energy star qualified homes

170
ENERGY STAR Qualified Homes HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST 1

Upload: colleen-sparks

Post on 03-Jan-2016

30 views

Category:

Documents


2 download

DESCRIPTION

ENERGY STAR Qualified Homes. HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST 1. TABLE OF CONTENTS. Section 1.Review of HVAC System Quality Installation Contractor Checklist 2 - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: ENERGY STAR Qualified Homes

ENERGY STAR Qualified Homes

HVAC SYSTEM QUALITY INSTALLATION RATER

CHECKLIST 1

Page 2: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

TABLE OF CONTENTS

Section 1. Review of HVAC System Quality Installation Contractor Checklist 2

Section 2. Duct Quality Installation - Applies to All Heating, Cooling, Ventilation, Exhaust, and Pressure Balancing Ducts

Section 3. Duct Insulation - Applies to All Heating, Cooling, Supply Ventilation, and Pressure Balancing Ducts 12

HVAC System Quality Installation Rater Checklist

Page 3: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

TABLE OF CONTENTS

Section 4. Duct Leakage - Applies to All Heating, Cooling, and Balanced Ventilation Ducts

Section 5. Whole-building Delivered Ventilation

Section 6. Controls

Section 7. Ventilation Air Inlets & Ventilation Source

HVAC System Quality Installation Rater Checklist

Page 4: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

TABLE OF CONTENTS

Section 8. Local Mechanical Exhaust

Section 9. Ventilation & Exhaust Fan Ratings (Exemptions for HVAC and

Remote- Mounted Fans) 30

Section 10. Combustion Appliances

Section 11. Filtration

HVAC System Quality Installation Rater Checklist

Page 5: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 1. REVIEW OF HVAC SYSTEM QUALITY INSTALLATION CONTRACTOR CHECKLIST 2

1.1. HVAC System Quality Installation Contractor checklist completed in its entirety and collected for records, along with documentation on ventilation system (1.3), full load calculations (2.18), AHRI certificate (3.15), and balancing report (10.2).

HVAC System Quality Installation Rater Checklist

Page 6: ENERGY STAR Qualified Homes
Page 7: ENERGY STAR Qualified Homes
Page 8: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 1. REVIEW OF HVAC SYSTEM QUALITY INSTALLATION CONTRACTOR CHECKLIST

1.2 Review the following parameters related to system cooling design, selection, and installation from the HVAC Contractor checklist

(Contractor checklist item # indicated in parenthesis):

HVAC System Quality Installation Rater Checklist

Page 9: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 1. REVIEW OF HVAC SYSTEM QUALITY INSTALLATION CONTRACTOR CHECKLIST 2

1.2 Review the following parameters related to system cooling design, selection, and installation from the HVAC Contractor checklist

(Contractor checklist item # indicated in parenthesis):

1.2.1 Outdoor design temperatures (2.4) are equal to the 1% and 99% ACCA Manual J design temperatures for contractor-designated design location 4

HVAC System Quality Installation Rater Checklist

Page 10: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 1. REVIEW OF HVAC SYSTEM QUALITY INSTALLATION CONTRACTOR CHECKLIST 2

1.2.2 Home orientation (2.5) matches orientation of rated home

1.2.3 Number of Occupants (2.6) equals number of occupants in rated home 5

1.2.4 Conditioned floor area (2.7) is within ±10% of conditioned floor area of rated home

1.2.5 Window area (2.8) is within ±10% of calculated window area of rated home

1.2.6 Predominant window SHGC (2.9) is within 0.1 of predominant value in rated home 6

HVAC System Quality Installation Rater Checklist

Page 11: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 1. REVIEW OF HVAC SYSTEM QUALITY INSTALLATION CONTRACTOR CHECKLIST 2

1.2.7 Listed latent cooling capacity (3.10) exceeds design latent heat gain (2.12)

1.2.8 Listed sensible cooling capacity (3.11) exceeds design sensible heat gain (2.13)

1.2.9 Listed total cooling capacity (3.12) is 95-115% (or 95-125% for Heat Pumps in Climate Zones 4-8) of design total heat gain (2.14), or next nominal size 7

1.2.10 HVAC manufacturer and model numbers on installed equipment, contractor checklist (3.1, 3.3, 5.1), and AHRI certificate or OEM catalog data all match 8

HVAC System Quality Installation Rater Checklist

Page 12: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 1. REVIEW OF HVAC SYSTEM QUALITY INSTALLATION CONTRACTOR CHECKLIST 2

1.2.11 Using reported liquid line (6.3) or suction line (6.5) pressure, corresponding temp. (as determined using pressure/temperature chart for refrigerant type) matches reported condenser (7.1) or evaporator (7.5) saturation temperature (+/- 3 degrees) 9

1.2.12 Calculated subcooling (7.1 minus 6.4) or superheat (6.6 minus 7.5) value equals reported target subcooling (7.3) or superheat (7.7) temperature 9

HVAC System Quality Installation Rater Checklist

Page 13: ENERGY STAR Qualified Homes
Page 14: ENERGY STAR Qualified Homes
Page 15: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 1. REVIEW OF HVAC SYSTEM QUALITY INSTALLATION CONTRACTOR CHECKLIST 2

1.3 Rater-verified supply & return duct static pressure<110% of contractor values (9.3, 9.4)

HVAC System Quality Installation Rater Checklist

Page 16: ENERGY STAR Qualified Homes
Page 17: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION - Applies to All Heating, Cooling, Ventilation, Exhaust, and Pressure Balancing Ducts

2.1 Connections and routing of ductwork completed without kinks or sharp bends.10

2.2 No excessive coiled or looped flexible ductwork.11

2.3 Flexible ducts in unconditioned space not installed in cavities smaller than outer duct diameter; in conditioned space not installed in cavities smaller than inner duct diameter

2.4 Flexible ducts supported at intervals as recommended by mfr. but at a distance < 5 ft.

Drop wire as an allowed flex duct support
Page 18: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION - Applies to All Heating, Cooling, Ventilation, Exhaust, and Pressure Balancing Ducts

2.5 Building cavities not used as supply or return ducts unless they meet items 3.2, 3.3, 4.1, and 4.2 of this checklist.

2.6 HVAC ducts, cavities used as ducts, and combustion inlets and outlets may pass perpendicularly through exterior walls but shall not be run within exterior walls unless at least R-6 continuous insulation is provided on exterior side of the cavity, along with an interior and exterior air barrier where required by the Thermal Enclosure System Rater Checklist.

HVAC System Quality Installation Rater Checklist

Page 19: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION

2.7 Quantity & location of supply and return duct terminals match contractor balancing report.

2.8 Bedrooms pressure-balanced using any combination of transfer grills, jump ducts, dedicated return ducts, and/or undercut doors to either:

a) provide 1 sq. in. of free area opening per 1 CFM of supply air, as reported on the contractor-provided balancing report; or

HVAC System Quality Installation Rater Checklist

Page 20: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION

b) achieve a Rater-measured pressure differential < 3 Pa (0.012 in. w.c.) with respect to the main body of the house when bedroom doors are closed and the air handler is operating.12,13

HVAC System Quality Installation Rater Checklist

Page 21: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION

2.1 Connections and routing of ductwork completed without kinks or sharp bends.10

HVAC System Quality Installation Rater Checklist

Page 22: ENERGY STAR Qualified Homes
Page 23: ENERGY STAR Qualified Homes

2.1

Duct is kinked in cavity.

HVAC System Quality Installation Rater Checklist

Connections and routing of ductwork completed without kinks or sharp bends.9

Duct is run straight and supported properly.

A A

Page 24: ENERGY STAR Qualified Homes

2.1

Ducks crammed into cavity, kinked and sharply bent.

HVAC System Quality Installation Rater Checklist

Connections and routing of ductwork completed without kinks or sharp bends.9

Ducts are run straight and supported properly.

BB

Page 25: ENERGY STAR Qualified Homes

2.1

Excessive length of duct installed causing sharp bends.

HVAC System Quality Installation Rater Checklist

Connections and routing of ductwork completed without kinks or sharp bends.9

Fan housing was oriented in the correct direction to allow proper exhaust duct installation.

CC

Page 26: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION

2.2 No excessive coiled or looped flexible ductwork.11

Page 27: ENERGY STAR Qualified Homes
Page 28: ENERGY STAR Qualified Homes

2.2

Excessive length of duct installed.

HVAC System Quality Installation Rater Checklist

No excessive coiled or looped flexible ductwork.11

Duct is run straight and supported properly.

AA

Page 29: ENERGY STAR Qualified Homes

2.2

No mechanical damper installed.

HVAC System Quality Installation Rater Checklist

No excessive coiled or looped flexible ductwork.11

Mechanical damper installed.

BB

Where are the dampers?
Page 30: ENERGY STAR Qualified Homes

2.2

Excessive length of duct installed causing sharp bends.

HVAC System Quality Installation Rater Checklist

No excessive coiled or looped flexible ductwork.11

Fan housing was oriented in the correct direction to allow proper exhaust duct installation.

CC

Page 31: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION

2.3 Flexible ducts in unconditioned space not installed in cavities smaller than outer duct diameter; in conditioned space not installed in cavities smaller than inner duct diameter

Page 32: ENERGY STAR Qualified Homes
Page 33: ENERGY STAR Qualified Homes

2.3

Duct is compressed.

HVAC System Quality Installation Rater Checklist

Flexible ducts in unconditioned space not installed in cavities smaller than outer duct diameter; in conditioned space not installed in cavities smaller than inner duct diameter

Framing allowed ductwork to be properly installed without compression.

AA

Page 34: ENERGY STAR Qualified Homes

2.3

Recessed can light is compressing ductwork.

HVAC System Quality Installation Rater Checklist

Flexible ducts in unconditioned space not installed in cavities smaller than outer duct diameter; in conditioned space not installed in cavities smaller than inner duct diameter

Ducts properly installed without compression and appropriately supported.

AA

Picture also shows flex tight to recessed can. Bad
Page 35: ENERGY STAR Qualified Homes

2.3

Duct is compressed.

HVAC System Quality Installation Rater Checklist

Flexible ducts in unconditioned space not installed in cavities smaller than outer duct diameter; in conditioned space not installed in cavities smaller than inner duct diameter

Ducts properly installed without compression and appropriately supported.

AA

Page 36: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION

2.4 Flexible ducts supported at intervals as recommended by mfr. but at a distance ≤ 5 ft.

Page 37: ENERGY STAR Qualified Homes
Page 38: ENERGY STAR Qualified Homes

2.4

Duct sagging because supports not installed at regular intervals.

HVAC System Quality Installation Rater Checklist

Flexible ducts supported at intervals as recommended by mfr. but at a distance ≤ 5 ft.

Ducts well supported.

AA

Page 39: ENERGY STAR Qualified Homes

2.4

Metal strap is too small and is compressing duct.

HVAC System Quality Installation Rater Checklist

Flexible ducts supported at intervals as recommended by mfr. but at a distance ≤ 5 ft.

Ducts well supported.

CC

Page 40: ENERGY STAR Qualified Homes

2.4

Straps are spaced too far apart causing the straps to compress the duct under its own weight.

HVAC System Quality Installation Rater Checklist

Flexible ducts supported at intervals as recommended by mfr. but at a distance ≤ 5 ft.

Ducts well supported by framing and straps as needed.

CC

Page 41: ENERGY STAR Qualified Homes

2.4

Metal strap is too small and is compressing duct.

HVAC System Quality Installation Rater Checklist

Flexible ducts supported at intervals as recommended by mfr. but at a distance ≤ 5 ft.

Ducts well supported.

CC

Page 42: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION

2.5 Building cavities not used as supply or return ducts unless they meet items 3.2, 3.3, 4.1, and 4.2 of this checklist.

Page 43: ENERGY STAR Qualified Homes
Page 44: ENERGY STAR Qualified Homes

2.5

Cavity used for return is not insulated and is not air sealed, which will pull in air from outside.

HVAC System Quality Installation Rater Checklist

Building cavities not used as supply or return ducts unless they meet items 3.2, 3.3, 4.1, and 4.2 of this checklist.

Cavity used for duct has been lined with rigid insulation and is ready to be air sealed.

BB

Page 45: ENERGY STAR Qualified Homes

2.5

BAD PIC OF INSULATION INSTALLED WITHOUT AIR BARRIER IN BUILDING CAVITY USED AS A DUCT

HVAC System Quality Installation Rater Checklist

Building cavities not used as supply or return ducts unless they meet items 3.2, 3.3, 4.1, and 4.2 of this checklist.

GOOD PIC OF RIGID AIR BARRIER INSTALLED IN BUILDING CAVITY USED AS A DUCT

CC

Page 46: ENERGY STAR Qualified Homes

2.5

Cavity was not air sealed.

HVAC System Quality Installation Rater Checklist

Building cavities not used as supply or return ducts unless they meet items 3.2, 3.3, 4.1, and 4.2 of this checklist.

Cavity has been air sealed with mastic.

DD

Page 47: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION

2.6 HVAC ducts, cavities used as ducts, and combustion inlets and outlets may pass perpendicularly through exterior walls but shall not be run within exterior walls unless at least R-6 continuous insulation is provided on exterior side of the cavity, along with an interior and exterior air barrier where required by the Thermal Enclosure System Rater Checklist.

Page 48: ENERGY STAR Qualified Homes
Page 49: ENERGY STAR Qualified Homes

2.6

Inadequate amount of insulation installed with compression, misalignment, and voids.

HVAC System Quality Installation Rater Checklist

HVAC ducts, cavities used as ducts, and combustion inlets and outlets may pass perpendicularly through exterior walls but shall not be run within exterior walls unless at least R-6 continuous insulation is provided on exterior side of the cavity, along with an interior and exterior air barrier where required by the Thermal Enclosure System Rater Checklist.

GOOD PIC OF PROPERLY INSTALLED INSULATION IN BUILDING CAVITY USED AS A DUCT

AA

Page 50: ENERGY STAR Qualified Homes

2.6

BAD PIC OF INSULATION INSTALLED WITHOUT AIR BARRIER IN BUILDING CAVITY USED AS A DUCT

HVAC System Quality Installation Rater Checklist

HVAC ducts, cavities used as ducts, and combustion inlets and outlets may pass perpendicularly through exterior walls but shall not be run within exterior walls unless at least R-6 continuous insulation is provided on exterior side of the cavity, along with an interior and exterior air barrier where required by the Thermal Enclosure System Rater Checklist.

GOOD PIC OF RIGID AIR BARRIER INSTALLED IN BUILDING CAVITY USED AS A DUCT

BB

Page 51: ENERGY STAR Qualified Homes

2.6

No insulation installed in cavity and not air sealed.

.

HVAC System Quality Installation Rater Checklist

HVAC ducts, cavities used as ducts, and combustion inlets and outlets may pass perpendicularly through exterior walls but shall not be run within exterior walls unless at least R-6 continuous insulation is provided on exterior side of the cavity, along with an interior and exterior air barrier where required by the Thermal Enclosure System Rater Checklist.

GOOD PIC OF PROPERLY SEALED BUILDING CAVITY USED AS A DUCT

CC

Page 52: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION

2.7 Quantity & location of supply and return duct terminals match contractor balancing report.

Page 53: ENERGY STAR Qualified Homes
Page 54: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION

2.8 Bedrooms pressure-balanced using any combination of transfer grills, jump ducts, dedicated return ducts, and/or undercut doors to either:

a) provide 1 sq. in. of free area opening per 1 CFM of supply air, as reported on the contractor-provided balancing report; or

Page 55: ENERGY STAR Qualified Homes
Page 56: ENERGY STAR Qualified Homes

2.8a

GOOD PIC OF NO/UNDERSIZED GRILL OR DUCTS INSTALLED TO PRESSURE BALANCE ROOM

HVAC System Quality Installation Rater Checklist

Bedroom pressure-balanced by providing 1 sq. in. of free area opening per 1CFM of supply air, as reported on the contractor-provided balancing report

Grill and duct size based on calculated requirements for net free area.

AA

Page 57: ENERGY STAR Qualified Homes

2.8a

Transfer grill not sealed.

Bedroom pressure-balanced by providing 1 sq. in. of free area opening per 1CFM of supply air, as reported on the contractor-provided balancing report

Transfer grill sealed with mastic.

BB

Page 58: ENERGY STAR Qualified Homes

2.8a

Duct to boot connection of jump duct not fastened and sealed.

HVAC System Quality Installation Rater Checklist

Bedroom pressure-balanced by providing 1 sq. in. of free area opening per 1CFM of supply air, as reported on the contractor-provided balancing report

Duct to boot connection of jump duct is properly sealed with mastic.

CC

Page 59: ENERGY STAR Qualified Homes

2.8a

Door is not undercut therefore not contributing to pressure balancing.

HVAC System Quality Installation Rater Checklist

Bedroom pressure-balanced by providing 1 sq. in. of free area opening per 1CFM of supply air, as reported on the contractor-provided balancing report

Door has been undercut to allow for specified amount of air flow therefore contributing to pressure balancing.

DD

Page 60: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 2. DUCT QUALITY INSTALLATION

2.8 Bedrooms pressure-balanced using any combination of transfer grills, jump ducts, dedicated return ducts, and/or undercut doors to either:

b) achieve a Rater-measured pressure differential ≤ 3 Pa (0.012 in. w.c.) with respect to

the main body of the house when bedroom doors are closed and the air handler is operating.12,13

Page 61: ENERGY STAR Qualified Homes
Page 62: ENERGY STAR Qualified Homes

2.8b

Return has not been sealed.

HVAC System Quality Installation Rater Checklist

Bedrooms achieve a Rater-measured pressure differential ≤ 3 Pa (0.012 in. w.c.) with respect to the main body of the house when bedroom doors are closed and the air handler is operating.12,13

Return duct has been properly sealed with mastic.

AA

Page 63: ENERGY STAR Qualified Homes

2.8b

Return box has not been sealed.

HVAC System Quality Installation Rater Checklist

Bedrooms achieve a Rater-measured pressure differential ≤ 3 Pa (0.012 in. w.c.) with respect to the main body of the house when bedroom doors are closed and the air handler is operating.12,13

Return box has been properly sealed with mastic.

BB

Page 64: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 3. DUCT INSULATION: Applies to All Heating, Cooling, Supply Ventilation, and Pressure Balancing Ducts 14

3.1 All connections to trunk ducts in unconditioned space are insulated.

3.2 Prescriptive Path: Supply ducts in unconditioned attic have insulation > R-8.

Performance Path: Supply ducts in unconditioned attic have insulation > R-6.

3.3 All other supply ducts and all return ducts in unconditioned space have insulation > R-6.

Page 65: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 3. DUCT INSULATION

3.1 All connections to trunk ducts in unconditioned space are insulated.

Page 66: ENERGY STAR Qualified Homes
Page 67: ENERGY STAR Qualified Homes

3.1

Trunk to duct connections are only mechanically fastened and not sealed.

HVAC System Quality Installation Rater Checklist

All connections to trunk ducts in unconditioned space are insulated.

Trunk to duct connections are properly insulated and have been sealed with mastic.

AA

Page 68: ENERGY STAR Qualified Homes

3.1

Ductwork is uninsulated and not sealed at seams.

HVAC System Quality Installation Rater Checklist

All connections to trunk ducts in unconditioned space are insulated.

Seams are being properly sealed with mastic and mesh tape.

AA

Page 69: ENERGY STAR Qualified Homes

3.1

Boot is uninsulated.

HVAC System Quality Installation Rater Checklist

All connections to trunk ducts in unconditioned space are insulated.

Duct insulation is installed over boot.

BB

Page 70: ENERGY STAR Qualified Homes

3.1

Insulation does not cover boot and is not sealed.

HVAC System Quality Installation Rater Checklist

All connections to trunk ducts in unconditioned space are insulated.

Boot has been covered with insulation and sealed with mastic.

CC

Page 71: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 3. DUCT INSULATION

3.2 Prescriptive Path: Supply ducts in unconditioned attic have insulation ≥ R-8.

Performance Path: Supply ducts in unconditioned attic have insulation ≥ R-6.

Page 72: ENERGY STAR Qualified Homes
Page 73: ENERGY STAR Qualified Homes

3.2-3

Duct is located in unconditioned space and is not insulated.

HVAC System Quality Installation Rater Checklist

Prescriptive Path: Supply ducts in unconditioned attic have insulation ≥ R-8.Performance Path: Supply ducts in unconditioned attic have insulation ≥ R-6.

Duct is located in unconditioned space and is properly insulated.

AA

Page 74: ENERGY STAR Qualified Homes

3.2-3

Duct is insulated but strapping is compressing the insulation therefore reducing the R-value.

HVAC System Quality Installation Rater Checklist

Prescriptive Path: Supply ducts in unconditioned attic have insulation ≥ R-8.Performance Path: Supply ducts in unconditioned attic have insulation ≥ R-6.

Ducts are properly insulated and supported without compressing the insulation.

BB

Are these both good pictures?
Page 75: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 4. DUCT LEAKAGE

4.1 Total Rater-measured duct leakage < 6 CFM25 per 100 sq. ft. of conditioned floor area15,16

4.2 Rater -measured duct leakage to outdoors < 4 CFM25 per 100 sq. ft. of conditioned floor area.15, 16, 17

4.3 Duct boots sealed to floor, wall, or ceiling using caulk, foam, mastic tape, or mastic paste.

Page 76: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 4. DUCT LEAKAGE

4.1 Total Rater-measured duct leakage ≤ 6 CFM25 per 100 sq. ft. of conditioned floor area15,16

4.2 Rater -measured duct leakage to outdoors ≤ 4 CFM25 per 100 sq. ft. of conditioned floor area.15, 16, 17

Page 77: ENERGY STAR Qualified Homes
Page 78: ENERGY STAR Qualified Homes

4.1-2

Connection in place but not sealed.

HVAC System Quality Installation Rater Checklist

Total Rater-measured duct leakage ≤ 6 CFM25 per 100 sq. ft. of conditioned floor area15,16

Rater -measured duct leakage to outdoors ≤ 4 CFM25 per 100 sq. ft. of conditioned floor area.15, 16, 17

Mechanically fastened and sealed.

AA

Page 79: ENERGY STAR Qualified Homes

4.1-2

Insulation does not cover boot and is not sealed.

HVAC System Quality Installation Rater Checklist

Total Rater-measured duct leakage ≤ 6 CFM25 per 100 sq. ft. of conditioned floor area15,16

Rater -measured duct leakage to outdoors ≤ 4 CFM25 per 100 sq. ft. of conditioned floor area.15, 16, 17

Duct insulation is installed over boot.

BB

Page 80: ENERGY STAR Qualified Homes

4.1-2

Insulation does not cover boot and is not sealed.

HVAC System Quality Installation Rater Checklist

Total Rater-measured duct leakage ≤ 6 CFM25 per 100 sq. ft. of conditioned floor area15,16

Rater -measured duct leakage to outdoors ≤ 4 CFM25 per 100 sq. ft. of conditioned floor area.15, 16, 17

Boot has been covered with insulation and sealed with mastic.

CC

Page 81: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 4. DUCT LEAKAGE

4.3 Duct boots sealed to floor, wall, or ceiling using caulk, foam, mastic tape, or mastic paste.

Page 82: ENERGY STAR Qualified Homes
Page 83: ENERGY STAR Qualified Homes

4.3

Boot to floor connection not sealed.

HVAC System Quality Installation Rater Checklist

Duct boots sealed to floor, wall, or ceiling using caulk, foam, mastic tape, or mastic paste.

Boot to floor connection sealed.

AA

Page 84: ENERGY STAR Qualified Homes

4.3

Boot to drywall connection not sealed.

Duct boots sealed to floor, wall, or ceiling using caulk, foam, mastic tape, or mastic paste.

Boot to drywall connection sealed.

AA

Page 85: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 5. WHOLE-BUILDING DELIVERED VENTILATION

5.1 Rater-measured ventilation rate is within 100-120% of HVAC contractor design value (2.11).18

Page 86: ENERGY STAR Qualified Homes
Page 87: ENERGY STAR Qualified Homes

5.1

Ventilation tied into the return without a mechanical damper.

Rater-measured ventilation rate is within 100-120% of HVAC contractor design value (2.11).18

Ventilation tied into the return with a mechanical damper.

AA

Page 88: ENERGY STAR Qualified Homes

5.1

Exhaust fan installed but in wrong direction causing excessive bend and duct is uninsulated.

HVAC System Quality Installation Rater Checklist

Rater-measured ventilation rate is within 100-120% of HVAC contractor design value (2.11).18

In line exhaust ventilation installed.

BB

Page 89: ENERGY STAR Qualified Homes

HVAC System Quality Installation Rater Checklist

Properly installed ERV/HRV.

.

5.1Rater-measured ventilation rate is within 100-120% of HVAC contractor design value (2.11).18

Properly installed ERV/HRV.

CC

Page 90: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 6. CONTROLS

6.1 Air flow is produced when central HVAC fan is energized (set thermostat to “fan”).

6.2 Cool air flow is produced when the cooling cycle is energized (set thermostat to “cool”).19, 20

6.3 Heated air flow is produced when the heating cycle is energized (set thermostat to “heat”).19

6.4 Continuously-operating ventilation & exhaust fans include readily accessible override controls.

Page 91: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 6. VENTILATION CONTROLS

6.5 Function of ventilation controls is obvious (e.g., bathroom exhaust fan) or, if not, controls have been labeled.

Page 92: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 6. VENTILATION CONTROLS

6.1 Air flow is produced when central HVAC fan is energized (set thermostat to “fan”).

6.2 Cool air flow is produced when the cooling cycle is energized (set thermostat to “cool”).19,20

6.3 Heated air flow is produced when the heating cycle is energized (set thermostat to “heat”).19

Page 93: ENERGY STAR Qualified Homes
Page 94: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 6. VENTILATION CONTROLS

6.4 Continuously-operating ventilation & exhaust fans include readily accessible override controls.

Page 95: ENERGY STAR Qualified Homes
Page 96: ENERGY STAR Qualified Homes

6.4

BAD PIC OF EQUIPMENT INSTALLED WITHOUT OVERRIDE CONTROL OPTIONS? OR PIC OF EQUIPMENT INSTALLED WITHOUT IT

Continuously-operating ventilation & exhaust fans include readily accessible override controls.

GOOD PIC OF EQUIPMENT INSTALLED WITH OVERRIDE CONTROL OPTIONS

AA

Page 97: ENERGY STAR Qualified Homes

6.4

BAD PIC OF BAD LOCATION FOR OVERRIDE EQUIP.

Continuously-operating ventilation & exhaust fans include readily accessible override controls.

Override control switches centrally located near thermostat for ease of access.

BB

Page 98: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 6. VENTILATION CONTROLS

6.5 Function of ventilation controls is obvious (e.g., bathroom exhaust fan) or, if not, controls have been labeled.

Page 99: ENERGY STAR Qualified Homes
Page 100: ENERGY STAR Qualified Homes

6.5

Ventilation is not labeled.

Function of ventilation controls is obvious (e.g., bathroom exhaust fan) or, if not, controls have beenlabeled.

Manufacturer labeled ventilation switch.

AA

Page 101: ENERGY STAR Qualified Homes

6.5

Controls are not labeled.

Function of ventilation controls is obvious (e.g., bathroom exhaust fan) or, if not, controls have beenlabeled.

Manufacturer labeled controls.

AA

Page 102: ENERGY STAR Qualified Homes

6.5

Ventilation is not labeled.

Function of ventilation controls is obvious (e.g., bathroom exhaust fan) or, if not, controls have beenlabeled.

Installer permanently labeled ventilation switch.

BB

Page 103: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 7. AIR INLETS & VENTILATION SOURCE

7.1 All ventilation air inlets located ≥ 10 ft. of stretched-string distance from known contamination sources such as stack, vent, exhaust hood, or vehicle exhaust. Exception: ventilation air inlets in the wall ≥ 3 ft. from dryer exhausts and contamination sources exiting through the roof. 21

7.2 Ventilation air inlets ≥ 2 ft. above grade or roof deck in Climate Zones 1-3 or ≥ 4 ft. above grade or roof deck in Climate Zones 4-8 and not obstructed by snow, plantings, condensing units or other material at time of inspection.22

Page 104: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 7. AIR INLETS & VENTILATION SOURCE

7.3 Ventilation air inlets provided with rodent / insect screen with ≤ 0.5 inch mesh.23

7.4 Ventilation air comes directly from outdoors and not from adjacent dwelling units, garages, crawlspaces, or attics.

Page 105: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 7. AIR INLETS & VENTILATION SOURCE

7.1 All ventilation air inlets located ≥10 ft. of stretched-string distance from known contamination sources such as stack, vent, exhaust hood, or vehicle exhaust. Exception: ventilation air inlets in the wall ≥ 3 ft. from dryer exhausts and contamination sources exiting through the roof. 21

Page 106: ENERGY STAR Qualified Homes
Page 107: ENERGY STAR Qualified Homes

7.1

Ventilation air inlet is too close to exhaust outlet.

HVAC System Quality Installation Rater Checklist

All ventilation air inlets located ≥10 ft. of stretched-string distance from known contamination sources such as stack, vent, exhaust hood, or vehicle exhaust. Exception: ventilation air inlets in the wall ≥ 3 ft. from dryer exhausts and contamination sources exiting through the roof. 21

Ventilation inlet is greater than 10 ft. from known contamination source.

BB

Page 108: ENERGY STAR Qualified Homes

7.1

Ventilation air inlet is too close to exhaust outlet.

HVAC System Quality Installation Rater Checklist

All ventilation air inlets located ≥10 ft. of stretched-string distance from known contamination sources such as stack, vent, exhaust hood, or vehicle exhaust. Exception: ventilation air inlets in the wall ≥ 3 ft. from dryer exhausts and contamination sources exiting through the roof. 21

Ventilation inlet is greater than 10 ft. from known contamination source.

BB

Page 109: ENERGY STAR Qualified Homes

7.1

Ventilation inlet is too close to exhaust outlets and does not extend at least 2 ft. above the roof deck.

HVAC System Quality Installation Rater Checklist

All ventilation air inlets located ≥10 ft. of stretched-string distance from known contamination sources such as stack, vent, exhaust hood, or vehicle exhaust. Exception: ventilation air inlets in the wall ≥ 3 ft. from dryer exhausts and contamination sources exiting through the roof. 21

Ventilation inlet is not near any exhaust outlets/contamination sources and is at least 2 ft. above the roof deck.

BB

Page 110: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 7. AIR INLETS & VENTILATION SOURCE

7.2 Ventilation air inlets ≥ 2 ft. above grade or roof deck in Climate Zones 1-3 or ≥ 4 ft. above grade or roof deck in Climate Zones 4-8 and not obstructed by snow, plantings, condensing units or other material at time of inspection.22

Page 111: ENERGY STAR Qualified Homes
Page 112: ENERGY STAR Qualified Homes

7.2

Ventilation inlet does not terminate high enough above the roof deck.

HVAC System Quality Installation Rater Checklist

Ventilation air inlets ≥ 2 ft. above grade or roof deck in Climate Zones 1-3 or ≥ 4 ft. above grade or roof deck in Climate Zones 4-8 and not obstructed by snow, plantings, condensing units or other material at time of inspection.22

Ventilation inlet is not near any exhaust outlets/contamination sources and is at least 2 ft. above the roof deck.

BB

Page 113: ENERGY STAR Qualified Homes

7.2

Ventilation inlet is too close to the ground and is being blocked by the grass.

HVAC System Quality Installation Rater Checklist

Ventilation air inlets ≥ 2 ft. above grade or roof deck in Climate Zones 1-3 or ≥ 4 ft. above grade or roof deck in Climate Zones 4-8 and not obstructed by snow, plantings, condensing units or other material at time of inspection. 22

Ventilation inlet is appropriately located above grade.

CC

Page 114: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 7. AIR INLETS & VENTILATION SOURCE

7.3 Ventilation air inlets provided with rodent / insect screen with ≤ 0.5 inch mesh.23

Page 115: ENERGY STAR Qualified Homes
Page 116: ENERGY STAR Qualified Homes

7.3

Mesh screen is spaced wider than 0.5" allowing insects to enter.

HVAC System Quality Installation Rater Checklist

Ventilation air inlets provided with rodent / insect screen with ≤ 0.5 inch mesh.23

Mesh screen is correctly installed and gaps are less than 0.5".

AA

Page 117: ENERGY STAR Qualified Homes

7.3

Mesh screen is spaced wider than 0.5" allowing insects to enter.

HVAC System Quality Installation Rater Checklist

Ventilation air inlets provided with rodent / insect screen with ≤ 0.5 inch mesh.23

Mesh screen is correctly installed and gaps are smaller less than 0.5".

AA

Page 118: ENERGY STAR Qualified Homes

7.3

Air inlet is not convenient for cleaning and located next to exhaust outlets.

HVAC System Quality Installation Rater Checklist

Ventilation air inlets provided with rodent / insect screen with ≤ 0.5 inch mesh.23

Air inlet is located in a convenient place for homeowner to clean.

BB

Page 119: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 7. AIR INLETS & VENTILATION SOURCE

7.4 Ventilation air comes directly from outdoors and not from adjacent dwelling units, garages, crawlspaces, or attics.

Page 120: ENERGY STAR Qualified Homes
Page 121: ENERGY STAR Qualified Homes

7.4

Exhaust terminates inside of soffit and was just covered.

HVAC System Quality Installation Rater Checklist

Ventilation air comes directly from outdoors and not from adjacent dwelling units, garages, crawlspaces, or attics.

Exhaust terminates to the outside away from air inlets.

AA

Page 122: ENERGY STAR Qualified Homes

7.4

Exhaust duct only mechanically fastened and not sealed.

HVAC System Quality Installation Rater Checklist

Ventilation air comes directly from outdoors and not from adjacent dwelling units, garages, crawlspaces, or attics.

Kitchen exhaust properly installed and sealed with mastic.

BB

Page 123: ENERGY STAR Qualified Homes

HVAC System Quality Installation Rater Checklist

Ventilation duct is compressed because supporting strap is too small.

Ventilation air comes directly from outdoors and not from adjacent dwelling units, garages, crawlspaces, or attics.

7.4Ventilation air comes directly from outdoors and not from adjacent dwelling units, garages, crawlspaces, or attics.

C / DC / D

Page 124: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 8. LOCAL MECHANICAL EXHAUST

In each kitchen and bathroom, a system shall be installed that exhausts directly to the outdoors and meets one of the following Rater measured airflow standards: 18,24,25

Location Continuous Rate Intermittent Rate 26

8.1 Kitchen≥ 5 ACH, based on kitchen

volume 27 ≥ 100 CFM 28

8.2 Bathroom ≥ 20 CFM ≥ 50 CFM

Page 125: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 8. LOCAL MECHANICAL EXHAUST

8.3 If fans share common exhaust duct, back-draft dampers installed.

8.4 Common exhaust duct not shared by fans in separate dwellings.29

8.5 Clothes dryers vented directly to outdoors, except for ventless dryers equipped with a condensate drain.

Page 126: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 8. LOCAL MECHANICAL EXHAUST

In each kitchen and bathroom, a system shall be installed that exhausts directly to the outdoors and meets one of the following Rater measured airflow standards: 18,24,25

8.1 Kitchen

Continuous: ≥ 5 ACH, based on kitchen volume 27

Intermittent Rate 26 : ≥ 100 CFM 28

Page 127: ENERGY STAR Qualified Homes
Page 128: ENERGY STAR Qualified Homes

HVAC System Quality Installation Rater Checklist

CFM rating may not meet the performance specification once installed.

Fan CFM rating is higher than the requirement increasing the likelihood that it will meet the performance level once installed.

8.1In each kitchen and bathroom, a system shall be installed that exhausts directly to the outdoors and meets one of the following Rater measuredairflow standards: 18,24,25

≥ 5 ACH, based on kitchen volume 27 OR ≥ 100 CFM 28

A / BA / B

Page 129: ENERGY STAR Qualified Homes

8.1

Recirculating fan installed that does not exhaust to outside.

HVAC System Quality Installation Rater Checklist

In each kitchen and bathroom, a system shall be installed that exhausts directly to the outdoors and meets one of the following Rater measuredairflow standards: 18,24,25

≥ 5 ACH, based on kitchen volume 27 OR ≥ 100 CFM 28

Exhaust fan has terminates to the outside.

CC

Page 130: ENERGY STAR Qualified Homes

8.1

Exhaust ductwork and penetration to the exterior have not been sealed.

In each kitchen and bathroom, a system shall be installed that exhausts directly to the outdoors and meets one of the following Rater measuredairflow standards: 18,24,25

≥ 5 ACH, based on kitchen volume 27 OR ≥ 100 CFM 28

Exhaust ductwork and penetration to the exterior have been sealed with mastic.

DD

Page 131: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 8. LOCAL MECHANICAL EXHAUST

In each kitchen and bathroom, a system shall be installed that exhausts directly to the outdoors and meets one of the following Rater measured airflow standards: 18,24,25

8.2 Bathroom

Continuous: ≥ 20 CFM

Intermittent Rate 26 : ≥ 50 CFM

Page 132: ENERGY STAR Qualified Homes
Page 133: ENERGY STAR Qualified Homes

HVAC System Quality Installation Rater Checklist

CFM rating may not meet the performance specification once installed.

Fan CFM rating is higher than the requirement increasing the likelihood that it will meet the performance level once installed.

8.2In each kitchen and bathroom, a system shall be installed that exhausts directly to the outdoors and meets one of the following Rater measured airflow standards: 18,24,25

≥ 20 CFM OR ≥ 50 CFM

A / BA / B

Page 134: ENERGY STAR Qualified Homes

8.2

Two exhaust terminations, joined in a roughly cut hole restrictive hole and not air sealed.

HVAC System Quality Installation Rater Checklist

In each kitchen and bathroom, a system shall be installed that exhausts directly to the outdoors and meets one of the following Rater measured airflow standards: 18,24,25

≥ 20 CFM OR ≥ 50 CFM

Exhaust has been properly installed, sealed, and terminates to outdoors.

CC

Page 135: ENERGY STAR Qualified Homes

8.2

Exhaust duct only mechanically fastened and not sealed.

HVAC System Quality Installation Rater Checklist

In each kitchen and bathroom, a system shall be installed that exhausts directly to the outdoors and meets one of the following Rater measured airflow standards: 18,24,25

≥ 20 CFM OR ≥ 50 CFM

Exhaust duct has been mechanically fastened and sealed with mastic.

DD

Page 136: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 8. LOCAL MECHANICAL EXHAUST

8.3 If fans share common exhaust duct, back-draft dampers installed.

8.4 Common exhaust duct not shared by fans in separate dwellings.29

Page 137: ENERGY STAR Qualified Homes
Page 138: ENERGY STAR Qualified Homes

8.3-4

Fan shares exhaust and does not have a back-draft damper installed.

HVAC System Quality Installation Rater Checklist

If fans share common exhaust duct, back-draft dampers installed AND Common exhaust duct not shared by fans in separate dwellings.29

Fan shares exhaust and has a back-draft damper installed.

AA

Page 139: ENERGY STAR Qualified Homes

8.3-4

Back-draft damper still has a piece of tape that prevented it from rattling during shipping.

HVAC System Quality Installation Rater Checklist

If fans share common exhaust duct, back-draft dampers installed AND Common exhaust duct not shared by fans in separate dwellings.29

Packing tape has been removed and damper will be able to function properly once fan is installed.

BB

Page 140: ENERGY STAR Qualified Homes

8.3-4

Fans from separate dwellings exhausted together without back-draft dampers and not sealed.

If fans share common exhaust duct, back-draft dampers installed AND Common exhaust duct not shared by fans in separate dwellings.29

Separate dwellings with their own separate exhaust terminations.

CC

Page 141: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 8. LOCAL MECHANICAL EXHAUST

8.5 Clothes dryers vented directly to outdoors, except for ventless dryers equipped with a condensate drain.

Page 142: ENERGY STAR Qualified Homes
Page 143: ENERGY STAR Qualified Homes

8.5

Dryer vent is run vertical with a 90 degree bend and does not vent to the outside.

HVAC System Quality Installation Rater Checklist

Clothes dryers vented directly to outdoors, except for ventless dryers equipped with a condensate drain.

Dryer vents directly to the outdoors.

AA

Page 144: ENERGY STAR Qualified Homes

8.5

Dryer exhaust line terminates in the crawlspace.

HVAC System Quality Installation Rater Checklist

Clothes dryers vented directly to outdoors, except for ventless dryers equipped with a condensate drain.

Dryer vents directly to the outdoors.

AA

Page 145: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 9. VENTILATION & EXHAUST FAN RATINGS (EXEMPTIONS FOR HVAC AND REMOTE-MOUNTED FANS) 30

9.1 Intermittent supply & exhaust fans rated at ≤ 3 sones by mfr., unless rated flow ≥ 400 CFM

9.2 Continuous supply & exhaust fans rated at ≤ 1 sone by manufacturer.

9.3 Bathroom fans used as part of a whole-house mechanical ventilation system shall be ENERGY STAR qualified; unless rated flow rate ≥ 500 CFM.

Page 146: ENERGY STAR Qualified Homes
Page 147: ENERGY STAR Qualified Homes

9.1-3

INTERMITTENT FAN SONE RATING — Verify fans are installed with less than 3 sones by manufacturer.

HVAC System Quality Installation Rater Checklist

Intermittent supply & exhaust fans rated at ≤ 3 sones by mfr., unless rated flow ≥ 400 CFM

Page 148: ENERGY STAR Qualified Homes

9.1-3

Sone rating is greater than 1 on a continuous exhaust fan.

HVAC System Quality Installation Rater Checklist

Continuous supply & exhaust fans rated at ≤ 1 sone by manufacturer.

Sone rating is less than or equal to 1 on a continuous exhaust fan.

CC

Page 149: ENERGY STAR Qualified Homes

HVAC System Quality Installation Rater Checklist

The fan does not have an ENERGY STAR label.

The fan has an ENERGY STAR label.

9.1-3Bathroom fans used as part of a whole-house mechanical ventilation system shall be ENERGY STAR qualified; unless rated flow rate ≥ 500 CFM.

D / ED / E

Page 150: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 10. COMBUSTION APPLIANCES

10.1 Furnaces, boilers, and water heaters located within the home’s pressure boundary are mechanically drafted or direct-vented. As an exception, naturally drafted equipment is allowed in Climate Zone 1-3. For naturally drafted furnaces, boilers, and water heaters, the Rater has followed RESNET or BPI combustion safety test procedures and met the selected standard’s limits for depressurization, spillage, draft pressure, and CO concentration in ambient air, as well as a CO concentration in the flue of ≤ 25 ppm. 31,32,33

Page 151: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 10. COMBUSTION APPLIANCES

10.2 For fireplaces that are not mechanically drafted or direct-vented to outdoors, total net rated exhaust flow of the two largest exhaust fans (excluding summer cooling fans) is < 15 CFM per 100 sq. ft. of occupiable space when at full capacity or the Rater has verified that the pressure differential is ≤ -5 Pa using BPI’s or RESNET’s worst-case depressurization test procedure. 24,32,33,34,35

Page 152: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 10. COMBUSTION APPLIANCES

10.3 If unvented combustion appliances other than cooking ranges are located inside the home’s pressure boundary, the Rater has operated the appliance for at least 10 minutes and verified that the ambient CO level does not exceed 35 ppm. 36

Page 153: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 10. COMBUSTION APPLIANCES

10.1 Furnaces, boilers, and water heaters located within the home’s pressure boundary are mechanically drafted or direct-vented. As an exception, naturally drafted equipment is allowed in Climate Zone 1-3. For naturally drafted furnaces, boilers, and water heaters, the Rater has followed RESNET or BPI combustion safety test procedures and met the selected standard’s limits for depressurization, spillage, draft pressure, and CO concentration in ambient air, as well as a CO concentration in the flue of ≤ 25 ppm. 31,32,33

Page 154: ENERGY STAR Qualified Homes
Page 155: ENERGY STAR Qualified Homes

10.1

Atmospherically vented heater installed. Requires combustion safety testing.

HVAC System Quality Installation Rater Checklist

Furnaces, boilers, and water heaters located within the home’s pressure boundary are mechanically drafted or direct-vented to outdoors. If naturally drafted then combustion safety testing is required. 31, 32, 33

Direct vent appliance installed.

AA

Page 156: ENERGY STAR Qualified Homes

10.1

Atmospherically vented water heater installed. Requires combustion safety testing.

HVAC System Quality Installation Rater Checklist

Furnaces, boilers, and water heaters located within the home’s pressure boundary are mechanically drafted or direct-vented to outdoors. If naturally drafted then combustion safety testing is required. 31, 32, 33

Power vented water heater installed.

AA

Page 157: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 10. COMBUSTION APPLIANCES

10.2 For fireplaces that are not mechanically drafted or direct-vented to outdoors, total net rated exhaust flow of the two largest exhaust fans (excluding summer cooling fans) is < 15 CFM per 100 sq. ft. of occupiable space when at full capacity or the Rater has verified that the pressure differential is ≤ -5 Pa using BPI’s or RESNET’s worst-case depressurization test procedure. 24,32,33,34,35

Page 158: ENERGY STAR Qualified Homes
Page 159: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 10. COMBUSTION APPLIANCES

10.3 If unvented combustion appliances other than cooking ranges are located inside the home’s pressure boundary, the Rater has operated the appliance for at least 10 minutes and verified that the ambient CO level does not exceed 35 ppm. 36

Page 160: ENERGY STAR Qualified Homes
Page 161: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

SECTION 11. FILTRATION

11.1 At least one MERV 6 or higher filter installed in each ducted mechanical system.37

11.2 All return air and mechanically supplied outdoor air pass through filter prior to conditioning.

11.3 Filter located and installed so as to facilitate access and regular service by the owner.38

11.4 Filter access panel includes gasket or comparable sealing mechanism and fits snugly against the exposed edge of filter when closed to prevent bypass.39

Page 162: ENERGY STAR Qualified Homes
Page 163: ENERGY STAR Qualified Homes

11.1-4

The installed filter is not a MERV 6 filter.

HVAC System Quality Installation Rater Checklist

At least one MERV 6 or higher filter installed in each ducted mechanical system.37

The installed filter is at least a MERV 6 filter.

AA

Page 164: ENERGY STAR Qualified Homes

11.1-4

BAD PIC OF INCORRECT FILTER FOR SYSTEM INSTALLED

HVAC System Quality Installation Rater Checklist

At least one MERV 6 or higher filter installed in each ducted mechanical system.37

HVAC HOMEOWNER MANUAL SHOWING WHICH FILTER SHOULD BE INSTALLED OR PROPER FILTER INSTALLED

BB

Page 165: ENERGY STAR Qualified Homes

11.1-4

There is no filter installed in the HVAC system.

HVAC System Quality Installation Rater Checklist

All return air and mechanically supplied outdoor air pass through filter prior to conditioning.

GOOD PIC OF MERV 6 OR HIGHER FILTER INSTALLED.

CC

Page 166: ENERGY STAR Qualified Homes

11.1-4

There is no filter installed to filter the outdoor air.

HVAC System Quality Installation Rater Checklist

All return air and mechanically supplied outdoor air pass through filter prior to conditioning.

There is a filter installed to filter outdoor air.

DD

Page 167: ENERGY STAR Qualified Homes

11.1-4

BAD PIC OF FILTER LOCATION

HVAC System Quality Installation Rater Checklist

Filter located and installed so as to facilitate access and regular service by the owner.38

GOOD PIC OF ACCESSIBLE FILTER LOCATION WITH MERV 6 INSTALLED

EE

Page 168: ENERGY STAR Qualified Homes

11.1-4

The filter is installed in the crawlspace and is not easily accessible.

HVAC System Quality Installation Rater Checklist

Filter located and installed so as to facilitate access and regular service by the owner.38

GOOD PIC OF ACCESSIBLE FILTER LOCATION

FF

Page 169: ENERGY STAR Qualified Homes

11.1-4

No gasket at filter location.

HVAC System Quality Installation Rater Checklist

Filter access panel includes gasket or comparable sealing mechanism and fits snugly against the exposed edge of filter when closed to prevent bypass.39

GOOD PIC OF GASKET AT FILTER LOCATION

GG

Page 170: ENERGY STAR Qualified Homes

ENERGY STAR® QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER CHECKLIST

EPA Disclaimer

Any mention of trade names, commercial products and organizations in this document does not imply endorsement by the U.S. Environmental Protection Agency ("EPA") or the U.S. Government. The EPA and its collaborators make no warranties, whether expressed or implied, nor assume any legal liability or responsibility for the accuracy, completeness or usefulness of the contents of this publication, or any portion thereof, nor represent that its use would not infringe privately owned rights. Further, the EPA cannot be held liable for construction defects or deficiencies resulting from the proper or improper application of the content of this guidebook.