1 Presented by Michael Z. Lowenstein, Ph.D. Chief Technology Officer Harmonics Limited Eliminating Harmonic Neutral Current Problems Powering multiple computer loads creates problems in electrical distribution systems. Harmonic current flow generates heat in all parts of the distribution system, which wastes energy. Ridding the system of harmonic current flow saves energy and money. Basic Premises

Upload: doanphuc

Post on 06-Feb-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

1

Presented byMichael Z. Lowenstein, Ph.D.

Chief Technology OfficerHarmonics Limited

Eliminating Harmonic Neutral Current Problems

• Powering multiple computer loads creates problems in electrical distribution systems.

• Harmonic current flow generates heat in all parts of the distribution system, which wastes energy.

• Ridding the system of harmonic current flow saves energy and money.

Basic Premises

Page 2: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

2

• Why there is a problem• Power distribution in a Wye system• Powering computers• Accommodating harmonic currents• Preventing harmonic currents with the

Harmonic Suppression System (HSS)• Saving energy• HSS products• Who uses the HSS and the results they

obtain

Outline

• When an electric motor is connected to the AC line, it draws its power directly from the line. The power is not treated in any way.

• The same is true for a resistive load such as an electric heater.

Linear loads

Page 3: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

3

Voltage & current have the same mathematical relationship across the entire cycle

PEAKS ZERO CROSSINGS

CURRENTVOLTAGE

0 180 360

AM

PLIT

UD

E

WAVE ANGLE

Linear voltage-current relationship

• When a computer is connected to the AC line, it draws its power from an internal DC supply that contains rectifiers and capacitors.

Non-linear loads

Page 4: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

4

Non-linear voltage-current relationship

Mathematical relationships between voltage & current vary across the cycle

PEAKS ZERO CROSSINGS

VOLTAGECURRENT

0 180 360

AM

PLIT

UD

E

WAVE ANGLE

Linear & non-linear loads (1)

• Linear Load − The current looks like the voltage

• The more the current looks like the voltage, the more linear is the load

•Non-linear Load −The current does not look like the voltage

Page 5: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

5

• Linear Loads get their kW power at 60 Hz.

• Non-linear loads get their kW power at 60 Hz and in addition draw harmonic currents

Linear & non-linear loads (2)

What are harmonics?

3rd HARMONIC

5th HARMONIC

FUNDAMENTAL

0 90 180 270 360WAVE ANGLE

AM

PLIT

UD

E

Harmonics are continuousintegral multiples of thefundamental frequency

Page 6: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

6

FREQUENCYFREQUENCYHARMONIC

123579

11…49

60120180300420540660…

2940

40080012002000280036004400

…19600

Table of harmonics

Single-phase 2-pulse diode bridge (computer power supply)

+

_CAPACITIVE LOAD

Page 7: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

7

Single-phase 2-pulse diode bridge (waveform)

VOLT

S

AM

PS

0 90 180 270 360 450 540 630 720

WAVE ANGLE IN DEGREES

1 3 5 7 9 1113

1517

19

0102030405060708090

100

CU

RR

ENT

% F

UN

DA

MEN

TAL

HARMONIC NUMBER

Single-phase harmonic spectrum(typical for personal computers)

Page 8: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

8

3-phase wye distribution systems

(with phase-to-neutral loads)

Wye distribution systemServing Linear Loads

TRANSFORMER ENCLOSUREPHASE C

PHASE A

PHASE B

60HzCURRENTS

60Hz CURRENT

60Hz IMBALANCE CURRENT ONLY

PRIMARY CIRCUITBREAKER

TO BUILDING STEEL

X0

HEATER HEATER HEATER

Page 9: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

9

Standard transformer, phase A linear load

A = 12.4 Amps; B = 0.8 Amps; C = 0.8 Amps; N = 12.2 Amps

Standard transformer, phases A + B linear load

A = 12.4 Amps; B = 11.9 Amps; C = 0.7 Amps; N = 11.9 Amps

Page 10: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

10

Standard transformer, phases A + B + C linear load

A = 12.5 Amps; B = 11.9 Amps; C = 11.8 Amps; N = 0.8 Amps

• Harmonics currents do no work, but do contribute to the rms current the system must carry

• 3rd harmonic currents are additive in the system neutral

• 3rd harmonic currents return to the transformer over the neutral and are dissipated as heat in the transformer, cables and load devices

Reasons to be concerned about harmonic currents

Page 11: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

11

PHASE C

PHASE A

60Hz IMBALANCE CURRENT +SUMMED 3rd HARMONIC CURRENT

PHASE B

3rd HARMONIC CURRENTCIRCULATES IN DELTA WINDING

SAFETYGROUND

TRANSFORMER ENCLOSURE

60Hz CURRENT +HARMONIC CURRENT60Hz AND

NON-TRIPLENHARMONICCURRENTS

TO BUILDING STEEL

COMPUTER COMPUTER COMPUTER

PRIMARY CIRCUITBREAKER

X0

Wye Distribution SystemServing Non-Linear Loads

Standard Transformer, 10 non-linear loads, phase A

A = 24.8 Amps; B = 0.8 Amps; C = 0.8 Amps; N = 24.7 Amps

Page 12: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

12

A = 24.7 Amps; B = 23.4 Amps; C = 0.7 Amps; N = 33.9 Amps

Standard Transformer, 10 non-linear loads, phases A + B

A = 24.6 Amps; B = 23.4 Amps; C = 24.5 Amps; N = 41.5 Amps

Standard Transformer, 10 non-linear loads, phases A + B + C

Page 13: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

13

• k-Rated Transformers• Double Neutrals• Oversized switch gear• De-rated UPSs, and Power Distribution

Units (PDUs)

• Zig-zag or phase shifting transformers

Avoiding Harmonic Problems(Accommodation)

PHASE C

PHASE A

60Hz IMBALANCE CURRENT +SUMMED 3rd HARMONIC CURRENT

PHASE B

3rd HARMONIC CURRENTCIRCULATES IN DELTA WINDING

SAFETYGROUND

TRANSFORMER ENCLOSURE

60Hz CURRENT +HARMONIC CURRENT60Hz AND

NON-TRIPLENHARMONICCURRENTS

TO BUILDING STEEL

COMPUTER COMPUTER COMPUTER

PRIMARY CIRCUITBREAKER

X0

K-rated transformer to accommodate harmonic currents

Page 14: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

14

A = 26.0 Amps; B = 24.9 Amps; C = 25.8 Amps; N = 44.3 Amps

K-rated transformer, 10 non-linear loads, phases A+B+C

• k-Rated Transformers• Double Neutrals• Oversized switch gear• De-rated UPSs, and Power Distribution

Units (PDUs)

• Zig-zag or phase shifting transformers

Avoiding Harmonic Problems(Accommodation)

Page 15: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

15

• k-Rated Transformers• Double Neutrals• Oversized switch gear• De-rated UPSs, and Power Distribution

Units (PDUs)

• Zig-zag or phase shifting transformers

Avoiding Harmonic Problems(Accommodation)

Zig-zag transformer to accommodate harmonic currents

PHASE C

PHASE A

PHASE B

3rd HARMONIC CURRENT DISSIPATEDAS HEAT IN SECONDARY WINDING

SAFETYGROUND

TRANSFORMER ENCLOSURE

60Hz CURRENT +HARMONIC CURRENT

TO BUILDING STEEL

COMPUTER COMPUTER COMPUTER

60Hz ANDNON-TRIPLENHARMONICCURRENTS

PRIMARY CIRCUITBREAKER

60Hz IMBALANCE CURRENT +SUMMED 3rd HARMONIC CURRENT

Page 16: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

16

A = 26.4 Amps; B = 25.2 Amps; C = 26.4 Amps; N = 45.0 Amps

zig-zag transformer, 10 non-linear loads, phases A+B+C

• Introducing the Harmonic Suppression System (HSS)

• Blocks 3rd harmonic currents and prevents their flow anywhere in the system

• Eliminates need for oversized components and doubled neutrals.

• Minimizes waste heat from the transformer out to the furthest outlet.

Eliminating Harmonic Problems

Page 17: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

17

3rdHARMONIC

FLOW

HSS blocking 3rd harmonic currents

SINCE NO 3rd HARMONIC CURRENT CAN RETURN IN THE

NEUTRAL WIRE, NO 3rd HARMONIC CURRENT CAN FLOW

IN THE PHASE WIRES.

60Hz CURRENT and 3rd HARMONICCURRENT FLOWING IN ALL THREEPHASES

60 Hz 3rd HARMONIC

PHASE C

PHASE A

PHASE B

COMPUTER COMPUTER COMPUTER

60Hz IMBALANCE CURRENT PLUS 3RD HARMONIC CURRENT, COMBINED FROM ALL THREE PHASES, MUST

RETURN TO THE TRANSFORMER ON THE NEUTRAL WIRE`

NEUTRAL

X0

RLC Parallel-Resonant Tank Circuit HSS)

Page 18: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

18

TRANSFORMER ENCLOSUREPHASE C

PHASE A

PHASE B

60Hz ANDNON-TRIPLENHARMONICCURRENTS

COMPUTER COMPUTER COMPUTER

HSS

NO 3rd HARMONIC CURRENTSTO CIRCULATE IN DELTA WINDING

60Hz CURRENT & HARMONIC-CURRENTS OTHER THAN 3RD

60Hz IMBALANCE CURRENT ONLYIN COMBINED NEUTRAL

PRIMARY CIRCUITBREAKER

TO BUILDING STEEL

X0HSS ENCLOSURE

Wye distribution system with HSS

Computer Current (With & Without HSS)

no HSS

HSS

Page 19: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

19

With HSS Without HSS

1 3 5 7 9 11 13 15 17 190

102030405060708090

100

1 3 5 7 9 11 13 15 17 19

% o

f Fu

ndam

enta

l

Phase Harmonic Currents With & Without Harmonic Suppression System

Neutral Harmonic Currents With & Without Harmonic Suppression System

With HSS Without HSS

1 3 5 7 9 11 13 15 17 190

255075

100125150175200225250

1 3 5 7 9 11 13 15 17 19

Cur

rent

in a

mps

Page 20: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

20

• Reduces neutral currents by more than 90% by preventing 3rd harmonic current flow (from the transformer out to the furthest outlet)

• Lowers rms phase currents, leading to more useable capacity without the need to install a larger system.

• Reduces energy losses throughout the system

What the HSS Does (for your system)

“Proper Sizing” of the Distribution System

• System over-sizing to “handle”harmonic currents is eliminated.

• Useable system capacity is increased (single phase power factor is improved.)

Page 21: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

21

• Power factor is defined as “active power divided by apparent power”

• Power factor can be described as “a measure of the effective utilization of electrical system capacity”

Single-phase power factor

System Capacity

Unloaded system

Page 22: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

22

System Capacity

kW Power

Harmonics

Low power factor

System Capacity

kW PowerHarmonics

Slightly improved power factor

Page 23: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

23

System CapacitykW Power Harmonics

High power factor

*Single-phase power factor, is a measure ofthe efficiency of system capacity utilization.

TEST VOLTAGE(rms volts)

CURRENT(rms amps)

WATTS VOLT-AMPS

POWERFACTOR*

No HSS 116.7 4.972 360.4 580.4 0.62

With HSS 117.2 3.173 355.9 371.8 0.96

Single-phase power factor (with and without the HSS)

Page 24: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

24

System-wide I2R energy losses

• Losses due to system-wide heating show up on the energy bill as increased kWH usage

• The HSS reduces system-wide heating and provides real energy savings.

• This savings can be measured by examining a system with and without an HSS installed

• Measurements both in the laboratory and in the field confirm system-wide energy savings.

Power saved by removing harmonic currents varies with system loading and wiring method

% kW REDUCTION WITH VARYING WIRING OPTIONSAND LOADING, STANDARD TRANSFORMER

0

1

2

3

4

5

6

7

8

10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

% TRANSFORMER LOADING

% k

W R

EDU

CTIO

N

50' 50'+100'SN 50'+100'CN 50'+100'SN+100'CN

Page 25: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

25

The Energy Savings Estimator

The energy savings estimator(I2R waste heat savings)

Page 26: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

26

The energy savings estimator(avoided air conditioning)

Secondary currents (by transformer type)

0

5

10

15

20

25

30

35

40

45

CU

RR

ENT

IN A

MPS

std xfmr k-rated xfmr Zig-zag xfmr

TRANSFORMER TYPE

SECONDARY CURRENT BY PHASE AND TRANSFORMER TYPE (WITH HARMONICS) 50' + 100' COMMON NEUTRAL

phase a phase b phase c neutral

Page 27: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

27

0

5

10

15

20

25

30

35

40

45

CU

RR

ENT

IN A

MPS

std xfmr k-rated xfmr Zig-zag xfmr

TRANSFORMER

SECONDARY CURRENT BY PHASE AND TRANSFORMER TYPE (HARMONICS SUPPRESSED) 50' +

100' COMMON NEUTRAL

phase a phase b phase c neutral

Secondary currents (by transformer type) with HSS

6.206.306.406.506.606.706.806.907.007.10

POW

ER IN

kW

st d xf mr k-rat ed xf mr zig-zag xf mr

TRANSFORMER TYPE

POWER BY TRANSFORMER TYPE (WITH AND WITHOUT HARMONICS) 50' + 100' COMMON NEUTRAL

S OLI D = WI TH CHEC KERED = WI TH OUT

Power with and without HSS(by transformer type)

Page 28: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

28

-8.00%-7.00%-6.00%-5.00%-4.00%-3.00%-2.00%-1.00%0.00%1.00%2.00%3.00%

PER

CEN

T CH

ANG

E IN

POW

ER U

SED

std xfmr k-rated xfmr zig-zag xfmr

TRANSFORMER TYPE

COMPARISON OF POWER USED, BY TRANSFORMER TYPE (PERCENT INCREASE OR DECREASE) 50' + 100' COMMON

NEUTRAL (PAGE 2)

CHANGE IN POWER USE COMPARED TO STANDARD TRANSFORMERCHANGE IN POWER USE WITH HARMONIC REMOVAL

Power used with and without HSS, change(by transformer type)

Harmonic Suppression Products

Page 29: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

29

The SysteMax

is an add-on Harmonic

Suppression System That can be

added to your present transformer to remove harmonic

currents

The TransMax

combines a high quality TP-1 (formerly

energy star) transformer with the

Harmonic Suppression System in a single easy-to-install enclosure.

Page 30: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

30

500 kVA TransMax (installed in a basement vault)

Who uses the HSS and why?

• Data Centers

• Financial institutions

• Government institutions

• Casinos

• Educational institutions

• Hospitals

• Research laboratories

Page 31: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

31

Page 32: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

32

Stock exchange trading room floor

• Transformers2- 112 kVA & 1-75 kVA, K-20 TransformersAvg. transformer loading 64% of Rated Capacity

• Combined Neutral Current reduced by 75%, from 750 amps., to 186 amps..

• 3rd Harmonic Neutral Current reduced by 98%, from 712 amps., to 15 amps.,

• RMS Phase Current reduced by 9%• Using energy savings estimator-- ROI, 19

months• 3 Portable A/C units removed ($54,000.00

per yr.)

Page 33: eliminating Harmonic Neutral Current Problems no logot …ewh.ieee.org/conf/tdc/eliminating_Harmonic_Neutral_Current_Proble… · 1 Presented by Michael Z. Lowenstein, Ph.D. Chief

33

Software development center (before and after HSS)

• Every electrical distribution system powering multiple single-phase non-linear loads, is susceptible to harmonic neutral current problems

• Installing a Harmonic Suppression System increases electrical system reliability

• Installing a Harmonic Suppression System reduces heat and wasted energy system-wide

• Using the HSS saves you energy and money

Conclusions