electromech engineers · output 3 (optional) : for alarm or compressor control relay ssr drive : :...

2

Upload: others

Post on 20-Jul-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ElectroMech Engineers · Output 3 (Optional) : For Alarm or Compressor Control Relay SSR Drive : : 5A/230VAC or 5A/30VDC, Resistive 5VDC @ 40mA (non-isolated) » Features

Salient Features

Independent Displays for Temperature & %RH

Input Versions : 'Dry Bulb / Wet Bulb' or Temperature / RH Transmitters

Independent Self Tune PID Control Loop for Temperature & Humidity

Heater & Humidifier Control Outputs

Optional Relay Output for Alarm / Compressor Control (with Time Delay)

Optional Serial Communication Port

Specifications » User Interface

Display

Keyboard

:

:

2 Rows of 4 digits, 7 Segment High Intensity LED

Upper Row : Temperature in Red

Lower Row : % RH in Green

4 Front Panel Keys, Highly Simplified Operation

» Input

Temperature Input Type

(Dry Bulb)

Humidity Input Type

(Wet Bulb)

Accuracy

Measuring Rate

Corrections

:

:

:

:

:

RTD : Pt100 3-wire, DIN 43760

DC Linear

: 0 – 1VDC, 1-3, 6VDC, 0-3.3VDC.

± 0.25% of reading, ± 1 LSD, ± 1°C

2 Samples per second (500mS Update)

LRC for 3-wire Pt100

» Outputs

Output 1

Output 2

:

:

For Heating (Dry Bulb Temperature)

Relay

SSR Drive

:

:

5A/230VAC or 5A/30VDC, Resistive

5VDC @ 40mA (non-isolated)

For Humidification (Wet Bulb Temperature)

Relay

SSR Drive

:

:

5A/230VAC or 5A/30VDC, Resistive

5VDC @ 40mA (non-isolated)

Composite 'Temperature + Humidity' Self Tune PID Controller

HumiTherm-c

Nikunj Vihar, Office no:- 10, Sahid Chock, Valsad-396001 M:- 09662639239 www.electromecheng.in E:[email protected]

ElectroMech Engineers

Page 2: ElectroMech Engineers · Output 3 (Optional) : For Alarm or Compressor Control Relay SSR Drive : : 5A/230VAC or 5A/30VDC, Resistive 5VDC @ 40mA (non-isolated) » Features

Output 3 (Optional) : For Alarm or Compressor Control

Relay

SSR Drive

:

:

5A/230VAC or 5A/30VDC, Resistive

5VDC @ 40mA (non-isolated)

» Features

Control Action

Tuning

Alarms

Compressor Control

Communication Port

(Optional)

:

:

:

:

:

Independently Programmable as PID or On-Off

Self-Tune Algorithm, simultaneous Automatic Setting of Basic P, I, D Values

for Dry / Wet Loops

Independent 'Band Alarm' for Temperature & %RH (Can be ORed &

Assigned to Output 3)

Independent Set Point with Settable Time Delay. PV based On-Off Control or

Dry Bulb SP based Continuous On / Off.

Serial, 2-wire, Half Duplex, RS485, Slave Mode

Settable Baud (4800, 9600, 19200, 38400, 57600), ID (1 to 127), Parity

(None, Even, Odd)

Start-stop synchronized MODBUS RTU Protocol

» General

Supply Voltage

Environmental

Panel Sealing

Electromagnetic

Safety Standard

Dimensions (mm)

Panel Cutout (mm)

Weight (Approx)

:

:

:

:

:

:

:

:

85 to 264V AC, 50 / 60 Hz

Operating 0 to 55°C, Storage -10 to 70°C

5 to 95 %RH Non-condensing

Conforming to IP 65, NEMA 4X

Conforming to Generic Emissions standard

EN50081-2 and general immunity requirements of

EN50082-2 (95)

Conforming to EN61010, installation category 2

(Voltage transients must not exceed 2.5 KV)

48 (H) X 48 (W) X 110 (D)

45 (H) X 45 (W)

250 grams

AN ISO 9001:2008 COMPANY