C1RIA Environment WMr Agency CIRIA/ENVIRONMENT AGENCY JOINT GUIDELINES MASONRY BUNDS FOR OIL STORAGE TANKS This document provides guidance for the construction of simple, reinforced masonry bunds for oil storage tanks up to 3.5 metres wide and 1200mm high. It is based upon CIRIA Report 163 "Construction of bunds for oil storage tanks". Where circumstances dictate a larger or more complex construction reference ' should be made to the original report. A similar specification for concrete bunds is also available, free of charge, from the Environment Agency. Contact details will be found at the end of this document. Notes: To be read in conjunction with the enclosed construction drawings. The British Standards referred to in these guidelines are listed in Appendix 1. 1. SITING AND SITE PREPARATION a. Site investigation Avoid sites with:- variations in substrata which may give rise to differential settlement unstable slopes that may cause slip or other movement geological faults, below ground voids or fissures deleterious matter present, which may have an adverse "effect on construction materials a site history which may cause structural problems, e.g. previous mining, made-up ground, underground services, etc. low ground bearing pressure (the model designs are based on a permissible ground bearing pressure of not less than 200kN/m^). Note: the siting of a bund is dictated by the location of the primary tank, which may in turn be dictated by the general layout of the facility of which it is part. It may not be possible, therefore, to avoid sites with the characteristics listed above, in which case suitable precautions must be taken. The model drawings assume that the proposed site does not have any of the undesirable features listed above. Where sites with any of the above undesirable features cannot be avoided, specialist advice should be sought. b. Site preparation i. Remove all vegetation and organic top soil Suitable subsoils or substrata include: firm or stiff clay firm or stiff sandy clay boulder clay shale clay.(non sulphurous) compact sand or sandy gravel chalk rock. ii. Excavate and trim the surface of the excavations to the level surfaces necessary for If a larger or more complex construction is required, please refer to CIRIA Report 163 (see back page for details) fro °F»-the site to oxposo tho subso^i i r uTt ^ ii Li,, i u — u iu ju i . Environment Agency Information Centre Head Office Class No ....................... Accession N o .. / *?.. * A

Upload: others

Post on 06-Nov-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Environment W M r1674/OBJ/20000771.pdfBS sieve size Percentage by mass passing 75mm 100 37.5mm 85 -100 10mm 45 - 100 l 5mm 25 - 85 f 600(jm 8-45 75pm 0-10 Suitable materials include

C 1 R IA E n v iro n m e n t W M r A gen cy

C I R I A / E N V I R O N M E N T AGENCY J O I N T G U I D E L I N E S

M ASO N R Y B U N D S FOR OIL STORAGE

TANKS

This document provides guidance for the construction of simple, reinforced masonry bunds for oil storage tanks up to 3.5 metres wide and 1200mm high. It is based upon CIRIA Report 163 "Construction of

bunds for oil storage tanks". Where circumstances dictate a larger or more complex construction reference ' should be made to the original report. A similar specification for concrete bunds is also available, free of

charge, from the Environment Agency. Contact details will be found at the end of this document.

Notes:To be read in conjunction with the enclosed construction drawings. The British Standards referred to in

these guidelines are listed in Appendix 1.

1. S I T I N G AND S I T E P R E P AR A TI O N

a. S i t e i n v e s t i g a t i o nAvoid sites with:-variations in substrata which may give rise to differential settlement unstable slopes that may cause slip or other movement geological faults, below ground voids or fissuresdeleterious matter present, which may have an adverse "effect on construction materialsa site history which may cause structural problems, e.g. previous mining, made-up ground, underground services, etc.low ground bearing pressure (the model designs are based on a permissible ground bearing pressure of not less than 200kN/m^).

Note: the siting of a bund is dictated by the location of the primary tank, which may in turn be dictated by the general layout of the facility of which it is part. It may not be possible, therefore, to avoid sites with the characteristics listed above, in which case suitable precautions must be taken. The model drawings assume that the proposed site does not have any of the undesirable features listed above. Where sites with any of the above undesirable features cannot be avoided, specialist advice should be sought.

b. S i te p r e p a r a t i o ni. Remove all vegetation and organic top soil

Suitable subsoils or substrata include: firm or stiff clay firm or stiff sandy clay boulder clayshale c la y .(n o n sulphurous) compact sand or sandy gravel chalk rock.

ii. Excavate and trim the surface of the excavations to the level surfaces necessary for

If a larger or more complex construction is required, please refer to CIRIA Report 163 (see backpage for details)

fro °F»-the site to oxposo tho subso ii r u T t ii Li,, i u— u iu j u i .

Environment Agency Information Centre Head OfficeClass No.......................Accession No.. / *?..

*A

Page 2: Environment W M r1674/OBJ/20000771.pdfBS sieve size Percentage by mass passing 75mm 100 37.5mm 85 -100 10mm 45 - 100 l 5mm 25 - 85 f 600(jm 8-45 75pm 0-10 Suitable materials include

the formation of wall foundations and the base slab.iii. Soft ground should be excavated and removed, and the formation levelled down

to firm ground with a permissible ground bearing pressure of not less than 200kN/m^.

iv. Compact the excavated surfaces using a vibrating roller or vibrating plate compactor.

v. Protect the prepared formation from the elements prior to construction of base.

2. HARDCORE AND BLINDING CONCRETE ;Note: Blinding concrete. The British Standard for water retaining structures, BS 8007, requires that at least 75mm of C20 blinding concrete be placed directly over the prepared formation. The structural concrete is then poured onto a polythene slip membrane placed on top of the blinding concrete.

3\In accordance with BS 8007, this specification requires ground level reinforced concrete slabs and wall foundations to be built on blinding concrete rather than hardcore. Blinding concrete is also required for making up discrepancies in level between the formation and the underside of the structure.

jHardcore should only be used for make up beneath the blinding concrete where the method of placing and compaction gives the hardcore sufficient strength to support the structure without any long-term adverse effect.

a. Where hardcore is to be used for making up levels, it should conform with Granular Sub Base Type 2, Table 8/3 of the Department of Transport Specification. The following gradation should be used:

BS sieve size Percentage by mass passing75mm 10037.5mm 85 -10010mm 45 - 100 l5mm 25 - 85 f600(jm 8 - 4 575pm 0 - 1 0

Suitable materials include natural sands, gravels, crushed rock and concrete. The soluble sulphate content should be within the DoT specified limits.

b. The hardcore should be placed in uniform horizontal layers not exceeding 150mm in depth. Each layer must be compacted prior to the placing of the next.

c. The compaction method should be sufficient to achieve the required permissible bearing pressure of not less than 200kN/m^.

d. Suitable compaction plant includes vibrating rollers having a mass per metre equivalent to 1,300kg with a total weight of 1,000kg, and vibrating plate compactors having an equivalent mass of 1,000kg.

e. Granular fill in combination with geotextiles may be used to stabilise soft ground. Construction and design techniques are site-specific and expert advice should be obtained before using geotextiles.

3. R E I N F O R C E D M A S O N R Y WALLS

a. R e i n f o r c e d B l o c k w o r k t o BS 5 6 2 8i. Reinforced blockwork walls may be built off independent reinforced concrete strip

. * * foundations or constructed integrally with the reinforced concrete bund floor.

If a larger or more complex construction is required, please refer to CIRIA Report 163 (see backpage for details)

Page 3: Environment W M r1674/OBJ/20000771.pdfBS sieve size Percentage by mass passing 75mm 100 37.5mm 85 -100 10mm 45 - 100 l 5mm 25 - 85 f 600(jm 8-45 75pm 0-10 Suitable materials include

ii. In either case the 'L'-shaped reinforcement bars, which give the blockwork its tensile strength, must be set in the correct positions before the foundation or slab is cast. Longitudinal lacer reinforcement bars are required to maintain the alignment of the 'L'-shaped bars during concrete casting and, where appropriate, to tie the bottom leg of the bar to the mesh reinforcement of the foundations or slab.

iii. Hollow concrete blocks must comply with BS 6073. Block thickness must be not less than 215mm and net block strength should be not less than lON/mm^.

iv. The mortar mix for bedding and jointing the blocks shall conform to BS 5628 class (i) and comprise the following proportions by volume:1 part of ordinary Portland cement, 1/4 part of hydrated lime, 3 parts sand.

v. The concrete for infilling the block cores shall be GEN 2 or a mix comprising the following proportions measured by weight :1 part OPC, 3 parts sand to BS 882, 2 parts coarse aggregate to BS 882.The maximum size of the coarse aggregate shall be 10mm. The mix should have a high workability with a concrete slump of 150mm to 200mm. A superplasticiser may be used to help provide the necessary workability.

vi. The blocks must be laid and bonded so that the cores align vertically and that the completed work is in horizontal and vertical alignment and to the required dimensions. 'U'-shaped flat metal ties (one per core) may be used to bond the block cavities at straight bonded pier positions.

vii. In order to facilitate proper placing of the infill concrete, the cores of the blocks and the reinforcement must be kept clean of any extraneous or adhered mortar. This can be achieved by placing the joints of the first row of blocks on small concrete block or brick spacers (see drawing no. 16).

viii. The vertical reinforcement should be fixed prior to laying the blocks.ix. Horizontal reinforcement must be placed as the work proceeds.x. On completion of the blockwork, the hollow cores should be cleaned out and,

when the mortar has hardened sufficiently, filled with concrete. When concrete begins to flow out of the bottom of the wall, the voids between the spacer blocks should be shuttered. The infill concrete should be poured and tamped continuously until all core voids are filled. The cores should be slightly overfilled and the surplus concrete should be trowelled over to form a rounded coping along the top of the wall.

xi. External surfaces and joints should be finished or prepared as necessary to be compatible with any subsequent surface coatings.

xii. The wall should not be fully loaded until it has achieved the specified 28-day design strength.

xiii. Wall joints. It is extremely difficult to make watertight movement and construction joints in blockwork walls, joints should therefore be avoided wherever possible, although vertical movement joints are essential to help minimise shrinkage cracking in long walls, joint component and joint sealant manufacturers should be consulted about suitable products and techniques for forming joints. Hydrostatic pressure limitations on wall joints may dictate the maximum wall height and therefore the bund capacity.Where a masonry wall would be so long (e.g. in multi-tank installations) that a vertical contraction joint would be neededit is recommended that either more than one bund is constructed (thus negating the need for joints), or that the bund is constructed from reinforced concrete.

b. R e i n f o r c e d B r i c k w o r k t o BS 5 6 2 8i. Reinforced brickwork, either concrete filled cavity or concrete pocket construction,

may be founded on individual reinforced concrete strip footings or constructed directly off the reinforced concrete bund floor slab.

ii. In either case the specified wall reinforcement bars must be set into the concrete foundations and located at the correct positions to provide the reinforcement for

If a larger or more complex construction is required, please refer to CIRIA Report 163 (see backpage for details)

ij

Page 4: Environment W M r1674/OBJ/20000771.pdfBS sieve size Percentage by mass passing 75mm 100 37.5mm 85 -100 10mm 45 - 100 l 5mm 25 - 85 f 600(jm 8-45 75pm 0-10 Suitable materials include

the walls. Lacer bars are necessary to maintain the position of the reinforcement bars during concrete casting (see Baii). All wall reinforcement (including horizontal distribution bars in cavity fill construction) must be fixed prior to construction of the wall.

iii. Clay, solid class B engineering bricks to BS 3921 Table 1 and Table 6, (Class B) shall be used for reinforced brickwork.

iv. Cavity brickwork should be of bonded stretchers, with the two skins tied together with stainless steel wall ties.

v. 11 Omm thick walls and single skin blockwork shall be in stretcher bond: other walls shall be in English bond. j

vi. The mortar mix must conform to BS 5628 class (i) and comprise the following proportions by volume: |1 part of OPC, 1/4 part of hydrated lime, 3 parts sand.

vii. The concrete for infilling cavity brickwork should be high workability grade RC30.viii. The mix for infilling blockwork cores shall be GEN2 or a mix comprising the

following proportions measured by weight:1 part OPC, 3 parts sand to BS 882, 2 parts coarse aggregate to BS 882.The maximum size of the coarse aggregate shall be 10mm. The mix should have a high workability with a concrete slump of 150mm to 200mm. A superplasticiser may be used to help achieve the necessary workability.

ix. Beds shall be level with joints of uniform thickness and perpends plumb. All beds and joints should be flush and plumb. Ail bricks should be well wetted prior to laying. I

x. Brickwork should be true, square, and properly bonded and each course levelled round in a uniform manner. j

xi. Reinforcement must be fixed in the correct position and all cavities and pockets kept free from all deleterious matter and extraneous mortar prior to concrete infilling. !

xii. Concrete infill should be uniformly placed and properly compacted in a continuous operation taking care not to displace or damage the brickwork during this operation. 1

xiii. Internal surfaces of the walls should be prepared ready to receive any subsequent surface coatings. !

4 . C O A T I N G S A N D S U R F A C E T R E A T M E N T S

Masonry is inherently more permeable than in situ concrete. It is therefore recommended that all internal masonry surfaces are rendered with at least 19 mm of sharp sand/OPC 3:1 mix applied in two coats. Surfaces should be properly prepared and wetted prior to application. Special attention should be given to the junction of the wall and floor slab. A mastic sealant is recommended at the junction. Grooves should be cut in the concrete ready to receive the finished coatings. The second render coat should be applied so that joints in work areas do not coincide with joints in the first coat.

Appendix 1 List of British Standards referred to in this specificationBS 8007:1987 Design of concrete structures for retaining aqueous liquids BS 882: 1992 Specification for aggregates from natural sources for concrete BS 5628: Part 3: 1985 Use of masonry j BS 6073:1981 Precast concrete masonry units BS 3921:1985 Clay bricks !

If a larger or more complex construction is required, please refer to CIRIA Report 163 (see backpage for details)

Page 5: Environment W M r1674/OBJ/20000771.pdfBS sieve size Percentage by mass passing 75mm 100 37.5mm 85 -100 10mm 45 - 100 l 5mm 25 - 85 f 600(jm 8-45 75pm 0-10 Suitable materials include

bird wall

ii?f / / / / / / / / 7 rz\

/Crjannel primary lanK outline

supports as advised by lank supplier

Y2

X2

recommendedclearance750mm

bund wall

.lo r optional sump details refer to drg 1?

<4>-I drg 12

A // V/-77’ // // // // / / ’/ / ’

X I

Brickwork bund up to 3.5m wide where ground not

susceptible to frost heave -

v/ v yy / ; ' / / / / yy y z //" ? ? —/7200

cfiannel primary lank oulline

At

.1

s supports as advised by lank supplier

n

X2

.(o r oplionat sump details refer to

<Drdrg 12 / i

>y yy yy / / yy yy / / yy yy

X1

recommendedclearance750mm

Brickwork bund from 3.5m to 7m wide or where ground

susceptible to frost heave

Calculation ot length / width pf bund

XI (internal length of bund) m X2 (length or diam. of primary tank) • 15 m Y1 (internal length of bund) = Y2 (width or diam. d( primary tank) ♦ 15 m

C alcu lation ol height of bund w a ll

(a) Method 1 * 110% rule (see Section 12 ol report)

height of bund wall ■ (1.1 x primary tank volume / (X1 x YU) * (volume ol lank supports / (X1 x YD)

(b) Method 2 - alternative method (see Section 3.3 ol report)

height of bund wall = (primary tank volume / (X1 x YD) * (volume ol tank supports / (X1 x YD) + freeboard

Freeboard to be allowed (or rainwater, (ire fighting agenls and dynamic elfects as appropriate and as defined in Section 3.3 ol report.

This drawing to be read in coryunction with drawing No's 9 . 11 and specification

Drawng Title

Reinforced brickwork bund: general arrangement.

drg No

8

Page 6: Environment W M r1674/OBJ/20000771.pdfBS sieve size Percentage by mass passing 75mm 100 37.5mm 85 -100 10mm 45 - 100 l 5mm 25 - 85 f 600(jm 8-45 75pm 0-10 Suitable materials include

T10-

34-2

00

EF

•N1-MK-31-200M k-32-200 -

T "10-33-200

slip block

325

/

-— water bar

>-T 1 0 -34 -200

A193-36-B

Section A-A gSS"***10-T 1 0 -4 V 2 0 0

T10-41-200N2-M K-32-200

for optional sump delal refer lo drg 12

h------^ L------------------------------\1

t io-3V34-?oo Elevation 1-1

slip block

T10-43-200'N2 M k-32-200

waler bar

"polythene on blinding concrete 1100

T 1 0-42 -200 ■T1 0-34 -200______^ Section B-B

h— 3 U------------------ h

- It 10-33/34-200 Elevation 2- 2

■*N1 M k-32-200

member bar Mk type /s ize /cs shapecode

length A B c 0

wall/founds 31 T10<900hl&Tl2>900ht 37 H+580 H* 180 425wall/founds 32 T10<900hl&T12>900ht. 37 H+480 H*80 425

wall 33 T10-200 20 distribuf on lo sl f W t r Lwall corner 39 T10-200 3V 1175 600 $00wall corner 40 TIO 81 820 210 60floor /founds 34 T10-200 20 distribuf on lo sl r v w or L Ifloor/founds 35 A393 fabric Top -floor/founds 36 A193 fabric Bottom -floor/founds 41 T10-200 38 1530 750 80 750floor/founds 42 T10-200 41 1165*1 4 5 0 .. j7 5 *l 100floor/founds 43 T10-200 38 W 450 80 450floor/founds 47 R10-2000 83 630 250 80 150 150

This drawing to be read in conjunction with drawing No 8 . 11 and specification

* number Dl bars (N1.N2) * (wall length / 200) ♦ 1 H * height of bund wall t * I hickness of bund watt.W * Y1 - thickness of bund wall - 50mm Y1 * internal width of bund L * X I * thickness of bund wall » 50mm X1 * internal length of bund

Drawing Title

Reinforced brickwork bund: up fo 3.5m wide and 1200mm high.drg No

9

Page 7: Environment W M r1674/OBJ/20000771.pdfBS sieve size Percentage by mass passing 75mm 100 37.5mm 85 -100 10mm 45 - 100 l 5mm 25 - 85 f 600(jm 8-45 75pm 0-10 Suitable materials include

.100 ,125,100 !• -r -r -

water __________ m i y s i

concrete finish

_19mm 2 coat render "finish with waterproof

additive

engineering brickwork 'w ith concrete fill

concrete lilting file t Ih render finish

mastic sealantfabric reinforcement

19mm 2 coat render finish wilh waterproof additive — -stainless sleel

wall ties

polythene on 75mm Winding concrete

fabric reinforcement

concrete till to cavity void

Corner plan

engineeringbrickwork

Corner reinforcement detailDetails tor brickwork bund walls, (walls built off slab refer lo drq 9)

CONSTRUCTION NOTES:

• it is important to ensure that the reinforcement is correctly positioned, the cavity is clear and all surfaces are property prepared prior to filling the cavity with concrete. Special care is needed where water barsare provided

• it is recommended that the brickwork incorporates sufflcent openings, particularly at foundation level, to facilitate.cleaning of the cavity and to allow for preparation of the concrete surface prior to cavity filling during placing of the cavity fill the access holes should be shuttered once it has been observed that the concrete is property filling the cavity voids and that the reinforcement has not been displaced

• the concrete must be properly compacted to achieve the required strength and impermeability. Care must be taken to avoid damaging the brickwork and temporary supports may be necessaryduring casting

• the shuttering, and any temporary supports to the brickwork, must not be moved until at least 12 hours after casting.

This drawing lo be read in conjunction with drawing No 8 . 9 and speciation

Or awing Title

Reinforced brickwork bund construction details

erg no „ 11

Page 8: Environment W M r1674/OBJ/20000771.pdfBS sieve size Percentage by mass passing 75mm 100 37.5mm 85 -100 10mm 45 - 100 l 5mm 25 - 85 f 600(jm 8-45 75pm 0-10 Suitable materials include

bund wall

primary lank outline

> - SLpporls as advised by v tank supplier

rz

X2

for optional sump details reler to drg 17

recommendedclearance750mm

bund wall

'/ / /A / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /7 F Z l 77, Vx r-Jm V7 ^

harm el primary tank outline

±V/

y~ supports as advised b y ---- - \ 'tank sipplier v

n

X2

____ (or optional sump'* J>C details refer to ^ ----------- d r f l 7 “ -----------

recommendedclearance750mm

X1 X1

Reinforced biockwork bund up lo 3.5m wide where

ground not susceptible to frost heave

Reinforced blockwork bund from 3.5m to 7m wide or where

ground susceptible to frost heave

Calculation of lenoth / width ol bund

X1 (internal length of bund) - X2 (length or diam. of primary tank) •» 1.5 m Y1 (internal length of bund) = Y2 (width or diam. of primary tank) ♦ 1.5 m

Calculation of height of bund wall

(a) Method 1 -110% rute (see Section 3.2 ot report)

height of bund wall = [1.1 x primary tank volume / <X1 x YD) « [volume of tank supports / (X1 x YD]

(b) Method 2 - alternative method (see Section 3.3 of report)

height of bund wall = [primary tank volume / (X1 x Y1)l ♦ (volume of tank supports / (X1 x YD] ♦ freeboard

Freeboard lo be allowed for rainwater, fire fighting agents and dynamic effects as appropriate and as delined in Section 3.3 of report.

this drawing lo be read in conjunction wilh drawing No % , 16, 17 and specification

Drawing Title

Reinforced blockwork bund: general arrangement.

drg No

13

Page 9: Environment W M r1674/OBJ/20000771.pdfBS sieve size Percentage by mass passing 75mm 100 37.5mm 85 -100 10mm 45 - 100 l 5mm 25 - 85 f 600(jm 8-45 75pm 0-10 Suitable materials include

T10-

34-2

00

EF

* N1-Mk-31-cs lo suit hollows in blocks

M k-32-cs to suit hollows in blocks

T1 0 -3 3 -2 S

water bar-

1

215

J 10-9^-200

A193-36-B

Section A-A * 5 5 ? on “MnsVl-i

> 1 0 -4 1 -2 0 0

215

for optional delays refer lo drg 17

T10-41-200• N 2-M k-32-cs lo suil hollows in blocks

Mk-31-cs to .suit hollows in blocks T 10-33-215

H-------3 L----------------------------------\I

’ — tw-^-7k / Elevation 1~1

N2 M K-32-200 T10-A 3-200"polythene on blinding

concrete 110q

T10-42-200 T10-34-200

, Section B-B

T10-94-200

h— h----------------------------------\

i

t 10-33-215/ Elevation 2~2

N1 M k-32-200

T 10-34-200

member bar Mk type/size/cs snspecode

length A B c D

wall/founds 31 1 10<900m&T 12>900hl 37 H-580 H’ 180 425wall/founds 32 T10<900ht&T12>900hl. 37 H’ 480 H*80 425

wall 59 T10-215 20 distribul on to st t W cr Lwall corner 39 T10-215 97 1175 600 600floor/fouids 34 T10-215 20 distribut on to sii t W*t or L tfloor/founds 9S A393 fabric Tod -floor/founds f t A193 fabric Bottom *floor/foinds 41 T10-200 38 1530 750 M 759floor/foi/ids 42 T10-200 41 1165*1 450 140 575*t 100floor/fo irds 43 . T.10-200 38 990 450 BO 450floor/fom ds 47 R10-2000 83 690 250 80 150 150

This drawing lo be read in conjunction with drawing No 1 3 . 16 . 17 and specification

* number of bars (N1.N2) - (wall length / 200) ♦ 1 H * height ol bund wall i = thickness of bund wall.W » Y1 ♦ thickness of bund wall ♦ 50mm Y1 * internal width of bund L * X1 •* thickness ol bund wall ♦ 50mm X1 * internal length ol bund

Drawing Title

Reinforced blockwork bund: up lo 3.5m wide and 1200mm high.drg No

14

Page 10: Environment W M r1674/OBJ/20000771.pdfBS sieve size Percentage by mass passing 75mm 100 37.5mm 85 -100 10mm 45 - 100 l 5mm 25 - 85 f 600(jm 8-45 75pm 0-10 Suitable materials include

concrete finish

19mm 2 coal render finish with waterproof additive

hollow concrete block with concrete (ilt

water Bar

polylhene on 75mm blinding concrete

fabric reinforcement

concrete tilting fillet im render finish

fabric reinforcement

Blockwork bund wall built off strip foundation

polylhene on 75mm blinding concrete

Blockwork bund wall built off slab,

T10- 39-215

Corner reinforcement detail

CONSTRUCTION NOTES:In a reinforced blockwork wall it is important to ensure that the reinforcement is correctlypositioned and all voids in the blocks are filled with concrete.To achieve this the following procedure is recommended :

• position starter bars in foundation to line up with block cavities. It is important that reinforcement bars are positioned precisely as shown on the drawings.

• pour foundation concrete and allow to cure• start construction of wall by positioning concrete (or other suitable material) slip blocks, so

that the centre-line of each slip block coincides with the vertical joints in the blockwork. The slip block spacers form part of the wall and should be mortaredin position

• place first course of blocks over bars and bed in mortar. Proceed similarly for next three courses, positioning the vertical and horizontal reinforcement as detailed.

• before mortar has fully hardened, clean out hollows in blocks, removing all projecting nibs of mortar etc. This can be achieved using a length of reinforcing bar.

• clear away debris at base of wall, by way of the gaps created by the slip blocks• position remaining reinforcement, and fill hollows with high-workability concrete mix ( see

specification). When concrete appears at bottom of wail indicating that it is flowing properly in the hollows, position and secure formwork stop-ends to retain concrete.

• continue pouring concrete until ail hollows/voids are filled, using a reinforcing bar or timber batten to compact it and to ensure there are no air pockets

• allow at less 12 hours before removing formwork

Tfts drawing la be read in conjunction with drawing No 13 . K . 17 arid speciation

Drawing Title

Reinforced blockwork bund: construction details

drg No

■16

Page 11: Environment W M r1674/OBJ/20000771.pdfBS sieve size Percentage by mass passing 75mm 100 37.5mm 85 -100 10mm 45 - 100 l 5mm 25 - 85 f 600(jm 8-45 75pm 0-10 Suitable materials include

8

A142-37-T

A193-39-B

A393-35-T

-3 5 /3 6 -B 2NO-T10-48-EF

2NO-T10-3

S

kT 10-34-200

T1 0-49 -200 2NO-T10-50

2 N 0-T10-51 lolylhene on blinding

concrete

SNo-T10-48 polythene on blinding concrete f*

Section A -A sump detail for bund construction to dro 15

T10-34-200

/ / 7r —'

■3No-T10-50 ■3Na-T10-51

Section A-A sump detail for bund construction to drq %

lolylhene on blinding^ T1 0 -4 9 /5 2 -2 0 0 concrete

1000

Typical Section B-B

member barMk

type/s ize /cs shapecode

length A B C D E

Section A-A sump detail tor bund construction to drg 15wall/founds 61 T10<900&T12)900 37 H*800 H*40C 425

wall 33 T10-200 29 dstriixj ton lo s u it ' /foundations 34 T10-200 20 dstribu' ion lo suit \ Mfoundations 48 T10-200 20 distribu ion lo suit ' 5-eOmi ifoundations 49 110-200 41 1W5 ISO 425 456foundations 50 T10- 200 53 YS*13?<? 450 200 rs-120 200 450foundations 51 T10-200 53 *5*1529 ^50 200 r5*32C 200 450foundations 37 A142 labric 1*B -

foundations 38 A193 fabric T*B -

Section A-A sumo detail for bund construction to dra 14wall/founds 62 T10<900ST12>900 37 H*800 H*A0C 425

wall 33 T10-200 20 distribu ion to suit V/foundations 34 T10- 200 20 distribu ion to suit \ Mfoundations 48 T10-200 20 distribu ion to suit ' 5-80mifoundations 50 T 10-200 53 r5*13?0 450 200 Y5‘ 120 200 450foundations 51 T 10-200 53 rs -i5? o 450 200 Y5‘ 320 200 450foundations 52 T 10-200 41 1725 850 425 450foundations 35 A393 fabric T*B -

foundations 36 A193 fabric T*B -

<S>-

300

1S)

s i>

Plan ot Sump

H ■ height of bund wall W • Y1 ■* thickness ol bund wail L ■ X1 4 thickness ol bund wall

t • thickness ol bund wall.♦ 50mm Y1 * internal width of bund

50mm X1 - internal length of Dund

Drawing Title

Reinforcement details for optional sump in bund with blDCkwork wallsdrg No

17

Page 12: Environment W M r1674/OBJ/20000771.pdfBS sieve size Percentage by mass passing 75mm 100 37.5mm 85 -100 10mm 45 - 100 l 5mm 25 - 85 f 600(jm 8-45 75pm 0-10 Suitable materials include

© For almost 40 years CIRIA - the Construction Industry Research and Information Association - has managed collaborative research and produced information aimed at providing best practice solutions to industry problems. CIRIA stimulates the exchange of experience across the industry and its clients, and has an established reputation for practical, high quality information. Through networking and the dissemination of publications and newsletters, CIRIA seeks to improve the performance of all concerned with construction and the environment.

For further information please contact CIRIA by:Post: 6, Storey's Cate, Westminster, London SW1P 3AUTel: 01 71 222 8891 (General Enquiries) 01 71 799 3243 (Publications)Fax: 0171 222 1708 e-mail: ciria.org.uk

Further details are available on CIRIA's Web site: www.ciria.org.uk/ciria/

CIRIA Report.163 "Construction of bunds for oil storage tanks"ISBN 0 8601 7 468 9 Available from CIRIA, price £18

E N V I R O N M E N T AGENCY HEAD OFFICERio House, Waterside Drive, Aztec West, Almondsbury, Bristol BS12 4UD Tel: 01454 624 400 Fax: 01454 624 409

E N V I R O N M E N T AGENCY REGIONAL OFFICESAN G LIAN

National Information CentreThe Environment AgencyRio HouseWaterside DriveAztec WestBRISTOLBS1 2 4UD

Due fo r return

ise

PE2 5ZR 171 811 !31 840

: South

14 0191 |6 1889

ontact igency 5 111.

N O RTHW EST Richard Fairclough House Knutsford Road Warrington WA4 1HG Tel: 01925 653 999 Fax: 01925 415961

M IDLANDS Sapphire East 550 Streetsbrook Road Solihull B91 1QT Tel: 0121 711 2324 Fax: 0121 711 5824

SOUTHERN Cuildbourne House Chatsworth Road WorthingWest Sussex BN11 1LD Tel: 01903 832 000 Fax: 01903 821 832

SOUTHW EST Manley House Kestrel Way Exeter EX2 7LQ Tel: 01392 444 000 Fax: 01392444 238

THAMESKings Meadow House Kings Meadow Road Reading RG1 8DQ Tel: 0118 953 5000 Fax: 0118 950 0388

W ELSHRivers House/Plas-yr-Afon St Mellons Business Park St Mellons Cardiff CF3 0LT Tel: 01222 770 088 Fax: 01222 798 555

The 24-hour emergency hotline number for reporting all environmental incidents relating to air, land and water.

E N V I R O N M E N T A G E N C Y E M E R G E N C Y H O T L I N E

0800 80 70 60