energy recovery wheel feasibility study
DESCRIPTION
Energy Recovery Wheel Feasibility StudyTRANSCRIPT
Calculation sheet
Project vv
Project Consultant vvv
Client vv
Contractor vv
Subject Proposal for Energy Recovery Wheel with life cycle cost analysis
Location vv
Design By vv
Energy Recovery Wheel (ERW) calculation
Air flow data for energy recovery wheel
Out door air dry bulb temperature 32 ⁰C
Out door air RH 80 %
Toilet exhaust air temperature 25 ⁰C
Toilet exhaust air RH 50 %
Block 06
Enerdy recovery wheel 01 l/s Pa
Toilet exhaust air flow rate / external static pressure 3175 335
Supply air flow rate / external static pressure 5467 300
Enerdy recovery wheel 02
Toilet exhaust air flow rate / external static pressure 2740 365
Supply air flow rate / external static pressure 6338 300
Data from the selection sheet
Without ERW With ERW
Power of AHU riser 01 OA fan 5.50 kW Power S/A fan of ERW 01 8.96 kW
Power of AHU riser 02 OA fan 7.50 kW Power E/A fan of ERW 01 5.69 kW
Toilet exhaust riser 01 4.00 kW Power S/A fan of ERW 02 4.89 kW
Toilet exhaust riser 02 4.00 kW Power E/A fan of ERW 02 10.96 kW
Power Rotor drive motor ERW 01 0.18 kW
Toilet Toilet exhaust
Out door Supply
T1=DBT= 25 ⁰CRH1 = 50 %
T3=DBT= 32 ⁰C
T2=DBTRH2
T4=DBTRH4Q4
Calculation sheet
Power Rotor drive motor ERW 02 0.18 kW
ERW No 01 thermal energy saving 116 kWh
ERW No 02 thermal energy saving 100 kWh
Assumptions/ conditions:
1. Energy savings of individual equipments due to ERW are not considered
2. COP of the chiller (from the employer's requirement of the tendeder document) 5 COP = refrigerent effect in kW / input in kW
3. Thermal load saving due to ERW is equal to the thermal load saving of chillers
4. Electricity cost due to maximum demand is not considered
5. Electricity charge Unit charge Fixed charge
14.55 kW/kWh 3000 LKR/month
6. Working hours : 8 working hours per day
: 20 working days per month
: 12 months per year
7. Sensible effectiveness (εsensible) 0.7 for the calculation according to the AHRI guide line
8. Latent effectiveness (εsensible) 0.7 for the calculation according to the AHRI guide line
9. Air density, Specific heat (Cp) & humidity (from Data generated from the software developed by S.A.Klein and F.L.Alvarado.)
TemperatureDensity
Specific
Heat
t ρ cp
( o C) (kg/m 3 ) (kJ/(kg K)) ρ (kg/m3)
cp (kJ/(kg
K))
w (from
psychrome
tric chart)
20 1.204 1.007 t1 1.278 1.1564 0.0244
25 1.184 1.007 t3 1.184 1.007 0.0099
30 1.164 1.007
35 1.145 1.007
10. hfg 2501000 J/kg
11. Depreciation Allowance for Plant & Machinery (x) 30% Budget Highlights 2015 by SJMS ASSOCIATES
12. Descount rate (r) 10%
13. Electric differential escalation (z) 10%
Calculation sheet
Calculations
Calculation according to AHRI standard
ERW 01 ERW 02
Mass flow rate entering exhaust air me 3.76 3.27 kg/s
Mass flow rate supply air ms 3.76 3.27 kg/s
ERW 01 ERW 02
Sensible energy recovered (kW) Qsensible = ε sensible x m min x Cp (t1-t3) 21.30 18.56
Latent energy recovered (kW) Qlatent = ε latent x m min x hfg (w1-w3) 95.43 83.13
Total energy recovered (kW) Qtotal= Qsensible + Qlatent 116.73 101.69
- When recovered energy is considered, there is a little difference between product selection data and results of the calculation done according to the
AHRI guideline V -2011. Because actual effectivenesses of the product vary from 0.7.
- Technical data (power consumptions and pressure drops) for fans, and energy recovery wheels are taken from a manufacture's data of a ERWs system
(DRI ecofresh ERW) which fulfil our requirement.
Total thermal energy saving 218.42 kWh From the calculations done accrording to the AHRI guide lines
Electrical energy saving due to thermal energy saving (ES,ERW) 43.68 kWh ES,ERW = (Thermal energy saving / COP) x 1 hour
Total operating energy
Without an ERW system With an ERW system
E T = E0 + E FASF + E TEF E T,ERW = (E0 - ES,ERW) + E SAF + E EAF + E ERW
Where
E T : Total operating energy without an ERW system
E0 : Operating energy of all the equipment except fresh air supply fans and toilet exhaust fans
E FASF : Operating energy of Fresh air supply fans
E TEF : Operating energy of Toilet exhaust fans
E T,ERW : Total operating energy with an ERW system
E1 : Operating energy of all the equipment except supply fans and exhaust fans
E SAF : Operating energy of supply air fans
Calculation sheet
E EAF : Operating energy of exhaust air fans
E ERW : Operating energy recovery wheel
Total electrical energy saving per hour {ET - E T,ERW = E0 + E FASF + E TEF - [(E0 - ES,ERW) + E SAF + E EAF + E ERW]}
33.83 kWh
Total electrical energy saving per year 64,959.66 kWh
Total electrical energy cost saving per year 981,163.12 LKR/year
Life cycle cost analysis
Capital cost for the system without ERW = Cost for supply and installation of all the equipments except FASF & TEF + Supply and istallation cost of FASF &
TEF(without ERW) + supply and installation of ducting
Capital cost for the system with ERW = Cost for supply and installation of all the equipments except ERW complete with fans + Supply and istallation cost of
ERW complete with fans + supply and installation of ducting
In above two costs, first terms of right hand side are equal.
Therefore gross capital cost for the ERW = Supply and istallation cost of ERW complter with fans - Supply and istallation cost of FASF & TEF
Supply and installation cost for FASF & TEF - if there is no ERW + ducting ########## LKR
Supply and istallation cost for ERW complete with fans and ducting ########## LKR
Therefore gross capital cost for the ERW 842,720.63 LKR
Without
ERW
ERW 01 ERW 02
Fans operating cost per year
Supply fan operating cost 250,222.75 136,467.36 363,168.00
Exhaust fan operating cost 159,067.58 306,038.88 223,488.00
Motor of rotery wheel operating cost 5,028.48 5,028.48
Total electricity cost per year Operating cost per year due to ERW system
Maintenance cost per year 30,000.00 30,000.00
With ERW system
311,197.54
Calculation sheet
Des
crip
tio
n
Dis
cou
nte
d P
V
(a)
Dis
cou
nte
d r
esid
ual
valu
e
(b=P
V o
f a(
1-x
)^n
)
Mai
nte
nan
ce c
ost
(c=c
1(1
+r)^
n)
Dis
cou
nte
d P
V
(d=c
/(1
+r)^
n)
Elec
tric
ity
cost
( e=
q(1
+z)^
n)
Dis
cou
nte
d P
V
(f=e
/(1
+r)^
n)
Tota
l co
sts
(g=c
+e)
Dis
cou
nte
d P
V
(h
=d+f
)
Dis
cou
nte
d
cum
ula
tive
co
sts
(i)
An
nu
al S
avin
g d
ue
to
reco
very
(j)
Gro
ss s
avin
g
(k=j
-e)
Dis
cou
nte
d t
ota
l
savi
ng
(l=k
/(1
+r)^
n)
Dis
cou
nte
d
cum
ula
tive
sav
ing
(m)
0 Initial value 842,720.63 842,720.63 842,720.63 842,720.63 0.00 842,720.63
1 536,276.76 66,000.00 60,000.00 342,317.29 311,197.54 408,317.29 371,197.54 1,213,918.16 1,381,996.72 1,039,679.43 945,163.12 945,163.12 (267,521.72)
2 341,267.03 72,600.00 60,000.00 376,549.02 311,197.54 449,149.02 371,197.54 1,585,115.70 1,520,196.39 1,143,647.37 945,163.12 1,890,326.23 (646,477.57)
3 217,169.93 79,860.00 60,000.00 414,203.92 311,197.54 494,063.92 371,197.54 1,956,313.24 1,672,216.03 1,258,012.11 945,163.12 2,835,489.35 (1,096,346.04)
4 138,199.05 87,846.00 60,000.00 455,624.31 311,197.54 543,470.31 371,197.54 2,327,510.77 1,839,437.63 1,383,813.32 945,163.12 3,780,652.47 (1,591,340.74)
5 87,944.85 96,630.60 60,000.00 501,186.74 311,197.54 597,817.34 371,197.54 2,698,708.31 2,023,381.40 1,522,194.65 945,163.12 4,725,815.59 (2,115,052.13)
6 55,964.90 106,293.66 60,000.00 551,305.42 311,197.54 657,599.08 371,197.54 3,069,905.84 2,225,719.54 1,674,414.12 945,163.12 5,670,978.70 (2,657,037.76)
7 35,614.03 116,923.03 60,000.00 606,435.96 311,197.54 723,358.99 371,197.54 3,441,103.38 2,448,291.49 1,841,855.53 945,163.12 6,616,141.82 (3,210,652.47)
8 22,663.47 128,615.33 60,000.00 667,079.56 311,197.54 795,694.88 371,197.54 3,812,300.92 2,693,120.64 2,026,041.08 945,163.12 7,561,304.94 (3,771,667.50)
9 14,422.21 141,476.86 60,000.00 733,787.51 311,197.54 875,264.37 371,197.54 4,183,498.45 2,962,432.70 2,228,645.19 945,163.12 8,506,468.06 (4,337,391.81)
10 9,177.77 155,624.55 60,000.00 807,166.26 311,197.54 962,790.81 371,197.54 4,554,695.99 3,258,675.97 2,451,509.71 945,163.12 9,451,631.17 (4,906,112.96)
11 5,840.40 171,187.00 60,000.00 887,882.89 311,197.54 1,059,069.89 371,197.54 4,925,893.52 3,584,543.57 2,696,660.68 945,163.12 10,396,794.29 (5,476,741.17)
12 3,716.62 188,305.70 60,000.00 976,671.18 311,197.54 1,164,976.88 371,197.54 5,297,091.06 3,942,997.93 2,966,326.75 945,163.12 11,341,957.41 (6,048,582.97)
13 2,365.12 207,136.27 60,000.00 1,074,338.30 311,197.54 1,281,474.57 371,197.54 5,668,288.60 4,337,297.72 3,262,959.42 945,163.12 12,287,120.52 (6,621,197.05)
14 1,505.08 227,849.90 60,000.00 1,181,772.13 311,197.54 1,409,622.03 371,197.54 6,039,486.13 4,771,027.49 3,589,255.37 945,163.12 13,232,283.64 (7,194,302.59)
15 Residual value 957.78 250,634.89 60,000.00 1,299,949.34 311,197.54 1,550,584.23 371,197.54 6,410,683.67 5,248,130.24 3,948,180.90 945,163.12 14,177,446.76 (7,767,720.87)
- The results shows a negative life cycle cost. That means we have a saving in the life cycle of the ERWs system.
- According to the below chart, pay back period is 2 years.
Saving
Tota
l co
st a
fter
eac
h y
ear
(p=i
-m-b
)
Year
Investment related costsAnnual recurring costs
(maintenance)Electricity Total costs
Calculation sheet
Energy recovery system for toilet exhaust and fresh air sypply system - comparison between Run-Around loop and Energy Recovery Wheel
(6,000,000.00)
(4,000,000.00)
(2,000,000.00)
0.00
2,000,000.00
4,000,000.00
6,000,000.00
8,000,000.00
10,000,000.00
12,000,000.00
14,000,000.00
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Cumulative cost, saving and cost after each year Vs years
Discounted cumulative costs(i)
Discounted cumulative saving (m) Total cost after each year(p=i-m-b)
Calculation sheet
Data availble
Air flow data for energy recovery system
Out door air dry bulb temperature (t1) 32.2 ⁰C
Out door air RH1 80 %
Toilet exhaust air temperature (t3) 25 ⁰C
Toilet exhaust air RH3 50 %
Energy recovery for riser 01 l/s Pa
Toilet exhaust air flow rate | external static pressure 3175 335
Supply air flow rate | external static pressure 5467 300
Energy recovery for riser 02
Toilet exhaust air flow rate | external static pressure 2740 365
Supply air flow rate | external static pressure 6338 300
Calculation sheet
Assumptions/ conditions:
1. Energy savings of individual equipments due to an energy recovery system are not considered
2. COP of the chiller (from the employer's requirement of the tender document) = 6.2 COP = refrigerent effect in kW / input in kW
3. Thermal load saving due to ERW is equal to the thermal load saving of chillers
4. Sensible effectiveness (εsensible) 0.6 from AHRI guide line V
5. Latent effectiveness (εsensible) 0.6 from AHRI guide line V
6. Air density, Specific heat (Cp) & humidity (from Data generated from the software developed by S.A.Klein and F.L.Alvarado.)
ρ (kg/m3)
cp (kJ/(kg
K))
w (from
psychrome
tric chart)
t1 1.175 1.005 0.0244
t3 1.184 1.005 0.0099
7. hfg 2501000 J/kg
8. Equal volume of supply air and toilet exhaust air are passed through the wheel. The balance fresh air is mixed in the mixing box after the wheel.
Calculations
ERW 01 ERW 02
Mass flow rate entering exhaust air me 3.73 3.24 kg/s
Mass flow rate supply air ms 3.73 3.24 kg/s
Run-Around
loop - 01 ERW 01
Run-Around
loop - 02 ERW - 02
Recovered sensible heat transfer rate(kW) Qsensible = ε sensible x m min x Cp (t1-t3) 16.20 16.20 14.08 14.08
Recovered latent heat transfer rate(kW) Qlatent = ε latent x m min x hfg (w1-w3) 0 81.17 0 70.59
Recovered total heat transfer rate (kW) Qtotal= Qsensible + Qlatent 16.20 97.37 14.08 84.67
Electrical power saving (kW) (Qtotal/COP) 2.61 15.70 2.27 13.66
Riser 01 Riser 02
t2 = t1-Qs/(m1Cp1) 27.88 27.88 ⁰C
Energy Recovery System -
01
Energy Recovery System -
02
Calculation sheet
t3 = t3+Qs/(m1Cp1) 29.32 29.32 ⁰C
Calculation for the pump power
Note: - For the estimation circulation liquid is considered as water
- t1,t2 and t3 data are provided for a coil selection software (developed by S & P Coil Product Ltd, England) to findout fluid flow rates, pressure drops etc.
Result sheet is attached (Annex).
- Consider the 32mm Copper tubing for water stream, and same pipe arrangement is considered for both loops
- Flow velocity- 1m/s, Friction Loss- 400Pa/m
- As per Carrier Pipe Design Manual
Qty Equalent
Length (m) -
le
Length (m) -
l (=Qty x le) Friction Loss
(Pa) - l x 400
Straight Pipe 1 30.00 30 12000
90 0 screwed elbows 6 0.70 4.2 1680
Globe Valves 6 11.58 69.48 27792
Non-return Valves 1 4.27 4.27 1708
Strainer 1 2.74 2.74 1096
T joints 3 2.13 6.39 2556
46832
Pipe/Fitting/Valve
Calculation sheet
Total Pump pressure drop without coils 46.83 kPa
Riser 01 Riser 02
Drop through coil 57.80 57.6 kPa From coil selection sheet ()
Total Pump pressure drop with coils 104.63 104.43 kPa
Safety Factor to pressure drop 1.05 1.05 kPa
Pump pressure drop with SF 109.86 109.65 kPa
Water flow rate 0.90 0.8 l/s From coil selection sheet ()
Required Power to pump (QxH/η) 0.15 0.13 kW : η = 65%
Fans static pressure
Run - around coil
Riser 01 Riser 02
S/A Fans static pressure (external static pressure+pressure drop through coil) 539.7 453.9 Pa
TEA Fans static pressure (external static pressure+pressure drop through coil) 573.1 517.9 Pa
Energy recovery wheel
Pressure drop through wheel 200 200 Pa
S/A Fans static pressure (external static pressure+pressure drop through wheel) 500 500 Pa
TEA Fans static pressure (external static pressure+pressure drop through wheel) 535 565 Pa
Power consumption with ERW
Note: fan efficiency ( η ) is considered as 65%
ERW 01 ERW 02
Power S/A fan (QxH/η) 4.21 4.88 kW
Power E/A fan (QxH/η) 2.61 2.38 kW
Power Rotor drive motor 0.18 0.18 kW Data sheet attached
Total 7.00 7.44 kW
Power consumption with run around loop
Loop 01 Loop 02
Power S/A fan (QxH/η) 4.54 4.43 kW
Calculation sheet
Power E/A fan (QxH/η) 2.80 2.18 kW
Power for pump 0.15 0.13 kW Data sheet attached
Total 7.49 6.74 kW
Power consumption without ERU
Riser 01 Riser 02
Power of AHU OA fan (QxH/η) 2.52 2.93 kW
Power of toilet exhaust fan (QxH/η) 1.64 1.54 kW
Total 4.16 4.46 kW
Run around
loop ERW
Riser 01 -0.72 12.87 kW
Riser 02 -0.01 10.68 kW
Power saving {Consumption without
ERU-(Consumption with ERU-Saving
due to ERU)}