en 61000-4-11 : 2004 voltage dips short interruptions with ... · netwave 30 3-phase source 3 x 300...

25
CONDUCTED RF EQUIPMENT POWER AMPLIFIERS www.emtest.com EN 61000-4-11 : 2004 Voltage dips short interruptions with PFS and Netwave Markus Fuhrer EM TEST (swizterland) GmbH, CH-4153 Reinach 16.05.2017

Upload: others

Post on 18-Mar-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

CONDUCTED RF EQUIPMENT POWER AMPLIFIERS

www.emtest.com

EN 61000-4-11 : 2004

Voltage dips short interruptions with PFS and Netwave

Markus Fuhrer EM TEST (swizterland) GmbH, CH-4153 Reinach 16.05.2017

Page 2: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

2www.emtest.com2

IEC 61000-4-11 Ed.2 2004-03 IEC 61000-4-34 Ed.1.1 2009-11

Part 4-11/34 : Testing and measurement techniques- Voltage dips, short interruptions and voltage variations immunity tests

up to 16 A more than 16 A

Page 3: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

3www.emtest.com3

Definition of sources

Load change in the same electric circuit

Start and breaking characteristic of engines

Short circuits and electrical fault conditions

Switch on of systems with high peak current during start

General is considered in this EMC standard, that the voltage of the upper described sources can not be higher than 100%The standard simulate the following phenomena's:

Voltage dips Voltage interruptions Motorstart

Page 4: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

4www.emtest.com4

Changes in IEC 61000-4-11

1- Introduction of a new voltage level for voltage dips: 80% Level

Procedure : Fast switching between 100% and the selected level

Verification: The generator withstand a nominal current of 20A for 5s

Page 5: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

5www.emtest.com5

Changes in the standard IEC 61000-4-11

– New test level at 80%

– New times for DIPS ( at 50 / 60 Hz same duration)

– New classes for applications

Class 1 : Protected suppliesClass 2 : Point of common coupling to public network Class 3 : Company internal connection points and industrial environments.

Page 6: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

6www.emtest.com6

2- Voltage Variations: New Voltage profile

Old standard 61000-4-11fall and rise time are 2s

This mean that the motor variac perform the voltage changes

Variac output at 70%

Switch from the nominal 100% voltage to the reduced presetted variac voltage with the fast internal switch ( 1-5us).

After 20 ms, a slow voltage increase during 500ms back to the nominal voltage with the motorvariac.

New test standard IEC 61000-4-11 Ed.2

Changes in the standard IEC 61000-4-11

Page 7: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

7www.emtest.com7

Voltage DIPS as per IEC 61000-6-1 -2 overview

• IEC 61000-6-2 Industrial

• 1 cycle at 0% criteria B

• 200ms at 40% criteria C

• 500ms at 70% criteria C

• 5000ms at 0% criteria C

• IEC 61000-6-1 household

• 0.5 cycle at 0% criteria B

• 1 cycle at 0% criteria B

• 500ms at 70% criteria C

• 5000ms at 0% criteria C

Generic standard immunity for AC input ports

Page 8: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

8www.emtest.com8

• Interruption DIPS 0%, 0.5 cycle Criteria B

• Interruption DIPS 0%, 1 cycle Criteria B

• DIPS 70%, 25 cycle =500ms Criteria C

• Test a sequence of three dips/interruptions with intervals of 10s minimum between each test event.

100

%70

%10s

T [s]

U[%]

Household

Voltage DIPS as per IEC 61000-6-1 -2 overview

Page 9: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

9www.emtest.com9

• Interruption DIPS 0%, 1 Cycles Criteria B

• DIPS 40% 10/12 Cycles =200ms Criteria C

• DIPS 70% 25/30 Cycles =500ms Criteria C

• Test a sequence of three dips/interruptions with intervals of 10s minimum between each test event.

Industrial

100 %

70 %

10s

T [s]

U[%]

40 %

Voltage DIPS as per IEC 61000-6-1 -2 overview

Page 10: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

10www.emtest.com10

Voltage interruption as per IEC 61000-4-11

t [s]

100 % VT

V (rms) 5000 ms

• Interruption < 5% during 5000ms

• Criteria C

Check of the power on after an interruption.

Hausehold and Industrial as per IEC 61000-6-1/2

Page 11: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

11www.emtest.com11

Test procedure as per IEC 61000-4-11

• Each setting with 3 „Events“ with intervals of 10s minimum between each test event.

• For voltage dips, changes in supply voltage shall occur at zero crossings ( 0° and 180°) of the voltage.

• Additional angles considered critical by product committees or individual product specifications preferably selected from on each phase. 45°, 90°, 135°, 180°, 225°, 270° and 315°

• For the short interruption test of three-phase systems, all the three phases shall be simultaneously tested.

• Every representative operating mode must be tested.

• Interruptions and dips occurs in the phases and not in the neutral line.

Page 12: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

12www.emtest.com

Setup with motorized variac NX-1-260-xx

variac NX -1-260-16 compactac NX5 bsp

Page 13: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

13www.emtest.com13

Test setup with tapped transformer V 4780 S2

Model V4780 S2 : with manual selection of the taps

Page 14: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

14www.emtest.com14

Voltage dips as per IEC 61000-4-11

Correct phase between PF1 and PF2

Page 15: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

15www.emtest.com15

Votage interruption as per IEC 61000-4-11

EUT change with different connection power fail simulator connection.

•Interruption high impedance:

The EUT supply Ut is interrupted during the programmed time.

The simulator interrupt the power supply line.

•Interruption low impedance:

The EUT supply Ut is interrupted and switched to 0V. The EUT is shorted and internal buffer capacitors are discharged.

The simulator switches the supply to 0V and makes a short circuit at the EUT input.

0 V

Page 16: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

17www.emtest.com17

System for 3-phase DIPS testing

PFS 503N32.2

3-Phase

Power Fail Simulator

Netwave 30

3-phase source3 x 300 V 33 A

Hardware

EUTPublic mains

Page 17: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

18www.emtest.com18

System for 3-phase DIPS testing

Blockdiagram Setup for DIPS testing with Netwave

Page 18: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

22www.emtest.com22

Dips in 3-phase system IEC 61000-4-11

The EUT shall be tested for each selected combination of test level and duration with a sequence of three dips / interruptions with intervals of 10s minimum ( between each test event ). Each representative mode of operation shall be tested.

For voltage dips, changes in supply voltage shall occur at zero crossings of the voltage, and at additional angles considered critical by product committees or individual product specifications preferably selected from 45°, 90°, 135°, 180°, 225°, 270° and 315° on each phase.

General

Page 19: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

23www.emtest.com23

Dips in 3-phase system IEC 61000-4-11

Test procedure : Each phase alone one by one

Exception : All 3 phases simultaneously for short interruptions.

3 phase system with neutraleach individual voltage (phase-to neutral and phase-to-phase) shall be tested. One at a time. This implies six different series of tests.

Page 20: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

24www.emtest.com24

Dips in 3-phase system IEC 61000-4-11

3 phase system without neutral

Each phase-to-phase voltage shall be tested, one at a time. This implies three different series of tests.

preferred phase shift

acceptable phase shift

Page 21: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

25www.emtest.com25

Dips in 3-phase system IEC 61000-4-11

Not acceptable– phase-to-phase testing without phase shift

In this case a star connected source system reduces the voltage on two phases with a dip.

Page 22: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

26www.emtest.com26

Test setup for Delta connection

L3 (PF1)

L2 (PF1)

L1’ (PF2)

Vector diagram of a delta connection transformer with dips with on phase L1 only in a 3-phase system. The dips must be repeated for each phase.

The voltage L2-L3 keeps at 100%. The voltages between the phases L1’-L2 and L1’-L3are vectorially added voltages depends of the tap position in L1’.

Schematic diagram in delta connection

Page 23: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

29www.emtest.com29

System for 3-phase DIPS testing

Settings for system in star connection

Phase-to-neutral dip vectorsFor voltage dips test of three-phase systems with neutral, each individual voltage (phase-to neutral) shall be tested, one at a time.

Vector parameters for70% DIPS testsphase to neutral

Page 24: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

30www.emtest.com30

System for 3-phase DIPS testing

Settings for system in delta connection

Phase-to-phase dip vectorsFor voltage dips test of three-phase systems with neutral, each individual voltage (phase-to phase) shall be tested, one at a time.

Vector parameters for 70% DIPS tests phase to phase

Page 25: EN 61000-4-11 : 2004 Voltage dips short interruptions with ... · Netwave 30 3-phase source 3 x 300 V 33 A Hardware Public mains EUT. 18 18 System for 3-phase DIPS testing Blockdiagram

33www.emtest.com33

Any questions? We are at your disposal!

AMETEK CTS Germany GmbH Phone: +49 (0) 2307 / 260 70-0

Lünener Str. 211 Fax: +49 (0) 2307 / 170 50

59174 Kamen, Germany

[email protected]

EM TEST (Switzerland) GmbH Phone: +41 (0) 61 / 717 91 91TESEQ AG +41 (0) 32 / 681 40 40

Sternenhofstr. 15

4153 Reinach BL, Switzerland

[email protected]

Thank you for your attention!