ELECTRICAL SAFETY INSPECTION REPORT
A & B OUTERWEAR LTD.
Plot # 29-30, CEPZ, Chittagong, Bangladesh.
Factory List:
1. A & B Outerwear Ltd.
Inspected by: Al-Amin
Report Generated by: Al-Amin
Inspected on March 7th 2015
Page 2 of 12
A & B Outerwear Ltd.
SUMMARY
The A & B Outerwear Ltd. factory is established in owned three building and four shed. Building-1 is three
storied; Building-2 is two storied and building three is one storied. Building-1 was constructed in 2010 and
production started in same year. Building-2 was constructed in 2011 and production started in same year.
Building-3 was constructed in 2011. The factory had approximately 1114 workers.
The Factory was surveyed for electrical safety by Woosun Energy and Construction Co., Ltd. (WEC). The
purpose of the survey was to identify significant electrical safety issues and to provide recommendations for
remediation based on applicable standards specified by the Accord.
The scope of this initial electrical safety inspection was limited to the review and identification of major
electrical safety issues. The inspection did not include identification of minor deficiencies, which would be
further dealt with as part of follow-up inspections.
Table below summarizes the major electrical safety issues identified during the inspection.
Recommendations have been provided to address each issue.
The implementation schedule shall be developed by the factory to remediate each of the findings. The
specific timing of improvements, including any requested extensions due to design/installation constraints,
shall be submitted to the Accord for an approval.
Page 3 of 12
A & B Outerwear Ltd.
FINDINGS AND RECOMMENDATIONS
FINDING NO: E- 1
CATEGORY: DESIGN, DRAWINGS & RECORDS
FINDING: Thermographic scanning of the entire electrical system has not been performed.
RECOMMENDATION: Thermographic scanning of the entire electrical system must be performed twice in a year.
PRIORITY: P2
REMEDIATION TIMEFRAME: 8 WEEKS
FINDING NO: E-2
CATEGORY: DESIGN, DRAWINGS & RECORDS
FINDING: Electrical Single Line Diagram (SLD) is unavailable.
RECOMMENDATION: Have a qualified engineer to create an as-built electrical SLD, mentioning all the required information, and get it reviewed by Accord.
PRIORITY: P2
REMEDIATION TIMEFRAME: 12 WEEKS
FINDING NO: E- 3
CATEGORY: DESIGN, DRAWINGS & RECORDS
FINDING: Insulation resistance test of electrical equipment is not performed.
RECOMMENDATION: Insulation resistant test of all the cables must be performed once every 2 year cycle and recorded (this must require a complete power shut off).
PRIORITY: P2
REMEDIATION TIMEFRAME: 8 WEEKS
Page 4 of 12
A & B Outerwear Ltd.
FINDING NO: E- 4
CATEGORY: DESIGN, DRAWINGS & RECORDS
FINDING: Electric safety program is not initiated.
RECOMMENDATION: Electrical safety training and awareness program for the electrical personnel and workers must be initiated and recorded.
PRIORITY: P2
REMEDIATION TIMEFRAME: 8 WEEKS
FINDING NO: E- 5
CATEGORY: DESIGN, DRAWINGS & RECORDS
FINDING: Factory does not have maintenance record.
RECOMMENDATION: Maintenance Manager or Safety Officer must keep accurate records and ensure that they reflect actual factory day to day operations.
PRIORITY: P2
REMEDIATION TIMEFRAME: 8 WEEKS
FINDING NO: E- 6
CATEGORY: DESIGN, DRAWINGS & RECORDS
FINDING: Transformer Oil Test report is unavailable.
RECOMMENDATION: Check the transformer oil condition by performing oil test, this must be done twice a year and recorded.
PRIORITY: P2
REMEDIATION TIMEFRAME: 8 WEEKS
FINDING NO: E- 7
CATEGORY: DESIGN, DRAWINGS & RECORDS
FINDING: Earth Pit resistance record is unavailable.
RECOMMENDATION: Record earth pit resistances for all the earth pits, and do it once a year.
PRIORITY: P2
REMEDIATION TIMEFRAME: 8 WEEKS
Page 5 of 12
A & B Outerwear Ltd.
FINDING NO: E-8
CATEGORY: DESIGN, DRAWINGS & RECORDS
FINDING: Instruction for CPR (Cardiopulmonary Resuscitation) or Electrical shock restoration is not present.
RECOMMENDATION: Hang this first aid and CPR instructions near all electrical equipment (LT panel, MDB, FDB, DB, SDB) on a visible location.
PRIORITY: P2
REMEDIATION TIMEFRAME: 8 WEEKS
FINDING NO: E- 9
HT cable protected by DO fuse, dropping from pole.
CATEGORY: CABLE & CABLE SUPPORTS
FINDING: Wire is used in place of DO fuse and HT cables dropping from 11kV OH line not supported firmly to the pole.
RECOMMENDATION: Replace the wire with standard DO fuse and the HT cable dropping from 11kV pole must be firmly fixed to the pole with supports and clamps.
PRIORITY: P2
REMEDIATION TIMEFRAME: 6 WEEKS
FINDING NO: E- 10
315 kVA transformer in substation.
CATEGORY: TRANSFORMER ROOM
FINDING: No separation between LT panels and HT units (transformer, HT switchgear).
Recommendation: Make a brick built separation between LT and HT units; ensure that after making separator you have adequate ventilation (cross ventilation) and working clearance around each electrical equipment.
PRIORITY: P3
REMEDIATION TIMEFRAME: 16 WEEKS
Page 6 of 12
A & B Outerwear Ltd.
FINDING NO: E- 11
HT and LT cable.
CATEGORY: TRANSFORMER ROOM
FINDING: HT cable laid over the LT cables.
RECOMMENDATION: Cables of different voltage levels must be separated in different trays.
PRIORITY: P2
REMEDIATION TIMEFRAME: 6 WEEKS
FINDING NO: E- 12
500 kVA transformer in substation.
CATEGORY: TRANSFORMER ROOM
FINDING: No space around transformer for performing maintenance work.
Recommendation: Ensure a minimum 1.07m working space around the transformer.
PRIORITY: P2
REMEDIATION TIMEFRAME: 16 WEEKS
FINDING NO: E- 13
500 KVA transformer
CATEGORY: TRANSFORMER ROOM
FINDING: Oil leakage has been observed from transformer.
RECOMMENDATION: Stop oil leakage from transformer and keep top of transformer clean.
PRIORITY: P2
REMEDIATION TIMEFRAME: 8 WEEKS
Page 7 of 12
A & B Outerwear Ltd.
FINDING NO: E- 14
Transformer breather
CATEGORY: TRANSFORMER ROOM
FINDING: Silica gel inside the breather is replaced by pebbles.
Recommendation: Remove the pebbles from breather and replace it by silica gel after thorough cleaning of breather. The oil cup attached to breather must be filled by clean transformer oil.
PRIORITY: P1
REMEDIATION TIMEFRAME: 6 WEEKS
FINDING NO: E- 15
Main earthing busbar.
CATEGORY: EARTHING SYSTEM
FINDING: Impedance of main earthing of factory electrical system is very high (255.7 ohms)
Recommendation: Check properly may be loose connection is one of the cause.
PRIORITY: P2
REMEDIATION TIMEFRAME: 6 WEEKS
FINDING NO: E- 16
LT panel.
CATEGORY:DISTRIBUTION BOARD & PANEL
FINDING: No base plate and compression gland, excessive dust, lint and debris deposit underneath the panel (typical issue).
RECOMMENDATION: Dust, lint and debris must be thoroughly cleaned to avoid fire hazard. Provide covers (of noncombustible material) if any additional gap remains after installing cable glands.
PRIORITY: P1
REMEDIATION TIMEFRAME: 6 WEEKS
Page 8 of 12
A & B Outerwear Ltd.
FINDING NO: E- 17
MCCB inside the LT panel.
CATEGORY:DISTRIBUTION BOARD & PANEL
FINDING:
Cable connected MCCB without Lug. (Typical issue)
Recommendation: Cable must be connected to MCCB by cable lug.
PRIORITY: P1
REMEDIATION TIMEFRAME: 6 WEEKS
FINDING NO: E- 18
Bus bar inside the LT panel
CATEGORY:DISTRIBUTION BOARD & PANEL
FINDING: Cable connected to busbar without lug (typical).
Recommendation: Cables must be connected to busbar with proper size of cable lug.
PRIORITY: P1
REMEDIATION TIMEFRAME: 6 WEEKS
FINDING NO: E- 19
Inappropriate earthing
CATEGORY: EARTHING SYSTEM
FINDING: Earthing system of LT panel is not properly done. (Typical)
Recommendation: Every panel must be used earthing busbar.
PRIORITY: P1
REMEDIATION TIMEFRAME: 6 WEEKS
Page 9 of 12
A & B Outerwear Ltd.
FINDING NO: E- 20
Distribution cables
CATEGORY:CABLE & CABLE SUPPORTS
FINDING: Cable passes through wall are not protected and not supported.
RECOMMENDATION: Cable must be supported by cable tray and remaining gap is must be sealed.
PRIORITY: P2
REMEDIATION TIMEFRAME: 8 WEEKS
FINDING NO: E- 21
Cables terminating at MCCB in panel on production floor.
CATEGORY:DISTRIBUTION BOARD & PANEL
FINDING: Phase barrier/separator not installed (typical issue).
RECOMMENDATION: Put a purposely made phase separator (rubber type) between two phases; also terminate cables by proper sized cable lugs and cover cable lugs by heat shrink.
PRIORITY: P2
REMEDIATION TIMEFRAME: 8 WEEKS
FINDING NO: E- 22
Distribution cables
CATEGORY: CABLE & CABLE SUPPORTS
FINDING: Cables are covered by lint and dust.
RECOMMENDATION: Thoroughly clean the combustible materials. Suggested to include in routine cleanliness/maintenance work.
PRIORITY: P1
REMEDIATION TIMEFRAME: 8 WEEKS
Page 10 of 12
A & B Outerwear Ltd.
FINDING NO: E- 23
Cable raceways in production floor.
CATEGORY: WIRINGS
FINDING: Cable duct/channels have excessive lint/dust (typical issue).
RECOMMENDATION: Clean all the cable channels/ducts and cover them with checkered/perforated plates.
PRIORITY: P1
REMEDIATION TIMEFRAME: 8 WEEKS
FINDING NO: E- 24
Hot spot inside distribution board.
CATEGORY:DISTRIBUTION BOARD & PANEL
FINDING: Hot spots detected at termination point of MCCB due to loose connection. (72 degree)
RECOMMENDATION: Arrange periodic inspection & thermal scan to identify the overloading, loose connection, unbalanced load which may cause the excessive heat-rise and take action immediately
PRIORITY: P1
REMEDIATION TIMEFRAME: 4 WEEKS
FINDING NO: E- 25
Cable terminating at MCCB in panel.
CATEGORY:DISTRIBUTION BOARD & PANEL
FINDING: Multiple cable termination at a terminal of MCCB (typical issue).
RECOMMENDATION: Multiple cables connecting at a MCCB terminal must be disconnected. Existing multiple circuits may be distributed through bus bars.
PRIORITY: P2
REMEDIATION TIMEFRAME: 2 WEEKS
Page 11 of 12
A & B Outerwear Ltd.
FINDING NO: E- 26
Panel on ground floor.
CATEGORY:DISTRIBUTION BOARD & PANEL
FINDING: Cables inside distribution board is disorganized.
RECOMMENDATION: Organize all the power cables securely and neatly inside distribution board to prevent from electrical hazards.
PRIORITY: P1
REMEDIATION TIMEFRAME: 6 WEEKS
FINDING NO: E- 27
Cable terminating at MCCB inside distribution
board.
CATEGORY:DISTRIBUTION BOARD & PANEL
FINDING:
Power cables are bent excessively (typical issue).
RECOMMENDATION: Avoid power cable bending in electrical system;
in unavoidable case bend cables without any
stress but not less than 135 degrees.
PRIORITY: P2
REMEDIATION TIMEFRAME: 6 WEEKS
FINDING NO: E- 28
Wires terminating at busbar inside panel.
CATEGORY:DISTRIBUTION BOARD & PANEL
FINDING: Multiple cables connected in the busbar through a single lug (typical issue).
RECOMMENDATION: Every cable must be connected to the busbar through its own single lug (one lug per cable).
PRIORITY: P1
REMEDIATION TIMEFRAME: 4 WEEKS
Page 12 of 12
A & B Outerwear Ltd.
FINDING NO: E- 29
Cables terminating at MCCB.
CATEGORY:DISTRIBUTION BOARD & PANEL
FINDING: MCCB without enclosure and mounted on wooden plank.
RECOMMENDATION: Remove the wooden plank. Provide standard MCCB protective enclosures.
PRIORITY: P2
REMEDIATION TIMEFRAME: 4 WEEKS