energy analysis of commercial buildings in subtropical climates - … · 2015. 5. 22. ·...

8
AIVC 12,430 PERGAMON Building and Environment 35 (2000) 19-26 www.elsevier.com/locate/buildenv Energy analysis of commercial buildings in subtropical climates Joseph C. Lam* Building £11erg_r Rcsearclr Gro11p, Departmelll o f Building and Construction, City U11il'ersity o f Hong Kong, Tat Chee A l'mte, Ku1rloo11, Hong Kong Received 8 October 1997; received in revised form 20 October 1998; accepted 24 November 1998 Abstract The overall thermal transfer value ( OTTV) concept has been extended to correlate the OTTV of building envelope designs with other key building design parameters through DOE-2 computer simulations. A survey of 146 commercial buildings completed between 1975 and 1995 provides the inrmation on the prevailing architectural designs and construction practices in Hong Kong. This inrmation forms a basis for the development of a generic office building used in the computer analysis. Four major design aspects have been considered, namely the building envelope, indoor design conditions, internal loads and heating, ventilation and air-conditioning (HYAC). Implications r energy efficiency in the commercial sector energy use are discussed. 1999 Elsevier Science Ltd. All rights reserved. 1. Introduction THERE have been growing concerns about energy consumption and its implications for the environment. With high economic growth, Hong Kong has seen a dramatic increase in energy consumption in recent years, particularly electricity use in commercial and residential buildings [ l]. Fig. 1 shows the electricity consumption in the residential and commercial sectors during the 26-year period from 1971 to 1996. It can be seen that housing stocks consumed 1059 and 8109 GWh in 1971 and 1996, respectively. This represents an average annual growth rate of 8.5% during the 26- year period. In the commercial sector, electricity use rose from 1780 GWh in 1971 to 17,907 GWh in 1996, an increase of 906%. This corresponds to an average rate of increase of 9.7% per year. In 1996, electricity use in commercial buildings accounted r just over half of the total electricity consumption and rep- resented about one-third of the total primary energy requirement in Hong Kong. Most electricity is used r lighting and air-con- * Tel.: + 852-2788-7609; fax: + 852-2788-7612. E-mail address: bcex[email protected].hk (J.C. Lam) ditioning in subtropical Hong Kong, where the sum- mer is long, hot and humid. Cooling season runs om late March to early November r commercial build- ings. Recent surveys indicate that air-conditioning accounts for 50-60% of the total electricity use [1]. In response to the growing concerns about energy con- sumption and its implications for the environment, the Government decided to introduce legislative control of the building envelope designs through the overall ther- mal transfer value (O T TV) method. After consultation with the building professions, an O T TV limit of 35 W/ m 2 was set r all commercial buildings (i.e. offices, offices/shopping complexes and hotels) in 1995 [3]. Since then, there have been growing interests among researchers and building designers in building envelope designs in terms of the O T TV, its interactions with other major design considerations and their impli- cations for energy efficiency. Computer building simu- lation techniques have been used in the present study to investigate the interrelationship between the O T TV and other key design parameters and their impacts on electricity use in commercial buildings. This paper out- lines the O T TV concept, describes the energy analysis, presents the findings and discusses the implications for energy efficiency strategy in designing commercial building. 0360-1323/00/$ - sec front matter 1999 Elsevier Science Ltd. All rights reserved. Pll: S0360-l 323(98)00067-5

Upload: others

Post on 12-Nov-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Energy analysis of commercial buildings in subtropical climates - … · 2015. 5. 22. · requirement in Hong Kong. Most electricity is used for lighting and air-con-* Tel.: + 852-2788-7609;

AIVC 12,430

PERGAMON Building and Environment 35 (2000) 19-26

www.elsevier.com/locate/buildenv

Energy analysis of commercial buildings in subtropical climates Joseph C. Lam*

Building £11erg_r Rcsearclr Gro11p, Departmelll of Building and Construction, City U11il'ersity of Hong Kong, Tat Chee A l'<'mte, Ku1rloo11, Hong Kong

Received 8 October 1997; received in revised form 20 October 1998; accepted 24 November 1998

Abstract

The overall thermal transfer value ( OTTV) concept has been extended to correlate the OTTV of building envelope designs

with other key building design parameters through DOE-2 computer simulations. A survey of 146 commercial buildings completed between 1975 and 1995 provides the information on the prevailing architectural designs and construction practices in Hong Kong. This information forms a basis for the development of a generic office building used in the computer analysis. Four major design aspects have been considered, namely the building envelope, indoor design conditions, internal loads and heating,

ventilation and air-conditioning (HY AC). Implications for energy efficiency in the commercial sector energy use are discussed. � 1999 Elsevier Science Ltd. All rights reserved.

1. Introduction

THERE have been growing concerns about energy

consumption and its implications for the environment.

With high economic growth, Hong Kong has seen a

dramatic increase in energy consumption in recent

years, particularly electricity use in commercial and

residential buildings [ l]. Fig. 1 shows the electricity

consumption in the residential and commercial sectors

during the 26-year period from 1971 to 1996. It can be

seen that housing stocks consumed 1059 and 8109

GWh in 1971 and 1996, respectively. This represents

an average annual growth rate of 8.5% during the 26-

year period. In the commercial sector, electricity use

rose from 1780 GWh in 1971 to 17,907 GWh in 1996,

an increase of 906%. This corresponds to an average

rate of increase of 9.7% per year. In 1996, electricity

use in commercial buildings accounted for just over

half of the total electricity consumption and rep­

resented about one-third of the total primary energy

requirement in Hong Kong.

Most electricity is used for lighting and air-con-

* Tel.: + 852-2788-7609; fax: + 852-2788-7612.

E-mail address: [email protected] (J.C. Lam)

ditioning in subtropical Hong Kong, where the sum­mer is long, hot and humid. Cooling season runs from late March to early November for commercial build­ings. Recent surveys indicate that air-conditioning

accounts for 50-60% of the total electricity use [1]. In

response to the growing concerns about energy con­

sumption and its implications for the environment, the

Government decided to introduce legislative control of

the building envelope designs through the overall ther­mal transfer value (O T TV) method. After consultation

with the building professions, an O T TV limit of 35 W/ m2 was set for all commercial buildings (i.e. offices,

offices/shopping complexes and hotels) in 1995 [3].

Since then, there have been growing interests among

researchers and building designers in building envelope

designs in terms of the O T TV, its interactions with

other major design considerations and their impli­

cations for energy efficiency. Computer building simu­

lation techniques have been used in the present study

to investigate the interrelationship between the O T TV and other key design parameters and their impacts on

electricity use in commercial buildings. This paper out­

lines the O T TV concept, describes the energy analysis,

presents the findings and discusses the implications for

energy efficiency strategy in designing commercial building.

0360-1323/00/$ - sec front matter ([_1 1999 Elsevier Science Ltd. All rights reserved.

Pll: S0360-l 323(9 8)00 067-5

Page 2: Energy analysis of commercial buildings in subtropical climates - … · 2015. 5. 22. · requirement in Hong Kong. Most electricity is used for lighting and air-con-* Tel.: + 852-2788-7609;

20 J.C. Lam! Building and Environment 35 ( 2000) 19-26

:2 15000 s: � c: 0 � E 10000 ::i U) c: 0 u :(!;-·u ·;:::: u 5000 <ll UJ

0 ..__..___.__..__.___.___.___..__..___.__..__.__..____.___.'--L-..___.__..__.__.____.__,�.__ ........... 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96

Year

Fig. I. Electricity consumption in the residential and commercial sectors from 1971 to 1996.

2. OTTV concept

The overall thermal transfer value (OTTV ) concept was introduced in the ASHRAE Standard 90A- 1980 by the American Society of Heating, Refrigerating and Air-Conditioning Engineers [4]. The OTTV is basically a measure of heat transfer from outside to the indoor environment through the external envelope of a build­ing. Three components of heat gain are considered­conduction through the opaque surface, conduction through the glass and solar radiation through the glass. It is an index of the overall thermal performance of a building envelope : smaller the 0 TTV, less the energy use for cooling. The usual practice is to have two separate OTTVs-one for the external walls (including windows) and the other for the roof (includ­ing skylights, if any).

2.1. OTTV equ ation for the w alls

As walls at different orientations receive different amounts of solar radiation, the general procedure is to calculate first the OTTVs of individual walls with the same orientation and construction, then the OTTV of the whole exterior wall is given by the weighted aver­age of these values. Thus:

OTTV; = (Qw + Qg + Q,)/ Ai,

(Aw· Uw · TDeq) + (Ar· Ur· D T) + (Af · SC · SF)

Ai

( 1)

where OTTV; is overall thermal transfer value of walls

with same orientation and construction (W/m2), Qw is heat conduction through opaque walls (W), Qg is heat conduction through glass windows (W), Qs is solar radiation through glass windows (W), Aw is area of opaque wall (m2), Uw is U-value of opaque wall (W/ m2), TDcq i equivalent temperature difference (K), Ar is area of feneslrati n (m2), Ur is U-value of fenestra­tion (W/m2K), D T is temperature difference between exterior and interior design conditions (K), SC is shad­ing coefficient of fenestration, SF is solar factor for that orientation (W /m2), Ai is gross area of the walls (m2)=Aw+ A r, and,

OTTV _ r.(OTTVi · A;)

wall - A , lw

(2)

where OTTVwall is OTTV of the whole exterior wall (W /m2) and Atw is r.(Ai) =total gross exterior wall area (m2).

Alternatively, Eq. (1) can be expressed in terms of the window-to-wall ratio, WWR. Thus:

OTTV; = (1 - WWR). TDeq. Uw + WWR. D T

· Ur + WW R · SC· SF, (3)

where WWR = the ratio of window area to gross wall area= Ar/ Ai·

2.2. OTTV equ ation for the roof

The approach and equations for calculating the roof OTTV are similar to those for the walls. Calculation for the roof is often much simpler because a roof

Page 3: Energy analysis of commercial buildings in subtropical climates - … · 2015. 5. 22. · requirement in Hong Kong. Most electricity is used for lighting and air-con-* Tel.: + 852-2788-7609;

J.C. Lam/ Building and Environment 35 ( 2000) 19-26 21

usually does not contain large amount of glazing (except skylights over an atrium). Heat gain through the roof is generally small compared with the external walls for two reasons. Firstly, most commercial build­ings in Hong Kong are high-rise (20 storeys or more),

roof area is, therefore, small compared with the exter­nal wall area. Secondly, most of the roofs have 40-50 mm thermal insulation (with a U-value less than 0.64 W/m2 K) with no skylight. Hence, there is no solar heat gain and the heat conduction through the roof is insignificant. Therefore, only the wall OTTV has been analysed.

2.3. OTTV and cooling load

The space cooling load is the rate at which heat has to be removed from th.! space to maintain a constant indoor air temperature. The sum of all the instan­taneous heat gain into the space at any given time is not necessarily equal to the cooling load for that space at that time. The effect of radiant heat into a space is not immediate. Firstly, it has to be absorbed by the surfaces enclosing the space (walls, floor and ceiling) and by objects within the space (furniture, fittings, people, etc.). Some of the heat absorbed will later be transferred to the indoor air by convection when these surfaces and objects are warmer than the room air. The main difference between instantaneous heat gain and space cooling load is the thermal storage effect of these surfaces and objects, and to some extent the ther­mal mass of the building envelope. For commercial buildings with central air-conditioning plants and fixed operating hours, the original OTTV concept can be extended to deal with the cooling loads due to heat gains through the building envelopes. Turiel et al. [5] and Chou and Lee [6] have correlated the OTTVs with cooling loads using computer simulation techniques for a generic office building. A similar approach is adopted for the present study.

3. Generic office building

A survey of existing commercial buildings built between 1975 and 1995 was conducted to establish a database of the prevailing architectural designs and construction practices in Hong Kong. The main source of information is the Monthly Digest published by the Buildings Department [7]. The Digest contains lists of buildings in chronological order of building construc­tion in Hong Kong, address, number of storeys, build­ing cost, usable floor area and gross floor area. There were well over a thousand buildings certified for occu­pation during the 21-year period from 1975 to 1995. In order to restrict the number of buildings to be ana­lysed, only statistics from the month of January and

June in each year were selected. This provides a ran­dom sample over time and the survey represents a snapshot of the changing face of buildings in Hong Kong. There was no building completed in some months in certain years, and January and June were chosen because there were always buildings completed in either one or both. A total of 146 buildings with a total gross floor area of 1.3 million m2 were selected for the study. Information on the types of building envelope designs and building services installations were obtained mainly through on-site visual inspection. literature search of the local and international pro­fessional journals and interviews with architects and engineers involved in some of the building projects [8].

Most of the buildings are 20- to 40-storey high-rise development with either square or rectangular con­figurations. The prevailing building envelope designs are reinforced concrete with tile cladding and curtain walling. Windows are single glazing with either tinted or reflective glass. In subtropical Hong Kong, double glazing is seldom used except for acoustic reasons. All buildings have centralised air-conditioning systems. Based on the information gathered, a 40-storey generic office building was modelled for the computer simu­

lation in this study. The building is 35 x 35 m with a 14 x 14 m non-air-conditioned central core; floor-to­floor height is 3.4 m with curtain walling design, which is currently the preferred choice among architects and clients in most recent commercial development. U­values for windows and spandrels are 5.6 and 2.5 W / m2 K, respectively; WWR is 0.44 with single reflective glass which has a shading coefficient of 0.4. The OTTV of this envelope design was determined using Eq. (3). The weather parameters such as TDeq were obtained from [3]. The OTTV of this generic office building is 35 W/m2, just meeting the new legislative control of building envelope designs for commercial buildings [3]. Electric lighting is recessed fluorescent with a lighting load of 20 W/m2. Office equipment load is 15 W/m2 and the occupancy density is 4 m2/ person. Air-conditioning is a variable-air-volume (VA V) system, which is the prevailing air-conditioning design, especially in large scale commercial building projects. The cooling set point is 25SC. Chillers are packaged air-cooled hermetic reciprocating type with an average coefficient of performance (COP) of 3. The values chosen for these design parameters are based on the averages found in the building survey.

4. Computer simulations

The DOE-2.1 E computer program [9] was used to conduct hour-by-hour calculations of the cooling loads and energy performance for the generic office building. Weather data were based on the 8760 records of

Page 4: Energy analysis of commercial buildings in subtropical climates - … · 2015. 5. 22. · requirement in Hong Kong. Most electricity is used for lighting and air-con-* Tel.: + 852-2788-7609;

22 J.C. Lam/ Building and Environment 35 (2000) 19-26

50

� 40 c: � 11 30 "' � .0

-0 20 "' .Q Cl c: '6 10 0

u

0

-v r,

Windows

solar

-

:

Windows

Conduction

-

I•

Walls

Conduction Roof

Conduction

Fig. 2. Breakdown of building envelope cooling load for generic office building.

measured hourly weather data for 1989, the test refer­ence year for Hong Kong [10]. Fig. 2 shows the break­down of the computed building envelope cooling load. It can be seen that solar heat through the fenestration is the most significant component, accounting for about half of the building envelope cooling load. As expected in high-rise development, conduction heat gain through the roof is insignificant, representing only 0.6%. To get some idea about the energy performance, computed electricity consumption by various major items were analysed, and a breakdown of the electri­city use is shown in Fig. 3. Chillers consume about 40% of the total annual electricity expenditure, indi­cating the overwhelming importance of air-condition­ing in the subtropics. Together with the HVAC auxiliary (i.e. fans and pumps), air-conditioning accounts for nearly 60% of the total annual electricity use. Since the local winters are short and mild, energy demand for space heating is not significant.

From the DOE simulations, it has been observed that the building envelope only accounts for about 30% of the total building cooling load. Internal load (i.e. artificial lighting, office equipment and occupancy)

� � 40 § 0 � "' � 30 Il "' "' " � 20

·� dj n; 10 " c: c: <(

I� �-;:::<

•:_.: ..•. : .. :: . �· _:,._:·.····:···:·_.·:·· .:··· ; . w.

""::.:::·.r.�.;·: =�� ·. "· '::

. ;. ; . - � .. :'..;:·:.�_ .. [:_:f ..... � _.i ... �. -. :}t _.:. :: �;�:.:)=·. ·" · :-:: � 0..1.--L.-=.l��...l.:..:.;J..��....:.:.-L��_!!;.;21-��-1.::..-l.._J

Chillers Electric lighting

Space HVAC auxiliary Office heating (fans and pumps) equipment

Fig. 3. Breakdown of annual electricity consumption for generic

office building.

10000 Cooling set point 20°c

:2 9500 !!: � 22'c c: 9000 .g Cl. E 2•°C :J "' c: 8500 8 � ·o 2s0c 11 8000 Ill Oi jij :J 7500 2a•c • c: c: <(

7000 15 20 25 30 35 40 45

OTTV(W/rrr)

Fig. 4. Annual electricity consumption for different OTTVs and cool­

ing set points.

and fresh air load (i.e. ventilation) account for the remaining 70%. Thus, the energy use due to building envelope heat gain only accounts for about 20% of the total building energy consumption. The percentage would be lower for commercial buildings with shop­ping complexes where the lighting and occupancy loads are much higher than offices. This suggests that there are some other design parameters which may be more energy-sensitive than the building envelope. Broadly speaking, there are four major design aspects to consider, namely the building envelope, indoor de­sign conditions, internal loads and HY AC.

4.1. Indoor design conditions

Previous work on thermal comfort survey and analysis (11] has indicated that many commercial pre­mises tend to be over-cooled by 2-4°C from the usual indoor design temperature of 25.5°C recommended by a Government consultancy study [12]. To assess the correlation between different OTTVs and the indoor design temperatures and their energy implications, DOE simulations were carried out based on the gen­eric office building described earlier. Seven building envelope designs with OTTVs ranging from 15 to 45 W/m2 (in an interval of 5 W/m2) were considered. These values correspond to the OTTV range found in the survey of existing commercial buildings. Eq. (3) in­dicates that the key design variables for the OTTV are the WWR, shading coefficient and U-values for the opaque walls and windows. Among them, WW R and shading coefficient are the more dominant design vari­ables as solar radiation accounts for most of the build­ing envelope heat gain (see Fig. 2). These two variables were varied to achieve the seven OTTVs. The cooling set point was also varied, from 20 to 28°C in an interval of 2°C. Therefore, there are altogether 35

simulation runs.

Page 5: Energy analysis of commercial buildings in subtropical climates - … · 2015. 5. 22. · requirement in Hong Kong. Most electricity is used for lighting and air-con-* Tel.: + 852-2788-7609;

J.C. Lam/ Building and Environment 35 (2000) 19-26 23

10500

:c 10000 Lighting load 30 W/m2

� 9500 6

c: 25W/m2 0 9000 ., • a.

·----·---E :J 8500 "' 20 W/m2 c: 0 0 8000 ·----·-

Z' ·13 ii 7500 15W/m2

QJ Qi 7000 (ii :J

10 W/m2 c: 6500 c: <{ 6000

15 20 25 30 35 40

OTTV(W/m2)

Fig. 5. Annual electricity consumption for different OTTVs and

lighting loads.

Fig. 4 shows the computed annual electricity con­sumption. It can be seen that energy use increases with the O T TV for all the six different cooling set points. The energy use, however, does not increase a great deal over the entire O T TV range. The average sensi­tivity coefficient (i.e. the ratio of the percentage change in electricity use to the percentage change in O T TV) is only 0.03, which is very much smaller than the average sensitivity coefficient of 0.6 for the cooling set point. The energy use tends to decrease more rapidly with the increase in cooling set point. This indicates that indoor design temperature has a far greater influence on energy efficiency in commercial buildings than the variations in the building envelope designs. This also suggests that a simple effective no-cost energy-efficient measure to lower the electricity use in existing com­mercial buildings would be to raise the internal tem­perature to the 25.5°C recommended for commercial premises in Hong Kong.

4.2. Internal loads

Office equipment and occupancy are usually beyond the control of the architects and engineers. This study, therefore, only considers the electric lighting load, which was varied from 10 to 30 W/m2 in an interval of

5 W/m2. Fig. 5 shows the computed annual electricity use for the different O T TVs and lighting loads. Again, there are only moderate increases in the energy use over the whole O T TV range. The sensitivity coefficient for the lighting load is 0.27, much higher than the 0.03 for the O T TV. Most of the buildings in the survey have lighting loads between 20 and 30 W/m2. With the advance in lighting technology, in terms of lighting products and design techniques, energy-efficient loads of 2.5 W/m2 for every 100 lux can now be achieved [13]. This corresponds to a lighting load of 12.5 W/m2

for the usual 500 lux internal illuminance for offices. Many case-study designs have demonstrated the great

45

9000

8800 � 8600

6 8400 •

5 8200 � 8000

ii: 7800 c: 0 7600 0

·E' 7400

:e 7200 QJ Qi

7000 (ii :J 6800 c: c:

<{ 6600

6400 15

co� ------- ·

3 0

----------· �

4 5

-----·---�

20 25 30 35

OTTV (W/m2)

�---·

40 45

Fig. 6. Annual electricity consumption for different OTTVs and coef­

ficient of performance.

energy-saving potential of better and more energy-effi­cient lighting designs, and this should be a key design aspect to address in energy efficiency programmes for commercial buildings.

4.3. Heating, ventilation and air-conditioning ( HV AC)

It has been observed in Fig. 3 that chillers account for most of the electricity use in the air-conditioning system. Energy performance of chillers is largely gov­erned by the coefficient of performance (COP). Computer simulations based on six different COP were carried out for the whole O T TV range, and the com­puted results are shown in Fig. 6. The annual electri­city consumption drops more rapidly during the initial increase in COP from 2.5. The average sensitivity coef­ficient is 0.22. It appears that improving the energy efticiency of chillers could result in significant energy savings in the commercial sector-the higher the COP, the better the energy efficiency. Most of the chillers in local commercial buildings are air-cooled with a COP of around 3. Although water-cooled chillers tend to have higher COP (usually around 5), very few com­mercial developments install this type of refrigeration plant, except buildings near the harbour where sea­water cooling is used for the heat rejection process in the air-conditioning system. This phenomenon is mainly due to the local regulation restricting the use of fresh-water cooling for air-conditioning in the commer­cial sector. This restriction was mainly due to the severe water shortage during the 1960 s and 1970 s.

The water supply situation has improved in recent years, and there have been debates among various building professions and Government departments about the possibility of lifting the fresh-water cooling restriction. It is envisaged that a study on the techni­cal, financial and environmental aspects of fresh-water

Page 6: Energy analysis of commercial buildings in subtropical climates - … · 2015. 5. 22. · requirement in Hong Kong. Most electricity is used for lighting and air-con-* Tel.: + 852-2788-7609;

24 J.C. Lam/ Building and Enrironmellf 35 ( 2000) 19-26

:):. 260

'.§ .c 240 � B 220 .. " 'ti .s g 200 .. E 180 .g �

" 160 � � 140 0 z

2.5

onv -•-15W/m2 -•-20W/m2 -.0.-25W/m2 -T--30W/m2 --35W/m2 -+-40Wim2 � -X-45Wim2

� � 5 0 75 10 0

Characteristic length (m) 12 5

Fig. 7. Normalised performance indicator for different OTTVs and

characteristic lengths.

cooling for air-conditioning in the commercial sector would be commissioned in the near future.

4.4. Ch ar a ct eristi c l ength

Critics of the legislative control of building envelope designs via the OTTV method have argued that the OTTV is prescriptive and inflexible. It makes no allow­ance for different building forms, geometry and typical floor sizes. Many prescriptive building energy regu­lations tend to consider the building size and shape through the correlation of the building envelope mean heat transfer coefficient and the building characteristic length (i.e. the ratio of the building volume to the area of the building envelope (14). Over 80% of the build­ings in the survey have a characteristic length between 2.5 and 12.5 m. Assuming a square floor plan and a floor-to-floor height of 3.4 m, these characteristic lengths correspond to 10 x 10 m and 50 x 50 m. Based on the generic office building, computer simu­lations were carried out with floor plans ranging from 10 x 10 m to 50 x 50 m, in an interval of 10 m. The computed electricity consumption was analysed. In order to reveal the energy performance on a per unit floor area basis, the computed annual electricity use was expressed in terms of the normalised performance indicator (NP!). Fig. 7 shows the NP! for the different OTTVs and characteristic lengths. It can be seen that the N Pl falls almost exponentially with the increase in characteristic length. It is interesting to note that there is a sharp drop in the NP! between the characteristic lengths of 10 and 12.5 m. This has significant impli­cations for the future building code, which would probably be performance-based using energy targets similar to the NP I. Fig. 7 shows that a building with a characteristic length of 7.5 m would need an OTTV of 15 W/m2 for its building envelope design in order to have the same NP! as another building which has a characteristic length of 10 m and an OTTV of 30 W/ m2• This raises the issue of the need for different

OTTV limits and energy performance targets for build­ings with different building shapes and sizes. More

work is required in the study of building morphology and the scale of commercial development.

5. Discussion and conclusions

Buildings, energy and the environment are some of the key issues that the building professions have to address in the planning, design and construction pro­cess. Energy use, especially electricity consumption in commercial buildings, has increased a great deal over the past two decades in Hong Kong. Energy use due to heat gains through the building envelopes accounts for less than one-fifth of the total energy use in typical air-conditioned commercial buildings. Energy savings resulting from legislative control of the building envel­ope designs through the 0 TTV method may not be significant, particularly during the initial years (the legislation only applies to new buildings). However, as an initial step to create a more energy-conscious en­vironment among the building professions, this admit­tedly rather prescriptive energy standard should be supported. More attention must now be focused on other issues such as the air-conditioning and lighting designs and the subsequent operation of the buildings and building services equipment.

Lighting is a key design area to be addressed by the building professions. This study has shown that the lighting load has a much higher sensitivity coefficient than the building envelope, indicating greater influ­ences on the electricity use in commercial buildings in subtropical climates. Most office buildings have light­ing installations with lighting loads of 20 W /m2. It is believed that lighting load of 10-12.5 W/m2 are realis­tic design figures which will provide an indoor illumi­nance of 400-500 lux for office buildings. Through computer energy simulations, it has been estimated that lowering the lighting load from the current 20-12.5 W/m2 for an office with an indoor illuminance of 500 lux, the total building electricity consumption could be reduced by about 15%.

Another aspect of lighting design to be addressed is the use of natural daylight. None of the 146 buildings

surveyed has incorporated any energy-saving daylight­ing scheme. In cooling-dominated commercial build­ings in the subtropics, daylighting can result in significant energy savings. Firstly, natural daylight can reduce the use of electricity for artificial lighting. Secondly, daylight has a higher luminous efficacy than most electric lighting systems, thus generating less heat per lighting level provided. The average luminous effi­cacy for daylight in Hong Kong is 110 lumen/W (15], whereas the average installed lighting efficacy found in local commercial buildings is about 60 lumen/W.

Page 7: Energy analysis of commercial buildings in subtropical climates - … · 2015. 5. 22. · requirement in Hong Kong. Most electricity is used for lighting and air-con-* Tel.: + 852-2788-7609;

• • • t

� ,:\ . : 1 \

J.C. Lam/ Building and £11riro11n1e111 35 ( 2000) 19-16 25

The computed energy perfonnance of the generic office building based on different cooling set points has revealed that there could be a 3% reduction in total building electricity use for every°C rise in the indoor

design temperature. As many commercial premises are over-cooled by 2--4'C. a imple no-cost energy-efficient measure woµld be to rai.c the internal air temperarnre to the recommended 25.s<c. Howe,·cr. it is en,·isaged that there could be strong resistance to such a

measure. The local community is used to the over­cooling condition, to such an extent that. more often than n t. office workers tend ro wear a jacket or cardi­gan to keep warm. Educat ion and publicity campaign are. therefore, an integral part of any energy efficiency programme targeted at the commercial sector. 1t takes time to correct people's perception of che appropriate indoor built environment and to change their user behaviour. Air-conditioning is the single largest electri­

city end-u er in commercia l building . For the generic office building, it accounts for about 60% of the total building energy consumption. Within the air-condition­ing. system. c.hillers consume mo t of the electricity for sp:ice cool ine. Means to improve the energy efficiency of the chiller plant in term of the design. sdection and subsequent operation. should be carefully con­sidered. It has been found that an improvement of the chiller COP from 3 to 5 can reduce the totul building electricity use by 16% for the generic office building .

The use of simple methods like the OTTV limit to prescribe and evaluate the energy performance of com­

mercial building en\'elope designs has its ad \'antages and disadvantages. When the building energy perform­ance is correlated with different OTTVs and character­istic lengths, it has been founded that, for the same OTTV, buildings with smaller floor plans and hence smaller characteristic lengths tend to have a much higher normalised pe rformance indicator. AP! (i.e. annual energy use per unit floor area). This indicates that future work on the development of a more com­prehensive performance-based energy code should con­

sider the need for different energy targets or NP!s for buildings with different building forms and sizes. The simulated energy consumption data have been pre­sented in terms of simple correlation between different major design variables. These charts and figures show the general overall trends of how changes in certain k.::y design parameters can aff1::ct the energy use in commercial bui ldings. and. therefore. could be con­. idered as simple design guide · . However, given the t1dn1nce in computer technolog: and the wide-spre·1d u e of computer simuhtion techniques. one could argue that there is no need for the e simple design guides. We believe that both the simpk design tools and the detailed computer simulation ti::chniques would be complementar to one another. Simple approaches involving charts. nomognms and tables

are useful to designers, particularly during the initial design stage when different building schemes and con­cepts are being considered. These pro\'ide the designers some quick basic in.ights into the int<."frelationship between variou key design parameter . and how their intcr-dependenc can affect the energ_ performance of the buildi ng being developed . Detailed computer simu­lation techniques can then be u ·ed at a later stage to de,·elop further the initial conceptual scheme and to assess the detailed energy performance of the sub­seq uent design.

One of the limitations of the pre ent study is the use of the generic office building. Although this is based on the surH� of existing commercial buildings and contains many design feature commonly found in those commercial building-. it only considers one build ing form (i.e. square ) and one pa rticular air-con­ditioning system (i.e. centrali:ed VA V system). Howe\·er. this study i not meant to pro\'ide a compre­hensi\"e nnalysis of the energy perfornnnce of commer­cial buildings through an cxhau · Li \'e Ii. t of comput..:r simulation runs covering all po· ible pa rametric con­siderations. hnead, it p e·cnt · a general O\"erilll vi�\\' of a few key issues affe ting the building energy com­puter simulation of commercial buildings. and the im­plications for future research and development work on energy efficiency in buildings, including the devel­

opment of a performance-based building energy code. Although the work presented is only based on the Hong Kong environment. it is believed that the meth­odology and design considerations are relevant to other cooling-dominated commercial buildings in sub­tropical climates. \ ith the rapid commercial building de,·elopment programmes being pur ued in the neigh­

bouring cite· in southern China. this may ha,·e signifi·

cant energy and environmental implications. It is hoped that this )!·�per will be of interest to building dcsi2ners and re /•earche rs concerned about buildings. ener

-gy and envirc'·nmenul issu6 in this region.

Acknowledgements

Work was funded by an RGC Competiti,·e Earmarked Research Grant. The author would like to

thank A.LS. Chan for his help \\ith the DOE-2 com­

puter simulation and H.M. Wong \\ith the building data collection .

References

[I] Lam JC. Ng AK W. Energy consumption in Hong Kong.

Energy-·the International Journal 1 994:19:1 1 57-64. [�] Chan ALS. Dc,·elopment of guiddines for energy-efficient opcr-

Page 8: Energy analysis of commercial buildings in subtropical climates - … · 2015. 5. 22. · requirement in Hong Kong. Most electricity is used for lighting and air-con-* Tel.: + 852-2788-7609;

26 J.C. Lam B11ildi11g and £111·iro11111�111 35 r 100(); 19-16

ation of fully air-conditioned buildings in Hong KL'llg. !\I Phil Th�sis. Cit: Polyt�chnic of H0ng Kong t 99-l.

[:>] Buildings D.:r.irtmcnl. Code of prJcti'� fur 0' �r JI\ th�rmcil

tJnsfa \a\u.: in buildings. H0r.g Kot:g. 1992 (-l] .-\SH R.-\ E Sur.dJrd 90 . .\- \ 'l�t). E n;:r�; �·Jr«cr' . . lt!,'11 1r: 11�·.1

builJi:1g J�sign .-\:"':1eric:.lr. S\.'(i<:t; of H��tir.g. R..:fr:�::rJtin� J.r.,! .-\ir-C onditionir:� Engin��rs .. -\tb�tcl. I %0.

(:'] Turid I. Curtis R. Le·. inc \ID .-\na\�;i; of �;i�rg: C-L>n<�n.1tic>n st..inJ:.irds for Sin:;Jpoie or7k� bui'.Jrng�- En�:-g> - th::

lrH�rt!Jtion:il J,1urnal 19� :':I 0:95- !IT. (6] Ch0u SK. L�e YK . .-\ simpi1f.d 01erctll th�rmc.! t!.1�.;f�; 1.1!L,;:

Cl\'J .. H:1."n ft•r bei!di:!g en.,;:!1.."P(,,'S En�:-:;:. - th ... · lr:�;::-:i.t�'.\..lr�.d Jourr...i� 19�.�: l 3:65"7 -70.

r-J B"i!Jing; Dcp.1;:n:�:it. \lc,11:h!; 01��,: 19-5-\ll'l:'. H·.•::� K·>1:; I m•'rHhl; p•Jh!i..::iti•'n •-

[$} G1)1Jd��dl CJ. lC�:iu(:.ing �1ppr,)pi\Jlc! energ� ._:l)!b�;-\J.�;.�n ��:.!:.­eg:� for bui!L!in�s f1)r Hong Kong. '.\lP�1ll T:i ... �:-;.;, Cit; Pu1: �t.·..:hnic of �king Kong. \\.i�I-!

(9] LI\\ re nee Berkeley L1bor:itor). DOE-2 Supplement Version 2. \ E. L'ni\er;ity of C1\ifomi:i.. C:i.lif0rnia. 199;.

(I'll Hui SC\!. bm JC. Test referenc� ye:.1r for rnmp:.1r.iti1-e energ; stud:. Hc>ng Kung Engine�r 1992:20:13--6

(I!] Che'" TT. Lam JC. Tham.ii com(,,rt :ind en.:rg; <·,1n;��1;tlk'n

in c,,m :-::er.:ial buildin�; in Hong Kong r\rchite.:turctl Sci.:n.:�

R�-. :�" \ 9'J2:.1:':6--72 . [I 2] J R0�.:r Prestc'n & PJrtner (.-\si:.i Pacitkl. FinJ\ rc;1L>r: 0n the

l°c:1;ibilit:· m:J: on in1�oducti<'n of 0\c;:dl chc:·m.d tran<la \J\ue !OTT\') w air conJiU<'ned buik!:r.g; in H,1ng K n:;. f111ng Kong. 19'.l l .

(i :>] E'.J.n; B. LLrn enag:- otf1ces The Ar<:hit�ct>' l<,urncil Arri\ 199�:55 -5:-5.

[I�] \L1hJ:l'.i .-\. B;:.1hm� R. '.\!�1th�11 P. The 'LEK"- conc�rt allJ

it. .. .ipp!i(:lbil:�.: f\x th� �:1-:-rg: :.in�d:si') of ..:11mr;�(': ... : i ,d b'.ii�din�s

8:.::k::::.; J:i.C F:1•. ir,Jn;��..:�c \ 9'ih.3 l ..i.119 15. (! 5) L1111 JC. l i DH\\·, Lumir.L'US etlic·ac) of d:i; ii�!n unc!cr dirfer­

'�t sk:· conJiti011; Enag; Con\crsion und \L1n.1�cnKnt \'Nn:!-: 1-1;_: Ii