elevator consulting serviceselevatorconsultingservices.com/uspsdetroitmi/parsons detroit usps... ·...
TRANSCRIPT
DETROIT P AND DC Page 1
ELEVATOR
CONSULTING
SERVICES, INC.
17595 Italy Court ∙ Lakeville, MN 55044 ∙ Office: 952-435-2429 ∙ Fax: 952-435-6994
www.elevatorconsultingservices.com [email protected] [email protected]
∙ [email protected] [email protected] ∙
Maintenance Audits ∙ Code Evaluations ∙ Specifications
September 7th, 2016
Tony Marino
Parsons
Field Project Manager
USPS National Program
RE: Parsons Project B 13281
USPS Detroit P and DC
Facility 252492-G22
1401 Fort Street
Detroit, Michigan 48233-9706
Dear Tony;
We reviewed 1 passenger and 6 freights at this site. The USPS at the Detroit P and DC in Detroit
Michigan was reviewed by Thomas Branham of Elevator Consulting Services, Inc. on August 17, 18th,
2016. My QEI number is 1339 and I am certified by NAESA. NAESA is the National Association of
Elevator Safety Authorities. They are evaluated on and for the ASME 17.1 Safety Code for Elevators and
Escalators, Section 8.6 of the ASME 17.1 and ASME 17.3 Safety Code for Existing Elevators and
Escalators and ASME 17.2 Code for Inspectors Manual and industry standards for acceptable installation
and maintenance procedures.
Passenger Elevators 14
This is an employee elevator that has a high failure rate. The controller is a Montgomery
MiProm, has a Montgomery 208E machine that are both obsolete. The machine drive sheave is
bad due to poorly adjusted hoist ropes. KONE does not support either the controller or machine
anymore and the after-market has boards but not software. The car had been down for a couple
of days due to a clutch problem. This control was installed in 1992.
Freights 1, 2
The elevators have a MCE IMC- SCR logic controller and a Courion PLC door controller.
They also have a City number which is rare for a Post Office. The five year load tests are past
due and the level of maintenance is extremely poor. There is at best call back maintenance being
DETROIT P AND DC Page 2
performed and even that level is below par. The machine is an old Otis # 1 for elevator 1, an old
Otis # 2 for elevator 2. While still viable units, the bearing housings are original and would need
to be bored out to be replaced as they are considered obsolete by Otis. It is as cheaper to replace
the machine as it is to refurbish the existing machines. In addition, elevator one sheave is bad
and the ropes are starting to bottom on the groove due to poor tension adjustments.
Freight 3 & 4
The elevators have a MCE IMC- SCR logic controller and a Courion PLC door controller.
They also have a City number which is rare for a Post Office. The five-year load tests are past
due and the level of maintenance is extremely poor. There is at best call back maintenance being
performed and even that level is below par.
The machines are Otis # 2. While still viable units, the bearing housings are original and would
need to be bored out to be replaced as they are considered obsolete by Otis. It is as cheaper to
replace the machine as it is to refurbish the existing machines.
Freights 15A, 16B
The elevators have a MiProm Ultron DDC logic controller and a Courion model D door
controller.
The five-year load tests are past due and the level of maintenance is extremely poor. There is at
best call back maintenance being performed and even that level is below par.
The machine is a Montgomery 210E machine which is also obsolete.
The door equipment is obsolete and is better to be replaced now than get a surprise in the next
half life cycle.
We have the following recommendations.
All the controllers warrant replacement. It is likely some of the machines can be retained if a
new VVVF motor is used as the replacement. The door equipment is best to be replaced at this
time due to the skill set of the technicians. Although parts are available now, they will not be by
the end of the next life cycle and the current crop of technicians have a limited skillset on
working on freight elevators.
OPTION 1
Do little or nothing. This will eventually come to haunt the facility and handicap its function.
Any future upgrade would be more expensive and failures will only increase in scope and
quantity if left as is. It is more prudent to replace the obsolescence now than to delay it any
longer. At a minimum, Freight Tech or Peelle techs should be brought in to adjust and
refurbish the hoist way doors. A lot of rusted chains, chains out of stretch compliance and poor
motor control is crucial to getting the doors working again in a reliable manner. Having a
qualified third-party come in to do what your service company cannot or will not do is
worthwhile.
Budget for----------------------------------------------------------------------------- Option 1
Freights 1,2 ------------------------- $ 18,000.00 ea x 2 = $ 36,000.00
Freights 3, 4 ------------------------ $ 18,000.00 ea x 2 = $ 36,000.00
Freights 15A, 16B ----------------- $ 18,000.00 ea x 2 = $ 36,000.00
Total $ 108,000.00
DETROIT P AND DC Page 3
OPTION TWO
The second option is for replacement of some of the equipment in a staggered list of priorities.
The options from our observation of usage levels, liability and condition are:
1. Partially upgrade the freights 1, 2. Replace main and refurbish the door controllers, door
equipment, upgrade to VVVF technology, retain ascending protection, replace machine,
refurbish fixtures. Note, refurbishing the door equipment is making sure Freight Techs or
Peelle techs go over all the doors twice over the initial six months to get them in first
class condition
2. Upgrade the passenger elevators 14. Replace the controllers, keep the machines, new
motor, add ascending protection, new governors, refurbish door equipment, new fixtures.
3. Partially upgrade the freights 3, 4. Includes new controllers, machines, refurbish fixtures,
add ascending protection, refurbish door equipment. Refurbishing door equipment is
making sure Freight Tech or Peelle techs go over all the doors twice over the initial six
months to get them in first class condition.
4. Upgrade freight 15. Includes new controller, new fixtures, new machine, replacement of
the motor, refurbish the door equipment
The controllers for both the elevators and door equipment all warrant replacement but the
priority status above stretches out the upgrade. Some door controllers can last another year if
needs be but the main control equipment is more than obsolete, it is unreliable. The car would
get new bumper rails, light fixtures, painted and car operating panel fixtures. The machine room
would have some minor modifications for code compliance. This option includes the
modifications to the machine room, electrical requirements, door equipment and an updated cab.
Budget Option 2: Grand Total option 2 $ 1,434,000.00
Passenger 14 -------------------------------------------------- $ 189,000.00
Door equipment – 18,000 ---------- 18,000.00
Controllers ------ 27,000 -------- = 27,000.00
Machines -------- 14,000 ---------- = 14,000.00
Ascending Protection -9,000.00 - 9,000.00
Fixtures ---------26,000 ----------- 26,000.00
Labor ------------------------------- = 75,000.00
Misc, permits, bldg work, etc ----- = 20,000.00
Freights 1,2 ------- -------------------------------------------- $ 515,000.00
Door equipment – 12,000 ea x 2 = 24,000.00
Controllers 27,000 ea x 2 -------- = 54,000.00
Door Controllers 3,000 ea x 2--- = 6,000.00
Machines 24,000 ea x 2 ---------- = 48,000.00
Fixtures 9,000 ea x 2 ------------ 18,000.00
Labor --150,000 x 2 ------------ = 300,000.00
Misc, permits, building work---- = 65,000.00
DETROIT P AND DC Page 4
Freights 3, 4 --------------------------------------------- $ 457,000.00
Door equipment – 12,000 ea x 2 = 24,000.00
Controllers 27,000 ea x 2 -------- = 54,000.00
Door Controllers 3,000 ea x 2--- = 6,000.00
Machines 24,000 ea x 2 ---------- = 48,000.00
Fixtures 19,000 ea x 2 ------------ = 38,000.00
Ascending Protection 9,000 x 2 = 18,000.00
Labor ---120,000 x 2 ------------ = 240,000.00
Misc, permits, building work---- = 48,000.00
Freight 15 ----------------------------------------------- $ 273,000.00
Door equipment ----------------- 14,000.00
Controller ------------------------ 27,000.00
Machine -------------------------- 24,000.00
Fixtures ---------------------------- 26,000.00
Ascending Protection ------------ 9,000.00
Governors ------------------------ 3,000.00
Labor ----------------------------- 120,000.00
Misc, permits, building work---- 50,000.00
OPTION THREE
The best option is for replacement of all of the equipment under one contract. Any delay may
significantly increase the cost due to the five-year agreement ending in the middle of the
upgrades. The pricing is more inclusive for scope to replace all outdated or original items that
cannot last at least 2 more life cycles. The options from our observation of usage levels, liability
and condition are:
1. Upgrade the freights 1 and 2 both main and door controllers, door equipment, governors,
upgrade to VVVF technology, add ascending protection, replace machine, fixtures, cab
floor
2. Upgrade the freights 3, 4. Includes new main and door controllers, machines, door
equipment, new fixtures, add ascending protection, cab floor
3. Upgrade the passenger elevator 14. Replace the controller, machine, new motor, add
ascending protection, new governors, new door equipment, new fixtures
4. Upgrade service freight 15. Includes replacement of the machine and new car floors.
The controllers all warrant replacement. Some can last another year if needs be but the door
equipment is more than obsolete, it is unreliable. The car would get new floors as they are
damaged, bumper rails, light fixtures, painted and car operating panel or fixtures. The machine
rooms would have modifications for code compliance. This option includes the modifications to
the machine room, electrical requirements, door equipment and an updated cab.
Budget for Option 3:
DETROIT P AND DC Page 5
Freights 1, 2 -- ------------------------------------------- $ 769,000.00
Freights 3, 4 ------------------------------------------------ $ 821,000.00
Passenger 14 ---------------------------------------------- $ 312,000.00
Freight 15 --------------------------------------------------- $ 384,000.00
Total $ 2,286,000.00
Freights 1, 2 ----------------------------------------- = $ 769,000.00
Door equipment – 22,000 ea x 7 = 154,000.00
Controllers 27,000 ea x 2-------- = 54,000.00
Door Controllers 9,000 ea x 2 - = 18,000.00
Machines 24,000 ea x 2 ---------- = 48,000.00
Ascending Protection 9,000 x 2-- = 18,000.00
Governors --- 3,000 x 2 ----------- = 6,000.00
Fixtures 29,000 ea x 2 ------------ = 58,000.00
Cab flooring 8,000 x 2 ------------= 16,000.00
Labor ----150,000 x 2 ----------- = 330,000.00
Misc, permits, building work---- = 67,000.00
Freights 3, 4 ------------------------------------------- $ 821,000.00
Door equipment – 22,000 ea x 8 = 176,000.00
Controllers 27,000 ea x 2-------- = 54,000.00
Door Controllers 9,000 ea x 2 - = 18,000.00
Machines 24,000 ea x 2 ---------- = 48,000.00
Ascending Protection 9,000 x 2-- = 18,000.00
Governors --- 3,000 x 2 ----------- = 6,000.00
Fixtures 29,000 ea x 2 ------------ = 58,000.00
Cab flooring 8,000 x 2 ------------= 16,000.00
Labor ----150,000 x 2 ----------- = 360,000.00
Misc, permits, building work---- = 67,000.00
Passenger 14 ----------------------------------------- $ 312,000.00
Door equipment – 28,000---- -----= 28,000.00
Controllers 27,000 ea ------------ = 27,000.00
Machines 24,000 ----------------- = 24,000.00
Ascending Protection -------------- = 9,000.00
Governor ---------------------------- 3,000.00
Fixtures 26,000 ------- ------------ = 26,000.00
Cab cosmetics ---------------------- 15,000.00
Labor ------------------------------- = 105,000.00
Misc, permits, bldg work, etc ----- = 75,000.00
Freight 15 ----------------------------------------------= $ 384,000.00
Door equipment – 22,000 x 5 -----= 110,000.00
Controllers 27,000 ea ------------ = 27,000.00
Machines 24,000 ----------------- = 24,000.00
Ascending Protection -------------- = 9,000.00
DETROIT P AND DC Page 6
Governor ---------------------------- 3,000.00
Fixtures 26,000 ------- ------------ = 26,000.00
Cab flooring, fix cab -------------- 25,000.00
Labor ------------------------------- = 85,000.00
Misc, permits, bldg work, etc ----- = 75,000.00
DETROIT P AND DC Page 7
EQUIPMENT INVENTORY PASSENGER ELEVATOR 14
City / State ID: Elevator 14 –
Control Type: Existing Miprom Controller 1992 Installation
Proposed new MCE microprocessor
Contract Speed: Existing 100 FPM
Proposed 100 FPM
Machine Type: Existing Montgomery 208E
Proposed replacement of controller and machine, governor, add
ascending protection
Door Equipment: Existing MAC center parting doors
Proposed new GAL MOVFR door equipment
Door Size / Type: Existing single speed center opening 42” wide by 7’ 0” high
Proposed single speed center opening 42’ Wide by 7’ 0” high
Number of Openings: Existing (5), front in line,
Proposed (5) front in line
Travel: Field Verify
Floor Served: Existing *G,1, 2, 3, 4,
Proposed *G, 1, 2, 3, 4
Capacity: Existing 2500 lbs
Proposed 2500 lbs
Note: The full detail report and pictures will be posted on the web site.
DETROIT P AND DC Page 8
EQUIPMENT INVENTORY FREIGHT ELEVATORS 1, 2
City / State ID: Elevator 1 – 7845
Elevator 2 -- 7846
Control Type: Existing MCE IMC - SCR Controllers 2000 Installation
Proposed new MCE microprocessor VVVF controller
Contract Speed: Existing 100 FPM
Proposed 100 FPM
Machine Type: Existing Otis Geared OH Traction
Proposed replacement of controller, machine, add ascending
protection
Door Equipment: Existing Courion power bi parting vertical doors
Proposed new power bi parting doors due to damage to door
panels, obsolete model of controller
Door Size / Type: Existing 8’ 0” wide by 8’ 0” high
Proposed 8’ 0’ Wide by 8’ 0” high
Number of Openings: Existing (7), 5 front in line, 2 rear
Proposed (7) 5 front in line, 2 rear
Travel: Field Verify
Floor Served: G, GR, *1, 1R, 2, 3, 4
Capacity: Existing 12,000 lbs. elevator 1
Existing 8,000 lbs. elevator 2
Proposed 12,000 lbs. elevator 1
Proposed 8,000 lbs. elevator 2
Note: The full detail report and pictures will be posted on the web site.
DETROIT P AND DC Page 9
EQUIPMENT INVENTORY FREIGHT ELEVATORS 3, 4
City / State ID: Elevator 3 – 7853
Elevator 4 -- 7852
Control Type: Existing MCE IMC - SCR Controllers 2000 Installation
Proposed new MCE microprocessor VVVF controller
Contract Speed: Existing 100 FPM
Proposed 100 FPM
Machine Type: Existing Otis #2 Geared OH Traction
Proposed replacement of controller, machine, add ascending
protection
Door Equipment: Existing Courion power bi parting vertical doors
Proposed new power bi parting doors due to obsolete model of
controller
Door Size / Type: Existing 8’ 0” wide by 8’ 0” high
Proposed 8’ 0’ Wide by 8’ 0” high
Number of Openings: Existing (8), 6 front in line, 2 rear
Proposed (8) 6 front in line, 2 rear
Travel: Field Verify
Floor Served: G, GR, *1, 1R, 2, 3, 4, R
Capacity: Existing 8,000 lbs.
Proposed 8,000 lbs.
Note: The full detail report and pictures will be posted on the web site.
DETROIT P AND DC Page 10
EQUIPMENT INVENTORY FREIGHT ELEVATORS 15
City / State ID: Elevator 15 – none found
Control Type: Existing MiProm Ultron DDC Controllers 2003 Installation
Proposed new MCE microprocessor VVVF controller
Contract Speed: Existing 100 FPM
Proposed 100 FPM
Machine Type: Existing Montgomery 210 geared OH Traction
Proposed replacement of controller, machine, add ascending
protection
Door Equipment: Existing Courion power bi parting vertical doors
Proposed new power bi parting doors due to damage to door
panels, obsolete model of controller
Door Size / Type: Existing 7’ 3” wide by 7’ 0” high
Proposed 7’ 3’ Wide by 7’ 0” high
Number of Openings: Existing (5), 5 front in line
Proposed (5) 5 front in line
Travel: Field Verify
Floor Served: G, *1, 2, 3, 4
Capacity: Existing 12,000 lbs.
Proposed 12,000 lbs.
Note: The full detail report and pictures will be posted on the web site.
DETROIT P AND DC Page 11
EQUIPMENT OBSERVATIONS
Although the facility has a wide selection of equipment, none of it is in good shape. In addition
to being old, well used and suffering from a lack of adequate maintenance, the callback rate is
abnormally high. Like so many of the USPS facilities, it has potential to be a lot better than it is
without a modernization. However, it still needs upgrades due to obsolescence. The lack of
adequate technical ability on the equipment is a factor on repetitive calls.
The machine rooms are fairly clean but there is too much mischief. The lack of test tags on the
governor or controller that is required by code. Late 5-year load tests.
The freights have old but can be better controls. All the freights had significant flooring
problems. The floor has ruts in the wood flooring. This can be somewhat dangerous to certain
loads that shift during loading and unloading.
The USPS team is resilient and knows how to get around problems. They do shift around as
needed to use whatever elevator is running. One thing that will improve the overall operation
when these units get modernized is some field training to the USPS personnel. The service
vendor is supposed to be a partner on site, not a phantom.
DETROIT P AND DC Page 12
Passenger Elevator, Evaluation of specific components is detailed below:
GUIDE RAIILS AND SUPPORTS
The guide rails and supports are suitable for reuse and should be retained.
BUFFERS
The existing oil buffers may be retained.
CAR SLING
The car sling (structural members which support the platform) shall be retained.
PLATFORM
The existing platform is suitable for reuse in modernization, and the isolation in this facility is
not crucial to performance.
SLIDE / ROLLER GUIDES
The existing roller guides are the original units and have reached the end of their useful life. It is
recommended they be replaced and upgraded.
LOAD WEIGHING
Load weighing is warranted in order to pre-torque the motor drives.
PIT LADDER
The existing pit ladders are adequate by current code and should be retained for each pit.
MOTOR
The motor will be upgraded to a VVVF unit to enhance energy savings.
CAR DOOR EQUIPMENT
The existing MAC door equipment should be replaced with similar or GAL door equipment.
New operators would allow the doors to perform efficiently for an additional 20 to 30 years.
New door operators would provide safer door operation, including ease of reversal, controlled
closing pressure, and smoother, quieter operation.
CONTROLLERS
The controller is at the end of its useful life. It is not fiscally responsible to try to save this
controller.
New non-proprietary microprocessor-based controls are recommended in modernization. The
definition of non-proprietary is where the manufacturer can support and train any technician on
the equipment regardless of employer. This prevents OEM manufacturers as they will not train
competitors.
MACHINE ROOM
DETROIT P AND DC Page 13
Conforming code compliant access already exists. Some main line disconnect and some 110 volt
disconnect improvements are warranted, fire rating the rooms is crucial for compliance.
Lighting will be added and relocation is necessary for compliance.
HOISTWAY WIRING
The hoistway wiring will be replaced.
TRAVELING CABLES
The existing traveling cables have reached the end of their useful life. It is recommended that
new traveling cables be provided.
CAR TOP INSPECTION STATION
The car top inspection station does meet current code and but warrants relocation or a new one as
it has to be accessible from the entrance. The new station should include a work light, operating
buttons, a I I 0-volt outlet, and fire fighter's requirements.
LIMIT SWITCHES
The present limit switches are original. They can be replaced or at a minimum be rewired and
retained. It is recommended that new limit switches be provided during modernization.
ACCESS SWITCHES
The elevators currently do have bottom access switches. Access switches are required by current
code and therefore should be upgraded during modernization of the elevators to match the
manufacturer of the new car operating panel.
PIT SWITCHES
The pit currently does not have a conforming pit switch. Elevator code requires a new style pit
switch. It is recommended that a new pit switch be provided during modernization.
PIT EQUIPMENT
The pit does not currently have adequate lights for code compliance. Additional lights will be
added to obtain the 10 foot candles needed for safety. LED florescent are the best option to add
for this parameter. The lights need to be above the 24 inches from the pit floor to avoid NEMA
upgrade requirements.
HOISTWAY DOOR SILLS
Existing hoistway door sills can be reused.
CAB
The existing cab has a steel shell and canopy. Minor repairs and minor cosmetic improvements
should be adequate for retaining the cabs.
CAR FIXTURES
The present car fixtures do meet Code requirements but not the reliability factor. The code
requires replacement in order to incorporate new firefighters' requirements and ADA
requirements.
DETROIT P AND DC Page 14
We recommend the following fixtures:
+ New vandal resistant car station, including emergency lighting
+ New communications system meeting Two Way Communication requirements
+ Locked service cabinet
+ New position indicator in the car operating panel
HALL STATIONS
The existing hall stations do meet code but not a reliability standard. We recommend that new
stations be installed. New hall station fixture plates will be engraved or embossed with "Do not
use in case of fire" and pictograph, as required. Illuminated door open, door close and door stop
buttons would be added at each station.
Phone monitoring will be added due to code. This includes an indicator light, buzzer and text on
the main egress landing hall button plate. Because the other car does not have this feature, if the
cars share a line, the other car would be monitored as well.
.
HOISTWAY ENTRANCES
The existing entrances, in which the frames support the door equipment, can be reused.
HOISTWAY DOOR EOUIPMENT
The hoistway doors do have the code required I 1/2hr fire label. It is recommended that the
hoistway doors be retained. The door tracks and related hardware shall be replaced due to their
style.
MAINLINE ELECTRICAL POWER
The mainline disconnect switches will be relocated. A new car light 110 volt fused disconnect
and a disconnect for the oil cooler shall also be added to the machine room.
FIREFIGHTERS'SERVICE
The elevators require firefighters' service to meet current code requirements. Smoke sensors and
related equipment for elevators were provided for the other car and need to be interfaced.
FIREFIGHTERS' SERVICE SIGNS
The fire recall floor pushbutton station and the new car stations are to be engraved with the
proper wording for phase I firefighters' service instructions.
DETROIT P AND DC Page 15
Modernization Plan / Passengers
NOTE: ITEMS MARKED WITH AN X ARE INCLUDED WITHIN THE SCOPE OF WORK, BUDGETED ON BUILDING WORK LINE.
ASSOCIATED WORK INCLUDED BY ELEVATOR CONTRACTOR:
The following minimum work is included in the project. It is the intent for the Contractor
to include all requirements needed to comply with current code.
Summary including but not limited to the following.
1. _____ Hardware cloth between hoistways during the modernization.
2. __X___ All cutting, patching, and painting made necessary by this project and
installation including the hoistway portion.
3. ___x__ Painting of all equipment. The controllers if not damaged can remain the
manufacturers standard color and not require painting. If just primed, paint an
enamel tool gray. The floors, machines, hoistway equipment will require at least one
coat of a quality grade of enamel.
4. __x___ Telephone line properly identified with a call back number will be provided
but will be pulled into the machine room by the EC. (Elevator Contractor will
provide a handi-box above the controllers piped to outside the machine room for the
phone company to connect the line to the controllers). It is the intent to only have one
phone line for each bank of elevators. Make provisions for compliance utilizing a
splitter and identifying each unit
5. __x___ Assistance to the General Contractor to complete the entire installation.
WORK CONSIDERED WORK BY OTHERS
ASSOCIATED WORK COORDINATED WITH ELEVATOR CONTRACTOR:
1. __x__ Signage on machine room doors, feeder tags on disconnects, other required
data tags and signage per code. Examples “Elevator Equipment Room” on the
machine room door, NEC distribution tags on each disconnect, Code Data Tags on
the controller
2. __x___ Smoke Detectors per floor, machine room. Address the lobby units and
machine room for the elevator recall functions. Wire to controllers. Main Egress is
1, Alternate floor is 2. Shunt trip module, fire hat or pit module. (On this site, smokes
exist for the other half of the duplex, will be tied into new controller)
Hoistways
1. __x___ Cut wall block outs and fire rated closure for control and signal fixture boxes
that penetrate walls.
DETROIT P AND DC Page 16
2. _____ Structural slab, concrete wall pockets and or structural steel beams for support
of the hoist machine, rope sheaves, dead end hitch beams.
3. _____ Motorized hoistway vent if facility has sleeping quarters. Venting per code
4. __x___ Protect open hoistways and entrances during modernizations per OSHA
regulations.
5. __x___ Seal or patch hoistways to meet current fire codes.
Machine room and machinery space
6. __x___ Machine Room venting, temperature control. Maintain minimum
temperature of 55 F, maximum of 90-degree F limits. Relative humidity 85 %, non-
condensing
7. _____ Labeled Lockable self-closing door.
8. _____ Fire Extinguisher in each respective machine room. (ABC 10 lbs)
9. ___x__ Fire rated enclosure, patch holes in the machine room wall (for this site, the
access area to the pit from the machine room should be redone with sheetrock rather
than the existing mesh piece)
10. __x___ Low voltage modules for fire recall. Quantity required, main floor, flashing
hat, other than main floor, shunt trip if used, pit if enforced on this site, existing
detectors can be paralleled for this new controller)
11. __x___ Room identified as “Elevator Equipment Room”. Minimum ½ high letters
Electrical
12. ___x__ Lighting in machine room to meet 19-foot candles, properly protected.
13. _____ Provide an earth ground to the main line disconnect and to the final destination
of the controller.
14. _____ Main line must be fused, lockable and tag out capable. (for this site, main line
has to be relocated)
15. _____ Shunt trip main line of proper sizing if sprinkled.
16. _____ Fused disconnect or breaker panel for car lights per elevator properly marked
and identified.
17. _____ GFCI receptacles in machine room.
18. ___x__ Telephone line for each individual elevator control. Line to be terminated
above each controller in an electrical 1900 box attached to the ductwork or top of
controller. The phone number shall be identified on the cover of the handibox. All
piping within the machine room shall be in conduit.
19. __x___ Fire alarm initiating devices in each elevator lobby, for each group of
elevators or single elevator and each machine room to initiate fire service Phase I
return feature. Devices at the top of the hoistway per code. Zoned appropriately to
the ASME 17.1 2000 Safety Code for Elevators.
20. _____ Conduit from the closest hoistway of each group or single elevator to the main
fire command center control room if one exists. Coordinate the size, number and
location of conduits or duct with the Elevator Contractor but large enough to include
spares for future security functions.
DETROIT P AND DC Page 17
21. __x___ Comply with prevailing code authority’s requirements
Pit area
22. __x___ Lighting in the pit area to meet minimum 10-foot candles per pit.
23. _____ GFI receptacle in each pit. Non GFI receptacle for each sump pump as needed.
We recommend a non gfi to prevent premature trip when water is in fact present.
24. ___x__ Hoistway compliance issues, patch any holes
25. _____ If a sump hole exists, it must have a grate over it.
26. _____ A sump should have a non gfi, single outlet, should not be plugged into a GFI
27. _____ Ladder that extends a minimum of 48 inches above the lowest landing. This
means either a grab bar to an existing ladder or a new ladder for the height
compliance. Also needs a 4.5” inch toe hold per rung, rungs to be skid free rungs
Standby Power if available
25. _____ Standby power to run one elevator at a time in each group and / or single
elevator unit at full speed and capacity and capture each unit if available at the main
egress landing. At least one elevator per tower that serves all floors shall be
designated to run on emergency power until normal power is restored.
26. _____ Provide conductors from auxiliary dry contacts located in the standby power
transfer switch to a selector key switch or device for each elevator group or single
elevator unit. A time delay of 60 seconds for pre transfer signals shall be provided.
27 _____ Emergency power to each group controller or primary controller and each
controller for car lighting, machine room ventilation, machine room lighting.
28. _____ Emergency power to emergency communication devices if the telephone line
is not supported by backup. If intercom service is used to an onsite security desk, it
shall be supported by emergency power.
29. ____ For hydros, provide a dry contact from the main line disconnect switch for a
battery rescuvator if no emergency power.
DETROIT P AND DC Page 18
All Freight Elevators, Evaluation of specific components is detailed below:
GUIDE RAIILS AND SUPPORTS
The guide rails and supports are suitable for reuse and should be retained.
BUFFERS
The existing buffers may be retained.
CAR SLING
The car sling (structural members which support the platform) shall be retained.
PLATFORM
The existing platform is suitable for reuse in modernization, and the isolation in this facility is
not crucial to performance.
SLIDE / ROLLER GUIDES
The existing slide guides are the original units and have reached the end of their useful life. It is
recommended they be replaced and upgraded.
LOAD WEIGHING
Load weighing is warranted in order to pre-torque the motor drives.
PIT LADDER
The existing pit ladders are adequate by current code and should be retained for each pit.
MOTOR
The motor will be upgraded to a VVVF unit to enhance energy savings.
CAR DOOR EQUIPMENT
The existing Courion door equipment should be replaced with similar or better door equipment.
Many of the hoistway door panels are damaged and warrant replacement. New operators would
allow the doors to perform efficiently for an additional 20 to 30 years. New door operators
would provide safer door operation, including ease of reversal, controlled closing pressure, and
smoother, quieter operation.
CONTROLLERS
The controller is at the end of its useful life. It is not fiscally responsible to try to save this
controller.
New non-proprietary microprocessor-based controls are recommended in modernization. The
definition of non-proprietary is where the manufacturer can support and train any technician on
the equipment regardless of employer. This prevents OEM manufacturers as they will not train
competitors.
DETROIT P AND DC Page 19
MACHINE ROOM
Conforming code compliant access already exists. Some main line disconnect and some 110 volt
disconnect improvements are warranted, fire rating the rooms is crucial for compliance.
Lighting will be added and relocation is necessary for compliance.
HOISTWAY WIRING
The hoistway wiring will be replaced.
TRAVELING CABLES
The existing traveling cables have reached the end of their useful life. It is recommended that
new traveling cables be provided.
CAR TOP INSPECTION STATION
The car top inspection station does meet current code but not accessible from the entrance. The
car top run station must be relocated or a stop switch mounted on the front side of the car top to
secure the car prior to getting on it. The new station should include a work light, operating
buttons, a 110-volt outlet, and fire fighter's requirements. It is to be located at a convenient
location on top of the crosshead. Additional stop switches shall be added to secure the car from
the entrance.
LIMIT SWITCHES
The present limit switches are original. They can be replaced or at a minimum be rewired and
retained. It is recommended that new limit switches be provided during modernization.
ACCESS SWITCHES
The elevators currently do have bottom access switches. Access switches are required by current
code and therefore should be upgraded during modernization of the elevators to match the
manufacturers style of the new fixtures.
PIT SWITCHES
The pit currently does not have a conforming pit switch. Elevator code requires a new style pit
switch. It is recommended that a new pit switch be provided during modernization.
PIT EQUIPMENT
The pit does not currently have adequate lights for code compliance. Additional lights will be
added to obtain the 10 foot candles needed for safety. LED florescent are the best option to add
for this parameter. The lights need to be above the 24 inches from the pit floor to avoid NEMA
upgrade requirements.
HOISTWAY DOOR SILLS
Existing hoistway door truckable sills can be reused and those with damage or are loose shall be
repaired and secured.
CAB
DETROIT P AND DC Page 20
The existing cab has a steel shell and canopy. Minor repairs and painting should be adequate for
retaining the cabs. Several cabs need the side walls pulled in and a new bumper rail installed
to limit future damage. All wooden flooring is damaged and warrants replacement or covered
with aluminum deckplates.
CAR FIXTURES
The present car fixtures do meet Code requirements but not the reliability factor. The code
requires replacement in order to incorporate new firefighters' requirements.
We recommend the following fixtures:
+ New vandal resistant car station, including emergency lighting
+ New communications system meeting Two Way Communication requirements
+ Locked service cabinet
+ New position indicator in the car operating panel
HALL STATIONS
The existing hall stations do meet code but not a reliability standard. We recommend that new
stations be installed. New hall station fixture plates will be engraved or embossed with "Do not
use in case of fire" and pictograph, as required. Illuminated door open, door close and door stop
buttons would be added at each station.
Phone monitoring will be added due to code. This includes an indicator light, buzzer and text on
the main egress landing hall button plate. Because the other car does not have this feature, if the
cars share a line, the other car would be monitored as well.
.
HOISTWAY ENTRANCES
The existing entrances, in which the frames support the door equipment, can be reused.
HOISTWAY DOOR EOUIPMENT
The hoistway doors do have the code required I 1/2hr fire label. It is recommended that the
hoistway doors be replaced due to the damage and wear. The door tracks, locks and related
hardware shall be replaced due to their wear and damage.
MAINLINE ELECTRICAL POWER
The mainline disconnect switches will be relocated. A new car light 110 volt fused disconnect
and a disconnect for the oil cooler shall also be added to the machine room.
FIREFIGHTERS'SERVICE
The elevators require firefighters' service to meet current code requirements. Smoke sensors and
related equipment for elevators were provided for the other car and need to be interfaced.
FIREFIGHTERS' SERVICE SIGNS
The fire recall floor pushbutton station and the new car stations are to be engraved with the
proper wording for phase I firefighters' service instructions.
DETROIT P AND DC Page 21
Modernization Plan / Freights
NOTE: ITEMS MARKED WITH AN X ARE INCLUDED WITHIN THE SCOPE OF WORK, BUDGETED ON BUILDING WORK LINE.
ASSOCIATED WORK INCLUDED BY ELEVATOR CONTRACTOR:
The following minimum work is included in the project. It is the intent for the Contractor
to include all requirements needed to comply with current code.
Summary including but not limited to the following.
6. __x___ Hardware cloth between hoistways during the modernization.
7. __X___ All cutting, patching, and painting made necessary by this project and
installation including the hoistway portion.
8. ___x__ Painting of all equipment. The controllers if not damaged can remain the
manufacturers standard color and not require painting. If just primed, paint an
enamel tool gray. The floors, machines, hoistway equipment will require at least one
coat of a quality grade of enamel.
9. __x___ Telephone line properly identified with a call back number will be provided
but will be pulled into the machine room by the EC. (Elevator Contractor will
provide a handi-box above the controllers piped to outside the machine room for the
phone company to connect the line to the controllers). It is the intent to only have one
phone line for each bank of elevators. Make provisions for compliance utilizing a
splitter and identifying each unit
10. __x___ Assistance to the General Contractor to complete the entire installation.
WORK CONSIDERED WORK BY OTHERS
ASSOCIATED WORK COORDINATED WITH ELEVATOR CONTRACTOR:
3. __x__ Signage on machine room doors, feeder tags on disconnects, other required
data tags and signage per code. Examples “Elevator Equipment Room” on the
machine room door, NEC distribution tags on each disconnect, Code Data Tags on
the controller
4. __x___ Smoke Detectors per floor, machine room. Address the lobby units and
machine room for the elevator recall functions. Wire to controllers. Main Egress is
1, Alternate floor is 2. Shunt trip module, fire hat or pit module. (On this site, smokes
exist for the other half of the duplex, will be tied into new controller)
Hoistways
28. __x___ Cut wall block outs and fire rated closure for control and signal fixture boxes
that penetrate walls.
DETROIT P AND DC Page 22
29. _____ Structural slab, concrete wall pockets and or structural steel beams for support
of the hoist machine, rope sheaves, dead end hitch beams.
30. _____ Motorized hoistway vent if facility has sleeping quarters. Venting per code
31. __x___ Protect open hoistways and entrances during modernizations per OSHA
regulations.
32. __x___ Seal or patch hoistways to meet current fire codes.
Machine room and machinery space
33. __x___ Machine Room venting, temperature control. Maintain minimum
temperature of 55 F, maximum of 90-degree F limits. Relative humidity 85 %, non-
condensing
34. _____ Labeled Lockable self-closing door.
35. _____ Fire Extinguisher in each respective machine room. (ABC 10 lbs)
36. ___x__ Fire rated enclosure, patch holes in the machine room wall (for this site, the
access area to the pit from the machine room should be redone with sheetrock rather
than the existing mesh piece)
37. __x___ Low voltage modules for fire recall. Quantity required, main floor, flashing
hat, other than main floor, shunt trip if used, pit if enforced on this site, existing
detectors can be paralleled for this new controller)
38. __x___ Room identified as “Elevator Equipment Room”. Minimum ½ high letters
Electrical
39. ___x__ Lighting in machine room to meet 19-foot candles, properly protected.
40. _____ Provide an earth ground to the main line disconnect and to the final destination
of the controller.
41. _____ Main line must be fused, lockable and tag out capable. (for this site, main line
has to be relocated)
42. _____ Shunt trip main line of proper sizing if sprinkled.
43. _____ Fused disconnect or breaker panel for car lights per elevator properly marked
and identified.
44. _____ GFCI receptacles in machine room.
45. ___x__ Telephone line for each individual elevator control. Line to be terminated
above each controller in an electrical 1900 box attached to the ductwork or top of
controller. The phone number shall be identified on the cover of the handibox. All
piping within the machine room shall be in conduit.
46. __x___ Fire alarm initiating devices in each elevator lobby, for each group of
elevators or single elevator and each machine room to initiate fire service Phase I
return feature. Devices at the top of the hoistway per code. Zoned appropriately to
the ASME 17.1 2000 Safety Code for Elevators.
47. _____ Conduit from the closest hoistway of each group or single elevator to the main
fire command center control room if one exists. Coordinate the size, number and
location of conduits or duct with the Elevator Contractor but large enough to include
spares for future security functions.
DETROIT P AND DC Page 23
48. __x___ Comply with prevailing code authority’s requirements
Pit area
49. __x___ Lighting in the pit area to meet minimum 10-foot candles per pit.
50. _____ GFI receptacle in each pit. Non GFI receptacle for each sump pump as needed.
We recommend a non gfi to prevent premature trip when water is in fact present.
51. ___x__ Hoistway compliance issues, patch any holes
52. _____ If a sump hole exists, it must have a grate over it.
53. _____ A sump should have a non gfi, single outlet, should not be plugged into a GFI
54. _____ Ladder that extends a minimum of 48 inches above the lowest landing. This
means either a grab bar to an existing ladder or a new ladder for the height
compliance. Also needs a 4.5 inch toe hold per rung, rungs to be skid free rungs
Standby Power if available
25. _____ Standby power to run one elevator at a time in each group and / or single
elevator unit at full speed and capacity and capture each unit if available at the main
egress landing. At least one elevator per tower that serves all floors shall be
designated to run on emergency power until normal power is restored.
26. _____ Provide conductors from auxiliary dry contacts located in the standby power
transfer switch to a selector key switch or device for each elevator group or single
elevator unit. A time delay of 60 seconds for pre transfer signals shall be provided.
27 _____ Emergency power to each group controller or primary controller and each
controller for car lighting, machine room ventilation, machine room lighting.
28. _____ Emergency power to emergency communication devices if the telephone line
is not supported by backup. If intercom service is used to an onsite security desk, it
shall be supported by emergency power.
29. ____ For hydros, provide a dry contact from the main line disconnect switch for a