71TO

IND. CONT. EQ.

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

1 st DIGIT

2 st DIGIT

POWER

ADDRESSSWITCHES

NEUTRAL 1

LINE 1

LOAD 1

LINE 2

LOAD 2

LINE 3

LOAD 3

LINE 4

LOAD 4

LINE 5

LOAD 5

LINE 6

LOAD 6

LINE 7

LOAD 7

LINE 8

LOAD 8

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

123456789

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE

LOAD

LED'S

INTERRLOCK

SWITCHES

REMOTE

MANUAL

ON

COMM ON

MANUAL

ON

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL DAMAGE M ODULE.

THIS IS NOT COVERED BY WARRANTY.TO TEST FOR SHORT, CONNECT LINE TO

LOADS AND A PPLY POWER BEFORECONNECTING LOADS TO SSC M ODULE.

TO AV OID POSSIBLE DAMAGE TO M ODULEAC POWER M UST BE R EMOVED BEFORE

CONNECTING OR DISCONNECTING LOADS.

WIRE RA NGE 12 -22 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLY

®

UL®UL®

SERIAL NO.

RELAY RATINGS

VOLTAGE

INC.

FLUOR.

LV.

LOAD TYPE RATING8.3A @ 120/250V AC

12A @ 120/250V AC

12A @ 120/250V AC

AC60 Hz

1/2 HP @ 120VAC1 HP @ 240VACMOTOR

SERIAL NO. _________________

C

12

34

56

78

Relay

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

® ®

LISTED71TO

IND. CONT. EQ.

1 st DIGIT

2 nd DIGIT

ADDRESSSWITCHES

ADDRESS

RATED 2 0 AM PS TOTAL, 12 0 V OLTS TUNGSTENNOT TO EXCEED 1 6 AM PS ON A NY SINGLE OUTPUT

CAUTION R ISK OF ELECTRICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT FROM POWER BEFORE SERVICING.

®

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE LOADLEDS

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL BLOW FUSE

AND CAN DAMAGE M ODULE.THIS IS NOT COVERED BY WARRANTY.

WIRE RA NGE 1 0-16 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLYUSE FAST A CTING 2 0 AM P FUSES.

12345678

MANUALOFF ON

SERIAL NO. ____________________________________

POWER

12345678

REMOTEMANUAL

ON

COMM ON

C

Dimm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

® ®

LISTED71TO

IND. CONT. EQ.

1 st DIGIT

2 nd DIGIT

ADDRESSSWITCHES

ADDRESS

RATED 2 0 AM PS TOTAL, 12 0 V OLTS TUNGSTENNOT TO EXCEED 1 6 AM PS ON A NY SINGLE OUTPUT

CAUTION R ISK OF ELECTRICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT FROM POWER BEFORE SERVICING.

®

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE LOADLEDS

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL BLOW FUSE

AND CAN DAMAGE M ODULE.THIS IS NOT COVERED BY WARRANTY.

WIRE RA NGE 1 0-16 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLYUSE FAST A CTING 2 0 AM P FUSES.

12345678

MANUALOFF ON

SERIAL NO. ____________________________________

POWER

12345678

REMOTEMANUAL

ON

COMM ON

C

Dimm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

® ®

LISTED71TO

IND. CONT. EQ.

1 st DIGIT

2 nd DIGIT

ADDRESSSWITCHES

ADDRESS

RATED 2 0 AM PS TOTAL, 12 0 V OLTS TUNGSTENNOT TO EXCEED 1 6 AM PS ON A NY SINGLE OUTPUT

CAUTION R ISK OF ELECTRICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT FROM POWER BEFORE SERVICING.

®

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE LOADLEDS

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL BLOW FUSE

AND CAN DAMAGE M ODULE.THIS IS NOT COVERED BY WARRANTY.

WIRE RA NGE 1 0-16 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLYUSE FAST A CTING 2 0 AM P FUSES.

12345678

MANUALOFF ON

SERIAL NO. ____________________________________

POWER

12345678

REMOTEMANUAL

ON

COMM ON

C

Dimm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

® ®

LISTED71TO

IND. CONT. EQ.

1 st DIGIT

2 nd DIGIT

ADDRESSSWITCHES

ADDRESS

RATED 2 0 AM PS TOTAL, 12 0 V OLTS TUNGSTENNOT TO EXCEED 1 6 AM PS ON A NY SINGLE OUTPUT

CAUTION R ISK OF ELECTRICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT FROM POWER BEFORE SERVICING.

®

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE LOADLEDS

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL BLOW FUSE

AND CAN DAMAGE M ODULE.THIS IS NOT COVERED BY WARRANTY.

WIRE RA NGE 1 0-16 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLYUSE FAST A CTING 2 0 AM P FUSES.

12345678

MANUALOFF ON

SERIAL NO. ____________________________________

POWER

12345678

REMOTEMANUAL

ON

COMM ON

C

Dimm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

® ®

LISTED71TO

IND. CONT. EQ.

1 st DIGIT

2 nd DIGIT

ADDRESSSWITCHES

ADDRESS

RATED 2 0 AM PS TOTAL, 12 0 V OLTS TUNGSTENNOT TO EXCEED 1 6 AM PS ON A NY SINGLE OUTPUT

CAUTION R ISK OF ELECTRICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT FROM POWER BEFORE SERVICING.

®

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE LOADLEDS

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL BLOW FUSE

AND CAN DAMAGE M ODULE.THIS IS NOT COVERED BY WARRANTY.

WIRE RA NGE 1 0-16 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLYUSE FAST A CTING 2 0 AM P FUSES.

12345678

MANUALOFF ON

SERIAL NO. ____________________________________

POWER

12345678

REMOTEMANUAL

ON

COMM ON

C

Dimm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

® ®

LISTED71TO

IND. CONT. EQ.

1 st DIGIT

2 nd DIGIT

ADDRESSSWITCHES

ADDRESS

RATED 2 0 AM PS TOTAL, 12 0 V OLTS TUNGSTENNOT TO EXCEED 1 6 AM PS ON A NY SINGLE OUTPUT

CAUTION R ISK OF ELECTRICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT FROM POWER BEFORE SERVICING.

®

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE LOADLEDS

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL BLOW FUSE

AND CAN DAMAGE M ODULE.THIS IS NOT COVERED BY WARRANTY.

WIRE RA NGE 1 0-16 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLYUSE FAST A CTING 2 0 AM P FUSES.

12345678

MANUALOFF ON

SERIAL NO. ____________________________________

POWER

12345678

REMOTEMANUAL

ON

COMM ON

C

Dimm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

® ®

LISTED71TO

IND. CONT. EQ.

1 st DIGIT

2 nd DIGIT

ADDRESSSWITCHES

ADDRESS

RATED 2 0 AM PS TOTAL, 12 0 V OLTS TUNGSTENNOT TO EXCEED 1 6 AM PS ON A NY SINGLE OUTPUT

CAUTION R ISK OF ELECTRICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT FROM POWER BEFORE SERVICING.

®

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE LOADLEDS

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL BLOW FUSE

AND CAN DAMAGE M ODULE.THIS IS NOT COVERED BY WARRANTY.

WIRE RA NGE 1 0-16 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLYUSE FAST A CTING 2 0 AM P FUSES.

12345678

MANUALOFF ON

SERIAL NO. ____________________________________

POWER

12345678

REMOTEMANUAL

ON

COMM ON

C

Dimm er

OUTPUT 5

OUTPUT 6

OUTPUT 7

OUTPUT 8

INPUT 120VAC 6 0Hz

01 2 3 456789ABCD

E F

01 2 3 456789ABCD

E F

NEUTRAL

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

6800-270

® ®

LISTED71TO

IND. CONT. EQ.

1 st DIGIT

2 nd DIGIT

ADDRESSSWITCHES

ADDRESS

RATED 2 0 AM PS TOTAL, 12 0 V OLTS TUNGSTENNOT TO EXCEED 1 6 AM PS ON A NY SINGLE OUTPUT

CAUTION R ISK OF ELECTRICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT FROM POWER BEFORE SERVICING.

®

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA IN

12345

RECEIVE +RECEIVE –TRANSMIT +TRANSMIT –GND/SHIELD

DATA OUT

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

ACTIVE LOADLEDS

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 2 68-8668 • FAX (801) 2 68-9200 • TECH HOT LINE 1 -800-527-5527

WARNINGA SHORTED LOAD WILL BLOW FUSE

AND CAN DAMAGE M ODULE.THIS IS NOT COVERED BY WARRANTY.

WIRE RA NGE 1 0-16 A WG.TORQUE 1 0-12 IN. LBS.

60 c M IN. COPPER WIRE ONLYUSE FAST A CTING 2 0 AM P FUSES.

12345678

MANUALOFF ON

SERIAL NO. ____________________________________

POWER

12345678

REMOTEMANUAL

ON

COMM ON

C

Dimm erR

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY.

WHEN DRIVING TRANSFORMER COUPLEDLOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/ARATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE Label P/N 6800-258.01

ADDRESS

MANUALON

ACTIVEOUTPUTLEDS

MANUALREMOTE

ON

INPUT120 VAC 60 Hz.

LOAD TYPELOAD TYPE

TUNGSTENTUNGSTEN

RELAY RATINGRELAY RATING

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

Dimm er

R

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY.

WHEN DRIVING TRANSFORMER COUPLEDLOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/ARATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE Label P/N 6800-258.01

ADDRESS

MANUALON

ACTIVEOUTPUTLEDS

MANUALREMOTE

ON

INPUT120 VAC 60 Hz.

LOAD TYPELOAD TYPE

TUNGSTENTUNGSTEN

RELAY RATINGRELAY RATING

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

Dimm er

R

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY.

WHEN DRIVING TRANSFORMER COUPLEDLOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/ARATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE Label P/N 6800-258.01

ADDRESS

MANUALON

ACTIVEOUTPUTLEDS

MANUALREMOTE

ON

INPUT120 VAC 60 Hz.

LOAD TYPELOAD TYPE

TUNGSTENTUNGSTEN

RELAY RATINGRELAY RATING

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

Dimm er

R

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY.

WHEN DRIVING TRANSFORMER COUPLEDLOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/ARATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE Label P/N 6800-258.01

ADDRESS

MANUALON

ACTIVEOUTPUTLEDS

MANUALREMOTE

ON

INPUT120 VAC 60 Hz.

LOAD TYPELOAD TYPE

TUNGSTENTUNGSTEN

RELAY RATINGRELAY RATING

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

Dimm er

R

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY.

WHEN DRIVING TRANSFORMER COUPLEDLOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/ARATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE Label P/N 6800-258.01

ADDRESS

MANUALON

ACTIVEOUTPUTLEDS

MANUALREMOTE

ON

INPUT120 VAC 60 Hz.

LOAD TYPELOAD TYPE

TUNGSTENTUNGSTEN

RELAY RATINGRELAY RATING

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

Dimm er

R

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY.

WHEN DRIVING TRANSFORMER COUPLEDLOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/ARATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE Label P/N 6800-258.01

ADDRESS

MANUALON

ACTIVEOUTPUTLEDS

MANUALREMOTE

ON

INPUT120 VAC 60 Hz.

LOAD TYPELOAD TYPE

TUNGSTENTUNGSTEN

RELAY RATINGRELAY RATING

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

Dimm er

R

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY.

WHEN DRIVING TRANSFORMER COUPLEDLOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/ARATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE Label P/N 6800-258.01

ADDRESS

MANUALON

ACTIVEOUTPUTLEDS

MANUALREMOTE

ON

INPUT120 VAC 60 Hz.

LOAD TYPELOAD TYPE

TUNGSTENTUNGSTEN

RELAY RATINGRELAY RATING

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

Dimm er

R

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY.

WHEN DRIVING TRANSFORMER COUPLEDLOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/ARATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE Label P/N 6800-258.01

ADDRESS

MANUALON

ACTIVEOUTPUTLEDS

MANUALREMOTE

ON

INPUT120 VAC 60 Hz.

LOAD TYPELOAD TYPE

TUNGSTENTUNGSTEN

RELAY RATINGRELAY RATING

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

Dimm er

R

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY.

WHEN DRIVING TRANSFORMER COUPLEDLOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/ARATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE Label P/N 6800-258.01

ADDRESS

MANUALON

ACTIVEOUTPUTLEDS

MANUALREMOTE

ON

INPUT120 VAC 60 Hz.

LOAD TYPELOAD TYPE

TUNGSTENTUNGSTEN

RELAY RATINGRELAY RATING

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

Dimm er

R

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY.

WHEN DRIVING TRANSFORMER COUPLEDLOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/ARATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE Label P/N 6800-258.01

ADDRESS

MANUALON

ACTIVEOUTPUTLEDS

MANUALREMOTE

ON

INPUT120 VAC 60 Hz.

LOAD TYPELOAD TYPE

TUNGSTENTUNGSTEN

RELAY RATINGRELAY RATING

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

Dimm er

R

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY.

WHEN DRIVING TRANSFORMER COUPLEDLOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/ARATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE Label P/N 6800-258.01

ADDRESS

MANUALON

ACTIVEOUTPUTLEDS

MANUALREMOTE

ON

INPUT120 VAC 60 Hz.

LOAD TYPELOAD TYPE

TUNGSTENTUNGSTEN

RELAY RATINGRELAY RATING

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

Dimm er

R

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY

CAUTION: RISK OF ELECTICAL SHOCK. HEAT SINKIS LIVE. DISCONNECT AT POWER BEFORE SERVICING.

A SHORTED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE. THIS IS NOT

COVERED BY WARRANTY.

WHEN DRIVING TRANSFORMER COUPLEDLOADS, THE ACTUALLOAD WATTAGE MUST

BE AT LEAST 60% OF THE TRANSFORMERS V/ARATING OR TRANSFORMER HUM, FLASHING

AND/OR DAMAGE MAY OCCUR.

TO AVOID POSSIBLE DAMAGE TO MODULE, AC POWER MUST BE REMOVED BEFORE CONNECTING OR

DISCONNECTING LOADS.

MFG. CODE Label P/N 6800-258.01

ADDRESS

MANUALON

ACTIVEOUTPUTLEDS

MANUALREMOTE

ON

INPUT120 VAC 60 Hz.

LOAD TYPELOAD TYPE

TUNGSTENTUNGSTEN

RELAY RATINGRELAY RATING

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

15 A/120 VAC MAX. PER OUTPUT20 A/120 VAC MAX. PER OUTPUT40 A/120 VAC MAX. PER OUTPUT

USE SLOW BLOW 15 AMP FUSES.

Dimm er

RECEIVE +RECEIVE +11

RECEIVE -RECEIVE -22

TRANSIT +TRANSIT +33

TRANSIT -TRANSIT -44

GND/SHIELDGND/SHIELD55

RECEIVE +RECEIVE +11

RECEIVE -RECEIVE -22

TRANSIT +TRANSIT +33

TRANSIT -TRANSIT -44

GND/SHIELDGND/SHIELD55

DATA INDATA IN

DATA OUTDATA OUT

ACTIVE OUTPUTLEDS

ACTIVE OUTPUTLEDS

MFG. CODEMFG. CODELabel P/N 6800-266.01Label P/N 6800-266.01

LOAD TYPELOAD TYPE

GENERAL PURPOSEGENERAL PURPOSE

ADDRESS ADDRESS SWITCHESSWITCHES

1st 1st DIGITDIGIT

2nd 2nd DIGITDIGIT

1

2

3

4

5

6

7

8

9

1

2

3

4

5

6

7

8

9 COMMONCOMMON

MANUALREMOTE

ON

MANUALREMOTE

ON

CC

RELAY RATINGSRELAY RATINGS

12 A/120 VAC MAX. PER OUTPUT96 A/120 VAC MAX. PER MODULE12 A/120 VAC MAX. PER OUTPUT96 A/120 VAC MAX. PER MODULE

A SHORTENED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE.

THIS IS NOT COVERED BY WARRANTY

A SHORTENED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE.

THIS IS NOT COVERED BY WARRANTY

WARNINGWARNING

LINE 1 AND NEUTRAL 1 MUST BE CONNECTED TO POWER THE MODULE

LINE 1 AND NEUTRAL 1 MUST BE CONNECTED TO POWER THE MODULE

3400 SOUTH WEST TEMPLE SLC, UTAH 84115 (801) 486-8500 FAX 801-486-8569 3400 SOUTH WEST TEMPLE SLC, UTAH 84115 (801) 486-8500 FAX 801-486-8569 TECHNICAL SUPPORT 1-800-527-5527TECHNICAL SUPPORT 1-800-527-5527

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

MANUAL ON

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY.

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY.

USE SLOW BLOW 12 AMP FUSES.USE SLOW BLOW 12 AMP FUSES.

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

MOTORMOTOR1 HP @ 240 VAC PER CHANNEL

1/2 HP @ 120 VAC PER CHANNEL1 HP @ 240 VAC PER CHANNEL

1/2 HP @ 120 VAC PER CHANNEL

POWERPOWER

ADDRESS

OFF/ON

1-23-45-67-8

1-23-45-67-8

OFF/ON

INTERLOCKSWITCHES

NEUTRALNEUTRAL

LOAD NO.LOAD NO.

1

2

3

4

5

6

7

8

Relay

RECEIVE +RECEIVE +11

RECEIVE -RECEIVE -22

TRANSIT +TRANSIT +33

TRANSIT -TRANSIT -44

GND/SHIELDGND/SHIELD55

RECEIVE +RECEIVE +11

RECEIVE -RECEIVE -22

TRANSIT +TRANSIT +33

TRANSIT -TRANSIT -44

GND/SHIELDGND/SHIELD55

DATA INDATA IN

DATA OUTDATA OUT

ACTIVE OUTPUTLEDS

ACTIVE OUTPUTLEDS

MFG. CODEMFG. CODELabel P/N 6800-266.01Label P/N 6800-266.01

LOAD TYPELOAD TYPE

GENERAL PURPOSEGENERAL PURPOSE

ADDRESS ADDRESS SWITCHESSWITCHES

1st 1st DIGITDIGIT

2nd 2nd DIGITDIGIT

1

2

3

4

5

6

7

8

9

1

2

3

4

5

6

7

8

9 COMMONCOMMON

MANUALREMOTE

ON

MANUALREMOTE

ON

CC

RELAY RATINGSRELAY RATINGS

12 A/120 VAC MAX. PER OUTPUT96 A/120 VAC MAX. PER MODULE12 A/120 VAC MAX. PER OUTPUT96 A/120 VAC MAX. PER MODULE

A SHORTENED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE.

THIS IS NOT COVERED BY WARRANTY

A SHORTENED LOAD WILL BLOW FUSE ANDCAN DAMAGE MODULE.

THIS IS NOT COVERED BY WARRANTY

WARNINGWARNING

LINE 1 AND NEUTRAL 1 MUST BE CONNECTED TO POWER THE MODULE

LINE 1 AND NEUTRAL 1 MUST BE CONNECTED TO POWER THE MODULE

3400 SOUTH WEST TEMPLE SLC, UTAH 84115 (801) 486-8500 FAX 801-486-8569 3400 SOUTH WEST TEMPLE SLC, UTAH 84115 (801) 486-8500 FAX 801-486-8569 TECHNICAL SUPPORT 1-800-527-5527TECHNICAL SUPPORT 1-800-527-5527

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

MANUAL ON

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY.

WIRE RANGE 10-16 AWG.TORQUE 7 IN. LBS.

60 c MIN. COPPER WIRE ONLY.

USE SLOW BLOW 12 AMP FUSES.USE SLOW BLOW 12 AMP FUSES.

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

NO. 1NO. 2NO. 3NO. 4NO. 5NO. 6NO. 7NO. 8

MOTORMOTOR1 HP @ 240 VAC PER CHANNEL

1/2 HP @ 120 VAC PER CHANNEL1 HP @ 240 VAC PER CHANNEL

1/2 HP @ 120 VAC PER CHANNEL

POWERPOWER

ADDRESS

OFF/ON

1-23-45-67-8

1-23-45-67-8

OFF/ON

INTERLOCKSWITCHES

NEUTRALNEUTRAL

LOAD NO.LOAD NO.

1

2

3

4

5

6

7

8

Relay

6800-218

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 268-8 668 • FAX (801) 268-9200 • TECH HOT LINE 1-800-527- 5527

WARNINGA SHO RTED LOA D WILL DAMAGE MODULE.

THIS IS NOT CO VERED BY WA RRANTY.

TO A VOID POSSIBLE DAMAGE TO MODULEAC POWER MUST BE REMOVED BEFORE

CONNECTING O R DISCONNECTING LOA DS.

RATINGSPRIMARY: 2 AM PS, 12 0 VA C MA X.

SECONDARY: 15 -20 V DC UNREGULATED

Neutral

120 VA C60 HZ

Neutral

120 VA C60 HZ

WIRE RANGE 10-16 AW G. / TO RQUE 10-12 IN. L BS. / 60 MIN. CO PPER WI RE ONL Y

POWER

DC Pos.

DC Com.

FUSE A GC 5 Amp.

NOT USE D

POWER

DC Pos.

DC Com.

FUSE A GC 5 Amp.

NOT USE D

®

CC

DATE:

Power

6800-218

3550 SO. 700 WEST • SLC., UTAH 84119 • (801) 268-8 668 • FAX (801) 268-9200 • TECH HOT LINE 1-800-527- 5527

WARNINGA SHO RTED LOA D WILL DAMAGE MODULE.

THIS IS NOT CO VERED BY WA RRANTY.

TO A VOID POSSIBLE DAMAGE TO MODULEAC POWER MUST BE REMOVED BEFORE

CONNECTING O R DISCONNECTING LOA DS.

RATINGSPRIMARY: 2 AM PS, 12 0 VA C MA X.

SECONDARY: 15 -20 V DC UNREGULATED

Neutral

120 VA C60 HZ

Neutral

120 VA C60 HZ

WIRE RANGE 10-16 AW G. / TO RQUE 10-12 IN. L BS. / 60 MIN. CO PPER WI RE ONL Y

POWER

DC Pos.

DC Com.

FUSE A GC 5 Amp.

NOT USE D

POWER

DC Pos.

DC Com.

FUSE A GC 5 Amp.

NOT USE D

®

CC

DATE:

Power

TransorbBoard

TransorbBoard

TransorbBoard

TransorbBoard

Fro

m p

ower

sup

ply

to C

CU

and

cont

rol s

tatio

n co

nnec

tor(

s)

TO F

IRST

ENC

LOSU

RE

TRAN

SORB

BO

ARD

Fro

m p

ower

sup

ply

to C

CU

and

cont

rol s

tatio

n co

nnec

tor(

s)

TO C

CU

,-$)./01('2-3)'*/&/3#Red

Black

White (spare)

Green

Bare (shielded)

OUT IN

Transorb Board

Installation! !

Transorb Board

Four-Module Enclosure

CAUTION: Before removing or installing a Transorb board in the Enclosure, disconnect all the power.

To install the Transorb board do the following:1. Remove theTransorb board from the anti-static bag .2. Place the Transorb board in the enclosure.3. Using the screws supplied, screw the Transorb board into the Enclosure with a Phillips head

screwdriver.

Grounding ProcedureTo avoid damage from electrostatic discharge (ESD) when handling boards, use a grounding strap as shown below:

Observe the following precautions to prevent ESD discharge damage:

1. Use an approved ESD wrist grounding strap or an approved wrist or ankle strap. Ensure the grounding strap makes good skin contact.

2. Before installing or removing a Savant Transorb board, connect the clip end of the ground strap to a grounded surface.

If you plan to return a replaced Transorb board to Savant Systems LLC: While wearing the grounded strap, place the board in the anti-static bag that it was originally shipped in or any static shielding bag to avoid ESD damage to the board.

NOTE: The wrist strap only protects the component from ESD voltages on the body; ESD voltages on clothing can still cause damage.

CAUTION: Keep these wires on their respective side of the enclosure. Do not cross over or under the voltage barrier with wires.

Additional Documentation

Additional Documentation is available at: dealers.SavantSystems.comKnowledge Base > Savant Hardware > Lighting Control > Enclosures

SmartLighting Transorb Board(ENC-TRANS)

Quick Reference Guide

009-0815-01ENC-TRANS-00

120612

Copyright © 2012 Savant Systems, LLC. SAVANT and RacePoint Blueprint are trademarks of Savant Systems, LLC.All brand names, product names and trademarks are the property of their respective owners. Savant Systems, LLC reserves the right to change product specifications without notice.