Energy Saving DDC Control Strategies
![Page 2: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/2.jpg)
BACnet
BCU
AH541CH530 ZN521
MP581
VV550
BCU
Operator Interface Level
Unit ControlLevel
Building ControlLevel
LonTalk
SQL Server
Ethernet LAN
DDC Controls Architecture
![Page 3: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/3.jpg)
Energy Saving Control Strategies for VAV Systems
Optimum Start/Stop
Fan Pressure Optimization
Supply Air Temperature Reset
Demand Controlled Ventilation
![Page 4: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/4.jpg)
Optimum Start/Stop
Lowers system run time Increases occupancy comfort
Tracer Summit Optimal Start
![Page 5: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/5.jpg)
Optimum Start/Stop
![Page 6: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/6.jpg)
Fan Pressure Optimization Fan Outlet Static Control (Good) Supply Duct Static Control
(Better) Critical Zone Reset (Best)
ASHRAE 90.1 Prescriptive Path
![Page 7: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/7.jpg)
Fan Outlet Static Control
VAVVAVterminal unitsterminal units
supplysupplyfanfan
static static pressure pressure sensorsensor
sensor locatedat fan outlet
![Page 8: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/8.jpg)
Fan Outlet Static Control
Sample Case
![Page 9: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/9.jpg)
Supply Duct Static Control
VAVVAVterminal unitsterminal units
supplysupplyfanfan
static static pressure pressure
sensorsensor
sensor located2/3 down supply duct
![Page 10: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/10.jpg)
Supply Duct Static Control
Sample Case
![Page 11: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/11.jpg)
Critical Zone Reset
damper damper positionspositions
communicating communicating BASBAS
fan speed fan speed
VAVVAVterminalterminalunitsunits
supplysupplyfanfan
static static pressure pressure sensorsensor
sensor locatedat fan outlet
![Page 12: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/12.jpg)
Critical Zone Reset
Sample Case
![Page 13: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/13.jpg)
Fan Pressure Optimization
controlcontrolmethodmethod airflowairflow
fan staticfan staticpressurepressure
fan inputfan inputpowerpower
% full-load% full-loadpowerpower
full load
fan outlet
supply duct
optimized
part load
24,000 cfm24,000 cfm[11.3 m[11.3 m33/s]/s]
18,000 cfm18,000 cfm[8.5 m[8.5 m33/s]/s]
18,000 cfm18,000 cfm[8.5 m[8.5 m33/s]/s]
18,000 cfm18,000 cfm[8.5 m[8.5 m33/s]/s]
2.7 in. H2.7 in. H22OO[672.5 Pa][672.5 Pa]
2.1 in. H2.1 in. H22OO[523.1 Pa][523.1 Pa]
1.9 in. H1.9 in. H22OO[473.3 Pa][473.3 Pa]
1.5 in. H1.5 in. H22OO[373.6 Pa][373.6 Pa]
22 hp22 hp[16.4 kW][16.4 kW]
13 hp13 hp[9.7 kW][9.7 kW]
12 hp12 hp[8.9 kW][8.9 kW]
9.5 hp9.5 hp[7.1 kW][7.1 kW]
100%100%
60%60%
55%55%
43%43%
![Page 14: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/14.jpg)
Fan Pressure Optimization
airflow
sta
tic p
ressu
re
1000 rpm800 rpm
900 rpm
duct static pressure control
fan-pressure optimization
surge
potential savings
![Page 15: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/15.jpg)
Fan Pressure Optimization Advantages
Reduced supply fan energy Lower sound levels Reduced risk of fan surge
![Page 16: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/16.jpg)
Supply Air Temperature Reset Advantages
Lower compressor and reheat energy
Increased economizing time Disadvantages
May increase fan energy Increased humidity level
Key to success: Combine as a balanced approach
with fan pressure optimization
![Page 17: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/17.jpg)
Basic Control Model ExampleSAT Reset, Pressure Optimization, Opt
Start
![Page 18: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/18.jpg)
Demand-Controlled Ventilation Methods of Ventilation:
Fixed Damper position OA method (min at design) ASHRAE method (min at worst case)
Flow Control Ventilation Reset
![Page 19: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/19.jpg)
Demand-Controlled Ventilation What kind of energy saving should
you expect?
30
40
50
60
70
80
90
100
% HVAC Energy Consumption
Miami Minneapolis Seattle Toronto
Ventilation Control Method Comparison
Fixed Damper
Flow Control
Ventilation Reset
![Page 20: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/20.jpg)
Demand-Controlled Ventilation How do I save more energy?
The right tools CO2 sensors Occupancy sensors TOD schedule
Advantages Ensures compliance with ASHRAE 62.1 Reduce outside air during low
occupancy Decreases reheat energy LEED EQ Credit 1: Outdoor Air delivery
monitoring
![Page 21: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/21.jpg)
LEED Credit Possibilities EA Prereq 1 – Commissioning EA Prereq 2 – Minimum Energy
performance EQ Prereq 1 – Minimum IAQ performance EA Credit 1 – Optimize Energy Performance
through energy simulation EQ Credit 1 – Outdoor air delivery
monitoring EQ Credit 2 – Increased Ventilation EQ Credit 6.2 – Controllability of systems:
Thermal Comfort EQ Credit 7.1 – Thermal Comfort: Design
![Page 22: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/22.jpg)
Chiller Plant Optimization
Chilled Water Reset Increasing chilled water temp to
reduce compressor energy Increases pumping energy
Plant optimization Weighing the energy use of CT vs.
Chiller vs. Pumps COP Weight
![Page 23: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/23.jpg)
Chiller Plant Optimization
Modeled Example
![Page 24: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/24.jpg)
Energy Management
“Intelligent Building”
Building Dashboards
Demand Control
![Page 25: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/25.jpg)
Energy Management
![Page 26: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/26.jpg)
Energy Management
![Page 27: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/27.jpg)
Retro-Commissioning
The Easiest Energy Saver
Building Operators Changes
How To Stay On Top Of This
![Page 28: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/28.jpg)
Constant Reporting
![Page 29: Energy Saving DDC Control Strategies. BACnet BCU AH541 CH530 ZN521 MP581 VV550 BCU Operator Interface Level Unit Control Level Building Control Level](https://reader037.vdocuments.us/reader037/viewer/2022110206/56649cfa5503460f949ccbaa/html5/thumbnails/29.jpg)