eMerge Browser Managed Security Platform

Module 2Hardware install

Panel layout

Power supply board

Tamper switch

Controller board

Access board

Input board

Input board

Ribbon cable

Empty expansion slot

Wire hold-down

Power cable

Power requirements

IEI eMerge systems must be AC powered using the grounded plug-in transformer provided. Power should come from a circuit with an isolated ground and must be wired to the power supply mounted inside the eMerge cabinet.

Transformer Input: 120 V AC 60 Hz 48W.

Transformer Output: 16.5V AC 2400mA.

The IEI eMerge includes a DC power supply. The eMerge power supply provides 12V DC at 3.3 amps.

The recommended battery which is not included 12V DC, 7 AH, SLA (sealed lead acid).

CAUTION!!! MAKE SURE ALL POWER IS OFF BEFORE CONNECTING OR DISCONNECTING MODULES IN THE IEI eMerge.

Network Controller board layout

Compact flash

socket

I-buttonsocket

Battery

Ribbon cable connector

NetworkController

Reset

Processor

PanelLED

2-portNetworkswitch

Ribbon cable connector

Node Reset

CabinetTamperSwitch input

Network port(reserved for future use)

Power supplyInput2-pin

BatteryInput/

Charger3-pin

Top side of board

Bottom side of board

The network controller board must be located in the top

position

Expansion Node Card

Battery

Ribbon cable connector

Ribbon cable connector

Node Reset

CabinetTamperSwitch Input

Network port

Power supplyInput2-pin

BatteryInput/

Charger3-pin

Panel LED

The Expansion Node board must be located in

the top position

I-button and tamper switch

Processor

Cabinet tamper switch connector

Compact flash

socket

Controler I-buttonsocket

Battery

Ribbon cable connector

MODEL

XXXSerial Number

Revision

xxxxxxxxREV.X

The label

is here

This side goes down into socket

Tamper switch mounts

Mounting holes

The tamper switch is installed on the tamper switch mounts and wired to the provided cord which is then plugged into the tamper switch connector on the control board

The controller I-button comes pre installed

The I-button contains system licensing.

Installing board in panel

standoff tube

lock washer

Boardgoes down

into slot

Standoff comesflush to flange

1. Power down the eMerge.

2. Thread the standoff tube provided down onto the threaded post on the chassis next to the slot where you will insert the additional module.

3. Be sure that you are grounded and insert the additional module into the slot on the chassis with the ribbon cable connector toward the left of the eMerge cabinet. See diagram below.

4. Place the lock washer provided over the top of the standoff and thread the screw provided through the flange and down into the top of the standoff and snugly down onto the lock washer. See diagram below.

5. Connect the ribbon cable from the Controller/Node module in the topmost slot to the newly installed module. The connector is polarized. Make sure that the center bump fits into the opening for it on the connector on the module. Press the connector firmly into place until you hear the click of the extraction levers snapping into vertical position. You may have to press the extraction levers into full vertical position before you will hear the click.

Ribbon cable

Slot numbers are determined by the connector on the ribbon cable that is plugged into the module. The ribbon cable (see diagram below) is a bus and a module’s place on the bus determines the slot number. You will see that it is possible to place a module in physical slot 5 and yet attach ribbon cable connector 6 to the module. If this occurs the module will be in slot 6 on the bus.

Controller/Nodeconnector

Connectors for slots 1 2 3 4 5 6 7

Note: When connecting the modules to the ribbon cable be sure the connector is fully seated in the board

(push on cable do not rely on the tabs on the boards)

Access Control module (ACM)

Ribbon cable connector

Form C relay outputs

2-pin supervised inputs

Position 4 3 2 1 4 3 2 1

#2

#1

Weigand reader connections

The access control module can be used for 2 doors with both in reader or 1 door for

in and out readers.

The ACM board can be located in slot positions

2-7

Input Board layout

2-pin supervised inputs

Position 8 7 6 5 4 3 2 1

Ribbon cableconnector

The input board is used for monitoring alarm points, or when multi supervised inputs are

needed.

The Input board can be located in slot positions

2-7

Output Board layout

Form C relay outputs

Position 8 7 6 5 4 3 2 1

Ribbon cableconnector

The Output board is Used for elevator control or

when additional form C relays are required.

The Output board can be located in slot

positions 2-7

Wiring battery and power to controller.

Batteryinput3-pin

Power supplyinput2-pin

Processor

pin 2ground

pin 1+12V DC

pin 1+12V DC

pin 3ground

AC GND AC

AC IN +V NEG +BATT-

The power supply is pre wired to the

network controller.

Note: Do Not connect Battery to power supply board connect to the controller

board

Wiring Weigand readers

Bpr

Grn LED control

Red LED controlD1(white)

D0(green)

Gnd(black)

Pwr(red)

CAUTION!!! Each eMerge Access module can supply a total of 400 milliamps of power for readers. If the reader(s) connected to the Access module draw more than 400 milliamps then external power must be supplied to these readers.

The maximum distance for wiring weigand devices to the access board is 500 Ft.

For distances longer then 500 ft. you need to use an additional expansion node with acm or there are 3rd party devises made

to extend the distance.

Access Control module (ACM)

Supervised Inputs wiring

2-pin input connector

Input deviceNormally Open (NO)

1K Resistors - Install at or near input device

2-pin input connector

Input deviceNormally Closed (NC)

1K Resistors - Install at or near input device

Input state Resistance Value

Normal 1k Ohms ±5%

Alarm 0.5k Ohms ±5%

Short 0 Ohms

Open No current (∞ Ohms)

Input State Resistance Value

Normal 1k Ohms ±5%

Alarm 2k Ohms ±5%

Short 0 Ohms

Open No current (∞ Ohms)

2-pin inputs

Position 8 7 6 5 4 3 2 1

Ribbon cableconnector

Ribbon cable connector

2-pin inputs

4 3 2 1 positions

ACM

Supervised input board

The inputs on the eMerge panel are supervised that allows the panel to monitor the status including if the input is in a normal state, alarmed or triggered, and if

the wires before the devise is shorted or the same is opened.

Wiring Outputs

3-pin outputconnector

DCpowersupply

-+

Pin 2common

Pin 3normally open

DC outputdevice

Diode - 1N4933 or equivalent

+

-

3-pin outputconnector

DCpowersupply

-+

Pin 2common

DC outputdevice

Diode - 1N4933 or equivalent

Pin 1normally closed

+

-

Ribbon cable connector

3-pin outputs 1 2 3 4

Ribbon cable connector

3-pin outputs

positions 8 7 6 5 4 3 2 1

ACM

Output board

The dry contact relay is wired up as shown we show using a DC power supply for the lock. A diode is used for dc this is so the relay does not fail prematurely from a voltage spike from the lockset. When using AC voltage use a mov SNR- D56k2 or equivalent. Diodes and movs are supplyed with the access boards and output boards.

Connecting to the network

When connecting to the controller board use a patch cord. A router or DHCP server needs to be connected so the node will get an IP address issued through DHCP.

Panel Led operation

Green steady The network communication is functioning and external power is on.

Green flashing The network communication is functioning and the eMerge is using battery power.

Yellow steady The network communication is not functioning and external power is on.

Yellow flashing The network communication is not functioning and the eMerge is using battery power.