Voting for Enhanced Security – How Far is Far Enough
Roy Moxley, Siemens
![Page 2: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/2.jpg)
• About 1500 False trips
in 16 months (NERC)
• 16 Times more False
Trips than Failure to
Trip
• 41% of False trips are
during an external fault
Unpleasant Facts
![Page 3: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/3.jpg)
From NERC Report, Jan 2011 – April 2012
![Page 4: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/4.jpg)
From NERC Report, Jan 2011 – April 2012
![Page 5: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/5.jpg)
Restricted © Siemens AG 2013 All rights reserved.
Cost of Relays has come down an inflation adjusted 90% since 1980
Pleasant Fact
![Page 6: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/6.jpg)
Why Do We Apply Redundant Protection ?
It Costs More
Extra Engineering
Extra Maintenance
Extra Wiring
![Page 7: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/7.jpg)
Hole Filling
![Page 8: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/8.jpg)
So what Constitutes a Hole ?
Arc Resistance Coverage
Communication Failure Coverage
Power Swing Response
Fuse Failure (loss of potential) Response
It’s only a holeIf you hit it.
![Page 9: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/9.jpg)
Maintenance Backup
![Page 10: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/10.jpg)
Relay Failure Backup
![Page 11: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/11.jpg)
OR
A+B A+C B+C
Two of Three Logic Improves Dependability and Security
Let’s Define (A,C,B):1% chance of False Trip95% chance of Correct Trip
A+B = 1%2 = .01% Chance of False Trip(A+B)*(A+C)*(B+C)= 0.03% Chance of False Trip
A+B = 95%2 = 90.25% Chance of Correct Trip(A+B)*(A+C)*(B+C)= 99.9% Chance of Correct Trip
OR
AND AND AND
![Page 12: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/12.jpg)
Page 12
Implementing 2 of 3 is Not difficult
A
C
B C
B A
Details: On Loss of Relay, Revert to 1/2 or 2/2? Use Contacts or Logical Derivation? Use Same or Different Relays?
![Page 13: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/13.jpg)
What Does It Mean to be Different ?
Voting Must be Different to Count
![Page 14: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/14.jpg)
Human Error and Training Considerations
• Settings and Calculations
• Different Schemes
• Operations
• Maintenance
• Relay Out-of-Service
![Page 15: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/15.jpg)
Testing Changes
• Test of Relay Modifies
Scheme Logic
• Voting Logic is Part of
System Test
![Page 16: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/16.jpg)
Questions to Ask
How Many False Trips per Year are Acceptable?
What is the System Cost of a False Trip Coupled with a Correct Trip? Is This Condition Modeled
![Page 17: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/17.jpg)
Conclusions
• Two of Three Voting can Reduce False Trips Significantly
• Costs of Voting Schemes are 15% of Dual Schemes 35 Years Ago
![Page 18: Enhanced Power System Protection](https://reader030.vdocuments.us/reader030/viewer/2022013108/5695d2801a28ab9b029ab015/html5/thumbnails/18.jpg)
“Sometimes the questions are complicated and the
answers are simple”
Dr. Suess