Power DistributionControl Systems
Power StationControl Systems
Control Room Technology
AutomationEquipment
Electronic Alarm Indication Systems
ME 3011 compact
22
3
Contents Page
System Characteristics 4
Housing Versions 6
Signaling Sequences 6
Technical Data 8
Terminal Assignment 10
Software Tools 11
Table of Contents
4
The ME 3011 compact series of our ME 3011 alarm system family is characterized by its small installation size for the standard formats with 96 mm grid dimension and the high packing density of the available messages.
ME 3011 compact is available in three versions:
• ME 3011 compact with LED display
- Intelligent message processing, indication and transmission
- 12, 28, 44 or 60 messages, expandable
- Message indication on yellow LED display
- Different signaling methods
- Message texts on printed paper labels
- Operation by means of front pushbuttons or external inputs - Communication capability
• ME 3011 compact with backlight display
- Intelligent message processing, indication and transmission
- 4, 10 or 16 messages, expandable
- Message indication by means of innovative wide band backlight LED rear illumination
- Signalizing colors: red, green, white, yellow and blue
- Different signaling methods
- Message texts on printable front foil
- Operation by means of front pushbuttons or external inputs- Communication capability
• ME 3011 compact Signalizing with backlight display
- Solely for message indication
- 6, 12 or 18 messages
- Expanding unit for ME 3011 compact or standalone unit
- Signalizing by means of innovative wide band backlight LED rear illumination
- Signalizing colors: red, green, white, yellow and blue
- Connection via ribbon cable for expandable units or terminals - Message texts on printable front foil
Communication options such as an IEC 60870-5-104/101 interface can be easily integrated.
ME 3011 compact combines modular design with compact size and a defined number of messages to provide a powerful yet cost-effective alarm indication solution.
System Characteristics
5
Housing robust metal housing
No. of points 4 to 60 points
Housing versions housing versions (in mm) 96 x 96, 192 x 96, 288 x 96, 384 x 96
Cut out table 91 x 91, 187 x 91, 283 x 91, 379 x 91 (in mm)
Arrangement gap less stack mounting
Mounting depth 117 mm for all housing versions
Terminals plug-in spring terminals
Supply voltage 24 V DC or 110/220 V DC and/or 110/230 V AC redundant
Message input voltage 24 to 220 V DC
Configuration RS 232 interface for configuration via PC
BUS integrated slave Modbus interface up to 19.200 Baud
Message memory event memory with 2,5 ms accuracy
Signaling different ISA signaling methods
Flashing synchronization integrated flashing synchronization input/output
Optical alarm indication LED or new backlight LED indicator
message indication easily replaceable labels or printable plastic front foil
Message dissemination relays for all messages
Group message outputs 3 relays for groups messages or external horns
Potential separation all interfaces galvanically isolated
Sound signal 2 internal horns
Operation push buttons at the front or separate function inputs
EMV acc. to DIN EN 61000-4
Environmental temperature range 0 to 55 °C
Configuration configuration software for free
Optional visualization tool e-view
Optional IEC 60870-5-101- and IEC 60870-5-104 interface
6
ME 3011 compact
Dimensions W x H in mm
96 x 96
91 x 91
192 x 96
187 x 91
288 x 96
283 x 91
384 x 96
379 x 91
bezel
panel cutout
ME 3011 compact with LED indicator
ME 3011 compact with backlight indicator
ME 3011 compact Signaling with backlight indicator
Rear view
Housing Versions
7
The ME 3011 can be configured in order to comply with 16 signaling sequences. Among them the most important are the following:ISA-RP 18.1/(ISA-S18.1)ISA-1/ (A), ISA-1A/ (A-5), ISA-1B/ (A-4), ISA-2A/ (R-8), ISA-2C/ (M), ISA-4A/ (F1A), ISA-4AR/ (F1M) etc.Other sequences can be implemented on request.
Alarm sequences
REF ISA ALARM NORMAL ABNORMAL Acknowledge Back to Back to Acknowledge RESET Sound Light NORMAL NORMAL before Sound Light Acknowledge
ISA 1 Light
Sound
ISA 1A Light
Sound
ISA 1B Light
Sound
ISA 2A Light F F S F F S
Sound
ISA 2C Light
Sound
PRIMARY SIGNAL SEQUENCES (1st Event)
Back to NORMAL REF ALARM NORMAL ABNORMAL Acknowledge Back to NORMAL before Acknowledge Acknowledge RESET ISA Initial Subseq. Initial Subseq. Initial Subseq Initial Subseq. Initial Subseq
ISA 4A Light
Sound
ISA 4R Light
Sound
(M) default
LEGEND F = Fast LED Off Siren = Off LED On S = Slow LED intermittent Siren = On
Signaling Sequences
8
Technical Data
Electronic Alarm Indication SystemsME 3011 compact
1 Supply Voltage
1.1 Power Supply Standard 24 V DC ± 20 %
1.2 Power Supply Input 110 to 220 V DC, ± 20 % and/or 110 to 230 V AC, ± 20 % redundant contingent
Output 24 V DC/0,075 A
1.3 Power supply fault detection AC and/or DC
2 Alarm or message inputs
2.1 Input 4 to 60 Potential separation optocoupler
Input voltage 24, 48, 60, 110/250 V DC, ±20 %
Input current 3 mA (typical)
Input filter lower value = 5 ms, configur-able in steps of 2,5 ms
2.2 External push button inputs Input voltage 24 V DC
Potential separation optocoupler
Functions: Sound acknowledgement (HA) like push button
Light acknowledgement (LA) like push button
Delete/Reset (RE) like push button
Light test/ Function test (LT) like push button T
Push button inputs without function Keyboard OFF KB/O
Sleep Mode SLM
2.3 Flash synchronism output/input and/or flash 24 V DC
Potential separation optocoupler
2.4 Minute pulse input 24 V DC
Potential separation optocoupler
3 Outputs
3.1 Relays 3 freely programmable relays for various functions, e. g. external buzzer, voltage fault, alarm group
3.2 Sound indication 90 dB / 10 cm, 4 kHz
3.3 Repeat relays (option) 1 floating contact for each alarm point
3.4 Repeat relays for power 1 floating contact for each supply fault detector PSFD
Note: Contact capacity for all relays is 5A / 24V DC for resistive load. Maximal switching voltage: 125V DC / 250 V AC
4 Interfaces
4.2 Communication for configuration RS 232 RS 232 bi-directional (option) Baud rate 9 600, n, 8, 1
4.3 Communication for- Modbus RS 485 RS 485 bi-directional, serial (option) communication (configurable) Baud rate 110 to 19 200 Parity even, odd or none Stop bit 1 or 2 Protocol Modbus RTU (Slave)
9
5 Event register
5.1 Events 1.000 with time stamp
5.2 Resolution 1 ms, samples 2,5 ms
5.3 Interface RS 485
5.4 Protocol Modbus RTU (Slave)
6 Visualization
6.1 Light indicators
LED indication color: yellow
Wide band backlight available in red, green, white
yellow and blue
6.2 Flashing frequency fast: approx. 1,2 Hz
slow: approx. 0,4 Hz
7 General
7.1 Alarm sequence ISA 1, 1A, 1B, 2A, 2C, 4A; others on request
7.2 Environment Operation temperature 0 to + 55 °C
Storage temperature - 20 to + 80 °C
Relative Humidity 0 to 95 %, without condensa-tion
7.3 Protection class IP40
7.4 Isolation 2 kV, 50 Hz, IEC 60255-5
7.5 Emission DIN EN 55011
7.6 ESD DIN EN 61000-4-2
7.7 EM HF field DIN EN 61000-4-3
7.8 HF inflow DIN EN 61000-4-6
7.9 Burst DIN EN 61000-4-4
7.10 Surge DIN EN 61000-4-5
7.11 Terminals Teminal connectors (remov-able) for cables up to 1,5 mm2
Phönix Combicon 5,08 grid
7.12 Tropicalized type special option on request
10
��
��
�
� �
� �
� �
� �
� �
� �� �� �
� �
� � � �
� � �
� � �
� � � �
� � �
� �
� �
� �
� � � � �
�
� � � �
� � �
�
�
�
� �
� �
� �
� �
� �
� �
� �
� �
� �
� � �
� � �
� � �
�
� �
� �
� �
� �
� �
� �
� �
� �
� �
� � �
� � �
� � �
� �
�
� � �
� � �
�
� � � � � � �
� � � � � � �
� � � �
� � � �
� � � �
� � � �
� � � �
� � � �
� � � � � �
� � � � � �
� �
� ��
� � ��
� � ��
� � ��
� � �
� � �
� � �
� � �
� � �
� � �
� � �
� � �
�
� � �
� � �
� � �
� � �
� � �
� � �
� � �
� � �
� �
� � �
� � �
� � �
� � �
� � �
� � �
� � �
� � �
�
� � �
� � �
� � �
� � �
� � �
� � �
� � �
� � �
� �
externalHorn
Input 5
Input 6
Input 7
Input 8
M
9
5
6
7
8
Rep.1
Rep.2
Rep.3
Rep.4
Signal-Input Repeater-Output
Input 1
Input 2
Input 3
Input 4
1
2
3
4
Input 9
Input 10
Input 11
Input 12
10
11
12
Rep.5
Rep.6
Rep.7
Rep.8
Rep.9
Rep.10
Rep.11
Rep.12
9
5
6
7
8
1
2
3
4
10
11
12
L+
extern extern
KB off 1
FT/LT
2
RE
3
LA 4
HA
5
SLM
6
Remote Push-Buttons
7
optional+24V extern
M
Mod
bus
FlashSync.
Min.Imp
ConfigPC
4
5
6
7
8
9
10
11
12
13
14
+24V
+24V
–24V 5
4
M (24V)
L1+
L2+
–24V
RL4a
RL4b
RL5a
RL5b
RL6a
RL6b
ProgrammableRelay Output 4, 5, 6
ModbusTermination
PE
ME
3011
c_19
2x09
6_A
nsch
altu
ng_e
.EP
S
F1 1
2F2
L1+
L2+
3M
Power Supply
24 V DC
Power SupplyOutput +24 V
13
++
13
FirmwareUpload
L+
extern+ +
+
+
Input 13
Input 14
Input 15
Input 16
M
5
6
7
8
Signal-Input
1
2
3
4
Input 17
Input 18
Input 19
Input 20
extern+
Repeater-Output
Rep.13
Rep.14
Rep.15
Rep.16
Rep.17
Rep.18
Rep.19
Rep.20
L+
extern+
9
5
6
7
8
1
2
3
4
9
Input 21
Input 22
Input 23
Input 24
M
5
6
7
8
Signal-Input
1
2
3
4
Input 25
Input 26
Input 27
Input 28
extern+
Repeater-Output
Rep.21
Rep.22
Rep.23
Rep.24
Rep.25
Rep.26
Rep.27
Rep.28
L+
extern+
9
5
6
7
8
1
2
3
4
9
Terminal Assignment
11
Software e.Tools
• RS 485 interface
• up to 10 annunciators in one NET
• advanced communication protocols
• enhanced maintenance oriented functions
• event recording with 1,0 ms resolution with samples each 2,5 ms
RS232C interface (option)with 5, 10 or 15 m cables
This annunciator can total be represent for software. Software e.Tool ME 3011 config presents ample functionality that facilitates its use, bringing to the user all the configuration possibilities of the product.
ME 3011 brings powerful tools of dedicated supervision and control for applications in nets of indication systems. With intelligent user and not complicated an interface of, e.Tool ME 3011 view brings to the screen annunciating virtual with information in real time, beyond register events with resolution 1 ms. �
���
�
� �
� �
� �
� �
� �
� �� �� �
� �
� � � �
� � �
� � �
� � � �
� � �
� �
� �
� �
� � � � �
�
� � � �
� � �
�
�
�
� �
� �
� �
� �
� �
� �
� �
� �
� �
� � �
� � �
� � �
�
� �
� �
� �
� �
� �
� �
� �
� �
� �
� � �
� � �
� � �
� �
�
� � �
� � �
�
� � � �
� � � �
�
�
�
� � �
� � �
� �
www.mauell.com
Head officeGermanyHelmut Mauell GmbHAm Rosenhügel 1-742553 VelbertGermany
BrazilHelmut Mauell do Brasil Ltda.Klaus LiesenbergEstr. Est. Salvador de Leone 2998ITAPECERICA DA SERRA 06850-000 ITAPECERICA DA SERRA SAO PAULOBrazil
NetherlandsHelmut Mauell B.V.Jan GrootFahrenheitstraat 38-403846 AB HARDERWIJKNetherlands
SwitzerlandMauell AGMarkus HuberFurtbachstraße 178107 BUCHSSwitzerland
USAMauell CorporationGary M. Suchy31 Old Cabin Hollow RoadDILLSBURG PA 17019USA
Africa
Argentina
Australia
Austria
Belgium
Czech Republic
Denmark
Finland
France
Great Britain
Hungary
Indonesia
Iran
Korea
Kuwait
Malaysia
Norway
Poland
Portugal
Rumania
Russia
Sweden
Singapore
Spain
Thailand
Turkey
U.A.E.
05.3011.05E091