Engineering Manual
AIR PURIFICATION UNIT - APU
File #MH26289
23 Vreeland Road, Florham Park, New Jersey 07932 Phones (973) 966-6000, (800) 444-9696
Fax (973) 966-0315 Website: www.carrollmi.comEmail: [email protected]
H E L P I N G T O K E E P O U R E N V I R O N M E N T C L E A N E R
CARROLL MANUFACTURING INTERNATIONAL ®
Grease, Smoke, and Odor Abatement
for Commercia l K i tchen Appl icat ions
Sales and Engineering 25 Johnson Street, Thornhill, Ontario L3T 2N8 Phone (905) 731-1050 Fax (905) 731-8547
The quality of the air we breath isincreasingly becoming a world wideconcern. In the United States all levels
of government are involved in the regulationof air quality. On the federal level, the CleanAir Act (CAA) and its amendments wereenacted by Congress to oversee and regu-late the impact of air pollution caused byindustries within the United States. TheEnvironmental Protection Agency (EPA) wascreated as the primary support and imple-mentation body for the CAA. The actualenforcement of the CAA is delegated to localgovernment regulatory agencies called AirQuality Management Districts (AQMD’s). Insome areas, such as Southern California, theAQMD, South Coast Air Quality Manage-ment District (SCAQMD), has found it neces-sary to evaluate and regulate sources of pol-lutants not previously recognized. In thepast, the need for pollution control equip-ment in commercial kitchen exhaust sys-tems has been required only in particular sit-uations, such as an existing high rise build-ing, where it was impractical to run new ductwork to the roof. Increasingly, environmen-tal control agencies are making moredemands for the elimination or reduction ofpollutants from commercial kitchen exhaustsystems. In fact current legislation wasadopted by SCAQMD in November 1997requiring pollution control devices overchain driven and under-fired char-broilers. Itis probable that such legislation will beapplied to other regions in the U.S., in thenear future.
The Carroll pollution control unit, trade-marked EnvironAir® Air Purification Unit(APU), utilizes a three-stage filter system toeliminate particulate grease and smoke fromthe exhaust air stream. Optionally available
is an odor removal module that, through theuse of odor media trays or a liquid odorspray cabinet, effectively controls the mal-odors produced by commercial kitchencooking. Carroll has a longer history indesigning and engineering these type unitsthan any other manufacturer, having firstdeveloped pollution control units in the mid-1970’s. Carroll has steadily improved andrefined the EnvironAir® APU over the past 25years. Today, the EnvironAir® APU offers thefoodservice operator the most efficient andeconomical pollution control equipment onthe market. Additionally, the EnvironAir®
APU system has been engineered to operatewith all Carroll series ventilators in order toprovide the optimum in filter life. The Envi-ronAir® APU is available in models to coverany CFM range between 500 and 40,000. AllEnvironAir® APU models are UL and ULCListed and meet all requirements of NFPA96, the local authority having jurisdictionand national building codes.
From throbbing city hearts such as Boston,Las Vegas, New York, Philadelphia, Torontoand Vancouver; to far-away trading centerslike Dubai and Sharm El Sheik; from bustlingcorporate centers to the tranquility of Mid-west schools, Floridian oases and suburbancountry clubs; Carroll’s EnvironAir® APU’shave been instrumental in resolving thechallenges of commercial air pollution.Ruggedly constructed, yet uncomplicatedindesign, the EnvironAir® APU is truly a silentsentry indispensible to ever so many com-mercial cooking operations.
APU FOR POLLUTION CONTROLFROM COMMERCIAL KITCHEN EXHAUST
- TABLE OF CONTENTS -
Page
Product Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
Product Description Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-8
Engineering Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-22
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23-26
Engineering Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27-28
Through our on-going program of product development, Carroll Manufacturing International® reservesthe right to alter the goods and the specification of the goods represented within this Manual
Air Purification Unit
GENERAL DESCRIPTION: Provide a Carroll Mfg. Int’l.EnvironAir® Air Pollution Control Unit (APU), Model # � APU (with fire damper)-, or � NAPU (without firedamper) -_______– _____–______ –_______–_______–______,assembled, wired, and fully factory-tested prior to ship-ment. Unit shall be complete, including a Filter Section, AirMonitor Cabinet, Status Panel, and all other options andcomponents as specified below and as shown on thedrawings. The APU shall have a capacity of___________________CFM (______________ Liters/Sec.).
The complete APU assembly provided shall be UL andULC listed, and the construction shall meet the require-ments of national building codes, the local authority hav-ing jurisdiction, and the 1998 edition of NFPA 96.
The APU shall be used in conjunction with a listed water-wash or dry grease extracting exhaust ventilator(hood) having a minimum grease extraction rate of 90% by weight.
FILTER SECTION: The filter section housing shall be of dou-ble-wall construction with welded channel bracing formaximum rigidity and strength, and include a minimumof 1 1/2” (38mm) rigid UL/ULC listed fire-rated thermalinsulation sandwiched between the walls. The inner housing wall shall be of 16-gauge steel, with all seamsfully-welded liquid-tight. The outer housing wall shall beof 20-gauge steel, primed and painted after fabrication.The housing is to include a supporting base comprised offull-length 3” (76mm) minimum structural longitudinaland cross-bracing channel members. Refer to projectdrawings for actual channel member sizing. The base shall be configured so the Filter Section can optionally be suspended from above. The Filter Section shall further comprise:
A. For particulate grease and smoke abatement, a three-stage filtration system, with a nominal 500 FPM filterface velocity, and comprising:1. A first stage having an array of 4” (102mm) deep
pleated UL/ULC Class II pre-filters, rated at 40% dustspot efficiency (ASHRAE Standard 52.1-92);
2. A second stage having an array of 22” (559mm) deep UL/ULC Class I bag-type filters, rated at 95% (ASHRAE Standard 52.1-92); and
3. A third stage having an array of 12” (305mm) deep UL/ULC Class I fire-rated absolute box filters, rated at 99+% dust spot efficiency (ASHRAE Standard 52.1-92), 95% efficiency on 0.3 micron size (DOP smoke test).
B. Fully removable hinged access door, with toggle-typelatches and two access panels , for complete access tothe interior components. Doors and panels shall bedouble-wall construction with the outer wall of 18gauge steel and the inner wall of 16 gauge steel and fur-ther include UL/ULC fire rated gaskets to form a grease-tight seal when closed.
ITEM NO.
Grease, Smoke, and Odor Abatement for Commercial Kitchen Applications
C. A UL/ULC listed fire damper (APU model only) at thedischarge end. The damper shall be actuated by a212°F (100°C) fusible link.
D. A firestat, located at the inlet end, set at 200°F (93°C) to shut off the exhaust fan and transmit a firealarm signal.
E. An air pressure-drop monitoring system, measuringthe air pressure drop across each filter stage, and alsomonitoring a filter out condition, a low air condition,and a nil air condition. Inter-piped corresponding pres-surestats, for sending signals to the remotely-locatedStatus Panel, shall be housed within a water-tight, unit-mounted, Air Monitor Cabinet at the inlet end ofthe Filter Section. This cabinet is also to house the firestat control.
ODOR CONTROL: If odor abatement is to be included, theFilter Section housing shall be extended for the incorpora-tion of odor control means immediately following the thirdfilter stage. This means shall include either:
� Odor Neutralization. Provide a unit-mounted OdorSpray Cabinet housing one or two 5 gallon (19 Liter)reservoirs of Carroll’s liquid EnvironSafe™ Odor Elim-inator, a liquid spray compressor, one or more spraynozzles, and fuse-protected circuitry with spray anddelay period adjustable timers, all inter-connected toimplement a neutralizer-rich environment between thethird stage filter and the fire damper, to break downorganic odor molecules.� Equip the Odor Spray Cabinet with the “HS” heater
option for use in environments that fall below 32°F (0°C).
or� Odor Oxidation. Provide a �single-pass, or a �double
pass, V-bank array of 2” (51mm) deep 22-gauge perfo-rated steel trays containing Activated Alumina Spheresimpregnated with Potassium Permanganate for oxidiz-ing the odor molecules in the passing airstream.
or� Odor Absorption/Adsorption: Provide a � single-pass,
or a �double pass, V-bank array of 2” (51mm) deep 22-gauge perforated steel trays containing Activated Car-bon for absorption/adsorption of the odor moleculesin the passing airstream.
or� 50/50 Blend of Potassium Permanganate and Activated
Carbon: Provide a �single-pass, or a �double pass, V-bank array of 2” (51mm) deep 22-gauge perforatedsteel trays containing a 50/50 blend of Activated Alu-mina Spheres impregnated with Potassium Perman-ganate for oxidizing the odor molecules, and ActivatedCarbon for absorption/adsorption of the odor mole-cules in the passing airstream.
The trays are to include removable front panels to facili-tate the changing of the media spheres.
PRODUCT SPECIFICATIONS
1
BLOWER SECTION:� Blower Section to be included.
Blower to have a capacity of__________________CFMat__________inches w.g. external static pressure.
This section to include a complete backwardly-inclined fanwheel and scroll assembly, of Class I, II, or III constructionas is appropriate for the application, operably connected toa TEFC motor by a V-belt drive, and a UL/ULC listed com-bination Magnetic Motor Starter and Disconnect Panel,surface mounted on the section housing, and interwiredand factory-tested prior to shipment. The Starter and Dis-connect Panel shall be � TYPE 1 for indoor installation, �TYPE 3R for outdoor installation. The fan and drive assem-bly shall be mounted on rubber-in-shear or spring typevibration isolators, as is appropriate for the particularapplication. Fan motor to be _____________HP(___________KW), ____________Volts, ___________Phase,____________Hz.
The centrifugal blower scroll and inlet venturis shall beconstructed of heavy gauge steel, with all seams continu-ously welded. The blower shall be � DWDI or � SWSI(depending on the application), and the fan wheel shallinclude backwardly inclined, non-overloading type blades,of the flat or airfoil type. The blower shall be licensed tobear the AMCA Certification Seal, and be UL/ULC listed.The fan shaft be AISI C-1040 or C-1045 hot rolled steel, andaccurately turned and polished. Fan bearings shall be ofthe grease lubricating, anti-friction ball pillow block type,with Zerk fittings for periodic lubricating. The V-belt driveand motor shall be on a common chassis base with theblower, shall include oil resistant, non-static belts, andhave capacity of at least 25% more than the motor brake horsepower.
� This Section is mated to the Filter Section, forming asingle integral packaged unit. See project drawings forsection and air discharge arrangements.
� This Section is to be remoted from the Filter Section.See project drawings for section and air dischargearrangements.
� Magnetic Motor Starter to include a Hand/Off/Auto-matic (H.O.A.) switch in its face.
The top and bottom outer housing walls shall be of 20-gauge steel. The top and bottom inner housing walls shallbe of 18-gauge sheet steel, with a minimum of 1 1/2”(51mm) rigid UL/ULC listed fire-rated thermal insulationsandwiched between the walls. The vertical outer housingwalls shall be 16-gauge steel. �Optionally, the inner verti-cal housing walls shall be 16-gauge expanded metal steel,with a minimum of 2” acoustical insulation sandwichedbetween the walls. The entire section to be primed andpainted after fabrication. The section housing to include abase similar to that provided with the Filter Section, alsoconfigured so the section can be optionally suspendedfrom above.
STATUS PANEL: Provide a Status Panel, for remotely locat-ing, with a housing constructed of 18-gauge stainless steel,with a number 4 finish, and with a fully hinged water-tightgasketed access door with security fasteners. The Cabinetis to include a fuse-protected circuity including a step-down transformer with a 24-volt secondary winding, unitproving out timer, relays, and status pilot light indicators inthe face of the panel to continually monitor the status ofthe APU. Individual indicators shall be designated “FanON/OFF” (ACD) or “Fan ON” (ACW),” “Normal,” “Nil Air,”“Low Air,” “Filter Out,” “Fire,” “Reset,” “Replace Pre-Fil-ter,” “Replace Bag-Filter,” “Replace Box-Filter,” and “Con-trol Bypass.”
“Nil Air” and “Filter Out” conditions are to de-energize theexhaust fan. Provide a Control Bypass Switch in the cir-cuitry to over-ride these conditions for a single cycle, tem-porary period only.
� Status Panel to be additionally provided with “ReplacePre-Filters,” “Replace Bag Filters,” and “Replace BoxFilters” relays, for sending status signals to buildingmonitoring station.
� Status Panel to be a Model ACD, including a FanON/OFF pilot switch in the panel face.
� Status Panel to be a Model ACW including a Fan ONpilot light in the panel face, and used when a FanON/OFF pilot switch is provided as part of another system.
� In conjunction with the use of the Odor Spray Cabinet,provide the optional “Low Odor Spray” status pilotlight, the “Low Odor Buzzer,” and the “Silence Buzzer”push button in the face of the Cabinet.
� In conjunction with the use of the Odor Spray Cabinet,additionally provide a “Low Odor Spray” relay forsending a low odor spray status signal to building monitoring system.
FIRE PROTECTION SYSTEM: The EnvironAir® APU is agrease interceptor. Therefore, NFPA Bulletin 96, NationalUniform Codes, and most local statutes and ordinancesrequire the unit to be protected by an approved automaticFire Suppression System, installed in accordance with themanufacturer’s installation instructions. The system can befully site-installed, internally factory pre-piped only withnozzle piping and detection line runs, or completely facto-ry provided with system tank and control assembliesenclosed within a side-wall mounted cabinet. For outdoorinstallations where temperatures can drop below waterfreezing temperatures, the side-wall mounted cabinet shallinclude an electrical heater.
Air Purification UnitGrease, Smoke, and Odor Abatement for Commercial Kitchen Applications
PRODUCT SPECIFICATIONS
2
PRODUCT DESCRIPTION CODES Air Purification Unit
PRODUCT DESCRIPTION CODESCarroll EnvironAir® APU’s are identified by a series of letters and numbers which designates features.
SERIAL DESIGNATION: 1.________ 2.________ 3.________ 4.________ 5.________ 6.________
Explanation of Codes:
1. Filter Section
APU..................The Basic Filter section which includes: Pre-Filter, Bag Filter, Box Filter, Fire Stat, Air MonitorCabinet, Status Panel, and Filter Enclosure Cabinet/Housing with Fire Damper.
NAPU............... Includes all of the components of the APU model but the Fire Damper is omitted.2. Unit Size
APU Model CFM Range APU Model CFM Range APU Model CFM RangeNumber Number Number
01 500-1100 08 6100-8000 18 16100-1800002 1100-2000 09 8100-9000 20 18100-2000003 2100-3000 10 9100-10000 24 20100-2400004 3100-4000 12 10100-12000 28 24100-2800005 4100-5000 14 12100-14000 32 28100-3200006 5100-6000 15 14100-15000 36 32100-36000
16 15100-16000 40 36100-40000
3. Odor Abatement Option
OS ....................Odor spray with indoor style cabinet.HS ....................Heated/Insulated odor spray outdoor style cabinet.OT ....................Odor media trays filled with alumina spheres impregnated with potassium permanganate or
activated carbon.
4. Exhaust Fan Section
The “Standard” Fan Section includes a non-insulated (“FIN”) Indoor Fan Enclosure Cabinet, and Exhaust Fan(consists of blower & motor), and a Combination Magnetic Motor Starter housed in a TYPE 1 General PurposeIndoor Cabinet.
FIN ....................“Standard” Indoor Fan Section w/ No Sound Insulation Package and a Combination Magnet-ic Motor Starter housed in a TYPE 1 General Purpose Indoor Cabinet.
FIS ....................Optional Indoor Fan Section w/ Sound Insulation Package and a Combination MagneticMotor Starter housed in a TYPE 1 General Purpose Indoor Cabinet.
FON ..................Optional Outdoor Fan Section w/ No Sound Insulation Package and a Combination MagneticMotor Starter housed in a TYPE 3R Raintight Outdoor Cabinet.
FOS ..................Optional Outdoor Fan Section w/ Sound Insulation Package and a Combination MagneticMotor Starter housed in a TYPE 3R Raintight Outdoor Cabinet.
5. APU Status Panel
ACW ................Is used in conjunction with a separately controlling fan circuit, and consists of the following:S/S Cabinet, “Fan On” Light, “Low Air” Light, “Filter Out” Light, “Fire” Light, “Normal”Light, “Nil-Air” Light, “Reset” Momentary Push Button, “Control Bypass” Light, “ReplacePre-Filter” Light, “Replace Box-Filter” Light, “Replace Bag-Filter” Light, Relays, Timers, Con-trol Transformer, and Terminal Blocks.
ACD ..................Is used as a stand alone on/off fan control panel. This unit consists of the same parts as theACW except the “Fan On” light is replaced with a “Fan On/Off” illuminated maintained PushButton switch
6. Hand-Off-Auto
“H.O.A.” ..........The H.O.A. is a manual selector control, built into the Magnetic Motor Starter Panel to turnthe exhaust fan on or off, by-passing the APU monitoring controls.
EXAMPLE: A (APU–10–OS–FIS–ACW-HOA) is a Carroll EnvironAir® APU sized for 10,000 CFM nominal, with an indoorstyle liquid odor spray section, a sound insulated indoor fan package, and a control panel for use with a separately con-trolling fan circuit, and a hand-off-auto option.
3
The EnvironAir® APU is available in a variety of configu-rations to meet the foodservice operators requirementsfor the elimination of particulate grease, smoke, and/or
odor from the kitchen exhaust air stream. Integrated or standalone modules are available for the blower/fan, filter, andodor control functions of the system. Installation can be in aceiling space above the kitchen ventilator, or in a remote loca-tion such as a utility room, or on the roof top. The EnvironAir®
APU provides the foodservice operator an economical solu-tion to problems which in the past would have prevented theinstallation of a commercial kitchen operation. EnvironAir®
solves the problems associated with the following installa-tion problems:
� NEW HIGH-RISE BUILDINGSEnvironAir® provides the economical solution to the cost ofrunning expensive 16 gauge all welded ductwork to the roofof new high rise buildings. The cleaned kitchen exhaust airfrom the EnvironAir® unit can be exhausted out the side ofthe building at a minimum 10’ (3 meters) above ground levelor into another area of the building such as an undergroundparking garage. In the United States all ductwork is requiredto be 16 gauge all welded steel.
� EXISTING HIGH-RISE BUILDINGSEnvironAir® is the solution to running kitchen exhaust ductwork in existing buildings where it is impossible or cost pro-hibitive to run all welded ductwork to the roof. The cleanedkitchen exhaust air from the EnvironAir® unit can be exhaust-ed out the side of the building at a minimum 10’ (3 meters)above ground level or into another area of the building suchas an underground parking garage. In the United States allductwork is required to be 16 gauge all welded steel.
� MALL OPERATIONS WITH FOOD COURTSEnvironAir® provides pollution control for new and existingMall Food Court operations and the flexibility for futureexpansion of the system. Multiple hoods and APU filter sec-tions can be joined to common odor control and blower sec-tions of the system.
� KITCHEN EXHAUST ODOR ABATEMENTEnvironAir® will effectively control the malodors producedfrom commercial cooking operations when equipped withthe optional Odor Control Section. This option addresses theproblems of commercial kitchens located near residentialareas or areas that are under pollution control requirementsfrom their local Air Quality Management District or otherlocal authorities.
� REDUCED DUCTWORK COST IN CANADAIn Canada, and in conjunction with the EnvironAir® ULC List-ing, all exhaust ductwork downstream of the filter section canbe installed with standard HVAC requirements (non-welded,galvanized, standard clean air installation). Exhaust air canbe discharged at levels other than rooftop (i.e. side wall orparking garage), thereby eliminating costly continuouslywelded horizontal and vertical duct runs and fire barrier chas-es. Ductwork from the hood to the inlet of the EnvironAir®
unit is required to be 16 gauge all welded steel.
APPLICATIONS Air Purification Unit
APU
exhaust hood
Indoor / Horizontal Supported
exhaust hood
Indoor / Vertical Supported
exhaust hood
Indoor / Horizontal Suspended
exhaust hood
Outdoor / Horizontal Roof Mounted
exhaust hood
Indoor Split Fan / Filter Sections
exhaust hood exhaust hood
Indoor Split Fan / Multiple Filter Sections(Mall Applications)
APU
APU
APU
APU
APUAPU
4
OPERATION Air Purification Unit
Exhaust Outlet
EXHAUST INLET AND OUTLET MAY BE VERTICAL AS SHOWN OR HORIZONTALLY
STRAIGHT THROUGH OR HORIZONTALLY FROM THE LEFT OR RIGHT SIDE.
Exhaust Inlet
APU UNIT SHOWN IS WITH OPTIONAL LIQUID ODOR SPRAY AND BLOWER SECTIONS.
Air MonitorCabinet
Filter Section
Odor Spray Cabinet
Magnetic Motor Starter Panel
Blower/FanSection
Pre-FilterBag FilterBox Filter
Air, Nil Air, Filter Out, Replace PreFilter, Replace Bag-Filter,and Replace Box-Filter.� A Status Panel for remote mounting.
The three-stages of filtration comprises:
1. A first stage pre-filter is a 4” (102mm) deep pleated typeand is rated at 40% ASHRAE 52.1-92. The filter is Listed asUL/ULC Class II.
2. A second stage bag-filter is a 22” (559mm) deep bag typeand is rated at 95% ASHRAE 52.1-92. The filter is Listed asUL/ULC Class I.
3. A third stage box-filter is a 12” (305mm) deep, fire rated,absolute filter and is rated at 99% ASHRAE 52.1-92, 95% DOP.The filter is Listed as UL/ULC Class I.
The exhausted air from the cooking operations passesthrough the Carroll ventilator and is ducted to the Envi-ronAir® APU unit for the removal of remaining particu-
late grease and smoke. The EnvironAir® APU uses a three-stage filter system that is designed to progressively removethe exhaust grease, lint, dirt, and smoke particulate matterdown to an ASHRAE rated 99% clean air level. The filter sec-tion also includes:
� A UL/ULC Listed fire damper (APU model only) actuatedby a 212°F (100°C) fusible link that is located at the filter sec-tion outlet. (Where the optional Odor Control Section is spec-ified the fire damper is located at the Odor Control outlet).The fire damper is required in Canada and is optional in theUnited States.� A firestat set at 200°F (93°C) to shut off the exhaust fan andactuate an alarm at the firestat set point.� An Air Monitor Cabinet, water tight and housing the firestatrelay and seven (7) pressure switches for monitoring Low
FILTER SECTION
Box FilterBag Filter
Pre-Filter
5
OPERATION Air Purification Unit
When equipped with the optional odor control sec-tion, the EnvironAir® APU can effectively control themalodors produced from commercial cooking. The
exhaust airstream from the filter section is purified of grease,lint, dirt and smoke but will still contain malodors producedfrom the cooking process. Control of these odors is accom-plished by passing the exhaust air- stream from the filter sec-tion through one of three odor control options offered byCarroll.
� ENVIRONSAFE™Is a liquid specially formulated to safely and effectivelyremove malodors. The EnvironSafe™ liquid is sprayeddirectly into the exhaust air stream of the odor cabinet. Envi-ronSafe™ is a formulation of natural ingredients fromessential oils; it is non-toxic, biodegradable, water solubleand environmentally safe. EnvironSafe™ is not an enzymeor chemical mask, it works by encapsulating the odor to forma neutral substance. The combined molecular weight of themalodor and EnvironSafe™ causes the molecules to fall to alower atmospheric level and biodegrade naturally. A freshnatural scent results.
� ACTIVATED ALUMINA SPHERES IMPREGNATED WITHPOTASSIUM PERMANGANATEIs an oxidizing media arranged in steel trays inside the odorcontrol section. As the exhaust air stream passes through thetrays, the media causes a chemical reaction, oxidation, thatbreaks the odor causing molecules into odorless naturalsubstances.
� ACTIVATED CARBONIs an absorption/adsorption media arranged in steeltrays inside the odor control section. As the exhaustairstream passes through the trays, the media worksthrough a process of absorption and adsorption on the odorcausing molecules.
Also available is a 50/50 blend in equal amounts of activatedcarbon and alumina spheres impregnated with potassium permanganate.
ODOR CONTROL SECTION
The exhaust fan section includes a centrifugal blowerassembly constructed of a heavy gauge steel housingwith all seams continuously welded. The blower has a
steel backwardly inclined airfoil wheel of the non-overload-ing type, and all blades are continuously welded to both adeep spun inlet shroud and to the backplate. The blower isAMCA rated both for sound and air volume, UL and CSA List-ed, with a AISI C-1040 or C-1045 hot rolled and accuratelyturned and polished steel shaft. Bearings are grease lubri-cated, precision anti-friction ball and self aligning pillowblock type with lubricating nipples. Drives are V-belt with acapacity 25% greater than motor horsepower. The blowerand motor mounting base are equipped with anti-vibrationisolators. Oil resistant non-static belts are provided.
The discharge from the blower section can be� Straight Through � Out The Left Side � Out The Right Side � Vertically Up
The blower compartment is constructed with a fully remov-able combination access panel and hinged door on the driveside of the blower, allowing if necessary the completeremoval of the blower assembly during servicing. A fullyremovable access panel is provided on the opposite side ofthe blower compartment.
The blower section is complete with a UL/ULC listed Combi-nation Magnetic Motor Starter Panel with a TYPE 1 cabinetfor indoor usage or TYPE 3R water-proof cabinet for outdoorusage, and includes a fan motor starter, electrical overloads,disconnect switch, and terminal blocks for remote annunci-ation and control.
For indoor and other noise-sensitive applications, an acousti-cal insulation liner is provided behind an expanded metalretaining wall.
BLOWER SECTION
CombinationMagneticMotor StarterPanel
BLOWER SECTION SHOWN WITHOUT ACCESS PANEL AND HINGED DOOR
Odor Spray CabinetFilter SectionOdor Media Section
6
OPERATION Air Purification Unit
STATUS PANEL
The Status Panel is constructed of 18 gauge stainlesssteel and is designed for remote mounting. The panelfeatures a fully hinged, water tight gasketed, front
access door with security fasteners. The panel is an ACD (foruse with dry ventilators) with the Fan ON/OFF pilot switch inthe panel face, or ACW with the Fan ON pilot light (for usewith water-wash ventilators) when the Fan ON/OFF pilotswitch is furnished as part of another system. The panel iscomplete with relays, timers, step down 120/24 VAC trans-former and status indicator pilot lights and/or push buttoncontrols for Fan ON/OFF (ACD) or Fan ON (ACW), Normal, NilAir, Low Air, Filter Out, Fire, Reset, Replace Pre-Filter, ReplaceBag-Filter, Replace Box-Filter, and Control Bypass. Fieldwiring between the Status Panel (ACD or ACW) and the AirMonitor Cabinet on the filter section is low voltage 24 VAC.The panel can be optionally equipped with Low Odor SprayIndicators consisting of: Low Odor Spray Pilot, Low OdorSpray Buzzer and Silence Buzzer Push Button. Also availableare sets of dry contacts for sending status signals to the build-ing management station.
FANON/OFF
LOWAIR
FILTEROUT
FIRE
REPLACEBAG
FILTERS
CONTROLBYPASS
NORMAL
NILAIR
RESET
REPLACEPRE
FILTERS
REPLACEBOX
FILTERS
FANON
LOWAIR
FILTEROUT
FIRE
REPLACEBAG
FILTERS
CONTROLBYPASS
SILENCEBUZZER
NORMAL
NILAIR
RESET
REPLACEPRE
FILTERS
REPLACEBOX
FILTERS
LOW ODORSPRAY
LOW ODORBUZZER
ACD PANEL ACW PANEL
STANDARD STATUS PANEL INDICATORS
• FAN ON/OFF Switch (ACD Only). Green push button that when depressed will illuminate to indicate that power isbeing fed to the Magnetic Motor Starter Panel to start the blower.
• FAN ON (ACW Only). Green pilot light that will illuminate when the Fan ON/OFF switch, otherwise provided, isenergized to start the blower.
• NORMAL. Green pilot light will illuminate within 30 seconds after the blower has been started to indicate that aninternal proving timer has reached its set point and the monitoring circuits have been activated
• LOW AIR. Yellow pilot light that when illuminated provides an early indication that the APU filters are loading upand require replacement. Other conditions may also cause this pilot light to illuminate, see the Trouble Shootingsection of the Technical Manual for further explanation.
• NIL AIR. Red pilot light that when illuminated indicates that one or more sets of the APU filters are fully loadedand require immediate replacement. Once the red NIL AIR pilot illuminates, the system will automatically shutdown the blower. Other conditions may also cause this pilot light to illuminate, see the Trouble Shooting sectionof the Technical Manual for further explanation.
(Basic Panel Shown) (Deluxe Panel Shown)
(Deluxe Panel Shown)
7
OPERATION Air Purification Unit
• FILTERS OUT. Red pilot light that when illuminated indicates that one or more of the bag or box filters are miss-ing from the APU. Once the red FILTER OUT pilot light illuminates, the system will automatically shut down theblower. Other conditions may also cause this pilot light to illuminate, see the Trouble Shooting section of theTechnical Manual for further explanation.
• RESET. Yellow push button (non-illuminated), when pushed in, will place the APU back into operation after it hasbeen shut down by one or more of the monitoring systems. Note: The condition which caused the system shutdown must first be corrected prior to pushing the RESET button.
• FIRE. Red pilot light will illuminate and the N.O. dry contacts to the building’s annunciation system will close inthe even the pre-set firestat temperature of 200° has been reached or if the fire test button on the inside of theMonitor Cabinet has been pushed.
• REPLACE PRE-FILTER. Red pilot will illuminate indicating the PRE-FILTERS are loaded and need immediatereplacement.
• REPLACE BAG FILTER. Red pilot light will illuminate indicating the BAG FILTERS are loaded and need immediatereplacement.
• REPLACE BOX FILTER. Red pilot light will illuminate indicating the BOX FILTERS are loaded and need immediatereplacement.
• CONTROL BYPASS. Orange pilot light will illuminate once the bypass switch on the inside of the Monitor Cabi-net has been pushed. This indicates that the system controls have been put into a temporary bypass mode.Note: The condition causing the system to shut down in normal operating mode must be corrected immediately.
OPTIONAL STATUS PANEL INDICATORS
• LOW ODOR SPRAY. Blue pilot light will illuminate to indicate that the odor spray liquid needs to be immediatelyreplenished.
• SILENCE BUZZER. Blue push button that when depressed will shut off the LOW ODOR BUZZER.
• LOW ODOR BUZZER. Audible alarm that will sound to indicate that the odor spray liquid needs to be immediate-ly replenished.
8
THE COMPLETE CARROLL AIR PURIFICATION SYSTEM
A complete Air Purification System will consistof Carroll’s high velocity ventilator(s), controlpanel, fire suppression system, and Environ-Air® APU consisting of filter, odor control, andfan sections. The EnvironAir® APU has beenengineered to work with all types of ventilators.However, it is highly recommended that a high efficiency grease extractor be used in con-junction with the EnvironAir® unit. Ventilatorssuch as Carroll’s high velocity W-2 andW-1 water wash series or DX dry extractorseries offer up to 95% grease extraction effi-ciency by weight. These ventilators help pro-vide the optimum in filter life for the APU. Addi-tionally, Carroll’s high velocity ventilators cansubstantially reduce the overall exhaust rateover differing types of cooking equipmentunder the same ventilator.
W1 “Elite” Series Water-Wash Ventilators Westin Hotel, Taipei, Taiwan
c
2" (51 mm)
Hinged Access Door (with Media Trays option only)
Odor Spray Cabinet
25" L X 25" W X 13 1/4" D635mm X 635mm X 337mm(With Odor Spray Option)
2" (51 mm) 2" (51 mm)
Hinged Access Door Firestat
Air Monitor Cabinet28" L X 10" W X7" D711mm X 254mm X 178mm
AIR FLOW
PLAN VIEW
L = 63 1/4" (1505 mm) without Odor SectionL = 91 1/2" (2223 mm) with Media Trays or Odor Spray Section
Standard Size Cabinet FILTER/ODOR CONTROL SECTION - Straight Through Option
WA
L
9
ENGINEERING DATA Air Purification Unit
No. INCHES MM INCHES MM 24X24 24X12 24X24X2 12X24X2 INCHES MM INCHES MM INCHES MM
01 1000 14 1/4 362 32 813 0 1 0 5 10 254 15 381 6 15/16 176
02 2000 26 1/4 667 32 813 1 0 5 0 19 483 15 381 6 15/16 176
03 3000 38 1/4 972 32 813 1 1 5 5 29 737 15 381 6 15/16 176
04 4000 50 1/4 1276 33 838 2 0 10 0 38 965 15 381 6 15/16 176
05 5000 62 1/4 1581 33 838 2 1 10 5 48 1219 15 381 6 15/16 176
06 6000 50 1/4 1276 45 1143 2 2 14 2 38 965 22 1/2 572 9 1/8 232
08 8000 50 1/4 1276 58 1473 4 0 20 0 38 965 30 762 11 3/8 289
09 9000 74 1/4 1886 46 1168 3 3 22 1 57 1448 22 1/2 572 9 1/8 232
10 10,000 62 1/4 1581 58 1473 4 2 20 10 48 1219 30 762 11 3/8 289
12 12,000 74 1/4 1886 58 1473 6 0 30 0 57 1448 30 762 11 3/8 289
14 14,000 74 1/4 1886 70 1778 6 2 34 2 57 1448 35 1/2 902 14 9/16 370
15 15,000 74 1/4 1886 70 1778 6 3 37 1 57 1448 37 1/2 953 13 9/16 344
16 16,000 74 1/4 1886 82 2083 8 0 40 0 57 1448 40 1/2 1029 18 457
18 18,000 74 1/4 1886 82 2083 9 0 45 0 57 1448 45 1143 15 3/4 400
20 20,000 86 1/4 2191 83 2108 9 2 45 15 64 1626 45 1143 15 3/4 400
24 24,000 98 1/4 2496 83 2108 12 0 60 0 77 1956 45 1143 15 3/4 400
28 28,000 98 1/4 2496 95 2413 12 4 70 0 77 1956 52 1/2 1334 18 457
32 32,000 98 1/4 2496 107 2718 16 0 80 0 77 1956 60 1524 20 3/16 513
36 36,000 110 1/2 2807 107 2718 16 4 80 20 86 2184 60 1524 20 3/16 513
40 40,000 122 1/4 3105 107 2718 20 0 100 0 96 2438 60 1524 20 3/16 513
APU # Standard Filter/Odor Section Dimension Inlet Dimension
Model CFM W H **No .of Filters *No. of Odor Trays A B E
Nominal
c
2" (51 mm)
Note: Filter Section Inlet & Outlet are centered Horizontally
Hinged Access Door (with Media Trays option only)
Odor Spray Cabinet
25" L X 25" W X 13 1/4" D635mm X 635mm X 337mm(With Odor Spray Option)
2" (51 mm) 2" (51 mm)
Hinged Access Door Firestat
Air Monitor Cabinet28" L X 10" W X7" D711mm X 254mm X 178mm
AIR FLOW
PLAN VIEW
L = 63 1/4" (1505 mm) without Odor SectionL = 91 1/2" (2223 mm) with Media Trays or Odor Spray Section
WA
L
Dimension and Weight Table (continued on pg.10)
Weight for 24X24X2 Odor TrayMedia Only Empty Tray Tray + MediaLB KG LB KG Lb KG
33 15.0 8 3.6 41 18.6Weight for 12X24X2 Odor Tray
LB KG LB KG Lb KG
17 7.7 4 1.8 21 9.5
# Consult factory for special sizes(not shown)
* Number of trays is for a single pass
** Number of filters is for Pre, Bag,and Box filters
Note: All Dimensions are approxi-mate, refer to submittal drawings forconstruction dimensions
Dimension and Weight Table (continued from pg. 9)
10
ENGINEERING DATA Air Purification Unit
c
2" (51 mm)
Hinged Access Door (with Media Trays option only)
Odor Spray Cabinet
25" L X 25" W X 13 1/4" D635mm X 635mm X 337mm(With Odor Spray Option)
2" (51 mm) 2" (51 mm)
Hinged Access Door Firestat
Air Monitor Cabinet28" L X 10" W X7" D711mm X 254mm X 178mm
AIR FLOW
PLAN VIEW
L = 63 1/4" (1505 mm) without Odor SectionL = 91 1/2" (2223 mm) with Media Trays or Odor Spray Section
Standard Size Cabinet FILTER/ODOR CONTROL SECTION - Straight Through Option
WA
L
Fire Damper (optional)Odor Media Trays
Box Filter
3" (76mm) Base Frame for APU 01 - APU 074" (102mm) Base Frame for APU 08 - APU 185" (127mm) Base Frame for APU 20 - APU 40
Bag Filter
Pre-Filter
SIDE ELEVATION
HB
E
D
3 3/8"(86mm)
No. INCHES MM INCHES MM LBS. KG. LBS. KG. LBS. KG.
01 1000 9 229 23 7/8 606 450 204 346 157 260 118
02 2000 21 533 23 7/8 606 659 299 496 225 384 174
03 3000 31 787 23 7/8 606 917 416 603 273 490 222
04 4000 41 1041 23 7/8 606 1062 482 702 318 504 229
05 5000 53 1346 23 7/8 606 1268 575 804 365 589 267
06 6000 41 1041 34 864 1470 667 905 410 608 276
08 8000 41 1041 46 1168 1737 788 967 439 728 330
09 9000 65 1651 34 864 1908 865 1034 469 840 381
10 10,000 53 1346 46 1168 2079 943 1102 500 843 382
12 12,000 65 1651 46 1168 2410 1093 1230 558 951 431
14 14,000 65 1651 58 1473 2789 1265 1404 637 1069 485
15 15,000 65 1651 58 1473 2926 1327 1418 643 1083 491
16 16,000 65 1651 70 1778 3126 1418 1536 697 1183 537
18 18,000 65 1651 70 1778 3354 1521 1559 707 1185 537
20 20,000 77 1956 70 1778 3716 1685 1713 777 1373 623
24 24,000 89 2261 70 1778 4334 1966 1973 895 1523 691
28 28,000 89 2261 82 2083 4827 2189 2239 1015 1712 776
32 32,000 89 2261 94 2388 5484 2487 2404 1090 1860 844
36 36,000 101 2565 94 2388 6100 2766 2606 1182 2077 942
40 40,000 113 2870 94 2388 6684 3031 2784 1263 2405 1091
APU CFM Outlet Dimension Tot. Wt. w/ Tot. Wt. w/ Tot. Wt. w/
Model C D Media Trays Spray Cabinet no Odor control
Nominal
Optional Size Cabinet FILTER/ODOR CONTROL SECTION - Straight Through Option
11
ENGINEERING DATA Air Purification Unit
c
2" (51 mm)
Note: Filter Section Inlet & Outlet are centered Horizontally
Hinged Access Door (with Media Trays option only)
Odor Spray Cabinet
25" L X 25" W X 13 1/4" D635mm X 635mm X 337mm(With Odor Spray Option)
2" (51 mm) 2" (51 mm)
Hinged Access Door Firestat
Air Monitor Cabinet28" L X 10" W X7" D711mm X 254mm X 178mm
AIR FLOW
PLAN VIEW
L = 63 1/4" (1505 mm) without Odor SectionL = 91 1/2" (2223 mm) with Media Trays or Odor Spray Section
WA
L
No. INCHES MM INCHES MM 24X24 24X12 24X24X2 12X24X2 INCHES MM INCHES MM INCHES MM
01 1000 26 1/4 667 21 533 0 1 2 1 19 483 7 3/4 197 4 9/16 116
02 2000 50 1/4 1276 21 533 0 2 5 0 38 965 7 3/4 197 4 9/16 116
03 3000 26 1/4 667 45 1143 1 1 7 1 19 483 22 7/8 581 8 15/16 227
04 4000 26 1/4 667 57 1448 2 0 10 0 19 483 30 762 11 3/8 289
05 5000 26 1/4 667 69 1753 2 1 12 1 19 483 38 965 13 3/8 340
06 6000 74 1/4 1886 33 838 3 0 15 0 57 1448 15 381 6 15/16 176
08 8000 98 1/4 2496 34 864 4 0 20 0 76 1930 15 381 6 15/16 176
09 9000 38 1/4 972 82 2083 3 3 15 15 28 7/8 733 45 1143 15 7/8 403
10 10,000 50 1/4 1276 70 1778 4 2 25 0 38 965 38 965 11 3/8 289
12 12,000 50 1/4 1276 82 2083 6 0 30 0 38 1/2 978 45 1143 15 7/8 403
14 14,000 86 1/4 2191 58 1473 6 2 30 10 67 1/4 1708 30 762 11 3/8 289
16 16,000 98 1/4 2496 58 1473 8 0 40 0 77 1956 30 762 11 3/8 289
18 18,000 110 1/4 2800 58 1473 8 2 40 10 86 1/2 2197 30 762 11 3/8 289
APU # Standard Filter/Odor Section Dimension Inlet Dimension
Model CFM W H **No. of Filters *No. of Odor Trays A B E
Nominal
Dimension and Weight Table (continued on pg. 12)
Dimension and Weight Table (continued from pg. 11)
12
ENGINEERING DATA Air Purification Unit
Optional Size Cabinet FILTER/ODOR CONTROL SECTION - Straight Through Option
Fire Damper (optional)Odor Media Trays
Box Filter
3" (76mm) Base Frame for APU 01 - APU 074" (102mm) Base Frame for APU 08 - APU 185" (127mm) Base Frame for APU 20 - APU 40
BagFilter
Pre-Filter
SIDE ELEVATION
HB
E
D
3 3/8"(86mm)
No. INCHES MM INCHES MM LBS. KG. LBS. KG. LBS. KG.
01 1000 21 533 11 7/8 302 450 204 346 157 260 118
02 2000 41 1041 11 7/8 302 659 299 496 225 384 174
03 3000 21 533 34 864 917 416 603 273 490 222
04 4000 21 533 46 1168 1062 482 702 318 504 229
05 5000 21 533 58 1473 1268 575 804 365 589 267
06 6000 65 1651 23 7/8 606 1470 667 905 410 608 276
08 8000 70 1778 23 7/8 606 1737 788 967 439 728 330
09 9000 31 787 70 1778 1908 865 1034 469 840 381
10 10,000 41 1041 58 1473 2079 943 1102 500 843 382
12 12,000 41 1041 70 1778 2410 1093 1230 558 951 431
14 14,000 77 1956 46 1168 2789 1265 1404 637 1069 485
16 16,000 89 2261 46 1168 3126 1418 1536 697 1183 537
18 18,000 101 2565 46 1168 3354 1521 1559 707 1185 537
APU Outlet Dimension Tot. Wt. w/ Tot. Wt. w/ Tot. Wt. w/
Model CFM C D Media Trays Spray Cabinet no Odor control
Nominal
Weight for 24X24X2 Odor TrayMedia Only Empty Tray Tray + MediaLB KG LB KG Lb KG
33 15.0 8 3.6 41 18.6Weight for 12X24X2 Odor Tray
LB KG LB KG Lb KG
17 7.7 4 1.8 21 9.5
# Consult factory for special sizes(not shown)
* Number of trays is for a single pass
** Number of filters is for Pre, Bag,and Box filters
Note: All Dimensions are approxi-mate, refer to submittal drawings forconstruction dimensions
Standard Size Cabinet FILTER/ODOR CONTROL SECTION - Top (shown) or Bottom Inlet Option
13
ENGINEERING DATA Air Purification Unit
c
2" (51 mm)Hinged Access Door(with Odor Media trays ONLY)
Odor Spray Cabinet
25" L X 25" W X 13 1/4" D635mm X 635mm X 337mm(with Odor Spray Option)
2" (51 mm)
Hinged Access Door Firestat
AIR PRESSURE SWITCH HOUSING28" L X 10" W X7" D711mm X 254mm X 178mm
PLAN VIEW
L = 59 1/4" (1505 mm) without Odor SectionL = 87 1/2" (2223 mm) with Media Tray or Odor Spray Section
AW
B
Total Length = L+B
1 5/8" (41mm)
Note: Filter Section Inlet & Outlet are centered Horizontally
No. INCHES MM INCHES MM 24X24 24X12 24X24X2 12X24X2 INCHES MM INCHES MM
01 1000 14 1/4 362 32 813 0 1 0 5 10 83 15 762
02 2000 26 1/4 667 32 813 1 0 5 0 13 330 15 381
03 3000 38 1/4 972 32 813 1 1 5 5 19 1/4 489 15 381
04 4000 50 1/4 1276 33 838 2 0 10 0 25 1/2 648 15 381
05 5000 62 1/4 1581 33 838 2 1 10 5 32 1/4 819 15 381
06 6000 50 1/4 1276 45 1143 2 2 14 2 38 1/2 978 15 381
08 8000 50 1/4 1276 58 1473 4 0 20 0 32 813 24 610
09 9000 74 1/4 1886 46 1168 3 3 22 1 57 3/4 1467 15 381
10 10,000 62 1/4 1581 58 1473 4 2 20 10 40 1016 24 610
12 12,000 74 1/4 1886 58 1473 6 0 30 0 48 1219 24 610
14 14.000 74 1/4 1886 70 1778 6 2 34 2 56 1422 24 610
15 15,000 74 1/4 1886 70 1778 6 3 37 1 60 1/4 1530 24 610
16 16,000 74 1/4 1886 82 2083 8 0 40 0 51 1/2 1308 30 762
18 18,000 74 1/4 1886 82 2083 9 0 45 0 57 3/4 1467 30 762
20 20,000 86 1/4 2191 83 2108 9 2 45 15 64 1/4 1632 30 762
24 24,000 98 1/4 2496 83 2108 12 0 60 0 77 1956 30 762
28 28,000 98 1/4 2496 95 2413 12 4 70 0 75 1905 36 914
32 32,000 98 1/4 2496 107 2718 16 0 80 0 85 3/4 2178 36 914
36 36,000 110 1/2 2807 107 2718 16 4 80 20 96 1/2 2451 36 914
40 40,000 122 1/4 3105 107 2718 20 0 100 0 107 2718 36 914
APU # Standard Filter/Odor Section Dimension Inlet Dimension
Model CFM W H **No. of Filters *No. of Odor Trays A B
Nominal
Dimension and Weight Table (continued on pg. 14)
14
ENGINEERING DATA Air Purification Unit
Standard Size Cabinet FILTER/ODOR CONTROL SECTION - Top (shown) or Bottom Inlet Option
2" (51 mm)Fire Damper (optional)
Odor Media Trays
Box Filter
3" (76mm) Base Frame for APU 01 - APU 074" (102mm) Base Frame for APU 08 - APU 185" (127mm) Base Frame for APU 20 - APU 40
Bag Filter
Pre - Filter
SIDE ELEVATION
H
B
D
3 3/8"(86mm)
AIR FLOW
No. INCHES MM INCHES MM LBS. KG. LBS. KG. LBS. KG.
01 1000 9 229 23 7/8 606 465 211 361 164 275 125
02 2000 21 533 23 7/8 606 677 307 514 233 402 182
03 3000 31 787 23 7/8 606 938 425 624 283 511 232
04 4000 41 1041 23 7/8 606 1087 493 727 330 529 240
05 5000 53 1346 23 7/8 606 1296 588 832 377 615 279
06 6000 41 1041 34 864 1517 688 950 431 655 297
08 8000 41 1041 46 1168 1811 821 1041 472 802 364
09 9000 65 1651 34 864 1966 892 1092 495 898 407
10 10,000 53 1346 46 1168 2159 979 1183 537 923 419
12 12,000 65 1651 46 1168 2497 1132 1317 597 1038 471
14 14,000 65 1651 58 1473 2911 1320 1526 692 1191 540
15 15,000 65 1651 58 1473 3048 1382 1540 698 1205 546
16 16,000 65 1651 70 1778 3286 1490 1696 769 1343 609
18 18,000 65 1651 70 1778 3514 1594 1719 780 1345 610
20 20,000 77 1956 70 1778 3891 1765 1888 856 1548 702
24 24,000 89 2261 70 1778 4554 2065 2193 995 1743 790
28 28,000 89 2261 82 2083 5060 2294.8 2523 1144 1945 882
32 32,000 89 2261 94 2388 5768 2616 2688 1219 2144 972
36 36,000 101 2565 94 2388 6399 2902 2905 1318 2376 1078
40 40,000 113 2870 94 2388 6997 3173 3098 1405 2718 1233
APU Outlet Dimension Tot. Wt. w/ Tot. Wt. w/ Tot. Wt. w/
Model CFM C D Media Trays Spray Cabinet no Odor Control
Nominal
Dimension and Weight Table (continued from pg. 13)
Weight for 24X24X2 Odor TrayMedia Only Empty Tray Tray + MediaLB KG LB KG Lb KG
33 15.0 8 3.6 41 18.6Weight for 12X24X2 Odor Tray
LB KG LB KG Lb KG
17 7.7 4 1.8 21 9.5
# Consult factory for special sizes(not shown)
* Number of trays is for a single pass
** Number of filters is for Pre, Bag,and Box filters
Note: All Dimensions are approxi-mate, refer to submittal drawings forconstruction dimensions
DWDI Fan Section/Straight Through Discharge (shown) (Up Blast & Side Discharge Options also Available)
15
ENGINEERING DATA Air Purification Unit
No. INCHES MM INCHES MM INCHES MM
01 500-1000 120 13 1/8 333 9 3/16 233 16 5/8 422
02 1100-2000 120 13 1/8 333 9 3/16 233 16 5/8 422
03 2100-3000 120 12 1/8 308 17 11/16 449 17 3/4 451
04 3100-4000 135 13 5/8 346 19 15/16 506 19 483
05 4100-5000 135 13 5/8 346 19 15/16 506 19 483
06 5100-6000 150 15 1/4 387 22 559 20 1/4 514
08 6100-8000 150 15 1/4 387 22 559 20 1/4 514
09 8100-9000 165 16 15/16 430 24 610 21 3/8 543
10 9100-10000 165 16 15/16 430 24 610 213/8 543
12 10100-12000 195 19 1/2 495 28 7/16 722 25 1/2 648
14 12100-14000 210 21 5/8 549 30 3/8 772 26 3/4 679
15 14100-15000 210 21 5/8 549 30 3/8 772 26 3/4 679
16 15100-16000 225 23 3/16 589 32 1/2 826 28 711
18 16100-18000 225 23 3/16 589 32 1/2 826 28 711
20 18100-20000 245 25 1/2 648 35 1/16 891 29 5/8 752
24 20100-21400 245 25 1/2 648 35 1/16 891 29 5/8 752
21500-24000 270 27 1/2 699 39 7/16 1002 33 1/8 841
28 24100-26300 270 27 1/2 699 39 7/16 1002 33 1/8 841
26400-28000 300 31 3/16 792 43 1092 35 1/8 892
32 28100-32000 300 31 3/16 792 43 1092 35 1/8 892
36 32100-32700 300 31 3/16 792 43 1092 35 1/8 892
32800-36000 330 34 1/2 876 47 1/16 1195 37 3/4 959
40 36100-39700 330 34 1/2 876 47 1/16 1195 37 3/4 959
39800-40000 365 38 11/16 983 52 3/16 1326 40 1/2 1029
APU Blower Outlet Dim.
Mod. CFM A B C
BlowerModel
No.DWDINominal
2" (51 mm)
Flange is provided ONLYwhen fan section is installedremotely from filter section
Hinged Access DoorAccess Panel
Magnetic MotorStarter
Blower Outlet iscentered horizontallyunless otherwise noted
Fan Sec. Inlet iscentered Horizontally
Access Panel HANGER BRACKET (Typical )
w
D
L
B
2" (51 mm)
2" (51 mm)
AIR FLOW
Magnetic Motor Starters(X) Dimension
PLAN VIEW
200-208
7 3/4
10 19/32
10 17/32
10 17/32
10 17/32
15 1/2
15 1/2
230-240
7 3/4
9 19/32
10 17/32
10 19/32
10 17/32
10 17/32
15 1/2
460-480
7 3/4
7 3/4
7 3/4
7 3/4
10 19/32
10 19/32
10 17/32
575-600
7 3/4
7 3/4
7 3/4
7 3/4
10 19/32
10 19/32
10 17/32
2-10 HP
15 HP
20-25 HP
30 HP
40 HP
50 HP
60-75 HP
X
Insulation(optional)
HPVoltage
No. INCHES MM INCHES MM INCHES MM
01 500-1000 120 13 1/8 333 9 3/16 233 16 5/8 422
02 1100-2000 120 13 1/8 333 9 3/16 233 16 5/8 422
03 2100-3000 120 12 1/8 308 17 11/16 449 17 3/4 451
04 3100-4000 135 13 5/8 346 19 15/16 506 19 483
05 4100-5000 135 13 5/8 346 19 15/16 506 19 483
06 5100-6000 150 15 1/4 387 22 559 20 1/4 514
08 6100-8000 150 15 1/4 387 22 559 20 1/4 514
09 8100-9000 165 16 15/16 430 24 610 21 3/8 543
10 9100-10000 165 16 15/16 430 24 610 213/8 543
12 10100-12000 195 19 1/2 495 28 7/16 722 25 1/2 648
14 12100-14000 210 21 5/8 549 30 3/8 772 26 3/4 679
15 14100-15000 210 21 5/8 549 30 3/8 772 26 3/4 679
16 15100-16000 225 23 3/16 589 32 1/2 826 28 711
18 16100-18000 225 23 3/16 589 32 1/2 826 28 711
20 18100-20000 245 25 1/2 648 35 1/16 891 29 5/8 752
24 20100-21400 245 25 1/2 648 35 1/16 891 29 5/8 752
21500-24000 270 27 1/2 699 39 7/16 1002 33 1/8 841
28 24100-26300 270 27 1/2 699 39 7/16 1002 33 1/8 841
26400-28000 300 31 3/16 792 43 1092 35 1/8 892
32 28100-32000 300 31 3/16 792 43 1092 35 1/8 892
36 32100-32700 300 31 3/16 792 43 1092 35 1/8 892
32800-36000 330 34 1/2 876 47 1/16 1195 37 3/4 959
40 36100-39700 330 34 1/2 876 47 1/16 1195 37 3/4 959
39800-40000 365 38 11/16 983 52 3/16 1326 40 1/2 1029
APU Blower Outlet Dimension
Model CFM A B C
BlowerModel
No.DWDINominal
Dimension and Weight Table (continued on pg. 16)
*Weight includes Blower, BlowerCabinet, Motor & Drives
Note: All Dimensions are approxi-mate, refer to submittal drawingsfor construction dimensions
16
ENGINEERING DATA Air Purification Unit
DWDI Fan Section/Straight Through Discharge (shown) (Up Blast & Side Discharge Options also Available)
2" (51 mm)
3 3/8" (86mm)
Vibration Isolators
H
G
A
C
SIDE ELEVATION
Motor Slide Base
3" (76mm) base frame for APU 01-APU 074" (102mm) base frame for APU 08-APU 185" (127mm) base frame for APU 20-APU 40
No. INCHES MM INCHES MM INCHES MM LBS. KG. INCHES MM INCHES MM
01 500-1000 120 38 1/4 972 52 1321 40 1016 763 346 9 229 23 7/8 606
02 1100-2000 120 38 1/4 972 52 1321 40 1016 763 346 21 533 23 7/8 606
03 2100-3000 120 38 1/4 972 52 1321 40 1016 763 346 31 787 23 7/8 606
04 3100-4000 135 50 1/4 1276 56 1422 44 1118 934 424 41 1041 23 7/8 606
05 4100-5000 135 62 1/4 1581 56 1422 44 1118 1012 459 53 1346 23 7/8 606
06 5100-6000 150 50 1/4 1276 60 1524 48 1219 1086 493 41 1041 34 864
08 6100-8000 150 50 1/4 1276 60 1524 58 1473 1265 574 41 1041 46 1168
09 8100-9000 165 74 1/4 1886 66 1676 58 1473 1553 704 65 1651 34 864
10 9100-10000 165 62 1/4 1581 66 1676 58 1473 1485 673 53 1346 46 1168
12 10100-12000 195 74 1/4 1886 72 1829 58 1473 1783 809 65 1651 46 1168
14 12100-14000 210 74 1/4 1886 72 1829 70 1778 1826 828 65 1651 58 1473
15 14100-15000 210 74 1/4 1886 72 1829 70 1778 1956 887 65 1651 58 1473
16 15100-16000 225 74 1/4 1886 75 1905 82 2083 2103 954 65 1651 70 1778
18 16100-18000 225 74 1/4 1886 75 1905 82 2083 2103 954 65 1651 70 1778
20 18100-20000 245 86 1/4 2191 78 1981 83 2108 2457 1114 77 1956 70 1778
24 20100-21400 245 98 1/4 2496 82 2083 83 2108 2731 1239 89 2261 70 1778
21500-24000 270 98 1/4 2496 82 2083 83 2108 2895 1313 89 2261 70 1778
28 24100-26300 270 98 1/4 2496 90 2286 95 2413 3097 1405 89 2261 82 2083
26400-28000 300 98 1/4 2496 90 2286 95 2413 3677 1668 89 2261 82 2083
32 28100-32000 300 98 1/4 2496 90 2286 107 2718 3773 1711 89 2261 94 2388
36 32100-32700 300 110 1/2 2807 96 2438 107 2718 4198 1904 101 2565 94 2388
32800-36000 330 110 1/2 2807 96 2438 107 2718 4795 2175 101 2565 94 2388
40 36100-39700 330 122 1/4 3105 104 2642 107 2718 5250 2381 113 2870 94 2388
39800-40000 365 122 1/4 3105 104 2642 107 2718 5247 2380 113 2870 94 2388
APU Fan Section Dimension Fan Section Inlet Dimension
Model CFM W L H Weight* D G
BlowerModel
No.DWDI
Dimension and Weight Table (continued from pg. 15)
Nominal
Notes:
(1) APU
sizes shown are the standard blow
er/cabinet combinations, C
MI reserves the right to change those com
binations to accomm
odate job specifications.(2) For S
tatic pressures not shown please contact C
MI
(3) Break horsepow
er (BH
P) includes drive losses* S
WS
I-High Pressure B
lower is utilized
** SW
SI (standard) B
lower is utilized
# Static pressure show
n is for units without M
edia trays. When M
edia Trays are specified, increase E.S.P. by 0.375” w
.g. before using the table for your fan selection.
141006655
200016.86
12.572050
18.0613.47
21051945
14.502160
20.9015.58
221422.40
16.702269
23.9817.88
232325.57
19.06
1514500
684421.0
5332029
176513.16
208018.92
14.112132
202515.10
218521.70
16.182238
23.1917.29
229124.77
18.472344
26.3819.67
150007080
20651867
13.922117
19.9914.90
21682137
15.932219
22.7816.98
227024.29
18.112322
25.8619.28
237327.49
20.50
151007127
18051739
12.971855
18.7713.99
19102037
15.191964
22.0316.43
201823.73
17.692072
25.4919.01
212527.29
20.35
1615500
731622.5
5721827
180813.48
187619.47
14.521930
210715.71
198322.72
16.942036
24.4718.24
208926.25
19.572141
28.0720.93
160007552
18551899
14161907
20.5015.28
19582207
16.462009
23.7117.68
206125.46
18.982112
27.2620.33
216329.09
21.69
161007599
186119.19
14.311907
20.5315.31
195722.07
16.462009
23.7417.70
206025.45
18.982111
27.2620.33
21.6229.10
21.70
1817000
802422.5
5721913
20.9415.61
195822.34
16.662007
23.9217.83
205525.53
19.042103
27.2420.31
215229.05
21.662200
30.9023.04
180008496
197323.09
17.222021
24.6818.40
206726.25
19.572113
27.9220.82
215929.63
22..092204
31.3623.38
225033.24
24.78
181008543
170620.25
15.101753
21.7916.25
180323.58
17.581851
25.4118.95
189927.36
20.401946
29.3021.85
199331.34
23.37
2019000
896824.5
6221742
21.7816.24
179123.41
17.451843
25.2918.86
189027.14
20.241937
29.1121.70
198231.10
23.192027
33.1324.70
200009440
178323.56
17.571834
23.5818.92
188427.73
20.301933
29.1521.73
197931.15
23.232023
33.1624.72
206735.28
26.30
201009487
24.5622
178723.73
17.691830
25.2818.85
188027.13
20.231929
29.0321.64
197631.04
23.142020
33.0324.63
206435.13
26.21
2421400
1010124.5
6221843
26.2419.56
188627.95
20.841934
29.8622.26
198231.84
23.742028
33.8325.22
207435.94
26802116
38.0528.37
2150010148
27.0686
148022.86
17.041522
24.6518.38
157026.76
19.951617
28.8921.54
166431.12
23.201711
33.3524.87
176035.76
26.66
2400011328
27.0686
154726.68
19.8915.96
28.9421.58
205136.17
26.971685
33.4524.94
172735.72
26.631769
38.0828.39
181140.50
30.20
2410011375
27.0686
155028.86
20.031591
28.7421.43
163831.06
23.161681
33.2724.81
172435.61
26.551766
37.9728.31
180840.39
30.11
2826300
1241427.0
6861612
30.6722.87
165432.83
24.481699
35.2526.28
174337.71
28.121785
40.1729.95
182542.64
31.791865
45.1733.68
2640012416
30.0762
129727.68
20.641334
29.8022.22
137432.20
24.011412
34.5425.75
145537.39
27.881496
40.1429.93
153943.15
32.17
2800013216
30.0762
133030.16
22.491370
32.6024.31
120733.76
25.171446
37.6428.06
148340.22
29.991521
42.9732.04
156045.82
34.16
2810013263
133230.31
22.601368
32.5224.25
1406.4.98
26.081443
37.4827.95
148040.07
29.881518
42.8231.93
155745.67
34.05
3230000
1416030.0
7621364
33.0224.62
140835.89
26.761447
38.6028.78
148441.29
30.791519
43.8932.72
155446.62
34.761589
49.4436.86
3200015104
139335.76
26.661443
39.2229.24
148842.51
31.701289
42.3431.57
156248.31
36.021596
51.1738.15
162954.03
40.28
3210015151
30.0762
139435.87
26.741438
38.9029.00
148442.25
31.501525
45.3833.84
156048.20
35.941594
51.0538.06
162753.91
40.20
3632700
1543430.0
7621403
36.7427.39
144739.83
29.701494
43.3132.29
153646.54
34.701573
49.5836.97
160652.40
39.071640
55.4141.31
3280015482
33.0838
119334.80
25.951226
37.4227.90
126140..33
30.071296
43.3632.33
133146.44
34.631397
49.7637.10
140555.36
39.79
3600016992
33.0838
123739.58
29.511278
43.1332.16
131346.30
34.521346
49.4636.88
137952.77
39.351410
55.9541.72
144259.29
44.21
3610017039
33.0838
123839.70
29.601276
42.9932.05
131146.15
34.411345
49.4236.85
137752.61
39.231409
55.9141.69
144059.14
44.09
4039700
1873833.0
8381277
44.6233.27
132048.65
36.271363
52.9139.45
132048.65
36.271433
60.3444.99
164663.89
47.641449
67.4450.28
3980018786
36.5927
107542.03
31.341108
45.5233.94
114049.09
36.601170
52.5539.18
1203565.45
421.601237
60.6745.24
127064.88
48.37
4000018880
36.5927
107742.31
31.551110
45.8134.16
114249.41
36.841174
53.1439.62
120656.94
42.451239
61.0445.51
127365.41
48.77
17
En
viro
nA
ir®
DW
DI F
an
Air P
erfo
rman
ce T
ab
le
ENGINEERING DATA Air Purification Unit
continued from pg.18
En
viro
nA
ir®
DW
DI F
an
Air P
erfo
rman
ce T
ab
le
AP
U
Exh
au
st R
ate
Wh
eel D
ia.
EX
TE
RN
AL S
TA
TIC
PR
ES
SU
RE
#
Mo
del
1.5
0"W
.G./0
.372 K
Pa
2.0
0"W
.G./0
.496 K
Pa
2.5
0"W
.G./0
.620 K
Pa
3.0
0"W
.G./0
.745 K
Pa
3.5
0"W
.G./0
.869 K
Pa
4.0
0"W
.G./0
..993 K
Pa
4.5
0"W
.G./0
.1.1
2 K
Pa
No.
Nom
inalL/S
ec
INM
MR
PM
BH
PK
WR
PM
BH
PK
WR
PM
BH
PK
WR
PM
BH
PK
WR
PM
BH
PK
WR
PM
BH
PK
WR
PM
BH
PK
W
01500*
23612.0
3053158
0.930.69
32721.03
0.773383
1.1340.85
34881.24
0.923592
1.341.00
36931.45
1.08---
------
1000*472
36161.37
1.023711
1.481.10
38041.59
1.193896
1.711.28
39851.83
1.374073
1.961.46
41602.086
1.56
1100*519
37681.52
1.133857
1.641.22
39441.76
1.314030
1.881.40
41152.01
1.504198
2.141.59
42822.27
1.69
021500*
70812.0
3054639
2.631.96
47102.78
2.074780
2.942.19
48503.10
2.314919
3.262.43
49883.42
2.555056
3.592.67
2000**944
36172.70
2.023711
2.932.18
38043.15
2.353896
3.392.53
39853.63
2.704072
3.872.88
41594.11
3.06
2100991
30062.72
2.033102
2.922.18
32493.25
2.423391
3.582.67
35273.93
2.933655
4.283.19
37794.66
3.47
032500
118012.0
3053076
3.102.31
31813.39
2.533314
3.782.82
34444.15
3.093573
4.533.38
37004.91
3.663824
5.303.95
30001416
32313.65
2.723346
4.012.99
34604.41
3.293574
4.843.61
36875.28
3.943800
5.744.28
39116.21
4.63
31001463
27233.84
2.862814
4.193.12
29344.67
3.483051
5.133.82
31675.61
4.183281
6.094.54
33926.57
4.90
043500
165213.5
3432800
4.223.15
28854.60
3.432995
5.113.81
31045.64
4.213211
6.184.61
33176.72
5.013421
7.245.40
40001888
29274.90
3.653025
5.364.00
31225.85
4.363218
6.384.76
33166.95
5.183410
7.535.61
35058.13
6.06
41001935
29565.06
3.773031
5.434.05
31265.91
4.413221
6.414.78
33156.97
5.203408
7.545.62
35018.14
6.07
054500
212413.5
3433067
5.714.26
31586.19
4.623247
6.694.99
33347.20
5.373420
7.725.76
35078.27
6.173593
8.866.61
50002360
32296.68
4.983318
7.225.38
34057.78
5.803488
8.336.21
35688.87
6.616347
9.427.02
37259.99
7.45
51002407
25325.71
4.262609
6.194.62
27026.79
5.062797
7.445.55
28958.15
6.082992
8.876.61
30889.61
7.17
065500
259615.0
3812607
6.314.70
26836.82
5.082774
7.465.56
28508.01
5.972936
8.674.46
30269.39
7.003116
10.137.55
60002832
27097.13
5.322787
7.735.76
28648.33
6.212939
8.936.66
30159.56
7.133092
10.227.62
317110.92
8.14
61002879
27307.30
5.442788
7.755.78
28648.36
6.232953
9.096.78
30139.59
7.153088
10.247.63
316410.91
8.13
087000
330415.0
3812924
8.966.68
29869.54
7.113058
10.237.63
312810.92
8.143196
11.628.66
326312.33
9.193328
13.039.72
80003776
314911.09
8.273221
11.908.87
328912.69
9.463354
13.4810.05
341914.27
10.643482
15.0811.24
354315.87
11.83
81003823
259710.09
7.522660
10.838.07
272611.64
8.682791
12.469.29
285413.27
9.892916
14.0710.49
297814.91
11.12
098500
401216.5
4192663
10.868.10
272611.66
8.692791
12.519.33
285413.36
9.962916
14.2110.59
297715.07
11.243036
15.9211.87
90004248
274811.91
8.882813
12.809.54
287613.68
10.202938
14.5810.87
299815.49
11.553057
16.3912.22
311517.28
12.88
91004295
276512.12
9.042826
12.979.67
288913.86
10.332950
14.7711.01
301015.68
11.693070
16.5912.37
312717.50
13.05
109500
448416.5
4192833
13.029.71
289513.91
10.372957
14.8511.07
301815.80
11.783076
16.7312.47
313417.68
13.183191
18.6413.90
100004720
291714.16
10.562982
15.1711.31
304416.17
12.063104
17.1512.79
316118.14
13.533217
19.1314.26
327220.11
14.99
101004767
198911.24
8.382044
12.139.04
211413.32
9.932183
14.5110.82
226415.98
11.912316
16.9512.64
327620.19
15.15
1211000
519219.5
4952055
12.529.33
210813.45
10.032173
14.6410.92
223715.87
11.832301
17.1512.79
236418.45
13.762426
19.7514.73
120005664
214014.26
10.632199
15.3811.47
225816.55
12.342318
17.8213.29
237719.13
14.262436
20.4715.26
249512.87
16.31
121005711
186913.54
10.101925
14.7210.98
198816.10
12.002051
17.5213.06
211218.95
14.132172
20.3915.20
223221.90
16.33
1413000
613621.0
5331925
14.9111.12
197816.10
12.002037
17.4713.03
209618.93
14.112155
20.4215.23
221321.96
16.372270
23.4917.51
140006608
199316.67
12.432047
17.9613.39
210219.35
14.432157
20.7915.50
221222.32
16.642267
23.8817.80
232125.47
18.99
18
ENGINEERING DATA Air Purification Unit
CFM
continued on pg.17
SWSI Fan Section/Side Discharge (shown) (Up-Blast & Straight Through Discharge options also available)
Access Panel
Hinged Access Door
Magnetic MotorStarter
X2" (51mm)
Air Flow
PLAN VIEW
2"X2" (51mmX51mm)Hanger Bracket (Typical)
Fan section inlet iscentered horizontally
Air FlowD
W
Inlet Flange is provided ONLYwhen fan sec. is installedremotely from filter section
Magnetic Motor Starters(X) Dimension
200-208
7 3/4
10 19/32
10 17/32
10 17/32
10 17/32
15 1/2
15 1/2
230-240
7 3/4
9 19/32
10 17/32
10 19/32
10 17/32
10 17/32
15 1/2
460-480
7 3/4
7 3/4
7 3/4
7 3/4
10 19/32
10 19/32
10 17/32
575-600
7 3/4
7 3/4
7 3/4
7 3/4
10 19/32
10 19/32
10 17/32
2-10 HP
15 HP
20-25 HP
30 HP
40 HP
50 HP
60-75 HP
HPVoltage
Insulation(optional)
ENGINEERING DATA Air Purification Unit
19
No. INCHES MM INCHES MM INCHES MM
01 500-1000 120 13 1/8 333 9 3/16 233 16 3/4 425
02 1100-2000 120 13 1/8 333 9 3/16 233 16 3/4 425
03 2100-3000 135 14 3/4 375 10 5/16 262 18 457
04 3100-4000 150 16 7/16 418 11 7/16 291 19 1/4 489
05 4100-5000 165 18 1/16 459 12 5/8 321 20 1/4 514
06 5100-6000 180 19 11/16 500 13 3/4 349 21 1/2 546
08 6100-8000 195 21 5/16 541 14 15/16 379 22 3/4 578
09 8100-9000 210 23 584 16 1/16 408 24 610
10 9100-10000 225 24 5/8 625 17 3/16 437 27 686
12 10100-12000 225 24 5/8 625 17 3/16 437 27 686
14 12100-14000 245 26 13/16 681 18 3/4 476 28 1/2 724
15 14100-15000 270 29 9/16 751 20 5/8 524 31 787
16 15100-16000 270 29 9/16 751 20 5/8 524 31 787
18 16100-18000 300 32 13/16 833 22 15/16 583 33 838
20 18100-20000 300 32 13/16 833 22 15/16 583 33 838
24 20100-21400 300 32 13/16 833 22 15/16 583 33 838
21500-24000 330 36 1/8 918 25 1/4 641 36 1/2 927
28 24100-28000 365 39 15/16 1014 27 7/8 708 39 1/4 997
32 28100-32000 365 39 15/16 1014 27 7/8 708 39 1/4 997
36 32100-32700 402 44 1/16 1119 30 3/4 781 42 1/2 1080
32800-36000 402 44 1/16 1119 30 3/4 781 42 1/2 1080
40 36100-40000 445 48 11/16 1237 49 1/2 1257 46 1168
APU Blower Outlet Dim.
Mod. CFM A B C
BlowerModel
No.DWDINominalNo. INCHES MM INCHES MM INCHES MM
01 500-1000 120 13 1/8 333 9 3/16 233 16 3/4 425
02 1100-2000 120 13 1/8 333 9 3/16 233 16 3/4 425
03 2100-3000 135 14 3/4 375 10 5/16 262 18 457
04 3100-4000 150 16 7/16 418 11 7/16 291 19 1/4 489
05 4100-5000 165 18 1/16 459 12 5/8 321 20 1/4 514
06 5100-6000 180 19 11/16 500 13 3/4 349 21 1/2 546
08 6100-8000 195 21 5/16 541 14 15/16 379 22 3/4 578
09 8100-9000 210 23 584 16 1/16 408 24 610
10 9100-10000 225 24 5/8 625 17 3/16 437 27 686
12 10100-12000 225 24 5/8 625 17 3/16 437 27 686
14 12100-14000 245 26 13/16 681 18 3/4 476 28 1/2 724
15 14100-15000 270 29 9/16 751 20 5/8 524 31 787
16 15100-16000 270 29 9/16 751 20 5/8 524 31 787
18 16100-18000 300 32 13/16 833 22 15/16 583 33 838
20 18100-20000 300 32 13/16 833 22 15/16 583 33 838
24 20100-21400 300 32 13/16 833 22 15/16 583 33 838
21500-24000 330 36 1/8 918 25 1/4 641 36 1/2 927
28 24100-28000 365 39 15/16 1014 27 7/8 708 39 1/4 997
32 28100-32000 365 39 15/16 1014 27 7/8 708 39 1/4 997
36 32100-32700 402 44 1/16 1119 30 3/4 781 42 1/2 1080
32800-36000 402 44 1/16 1119 30 3/4 781 42 1/2 1080
40 36100-40000 445 48 11/16 1237 49 1/2 1257 46 1168
APU Blower Outlet Dimension
Model CFM A B C
BlowerModel
No.SWSINominal
Dimension and Weight Table (continued on pg. 20)
* Weight includes Blower,Blower Cabinet, Motor &Drives
Note: All Dimensions areapproximate, refer to sub-mittal drawings for con-struction dimensions
ENGINEERING DATA Air Purification Unit
20
No. INCHES MM INCHES MM INCHES MM LBS. KG. INCHES MM INCHES MM
01 500-1000 120 38 1/4 972 52 1321 40 1016 648 294 9 229 237/8 606
02 1100-2000 120 38 1/4 972 52 1321 40 1016 648 294 21 533 237/8 606
03 2100-3000 135 38 1/4 972 52 1321 40 1016 668 303 31 787 237/8 606
04 3100-4000 150 50 1/4 1276 56 1422 44 1118 834 378 41 1041 237/8 606
05 4100-5000 165 62 1/4 1581 56 1422 44 1118 953 432 53 1346 23 7/8 606
06 5100-6000 180 50 1/4 1276 60 1524 48 1219 971 440 41 1041 34 864
08 6100-8000 195 50 1/4 1276 60 1524 58 1473 1164 528 41 1041 46 1168
09 8100-9000 210 74 1/4 1886 66 1676 58 1473 1361 617 65 1651 34 864
10 9100-10000 225 62 1/4 1581 66 1676 58 1473 1313 595 53 1346 46 1168
12 10100-12000 225 74 1/4 1886 72 1829 58 1473 1537 697 65 1651 46 1168
14 12100-14000 245 74 1/4 1886 72 1829 70 1778 1572 713 65 1651 58 1473
15 14100-15000 270 74 1/4 1886 72 1829 70 1778 1783 809 65 1651 58 1473
16 15100-16000 270 74 1/4 1886 75 1905 82 2083 1894 859 65 1651 70 1778
18 16100-18000 300 74 1/4 1886 75 1905 82 2083 2099 952 65 1651 70 1778
20 18100-20000 300 86 1/4 2191 78 1981 83 2108 2357 1069 77 1956 70 1778
24 20100-21400 300 98 1/4 2496 82 2083 83 2108 2631 1193 89 2261 70 1778
21500-24000 330 98 1/4 2496 82 2083 83 2108 2895 1313 89 2261 70 1778
28 24100-28000 365 98 1/4 2496 90 2286 95 2413 3177 1441 89 2261 82 2083
32 28100-32000 365 98 1/4 2496 90 2286 107 2718 3273 1484 89 2261 94 2388
36 32100-32700 402 110 1/2 2807 96 2438 107 2718 3960 1796 101 2565 94 2388
32800-36000 402 110 1/2 2807 96 2438 107 2718 3975 1803 101 2565 94 2388
40 36100-40000 445 122 1/4 3105 104 2642 107 2718 4750 2154 113 2870 94 2388
BlowerModel
No.SWSI
APU Fan Section Dimension Fan Section Inlet Dimension
Model CFM W L H Weight* D G
SWSI Fan Section/Side Discharge (shown) (Up-Blast & Straight Through Discharge options also available)
A (ID)
C
B (ID)
HG
3 3/8" (86mm)
3" (76mm) base frame for APU 01-APU 074" (102mm) base frame for APU 08-APU 185" (127mm) base frame for APU 20-APU 40
ELEVATION VIEW
2" (51mm)
Dimension and Weight Table (continued from pg. 19)
Nominal
141006655
160915.63
11.651661
16.9012.60
171118.20
13.571758
19.4914.53
180020.81
15.521839
22.1016.48
187823.42
17.46
1514500
684427.0
6861628
16.3212.17
168017.64
13.151730
18.9714.14
177820.31
15.141821
21.6216.12
186122.95
17.111899
24.2918.11
150007080
165417.22
12.841705
18.6213.88
175419.96
14.881802
21.3415.91
184722.70
16.931889
24.1017.97
192725.45
18.98
151007127
165517.30
12.901705
18.6813.93
175520.06
14.961803
21.4515.99
184822.78
16.991891
24.2118.05
192925.56
19.06
1615500
731627.0
6861677
18.0613.47
172519.47
14.521774
20.8915.58
182122.28
16.611867
23.6817.66
191125.13
18.741951
26.5319.78
160007552
170619.08
14.231752
20.5115.29
179921.97
16.381846
23.4117.45
189224.88
18.551936
26.3219.62
197427.66
20.62
161007599
138317.71
13.201425
19.1914.31
146520.67
15.411503
22.1516.52
154123.67
17.651578
25.2218.80
161526.80
19.98
1817000
802430.0
7621416
19.2214.33
146020.82
15.521500
22.3916.69
153823.93
17.841574
25.4518.98
161027.05
20.171646
28.6821.38
180008496
145521.06
15.701499
22.7616.97
154024.44
18.221578
26.0719.44
161527.75
20.691650
29.3821.91
168431.04
23.14
181008543
145220.99
15.651496
22.6816.91
153824.40
18.191577
26.0719.44
161327.70
20.651648
29.3321.87
168331.05
23.15
2019000
896830.0
7621488
22.7816.98
153224.59
18.331573
26.3319.63
161328.14
20.981650
29.8422.26
168531.57
23.541719
33.3224.84
200009440
152724.86
18.541570
26.7119.91
161128.55
21.291651
30.4522.70
168832.25
24.051725
34.1625.47
175835.94
26.80
201009487
30.0762
152324.74
18.451567
26.6319.86
160828.46
21.221648
30.3622.64
168632.21
24.021723
34.1125.43
175735.95
26.80
2421400
1010130.0
7621570
27.5320.53
161529.50
22.001655
31.4023.41
169533.43
24.931733
35.4326.42
177037.46
27.931805
39.4429.41
2150010148
33.0838
131124.75
18.451350
26.7119.91
138728.67
21.381422
30.6522.85
145532.58
24.291488
34.6225.81
151936.60
27.29
2400011328
33.0838
138329.64
22.401422
31.8423.74
154934.06
25.401495
36.3127.07
153038.61
28.791562
40.7930.41
159343.01
32.07
2410011375
112824.84
18.521167
26.9520.09
120329.08
21.681237
31.3223.35
126933.58
25.041301
35.9526.80
133338.39
28.62
2826300
1241436.5
9271170
28.4921.24
120730.74
22.921243
32.9524.57
127935.33
26.341312
37.6928.10
134340.14
29.931373
42.6431.79
2640012461
117228.67
21.381208
30.8623.01
124533.16
24.721281
35.5426.50
131437.89
28.251345
40.3530.08
137542.85
31.95
2800013216
120731.70
23.641241
34.0325.37
127536.35
27.101310
38.8128.94
134341.20
30.721376
43.7632.63
140646.25
34.48
2810013263
120531.60
23.561239
33.9525.31
127336.29
27.061308
38.7628.90
134141.15
30.681374
43.6832.57
140546.22
34.46
3230000
1416036.5
9271248
35.3926.39
127937.87
28.241311
40.4030.12
134342.90
31.991376
45.4733.90
140848.05
35.831439
50.6437.76
3200015104
129739.84
29.701326
42.4831.67
135545.08
33.611385
47.7835.62
141550.46
37.621445
53.1339.61
147555.83
41.63
3210015151
106234.72
25.891095
37.4127.89
112840.18
29.961160
43.0132.07
119045.80
34.151218
48.7636.36
124651.89
38.69
3632700
1543440.25
10221070
35.6926.61
110438.57
28.761136
41.3130.80
116844.14
32.911199
47.0935.11
122750.02
37.291254
53.0639.56
3280015482
107235.92
26.781105
38.7228.87
113841.58
31.001169
44.3033.03
120047.26
35.241229
50.3037.50
125643.34
39.77
3600016992
116242.27
31.521155
45.2233.72
118448.19
35.931214
51.2638.22
124454.39
40.551273
57.4342.82
130160.55
45.15
3610017039
92937.34
27.84961
40.5330.22
99143.78
32.641018
47.0235.06
104550.51
37.661071
54.0240.28
109757.59
42.94
4039700
1873844.5
1130967
43.4432.39
99846.91
34.981027
50.2437.46
105653.75
40.081082
57.0442.53
110860.76
45.301133
64.5548.13
3980018786
96843.60
32.51999
47.0935.11
102850.44
37.611057
53.9540.23
108357.24
42.681109
60.9545.44
113464.75
48.28
4000018880
97244.14
32.911001
47.4435.37
103150.96
38.001059
54.3540.52
108757.92
43.191113
61.6545.97
113765.31
48.70
ENGINEERING DATA Air Purification UnitE
nviro
nA
ir®
SW
SI F
an
Air P
erfo
rman
ce T
ab
le
21
Notes:
(1) APU
sizes shown are the standard blow
er/cabinet combinations, C
MI reserves the right to change those com
binations to accomm
odate job specifications.(2) For S
tatic pressures not shown please contact C
MI
(3) Break horsepow
er (BH
P) includes drive losses*
SW
SI-H
igh Pressure Blow
er is utilized# S
tatic pressure shown is for units w
ithout Media trays. W
hen Media Trays are specified, increase E.S
.P. by 0.375” w.g. before using the table for your fan selection.
continued from pg.22
AP
U
Exh
au
st R
ate
Wh
eel D
ia.
EX
TE
RN
AL S
TA
TIC
PR
ES
SU
RE
#
Mo
del
1.5
0"W
.G./0
.372 K
Pa
2.0
0"W
.G./0
.496 K
Pa
2.5
0"W
.G./0
.620 K
Pa
3.0
0"W
.G./0
.745 K
Pa
3.5
0"W
.G./0
.869 K
Pa
4.0
0"W
.G./0
..993 K
Pa
4.5
0"W
.G./0
.1.1
2 K
Pa
No.
Nom
inalL/S
ec
INM
MR
PM
BH
PK
WR
PM
BH
PK
WR
PM
BH
PK
WR
PM
BH
PK
WR
PM
BH
PK
WR
PM
BH
PK
WR
PM
BH
PK
W
01500*
23612.0
3053158
0.93 .69
32721.03
0.773383
1.130.85
34881.25
0.923592
1.341.00
36931.45
1.08----
--------
1000*472
36161.37
1.023711
1.481.10
38041.59
1.193896
1.711.28
39851.83
1.374073
1.961.46
41602.09
1.56
1100*519
37681.52
1.133857
1.641.22
39441.76
1.314030
1.881.40
41152.01
1.504198
2.141.59
42822.27
1.69
021500*
70812.0
3054639
2.63 1.96
47102.78
2.074780
2.942.19
48503.1
2.314919
3.262.43
59883.42
2.555056
3.592.67
2000944
36172.70
2.023711
2.932.18
38043.15
2.353896
3.392.53
39853.63
2.704072
3.872.88
41594.11
3.07
2100991
29142.57
1.923008
2.832.11
31003.09
2.303191
3.362.51
32813.64
2.713368
3.922.92
34514.2
3.13
032500
118013.5
3433176
3.29 2.45
32613.56
2.663344
3.842.86
34274.13
3.083506
4.433.30
35854.74
3.533663
5.053.77
30001416
35404.41
3.293614
4.743.53
36885.06
3.773761
5.404.02
38325.72
4.273902
6.064.52
39376.40
4.77
31001463
26173.53
25.632703
3.852.87
27874.18
3.122872
4.533.38
29564.88
3.643037
5.233.90
31185.59
4.17
043500
165215.0
3812774
4.20 3.13
28504.55
3.392925
43.913.66
30005.27
3.933075
5.644.21
31506.02
4.493225
6.404.77
40001888
30015.26
3.923069
5.654.21
31366.04
4.503203
6.444.80
32036.44
4.803334
7.245.40
34007.66
5.71
41001935
24814.83
3.602552
5.253.91
26235.67
4.232694
6.114.56
27646.55
4.882834
7.005.22
29047.46
5.56
054500
212416.5
4192613
5.62 4.19
26786.06
4.522742
6.504.85
28076.97
5.192871
7.435.54
29357.90
5.893000
8.396.26
50002360
27826.72
5.012842
7.195.36
29027.68
5.732960
8.166.08
30188.65
6.453077
9.156.82
31359.66
7.20
51002407
22085.65
4.212279
6.174.6
23466.71
5.002419
7.265.41
24867.81
5.822552
8.376.24
26178.93
6.66
065500
259618.0
4572287
6.30 4.69
23546.84
5.102420
7.405.51
24867.97
5.942551
8.556.38
26159.14
6.822678
9.757.27
60002832
23907.19
5.362454
7.775.79
25168.35
6.232578
8.956.68
26399.56
7.132699
10.177.58
275910.81
8.06
61002879
20476.71
5.002112
7.335.47
21767.97
5.942239
8.616.42
23029.28
6.922362
9.937.40
242210.59
7.90
087000
330419.5
4952190
8.25 6.15
22508.92
6.652308
9.67.16
236510.29
7.672422
11.008.20
247811.73
8.750533
12.479.30
80003776
236610.37
7.732420
11.098.27
247311.83
8.822524
12.579.37
257613.34
9.952327
14.1110.52
267714.91
11.12
81003823
20369.57
7.142091
10.347.71
214511.13
8.302198
11.948.90
225112.78
9.532303
13.6110.15
235514.48
10.80
098500
401221.0
5332089
10.33 7.70
214211.12
8.292194
11.938.90
224612.78
9.532297
13.6210.16
234714.48
10.802397
15.3711.46
90004248
215911.40
8.502210
12.239.12
226013.06
9.742310
13.9210.38
235914.8
110.32407
15.6911.70
245516.59
12.37
91004295
188110.64
7.931933
11.528.59
198412.43
9.272034
13.359.95
208414.28
10.652133
15.2411.36
218116.21
12.09
109500
448422.5
5721923
11.38 8.48
197412.29
9.162023
13.29.84
207214.14
10.542120
15.1011.26
216816.09
12.002215
17.0812.73
100004720
197812.39
9.232027
13.339.94
207514.26
10.632122
15.2311.36
216916.23
12.102214
17.2512.86
226018.25
13.61
101004767
197912.41
9.252027
13.339.94
207514.27
10642122
15.2411.36
216816.23
12.102214
17.2312.85
225918.25
13.61
1211000
519222.5
5722079
14.36 10.71
212615.37
11.462171
16.3712.21
221517.36
12.942259
18.413.72
230219.46
14.52345
20.5115.29
120005664
220217.01
12.682246
18.0713.47
228919.15
14.282331
20.2215.08
237321.34
15.912414
22.4316.72
245323.53
17.54
121005711
18.9115.18
11.321936
16.312.15
197917.41
12.982020
18.5313.82
206119.66
14.662101
20.7915.50
214021.89
16.32
1413000
613624.5
6221968
17.11 12.76
201518.34
13.672058
19.5314.56
209920.74
15.462139
21.9716.38
217723.15
17.262144
24.3518.16
140006608
204719.52
14.552102
20.8815.57
214922.24
16.582190
23.5117.53
223024.83
18.512367
26.0919.45
230427.41
20.44
En
viro
nA
ir®
SW
SI F
an
Air P
erfo
rman
ce T
ab
leENGINEERING DATA Air Purification Unit
CFM
22
continued on pg.21
EXHAUST FAN SUPPLY VOLTAGES
TYPE - 1(INDOOR) OR TYPE- 3R (OUTDOOR)BLOWER MAG. MOTOR STARTERLOCATED ON SIDE OF BLOWER UNIT
208VAC/3PH/60HZ
208VAC/3PH/50HZ
380VAC/3PH/50HZ
230VAC/3PH/60HZ
460VAC/3PH/60HZ
575VAC/3PH/60HZ
OR
XY
C
Z7A
6A
DISCONN
ECTSW
ITCH
FI
MI
M
0/L
EXHAUST FANOPTION
ALCOM
BINATION
STARTER
SEE NOTE 1
AC
D S
TAT
US
PA
NE
L (RE
MO
TE
LY LO
CA
TE
D)
AIR
MO
NITO
R C
AB
NET
(LOC
ATED O
N S
IDE O
F AP
U)
SEE NOTE 2
SEE NOTE 3
SEE NOTE 4
SEE NOTE 5
1415161721222324
1415161721222324 7 G86A7A9101112
FANON
/OFF
LOWAIR
FILTEROUT
CONTROL
BYPASS
FIRE
RESET
NIL
AIR
NORM
AL
REPLACEBAG
FILTERS
REPLACEBOX
FILTERS
REPLACEPRE
FILTERS
CONTROL FUSE2 AMP
FIRE TESTSWITCH
SUPPLY FUSE8 AMP
CONTROLBYPASS SWITCH
G
1)Pow
er supply from building @
15 AM
PS, 24 hour
uninterrupted, standardly 120 VAC
/1PH/60H
Z, oroptionally 220 VA
C/1PH
/60HZ, three (3) w
ire service(by electrical contractor).
2)#6A
& #7A
for 120 VAC
live output to optional combi-
nation starter fused internally @ 8 A
MPS
.
3) #9 & #10 are voltage free N
. O. contacts for building fire
alarm system
s, monitoring system
, etc. when required
(by electrical contractor).
GE
NE
RA
L A
CD
NO
TE
S
4)O
ptional wiring to hood m
ounted damper m
icroswitch(es) or ther-
mostat probe(s).
5)8 w
ires for 24 VAC
controls between the A
PU S
tatus Panel termi-
nals and the Air M
onitor Cabinet term
inals (by electrical contrac-tor).
6)The exhaust fan starter/contactor coil and integral control trans-form
er voltage must m
atch that of the AC
D status panel.
7)A
ll external control wiring shall be 12 G
A. m
inimum
or as perapplicable codes.
FIG
UR
E 7
STA
ND
AR
D W
IRIN
G D
IAG
RA
M F
OR
AP
U U
NIT
WIT
H A
CD
STA
TU
SPA
NE
L (B
AS
IC U
NIT
)
(SH
OW
N W
ITH
OP
TIO
NA
L C
OM
BIN
AT
ION
MA
GN
ET
IC M
OT
OR
STA
RT
ER
PA
NE
L)
Project wiring m
ay be different - refer to project drawings
NO
TE:- - - - -
BR
OK
EN LIN
ES IN
DIC
ATE W
IRIN
G B
Y
ELECTR
ICA
L CO
NTR
AC
TOR
SO
LID LIN
ESIN
DIC
ATE FA
CTO
RY
WIR
ING
ALL R
EQU
IRED
ELECTR
ICA
L FITTING
S TO
BE S
UP-
PLIED B
YELEC
TRIC
AL
CO
NTR
AC
TOR
23
SEE NOTE 1
AC
D S
TAT
US
PA
NE
L (RE
MO
TE
LY LO
CA
TE
D)
AIR
MO
NITO
R C
AB
NET
(LOC
ATED O
N S
IDE O
F AP
U)
SEE NOTE 2
SEE NOTE 3
SEE NOTE 4
OPTIIONAL (SEE NOTE 6)
OPTIIONAL (SEE NOTE 7)
OPTIIONAL (SEE NOTE 8)
OPTIIONAL (SEE NOTE 9)
OPTIIONAL (SEE NOTE 10)
OPTIIONAL (SEE NOTE 11)
OPTIIONAL (SEE NOTE 12)
OPTIIONAL (SEE NOTE 13)
OPTIIONAL (SEE NOTE 14)SEE NOTE 5
1415161721222324
1415161721222324 7 G86A7A
6A5AM
P
7A
9101112
5758596061626333 32 8A8B1545484950515253545556
FANON
/OFF
LOWAIR
FILTEROUT
CONTROL
BYPASS
FIRE
RESET
NIL
AIR
NORM
AL
REPLACEBAG
FILTERS
REPLACEBOX
FILTERS
REPLACEPRE
FILTERS
CONTROL FUSE2 AMP
FIRE TESTSWITCH
SUPPLY FUSE8 AMP
CONTROLBYPASS SWITCH
OPTIONAL ODOR SPRAY CABIN
ET(LOCATED ON
SIDE OF APU)
EXHAUST FAN SUPPLY VOLTAGES
TYPE - 1 (INDOOR) OR TYPE- 3R (OUTDOOR)BLOWER MAG. MOTOR STARTERLOCATED ON SIDE OF BLOWER UNIT
208VAC/3PH/60HZ
208VAC/3PH/50HZ
380VAC/3PH/50HZ
230VAC/3PH/60HZ
460VAC/3PH/60HZ
575VAC/3PH/60HZ
OR
XY
Z32
33
DISCONN
ECTSW
ITCH
FI
9695M
I
M
M
EXHAUST FANOPTION
AL COMBIN
ATION STARTER
AND "H.O.A." SW
ITCH OPTION
0/LFU1
SEC.
PRI
A1 A2
"HDA" SWITCH
HANDOFF
AUTO
3436G
2AMP
SEE NOTE 15
OPTIONAL ODOR SPRAY
CABINET HEATER
(LOCATED INSIDE SPRAY CABIN
ET)
FUSE
FUSE
LOWODORSPRAY
SILENCE
BUZZERLOW
ODORBUZZER
G
FIG
UR
E 8
STA
ND
AR
D W
IRIN
G D
IAG
RA
M F
OR
AP
U U
NIT
WIT
H A
CD
STA
TU
S P
AN
EL (D
ELU
XE
UN
IT)
(SH
OW
N W
ITH
TH
EO
PT
ION
AL
CO
MB
INA
TIO
NM
AG
NE
TIC
MO
TO
R S
TA
RT
ER
PA
NE
L W
ITH
H.O
.A.
SW
ITC
HO
PT
ION
, AN
DO
PT
ION
AL O
DO
R S
PR
AY
CA
BIN
ET
AN
D C
AB
INE
T H
EA
TE
R)
Project wiring m
ay be different - refer to project drawings
1.Pow
er supply from building @
15 AM
PS, 24 hour uninterrupted,
standardly 120 VAC
/1PH/60H
Z, or optionally 220 VAC
/1 PH/60 H
Z,three (3) w
ire service (by electrical contractor).2.
#6A &
#7A for 120 VA
C live output to optional odor cabinet, fused
internally @ 8 A
MPS
.3.
#9 & #10 are voltage free N
.O. contacts for building fire alarm
sys-tem
s, monitoring system
, etc. when required (by electrical contrac-
tor).4.
Optional w
iring to hood mounted dam
per microsw
itch(es) or ther-m
ostat probe(s).5.
8 wires for 24 VA
C controls betw
een the APU
Status Panel term
inalsand the A
ir Monitor C
abinet terminals (by electrical contractor).
6.R
eserved for AC
W unit only.
7.#15 &
#45 are optional terminals for the LO
W LIQ
UID
FLOA
T switch,
this wiring goes from
the AC
D status panel term
inals to the match-
ing odor spray cabinet terminals (by electrical contractor).
8.#48 &
#49 are optional terminals for LO
W O
DO
R S
PRA
Y to the
building monitor (by electrical contractor).
9.#50 &
#51 are optional terminals for FILTER
OU
T to the buildingm
onitor (by electrical contractor).10.
#52 & #53 are optional term
inals for NIL A
IR to the building m
onitor(by electrical contractor).
GE
NE
RA
L A
CD
NO
TE
S11.
#54 & #55 are optional term
inals for LOW
AIR
to the buildingm
onitor (by electrical contractor).12.
#56 & #57 are optional term
inals for FAN
STA
TUS
to the buildingm
onitor (by electrical contractor).13.
#58 & #59 are optional term
inals for REPLA
CE PR
E-FILTERS
, #60&
#61 are optional terminals for R
EPLAC
E BA
G FILTER
S, #62 &
#63 are optional terminals for R
EPLAC
E BO
X FILTER
S, to the
building monitoring system
(by electrical contractor).14.
#32 & #33 are optional term
inals for “H.O
.A.” feature (by electri-
cal contractor).The sequence of operation is as follow
s:A
. H
AN
D PO
SITIO
N = m
anually turns on the exhaust fanregardless of the A
PU m
onitoring controls.B
. O
FF POS
ITION
= both the exhaust fan and APU
are shutoff.
C.
AU
TOM
ATIC
POS
ITION
= the internal step-down control
transformer built into the com
bination starter will furnish
power to the exhaust fan starter coil only after the A
PUA
CD
status panel has closed the appropriate relay contactset. The exhaust fan w
ill continue to run until the AC
D sta-
tus panel opens the relay contact set.15.
Optional pow
er supply from building @
15 amps, 24 hour unin-
terrupted, 120VAC
/1 PH/60 H
Z, to terminals #34 (line), #36 (neu-
tral), and G (ground), three (3) w
ire service (by electrical contrac-
tor).N
ote: Required w
hen the optional cabinet heater isfurnished inside the odor spray cabinet.
16.The exhaust fan starter/contactor coil and integralcontrol transform
er voltage must m
atch that of theA
CD
status panel.17.
All external control w
iring shall be 12 GA
. minim
umor as per applicable codes.
NO
TE:
- - - - -B
RO
KEN
LINES
IND
ICA
TE WIR
ING
BY
ELECTR
ICA
L CO
NTR
AC
TOR
SO
LID LIN
ESIN
DIC
ATE FA
CTO
RY
WIR
ING
ALL R
EQU
IRED
ELECTR
ICA
L FITTING
S TO
BE S
UP-
PLIED B
YELEC
TRIC
AL
CO
NTR
AC
TOR
24
EXHAUST FAN SUPPLY VOLTAGES
TYPE- 1 (INDOOR) OR TYPE- 3R (OUTDOOR)BLOWER MAG. MOTOR STARTERLOCATED ON SIDE OF BLOWER UNIT
208VAC/3PH/60HZ
208VAC/3PH/50HZ
380VAC/3PH/50HZ
230VAC/3PH/60HZ
460VAC/3PH/60HZ
575VAC/3PH/60HZ
OR
XY
Z7A
6A
DISCONN
ECTSW
ITCH
FI
MI
M
0/L
EXHAUST FANOPTION
ALCOM
BINATION
STARTER
SEE NOTE 1
AC
W S
TAT
US
PA
NE
L (RE
MO
TE
LY LO
CA
TE
D)
AIR
MO
NITO
R C
AB
NET
(LOC
ATED O
N S
IDE O
F AP
U)
SEE NOTE 2
SEE NOTE 3
SEE NOTE 4
SEE NOTE 5
1415161721222324
1415161721222324 7 G86A7A9101112
FANON
LOWAIR
FILTEROUT
CONTROL
BYPASS
FIRE
RESET
NIL
AIR
NORM
AL
REPLACEBAG
FILTERS
REPLACEBOX
FILTERS
REPLACEPRE
FILTERS
CONTROL FUSE2 AMP
FIRE TESTSWITCH
SUPPLY FUSE8 AMP
CONTROLBYPASS SWITCH
C
G
1)Pow
er from w
ash control panel, 120 VAC
/1PH/60H
Z, fromterm
inals #8 (Line), #7 (Neutral), and G
(Ground) to the
matching A
PU term
inals (by electrical contractor).
2)#6A
& #7A
for 120 VAC
live output to optional combina-
tion starter, fused internally @ 8 A
MPS
.
3) #9 & #10 are voltage free N
. O. contacts for building fire
alarm system
s, monitoring system
, etc. when required
(by electrical contractor).
4)O
ptional wiring to hood m
ounted damper
GE
NE
RA
L A
CW
NO
TE
S
microsw
itch(es) or thermostat probe(s).
5)8 w
ires for 24 VAC
controls between the A
PU S
tatus Panel termi-
nals and the Air M
onitor Cabinet term
inals (by electrical contrac-tor).
6)The exhaust fan starter/contactor coil and integral control trans-form
er voltage must m
atch that of the AC
W status panel.
7)A
ll external control wiring shall be 12G
A. m
inimum
or as perapplicable codes.
FIG
UR
E 9
STA
ND
AR
D W
IRIN
G D
IAG
RA
M F
OR
AP
U U
NIT
AC
W S
TA
TU
S P
AN
EL (B
AS
IC U
NIT
)
(SH
OW
N W
ITH
TH
EO
PT
ION
AL C
OM
BIN
AT
ION
MA
GN
ET
IC M
OT
OR
STA
RT
ER
PA
NE
L)
Project wiring m
ay be different - refer to project drawings
NO
TE:
- - - - -B
RO
KEN
LINES
IND
ICA
TE WIR
ING
BY
ELECTR
ICA
L CO
NTR
AC
TOR
SO
LID LIN
ESIN
DIC
ATE FA
CTO
RY
WIR
ING
ALL R
EQU
IRED
ELECTR
ICA
L FITTING
S TO
BE S
UP-
PLIED B
YELEC
TRIC
AL
CO
NTR
AC
TOR
25
SEE NOTE 1
AC
W S
TAT
US
PA
NE
L (RE
MO
TE
LY LO
CA
TE
D)
AIR
MO
NITO
R C
AB
NET
(LOC
ATED O
N S
IDE O
F AP
U)
SEE NOTE 2
SEE NOTE 3
SEE NOTE 4
OPTIIONAL (SEE NOTE 6)
OPTIIONAL (SEE NOTE 7)
OPTIIONAL (SEE NOTE 8)
OPTIIONAL (SEE NOTE 9)
OPTIIONAL (SEE NOTE 10)
OPTIIONAL (SEE NOTE 11)
OPTIIONAL (SEE NOTE 12)
OPTIIONAL (SEE NOTE 13)
OPTIIONAL (SEE NOTE 14)SEE NOTE 5
1415161721222324
1415161721222324 7 G86A7A9101112
5758596061626333 32 8A8B1545484950515253545556
FANON
LOWAIR
FILTEROUT
CONTROL
BYPASS
FIRE
RESET
NIL
AIR
NORM
AL
REPLACEBAG
FILTERS
REPLACEBOX
FILTERS
REPLACEPRE
FILTERS
CONTROL FUSE2 AMP
FIRE TESTSWITCH
SUPPLY FUSE8 AMP
CONTROLBYPASS SWITCH
EXHAUST FAN SUPPLY VOLTAGES
TYOE-1 (INDOOR) OR TYPE-3R (OUTDOOR)BLOWER MAG. MOTOR STARTERLOCATED ON SIDE OF BLOWER UNIT
208VAC/3PH/60HZ
208VAC/3PH/50HZ
380VAC/3PH/50HZ
230VAC/3PH/60HZ
460VAC/3PH/60HZ
575VAC/3PH/60HZ
OR
XY
Z32
33
DISCONN
ECTSW
ITCH
FI
9695M
I
M
M
EXHAUST FANOPTION
AL COMBIN
ATION STARTER
AND "H.O.A." SW
ITCH OPTION
0/LFU1
SEC.
PRI
A1 A2
"HDA" SWITCH
HANDOFF
AUTO
6A5AM
P
7A
OPTIONAL ODOR SPRAY CABIN
ET(LOCATED ON
SIDE OF APU)
3436G
2AMP
SEE NOTE 15
OPTIONAL ODOR SPRAY
CABINET HEATER
(LOCATED INSIDE SPRAY CABIN
ET)
FUSE
FUSE
LOWODORSPRAY
SILENC E
BUZZERLOW
ODORBUZZER
G
FIG
UR
E 1
0 S
TA
ND
AR
D W
IRIN
G D
IAG
RA
M F
OR
AP
U U
NIT
WIT
H A
CW
STA
TU
S P
AN
EL (D
ELU
XE
UN
IT)
(SH
OW
N W
ITH
TH
EO
PT
ION
AL C
OM
BIN
AT
ION
MA
GN
ET
IC M
OT
OR
STA
RT
ER
PA
NE
L W
ITH
H.O
.A. S
WIT
CH
OP
TIO
N, A
ND
OP
TIO
NA
L O
DO
R S
PR
AY
CA
BIN
ET
AN
D C
AB
INE
T H
EA
TE
R)
Projectw
iring may be different - refer to project draw
ings
1.Pow
er supply from w
ash control panel, 120 VAC
/1 PH/ 60 H
Z fromterm
inals #8 (line), #7 (neutral), and G (ground) to the m
atchingA
PU term
inals (by electrical contractor).2.
#6A &
#7A for 120 VA
C live output to optional odor cabinet, fused
internally @ 8 A
MPS
.3.
#9 & #10 are voltage free N
.O. contacts for building fire alarm
sys-tem
s, monitoring system
, etc. when required (by electrical contrac-
tor).4.
Optional w
iring to hood mounted dam
per microsw
itch(es) or ther-m
ostat probe(s).5.
8 wires for 24 VA
C controls betw
een the APU
Status Panel term
i-nals and the A
ir Monitor C
abinet terminals (by electrical contrac-
tor).6.
Optional rem
ote APU
ON
/OFF control, rem
ove factory jumper and
install remote m
aintained ON
/OFF sw
itch across terminals #8A
B
(by electrical contractor).7.
#15 & #45 are optional term
inals for the LOW
LIQU
ID FLO
AT
switch, this w
iring goes from the A
CW
status panel terminals to
the matching odor spray cabinet term
inals (by electrical contrac-tor).
8.#48 &
#49 are optional terminals for LO
W O
DO
R S
PRA
Y to the
building monitor (by electrical contractor).
GE
NE
RA
L A
CW
NO
TE
S9.
#50 & #51 are optional term
inals for FILTERO
UT to the building
monitor (by electrical contractor).
10.#52 &
#53 are optional terminals for N
IL AIR
to the building moni-
tor (by electrical contractor).11.
#54 & #55 are optional term
inals for LOW
AIR
to the building mon-
itor (by electrical contractor).12.
#56 & #57 are optional term
inals for FAN
STA
TUS
to the buildingm
onitor (by electrical contractor).13.
#58 & #59 are optional term
inals for REPLA
CE PR
E-FILTERS
,#60 &
#61 are optional terminals for R
EPLAC
E BA
G FILTER
S,
#62 & #63 are optional term
inals for REPLA
CE B
OX
FILTERS
,to the building m
onitoring system(by electrical contractor).
14.#32 &
#33 are optional terminals for “H
.O.A
.” feature (by electricalcontractor).The sequence of operation is as follow
s:A
. H
AN
D PO
SITIO
N = m
anually turns a on the exhaust fanregardless of the A
PU m
onitoring controls.B
. O
FF POS
ITION
= both the exhaust fan and APU
are shut off.C
. A
UTO
MA
TIC PO
SITIO
N = the internal step-dow
n control trans-form
er built into the combination starter w
ill furnish power to
the exhaust fan starter coil only after the APU
AC
W status
panel has closed the appropriate relay contact set. The exhaustfan w
ill continue to run until the AC
W status panel opens the
relay contact set.
15.O
ptional power supply from
building @ 15 am
ps, 24hour uninterrupted, 120VA
C/1 PH
/60 HZ, to term
inals#34 (line), #36 (neutral), and G
(ground), three (3) wire
service (by electrical contractor).N
ote: Required w
hen the optional cabinet heater isfurnished inside the odor spray cabinet.
16.The exhaust fan starter/contactor coil and integral con-trol transform
er voltage must m
atch that of the AC
Wstatus panel.
17.A
ll external control wiring shall be 12 G
A. m
inimum
oras per applicable codes.
NO
TE:
- - - - -B
RO
KEN
LINES
IND
ICA
TE WIR
ING
BY
ELECTR
ICA
L CO
NTR
AC
TOR
SO
LID LIN
ESIN
DIC
ATE FA
CTO
RY
WIR
ING
ALL R
EQU
IRED
ELECTR
ICA
L FITTING
S TO
BE S
UP-
PLIED B
YELEC
TRIC
AL
CO
NTR
AC
TOR
26
27
ENGINEERING NOTES Air Purification Unit
CATEGORY AMCA STANDARD /
ENGLISH UNIT x CONVERSION
FACTOR = METRIC (SI) UNIT
VOLUME FLOW CFM 0.00047195 cu. meter per sec. (m 3/s)PRESSURE Inches (wg) 248.84 pascal (Pa or N/m 2)POWER H.P. 745.7 watt (W or J/s)TEMPERATURE Fahrenheit ( ° F) (° F - 32°) ÷ 1.8 celsiusHEAT Btu 1.055 kilojoules (kj)TIP SPEED ft/min 0.00508 meter per second (m/s)SPEED RPM 0.016 rev. per second (rps)VELOCITY ft/min 0.00508 meter per second (m/s)DIMENSIONS Inches 25.4 millimeter (mm)
Feet 0.3048 meter (m)Square Feet 0.0929 square meter (m2)Cubic Feet 0.0283 cubic meter (m3)
METRIC EQUIVALENTS
Many Carroll products are specified and installedoverseas. For your convenience, the table belowprovides conversion factors from English to Metric.
FAN LAWS
The following section includes engineering andtechnical data, guidelines and systemexplanations related to air moving and control
devices. Fan laws and system descriptions areconsistent with industry standards, definitions andaccepted practices. This information is provided toassist system designers in sizing, selecting anddefining their air moving and control systems as wellas explaining variables inherent in system design.
Of nine basic fan laws, four are of prime importanceto the understanding of ventilation systems. These,together with an appreciation of fan types, shouldhelp avoid most problems which cause poor airflowperformance. These four laws assume the same fanoperating with air at a constant density.
1. Airflow and fan speed are directly proportional.
CFM1 is the original flow rate in cu. ft. per minute.CFM2 is the desired flow rate in cu. ft. per minute.RPM1 is the original rotational speed of the fan.RPM2 is the desired rotational speed of the fan.
2. Pressure varies as the square of the speed orairflow.
P1 is the original static pressure.P2 is the desired static pressure.
3. Power varies as the cube of fan speed.
4. Fan Tip speed (FPM):Where T.S. =(D (in) X RPM X π)/12
D = Wheel Diameterπ = 3.14
EFFECT OF CHANGE IN DENSITY,
ALTITUDE AND TEMPERATURE
CORRECTIONS FACTORS
The resistance of a duct system is dependent on thedensity of the gas flowing through the system. A gasdensity of 0.075 lb/ft3 is standard in the fan industry.
The pressure and horsepower vary directly as theratio of the gas density at the fan inlet to standard
CFM2 RPM2
CFM1 RPM1=
P RPMP RPM
2
1
2
1
=
2P CFMP CFM
2
1
2
1
=
2
BHP RPMBHP RPM
2
1
2
1
=
3
ALTITUDE (FEET) WITH BAROMETRIC PRESSURE (Inches Hg)
0' 500' 1000' 1500' 2000' 2500' 3000' 3500' 4000' 4500' 500029.2 29.38 28.86 28.33 27.82 27.31 26.82 26.32 25.84 25.36 24.90
TEMP.°F
-40
0
40
70
80
100
120
140
160
180
200
250
300
350
400
.79 .81 .82 84 .85 .87 .88 .90 .92 .93 .95
.87 .88 .90 .92 .93 .95 .97 .99 1.00 1.02 1.04
.94 .96 .98 1.00 1.01 1.03 1.05 1.07 1.09 1.11 1.13
1.00 1.02 1.04 1.06 1.08 1.10 1.12 1.14 1.16 1.18 1.20
1.02 1.04 1.06 1.08 1.10 1.12 1.14 1.16 1.18 1.20 1.22
1.06 1.08 1.10 1.12 1.14 1.16 1.18 1.20 1.22 1.25 1.27
1.09 1.11 1.13 1.16 1.18 1.20 1.22 1.24 1.27 1.29 1.31
1.13 1.15 1.17 1.20 1.22 1.24 1.26 1.29 1.31 1.34 1.36
1.17 1.19 1.21 1.24 1.26 1.28 1.31 1.33 1.35 1.38 1.41
1.21 1.23 1.25 1.28 1.30 1.32 1.35 1.37 1.40 1.42 1.45
1.25 1.27 1.29 1.32 1.34 1.36 1.39 1.42 1.44 1.47 1.50
1.34 1.36 1.39 1.41 1.44 1.47 1.49 1.52 1.55 1.58 1.61
1.43 1.43 1.49 1.51 1.54 1.57 1.60 1.63 1.66 1.69 1.72
1.53 1.56 1.58 1.61 1.64 1.67 1.70 1.74 1.77 1.80 1.84
1.62 1.65 1.68 1.71 1.75 1.78 1.81 1.84 1.88 1.91 1.95
CORRECTION FACTORS
Unity Basis = Standard Air Density of 0.075 lb/ft3
At sea level (29.92 in. Hg barometric pressure) this isequivalent to dry air at 70°F.
Horsepower at standard �correction factor = horse-power at operating condition. Motors should be sizedfor highest density conditions at which they areexpected to operate.
density. This density ratio must always be consideredwhen selecting fans. To select a fan, pressure shouldbe corrected to standard air density, 0.075 lb/ft3, 70°at sea level. Static pressure at operating condition xcorrection factor = static pressure at standard. Referto Correction Factors Table below.
28
ENGINEERING NOTES Air Purification Unit
SOUND POWER LEVELS
Since any mechanical device generates some soundenergy into the air, fans will create some noise.Because of the great number of factors influencing
sound output it is invalid to compare fans based on RPM,tip speed or outlet velocity. The only accurate basis ofcomparison is the sound power level generated by the fanat the required point of operation.
Having sound power levels for a specific fan at a specificoperating point allows the system designer to determinethe theoretical sound pressure level at any point in theoccupied space. AMCA Publication 303 and the ASHRAEGuides provide more information on this process. Anothertypical application of sound power levels is to comparesimilar fans. Generally differences of 6 dB in the 63 Hz bandand 3 dB in all other bands are considered insignificant.
System designers use many methods to predict acousticacceptability of an occupied space.
The A-weighted sound pressure level provides a singlenumber that corresponds well to the human judgement ofrelative loudness. OSHA bases their requirementsregarding exposure to noise on A-weighted sound pressurelevels. The disadvantage of this method is that A-weightedsound pressure levels do not provide information as to thequality of the sound. Noise Criteria (NC) curves are alsowidely used. To determine the NC level, the sound powerspectrum is compared to defined limits.
Each method relies on sound pressure level informationbecause the human ear “hears” sound pressurefluctuations, not sound power (watts). Sound pressure is afunction of the attenuation of the space and the distancefrom the source. Consider a 100 watt light bulb. It providesadequate light for a closet, but not for a classroom, and ina stadium it would be imperceptible. While the light sourcewas the same power (100 watts), the brightness levelchanged dramatically. Similarly, the same sound powerlevel (acoustical energy) produces greatly different soundpressure levels (noise).
SUGGESTED LOUDNESS LEVELAREA SONE
LEVELNOISE
CRITERIA NC dBA (1) TYPES OF AREAS
Up to 9 32 to 54 35 to 60Bingo Hall, Auction Room, Hotel Ballroom, Social Club, Reception Room, Apartment House, Professional Office, Supervisor Office,Courtroom, School and Classroom, Hospital Ward, Operating Room, Correction Facility.
ModeratelyQuiet Sound
9.1 to 13 55 to 59 61 to 65Lobby/Corridor, Spectator Area, Chicken House, Greenhouse, General Open Office, Restaurant, Night Club, Department Store, Ticket SalesOffice, Casino, Spa, Control Room, Rail, Bus, Plane, Bowling Alley, Print Shop, Drafting Office, Convention Hall Average
13.1 to 18 60 to 64 66 to 70Washroom & Toilet, Retail Shop, Bus Terminal Lounge, Foreman's Office, Cocktail Lounge, Office Hall & Corridor, Tabulation &Computation Office, Kitchen Cafeteria, Hotel Garage, Computer Room, Warehouse, Battery Charging Room Commercial
18.1 to 50 65 to 78 71 to 84General Storage Area, Restaurant Banquet Room, Swimming Pool, Supermarket, Hotel Kitchen and Laundry, Welding Booth, DepartmentStore Main Floor, Paint Booth, Heat Treating Plant, Tool Maintenance Area High Sound
50.1 Plus 78.1 to 85+84.1 to 90+
(2)Manufacturing Area, Heavy Machine Foundry, Assembly Line, Machine Shops, Punch Press Shop, Light Machine Area, Boiler Room,Emergency Generator Room, Pump House, Power Plant, Transformer, Steel Mill, Engine Test Room, Compressor Room, Steel Stamping
Ext. HeavyIndustrial
SOUND CLASSIFICATION GUIDE
(1) dBA range of A-weighted sound levels, in decibels.Notes:
AMPERE RATINGS FOR THREE PHASE MOTORS
200 208 230 460 575Horsepower Volts Volts Volts Volts Volts
1 4.8 4.6 4.2 2.1 1.7
1 1/2 6.9 6.6 6.0 3.0 2.4
2 7.8 7.5 6.8 3.4 2.7
3 11.0 10.6 9.6 4.8 3.9
5 17.5 16.7 15.2 7.6 6.1
7 1/2 25.3 24.2 22 11 9
10 32.2 30.8 28 14 11
15 48.3 46.2 42 21 17
20 62.1 59.4 54 27 22
25 78.2 74.8 68 34 27
30 92 88 80 40 32
40 120 114 104 52 41
50 150 143 130 65 52
60 177 169 154 77 62
75 221 211 192 96 77
100 285 273 248 124 99
The above values of full-load currents are typical formotors running at speeds usual for belted motors andmotors with normal torque characteristics. Motorsbuilt for low speeds (1200 RPM or less) or high torquesmay require more running current, and multi-speedmotors will have full-load current varying with speed,in which case the nameplate current ratings shall be used.
The voltages listed are rated motor voltages. Thecurrents listed shall be permitted for system voltageranges of 230 to 240 and 440 to 480 volts.
The table data shown above is from the NEC 1999edition, table 430-150.
(2) Sound levels this high subject to OSHA Standards for safety, as well as state and local ordinances. Soundattenuation provisions should be considered. Source: ASHRAE, AMCA Publications.
(Air Purification Unit)
For Commercial Kitchen Applications
EnvironAir® is Working in Hundreds of Locations Around the World
to Help Keep Our Environment Cleaner
23 Vreeland Road, Florham Park, New Jersey 07932Phone: 973-966-6000, 800-444-9696
Fax: 973-966-0315Website: www.carrollmi.comEmail: [email protected]
Marlboro Country Club
Marlboro, New Jersey
Queens Quay
Toronto, Canada
University of Toronto
Toronto, Canada
Emirates Towers
Dubai, United Arab Emirates
Aladdin Casino & Hotel
Las Vegas, Nevada
Sel De La Terre Restaurant
Boston, Massachusetts
Photo courtesy of Vegas.com
Air Canada Center
Toronto, Canada
Sales and Engineering 25 Johnson Street, Thornhill, Ontario L3T 2N8 Phone (905) 731-1050 Fax (905) 731-8547